Rosemount Quick Start Guide: Rosemount 3144P Temperature Transmitters with FOUNDATION™ fieldbus Protocol Manuals & Guides

Quick Start Guide
00825-0100-4834, Rev FB
Rosemount™ 3144P Temperature Transmitters
with FOUNDATION™ Fieldbus Protocol
March 2021
Quick Start Guide March 2021
Contents
About this guide...........................................................................................................................3
Mount the transmitter..................................................................................................................5
Wire and apply power...................................................................................................................7
Verify tagging............................................................................................................................ 12
Product certifications................................................................................................................. 16
2 Rosemount 3144P
March 2021 Quick Start Guide

1 About this guide

This guide provides basic guidelines for installing the Rosemount 3144P Transmitter. It does not provide instructions for detailed configuration, diagnostics, maintenance, service, troubleshooting, Explosion-proof, Flameproof, or intrinsically safe (I.S.) installations. Refer to the Rosemount 3144P Transmitter Reference Manual for more instructions. The manual and this guide are also available electronically on Emerson.com/Rosemount.
WARNING
Explosions
Explosions could result in death or serious injury.
Installation of device in an explosive environment must be in accordance with appropriate local, national, and international standards, codes, and practices.
Review the Product Certifications section of this document for any restrictions associated with a safe installation.
In an Explosion-proof/Flameproof installation, do not remove the transmitter covers when power is applied to the unit.
Process leaks
Process leaks may cause harm or result in death.
Install and tighten thermowells and sensors before applying pressure. Do not remove the thermowell while in operation.
Conduit/cable entries
The conduit/cable entries in the transmitter housing use a ½–14 NPT thread form.
When installing in a hazardous location, use only appropriately listed or Ex certified plugs, glands, or adapters in cable/conduit entries.
Electrical shock
Electrical shock can result in death or serious injury.
Avoid contact with the leads and terminals. High voltage that may be present on leads could cause electrical shock.
Quick Start Guide 3
Quick Start Guide March 2021
WARNING
Physical access
Unauthorized personnel may potentially cause significant damage to and/or misconfiguration of end users’ equipment. This could be intentional or unintentional and needs to be protected against.
Physical security is an important part of any security program and fundamental to protecting your system. Restrict physical access by unauthorized personnel to protect end users’ assets. This is true for all systems used within the facility.
4 Rosemount 3144P
March 2021 Quick Start Guide

2 Mount the transmitter

Mount the transmitter at a high point in the conduit run to prevent moisture from draining into the transmitter housing.

2.1 Typical North American installation

Procedure
1. Mount the thermowell to the process container wall.
2. Install and tighten thermowells.
3. Perform a leak check.
4. Attach any necessary unions, couplings, and extension fittings. Seal the fitting threads with an approved thread sealant, such as silicone or PTFE tape (if required).
5. Screw the sensor into the thermowell or directly into the process (depending on installation requirements).
6. Verify all sealing requirements.
7. Attach the transmitter to the thermowell/sensor assembly. Seal all threads with an approved thread sealant, such as silicone or PTFE tape (if required).
8. Install field wiring conduit into the open transmitter conduit entry (for remote mounting) and feed wires into the transmitter housing.
9. Pull the field wiring leads into the terminal side of the housing.
10. Attach the sensor leads to the transmitter sensor terminals. The wiring diagram is located inside the housing cover.
11. Attach and tighten both transmitter covers.
2.2
Quick Start Guide 5

Typical European installation

Procedure
1. Mount the thermowell to the process container wall.
2. Install and tighten thermowells.
3. Perform a leak check.
4. Attach a connection head to the thermowell.
5. Insert sensor into the thermowell and wire the sensor to the connection head.
The wiring diagram is located inside the connection head.
6. Mount the transmitter to a 2-in. (50 mm) pipe or a panel using one of the optional mounting brackets.
Quick Start Guide March 2021
7. Attach cable glands to the shielded cable running from the connection head to the transmitter conduit entry.
8. Run the shielded cable from the opposite conduit entry on the transmitter back to the control room.
9. Insert shielded cable leads through the cable entries into the connection head/transmitter. Connect and tighten cable glands.
10. Connect the shielded cable leads to the connection head terminals (located inside the connection head) and to the sensor wiring terminals (located inside the transmitter housing).
6 Rosemount 3144P
March 2021 Quick Start Guide

3 Wire and apply power

3.1 Wire the transmitter

Table 3-1: Single Sensor
2-wire RTD and ohms
(1) Emerson provides 4-wire sensors for all single-element RTDs. You can use these RTDs in 3-
wire configurations by leaving the unneeded leads disconnected and insulated with electrical tape.
(2) Transmitter must be configured for a 3-wire RTD in order to recognize an RTD with a
compensation loop.
3-wire RTD and
(1)
ohms
4-wire RTD and ohms
T/Cs and millivolts
RTD with compensation
(2)
loop
Table 3-2: Dual Sensor
Emerson provides 4-wire sensors for all single-element RTDs. To use these RTDs in three-wire configurations, leave the unneeded leads disconnected and insulated with electrical tape This table refers to wiring dual sensors for ΔT and Hot Backup™.
With two RTDs
With two thermocouples
With RTDs/ thermocouples
With RTDs/ thermocouples
With two RTDs with compensation loop
Quick Start Guide 7
Quick Start Guide March 2021

3.2 Power the transmitter

A. Sensor terminals (1–5) B. Power terminals C. Ground
Procedure
1. Remove the terminal block cover.
2. Connect power to the power terminal. The terminals are polarity insensitive.
3. Tighten the terminal screws.
4. Reattach and tighten the cover.
WARNING
Enclosure
Enclosure covers must be fully engaged to meet explosion-proof requirements.
5. Apply power.
8 Rosemount 3144P
March 2021 Quick Start Guide

3.3 Ground the transmitter

3.3.1 Ungrounded thermocouple, mV, and RTD/ohm inputs

Each process installation has different requirements for grounding. Use the grounding options recommended by the facility for the specific sensor type or begin with grounding option 1 (the most common).
Ground the transmitter: option 1
Emerson recommends this option for ungrounded transmitter housing.
Procedure
1. Connect signal wiring shield to the sensor wiring shield.
2. Ensure the two shields are tied together and electrically isolated from the transmitter housing.
3. Ground shield at the power supply end only.
4. Ensure that the sensor shield is electrically isolated from the surrounding grounded fixtures.
5. Connect shields together, electrically isolated from the transmitter.
A. Sensor wire B. Transmitter C. Shield ground point
Ground the transmitter: option 2
Emerson recommends this method for grounded transmitter housing.
Procedure
1. Connect sensor wiring shield to the transmitter housing. Do this only if the housing is grounded.
2. Ensure that the sensor is electrically isolated from surrounding fixtures that may be grounded.
3. Ground signal wiring shield at the power supply end.
Quick Start Guide 9
Quick Start Guide March 2021
A. Sensor wire B. Transmitter C. Shield ground point
Ground the transmitter: option 3
Procedure
1. Ground sensor wiring shield at the sensor, if possible.
2. Ensure the sensor wiring and signal wiring shields are electrically isolated from the transmitter housing and other grounded fixtures.
3. Ground signal wiring shield at the power supply end.
A. Sensor wire B. Transmitter C. Shield ground point

3.3.2 Ground thermocouple inputs

Procedure
1. Ground sensor wiring shield at the sensor.
10 Rosemount 3144P
March 2021 Quick Start Guide
2. Ensure the sensor wiring and signal wiring shields are electrically isolated from the transmitter housing and other grounded fixtures.
3. Ground signal wiring shield at the power supply end.
A. Sensor wire B. Transmitter C. Shield ground point
Quick Start Guide 11
Quick Start Guide March 2021

4 Verify tagging

4.1 Commissioning (paper) tag

To identify which device is at a particular location use the removable tag provided with the transmitter. Ensure the physical device tag (PD Tag field) is properly entered in both places on the removable commissioning tag and tear off the bottom portion for each transmitter.
Note
The device description loaded in the host system must be at the same revision as this device. You can download the device description from
Emerson.com/Rosemount.

4.1.1 Verify transmitter configuration

Each FOUNDATION Fieldbus host or configuration tool has a different way of displaying and performing configurations. Some use Device Descriptions (DD) or DD methods for configuration and to display data consistently across platforms. There is no requirement that a host or configuration tool support these features.
12 Rosemount 3144P
Loading...
+ 28 hidden pages