Rosemount Quick Start Guide: Rosemount 3244MVF MultiVariable Temperature Transmitter Manuals & Guides

Quick Installation Guide
Product Discontinued
00825-0100-4769, Rev AA May 2003
Rosemount 3244MV
Rosemount 3244MVF MultiVariable Temperature Transmitter
Star t
Step 2: Wire and Apply Power
Step 3: Verify Tagging
Step 4: Verify Transmitter Configuration
End
¢00825-0100-4769;¤
www.rosemount.com
Quick Installation Guide
00825-0100-4769, Rev AA May 2003
© 2003 Rosemount Inc. All rights reserved. All marks property of owner.
Rosemount Division
8200 Market Boulevard Chanhassen, MN USA 55317 T (US) (800) 999-9307 T (Intnl) (952) 906-8888 Fax (952) 949-7001
Rosemount Temperature GmbH
Frankenstrasse 21 63791 Karlstein Germany T 49 (6188) 992 0 F 49 (6188) 992 112
Rosemount 3244MV
Emerson Process Management Asia Pacific Private Limited
1 Pandan Crescent Singapore 128461 T (65) 6777 8211 F (65) 6777 0947
IMPORTANT NOTICE
This installation guide provides basic guidelines for the Rosemount® Rosemount 3244MV. It does not provide instructions for detailed configuration, diagnostics, maintenance, service, troubleshooting, explosion-proof, flameproof, or intrinsically safe (I.S.) installations. Refer to the Rosemount 3244MV reference manual (document number 00809-0100-4769) for more instruction. The manual and this QIG are also available electronically on www.rosemount.com.
WARNING
Explosions could result in death or serious injury:
Installation of this transmitter in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices. Please review the approvals section of this manual for any restrictions associated with a safe installation.
In an Explosion-proof/Flame-proof installation, do not remove the transmitter covers when power is applied to the unit.
Process leaks may cause harm or result in death
• Install and tighten thermowells or sensors before applying pressure.
• Do not remove the thermowell while in operation.
Electrical shock can result in death or serious injury
• Avoid contact with the leads and terminals. High voltage that may be present on leads can cause electrical shock.
Quick Installation Guide
00825-0100-4769, Rev AA May 2003
Rosemount 3244MV
STEP 1: MOUNT THE TRANSMITTER
Mount the transmitter at a high point in the conduit run to prevent moisture from draining into the transmitter housing.
Typical Direct Mount Installation
1. Mount the thermowell to the process container wall. Install and tighten thermowells. Perform a leak check.
2. Attach any necessary unions, couplings, and extension fittings. Seal the fitting threads with silicone or tape (if required).
3. Screw the sensor into the thermowell or directly into the process (depending on installation requirements).
4. Verify all sealing requirements.
5. Attach the transmitter to the thermowell/sensor assembly. Seal all threads with silicone or tape (if required).
6. Install field wiring conduit into the open transmitter conduit entry (for remote mounting) and feed wires into the transmitter housing.
7. Pull the field wiring leads into the terminal side of the housing.
8. Attach the sensor leads to the transmitter sensor terminals (the wiring diagram is located inside the housing cover).
9. Attach and tighten both transmitter covers.
C
A
A = Thermowell D = Conduit for Field Wiring (dc power) B = Extension (Nipple) E = Extension Fitting Length C = Union or Coupling
B
E
D
3144-0433QIG
Quick Installation Guide
00825-0100-4769, Rev AA May 2003
Rosemount 3244MV
STEP 1 CONTINUED...
Typical Remote Mount Installation
1. Mount the thermowell to the process container wall. Install and tighten thermowells. Perform a leak check.
2. Attach a connection head to the thermowell.
3. Insert sensor into the thermowell and wire the sensor to the connection head (the wiring diagram is located inside the connection head).
4. Mount the transmitter to a 2-in. (50 mm) pipe or a panel using one of the optional mounting bracket (B4 bracket is shown below).
5. Attach cable glands to the shielded cable running from the connection head to the transmitter conduit entry.
6. Run the shielded cable from the opposite conduit entry on the transmitter back to the control room.
7. Insert shielded cable leads through the cable entries into the connection head / transmitter. Connect and tighten cable glands.
8. Connect the shielded cable leads to the connection head terminals (located inside the connection head) and to the sensor wiring terminals (located inside the transmitter housing).
A
B
C
A = Cable Gland B = Shielded Cable from Sensor to Transmitter C = Shielded Cable from Transmitter to Control Room D = 2-in. (50 mm) pipe E = B4 Mounting Bracket
D
E
644-0000b05b
Quick Installation Guide
*
00825-0100-4769, Rev AA May 2003
Rosemount 3244MV
STEP 2: WIRE AND APPLY POWER
1. Remove terminal block cover
2. Ensure the sensor wires are inside the terminal area.
3. Connect sensor wires according to Figure 1.
4. Tighten sensor terminal screws.
Power
Terminals
Sensor
Terminals
Transmitter
Terminals
Figure 1. Transmitter Sensor Wiring Diagram
2-wire RTD
and Ohms
W
R
**
**
Average.
Temp./DT/Hot
Backup/Dual
Sensor with 2
RTDs
* Transmitter must be configured for a 3-wire RTD in order to recognize an RTD
with a compensation loop.
** Rosemount provides 4-wire sensors for all single-element RTDs. You can use
these RTDs in 3-wire configurations by leaving the unneeded leads disconnected and insulated with electrical tape.
*** Typical wiring configuration of a Rosemount dual-element RTD is shown
(R=Red, W=White, G=Green, B=Black
**
W & G
G
B
Thermocouples
3-wire RTD
and Ohms
Average.
Temp./DT/Hot
Backup/Dual
Sensor with 2
4-wire RTD and Ohms
**
Average.
Temp./DT/Hot
Backup/Dual
Sensor with
RTDs/
Thermocouples
Thermocouples
and Millivolts
**
Average.
Temp./DT/
Hot Backup/Dual
Sensor with
RTDs/
Thermocouples
Ground Terminal
*
RTD with
Compensation
Loop
**
Avera ge.
Tem p. /DT /
Hot Backup/Dual
Sensor with 2
RTDs with
Compensation
Loop
Quick Installation Guide
00825-0100-4769, Rev AA May 2003
Rosemount 3244MV
STEP 2 CONTINUED...
Power the Transmitter
The transmitter requires between 9 and 32 Vdc to operate and provide complete functionality. The dc power supply should provide power with less than 2% ripple.
Power Filter
A fieldbus segment requires a power conditioner to isolate the power supply filter and decouple the segment from other segments attached to the same power supply.
Power Connections
Use copper wire of sufficient size to ensure that the voltage across the transmitter power terminals is not below 9 Vdc.
To connect power to the transmitter, follow the steps below:
1. Remove the transmitter cover to expose the transmitter terminal block. Do not remove transmitter covers in explosive atmospheres when the circuit it live.
2. Connect the power leads to the terminals marked “+” and “T”. The power terminals are not polar sensitive, meaning that the electrical polarity of the power leads is not significant when connected to the power terminals. The use of crimped lugs is recommended when wiring to screw terminals.
3. Tighten the terminal screws to ensure adequate contact. No additional power wiring is necessary.
4. Replace the transmitter cover, tightening the cover threads at least one-third turn after the o-ring contacts the housing. Both transmitter covers must be fully engaged to meet explosion-proof requirements.
NOTE
After installation, it may take several seconds for the LCD meter to function once power is applied to the transmitter.
Loading...
+ 14 hidden pages