This guide provides basic guidelines for installing the Rosemount 3144P
Transmitter. It does not provide instructions for detailed configuration,
diagnostics, maintenance, service, troubleshooting, Explosion-proof,
Flameproof, or intrinsically safe (I.S.) installations. Refer to the Rosemount
3144P Transmitter Reference Manual for more instructions. The manual and
this guide are also available electronically on Emerson.com/Rosemount.
WARNING
Explosions
Explosions could result in death or serious injury.
Installation of device in an explosive environment must be in accordance
with appropriate local, national, and international standards, codes, and
practices.
Review the Product Certifications section of this document for any
restrictions associated with a safe installation.
In an Explosion-proof/Flameproof installation, do not remove the
transmitter covers when power is applied to the unit.
Process leaks
Process leaks may cause harm or result in death.
Install and tighten thermowells and sensors before applying pressure.
Do not remove the thermowell while in operation.
Conduit/cable entries
The conduit/cable entries in the transmitter housing use a ½–14 NPT
thread form.
When installing in a hazardous location, use only appropriately listed or
Ex certified plugs, glands, or adapters in cable/conduit entries.
Electrical shock
Electrical shock can result in death or serious injury.
Avoid contact with the leads and terminals. High voltage that may be
present on leads could cause electrical shock.
Quick Start Guide3
Quick Start GuideMarch 2021
WARNING
Physical access
Unauthorized personnel may potentially cause significant damage to and/or
misconfiguration of end users’ equipment. This could be intentional or
unintentional and needs to be protected against.
Physical security is an important part of any security program and
fundamental to protecting your system. Restrict physical access by
unauthorized personnel to protect end users’ assets. This is true for all
systems used within the facility.
4Rosemount 3144P
March 2021Quick Start Guide
2Mount the transmitter
Mount the transmitter at a high point in the conduit run to prevent moisture
from draining into the transmitter housing.
2.1Typical North American installation
Procedure
1. Mount the thermowell to the process container wall.
2. Install and tighten thermowells.
3. Perform a leak check.
4. Attach any necessary unions, couplings, and extension fittings. Seal
the fitting threads with an approved thread sealant, such as silicone
or PTFE tape (if required).
5. Screw the sensor into the thermowell or directly into the process
(depending on installation requirements).
6. Verify all sealing requirements.
7. Attach the transmitter to the thermowell/sensor assembly. Seal all
threads with an approved thread sealant, such as silicone or PTFE
tape (if required).
8. Install field wiring conduit into the open transmitter conduit entry
(for remote mounting) and feed wires into the transmitter housing.
9. Pull the field wiring leads into the terminal side of the housing.
10. Attach the sensor leads to the transmitter sensor terminals.
The wiring diagram is located inside the housing cover.
11. Attach and tighten both transmitter covers.
2.2
Quick Start Guide5
Typical European installation
Procedure
1. Mount the thermowell to the process container wall.
2. Install and tighten thermowells.
3. Perform a leak check.
4. Attach a connection head to the thermowell.
5. Insert sensor into the thermowell and wire the sensor to the
connection head.
The wiring diagram is located inside the connection head.
6. Mount the transmitter to a 2-in. (50 mm) pipe or a panel using one of
the optional mounting brackets.
Quick Start GuideMarch 2021
7. Attach cable glands to the shielded cable running from the
connection head to the transmitter conduit entry.
8. Run the shielded cable from the opposite conduit entry on the
transmitter back to the control room.
9. Insert shielded cable leads through the cable entries into the
connection head/transmitter. Connect and tighten cable glands.
10. Connect the shielded cable leads to the connection head terminals
(located inside the connection head) and to the sensor wiring
terminals (located inside the transmitter housing).
6Rosemount 3144P
March 2021Quick Start Guide
3Wire and apply power
3.1Wire the transmitter
Table 3-1: Single Sensor
2-wire RTD and
ohms
(1) Emerson provides 4-wire sensors for all single-element RTDs. You can use these RTDs in 3-
wire configurations by leaving the unneeded leads disconnected and insulated with
electrical tape.
(2) Transmitter must be configured for a 3-wire RTD in order to recognize an RTD with a
compensation loop.
3-wire RTD and
(1)
ohms
4-wire RTD and
ohms
T/Cs and
millivolts
RTD with
compensation
(2)
loop
Table 3-2: Dual Sensor
Emerson provides 4-wire sensors for all single-element RTDs. To use these RTDs in three-wire
configurations, leave the unneeded leads disconnected and insulated with electrical tape This
table refers to wiring dual sensors for ΔT and Hot Backup™.
With two
RTDs
With two
thermocouples
With RTDs/
thermocouples
With RTDs/
thermocouples
With two RTDs
with
compensation
loop
Quick Start Guide7
Quick Start GuideMarch 2021
3.2Power the transmitter
A. Sensor terminals (1–5)
B. Power terminals
C. Ground
Procedure
1. Remove the terminal block cover.
2. Connect power to the power terminal.
The terminals are polarity insensitive.
3. Tighten the terminal screws.
4. Reattach and tighten the cover.
WARNING
Enclosure
Enclosure covers must be fully engaged to meet explosion-proof
requirements.
5. Apply power.
8Rosemount 3144P
March 2021Quick Start Guide
3.3Ground the transmitter
3.3.1Ungrounded thermocouple, mV, and RTD/ohm inputs
Each process installation has different requirements for grounding. Use the
grounding options recommended by the facility for the specific sensor type
or begin with grounding option 1 (the most common).
Ground the transmitter: option 1
Emerson recommends this option for ungrounded transmitter housing.
Procedure
1. Connect signal wiring shield to the sensor wiring shield.
2. Ensure the two shields are tied together and electrically isolated from
the transmitter housing.
3. Ground shield at the power supply end only.
4. Ensure that the sensor shield is electrically isolated from the
surrounding grounded fixtures.
5. Connect shields together, electrically isolated from the transmitter.
A. Sensor wire
B. Transmitter
C. Shield ground point
Ground the transmitter: option 2
Emerson recommends this method for grounded transmitter housing.
Procedure
1. Connect sensor wiring shield to the transmitter housing.
Do this only if the housing is grounded.
2. Ensure that the sensor is electrically isolated from surrounding
fixtures that may be grounded.
3. Ground signal wiring shield at the power supply end.
Quick Start Guide9
Quick Start GuideMarch 2021
A. Sensor wire
B. Transmitter
C. Shield ground point
Ground the transmitter: option 3
Procedure
1. Ground sensor wiring shield at the sensor, if possible.
2. Ensure the sensor wiring and signal wiring shields are electrically
isolated from the transmitter housing and other grounded fixtures.
3. Ground signal wiring shield at the power supply end.
A. Sensor wire
B. Transmitter
C. Shield ground point
3.3.2Ground thermocouple inputs
Procedure
1. Ground sensor wiring shield at the sensor.
10Rosemount 3144P
March 2021Quick Start Guide
2. Ensure the sensor wiring and signal wiring shields are electrically
isolated from the transmitter housing and other grounded fixtures.
3. Ground signal wiring shield at the power supply end.
A. Sensor wire
B. Transmitter
C. Shield ground point
Quick Start Guide11
Quick Start GuideMarch 2021
4Verify tagging
4.1Commissioning (paper) tag
To identify which device is at a particular location use the removable tag
provided with the transmitter. Ensure the physical device tag (PD Tag field)
is properly entered in both places on the removable commissioning tag and
tear off the bottom portion for each transmitter.
Note
The device description loaded in the host system must be at the same
revision as this device. You can download the device description from
Emerson.com/Rosemount.
4.1.1Verify transmitter configuration
Each FOUNDATION Fieldbus host or configuration tool has a different way of
displaying and performing configurations. Some use Device Descriptions
(DD) or DD methods for configuration and to display data consistently
across platforms. There is no requirement that a host or configuration tool
support these features.
12Rosemount 3144P
Loading...
+ 28 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.