Rosemount Quick Start Guide: Rosemount 3144P HART Temperature Transmitter Manuals & Guides

Quick Installation Guide
Step 1: Configure (Bench Calibration) Step 2: Set the Switches Step 3: Mount the Transmitter Step 4: Wire and Apply Power Step 5: Perform a Loop Test Safety Instrumented Systems Product Certifications
Star t
End
00825-0100-4021, Rev DA November 2009
Rosemount 3144P HART Temperature Transmitter
Rosemount 3144P
www.rosemount.com
¢00825-0100-4021e¤
Quick Installation Guide
IMPORTANT NOTICE
WARNING
Emerson Process Management Rosemount Division
8200 Market Boulevard Chanhassen, MN USA 55317 T (US) (800) 999-9307 T (Intnl) (952) 906-8888 F (952) 949-7001
Emerson Process Management Temperature GmbH
Frankenstrasse 21 63791 Karlstein Germany T 49 (6188) 992 0 F 49 (6188) 992 112
Emerson Process Management Asia Pacific Private Limited
1 Pandan Crescent Singapore 128461 T (65) 6777 8211 F (65) 6777 0947
00825-0100-4021, Rev DA
Rosemount 3144P
© 2009 Rosemount Inc. All rights reserved. All marks property of owner. The Emerson logo is a trade mark and service mark of Emerson Electric Co. Rosemount and Rosemount logotype are registered trademarks of Rosemount Inc. HART is a registered trademark of the HART Communications Foundation.
This installation guide provides basic guidelines for the Rosemount 3144P. It does not provide instructions for detailed configuration, diagnostics, maintenance, service, troubleshooting, explosion-proof, flameproof, or intrinsically safe (I.S.) installations. Refer to the 3144P reference manual (document number 00809-0100-4021) for more instruction. The manual and this QIG are also available electronically on www.rosemount.com.
Explosions could result in death or serious injury:
Installation of this transmitter in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices. Please review the approvals section of this manual for any restrictions associated with a safe installation.
In an Explosion-proof/Flame-proof installation, do not remove the transmitter covers when power is applied to the unit.
Process leaks may cause harm or result in death
• Install and tighten thermowells or sensors before applying pressure.
• Do not remove the thermowell while in operation.
Electrical shock can result in death or serious injury
• Avoid contact with the leads and terminals. High voltage that may be present on leads can cause electrical shock.
November 2009
2
Quick Installation Guide

STEP 1: CONFIGURE (BENCH CALIBRATION)

250 R
L
1100
3144-0000a04a
Power
Supply
Power/Signal Terminals
00825-0100-4021, Rev DA November 2009
Rosemount 3144P
The Rosemount 3144P communicates using a 375 Field Communicator (communication requires a loop resistance between 250 and 1100 ohms) or AMS. Do not operate when power is below 12 Vdc at the transmitter terminal. Refer to the 3144P Reference Manual (document number 00809-0100-4021) and 375 Field Communicator Reference Manual (document number 00809-0100-4276) for more information.
Update the 375 Field Communicator Software
The 375 Field Communicator Field Device Revision Dev v4, DD v1 or greater is required to fully communicate with the 3144P. The Device Descriptors are available with new communicators or can be loaded into existing communicators at any Emerson Process Management Service Center.
Perform the following steps to determine if an upgrade is required.
1. Connect the sensor (see the wiring diagram located on the inside of the housing cover)
2. Connect the bench power supply to the power terminals (“+” or “–”).
3. Connect a 375 Field Communicator to the loop across a loop resistor or at the power/signal terminals on the transmitter.
4. The following message will appear if the communicator has a previous version of the device descriptors (DDs).
NOTICE: Upgrade the communicator software to access new XMTR functions. Continue with old description?
NOTE:
If this notice does not appear, the latest DD is installed.
If the latest version is not available, the communicator will communicate properly, but when the transmitter is configured some new capabilities may not be visible.
To prevent this from happening, upgrade to the latest DD or answer NO to the question and default to the generic transmitter functionality.
Figure 1. Connecting a Communicator to a Bench Loop.
3
Quick Installation Guide
STEP 1 CONTINUED...
00825-0100-4021, Rev DA
Rosemount 3144P
November 2009
Verify Transmitter Configuration
The HART Fast Key sequences in Table 1 may be used for transmitter configuration and startup.
Table 1. HART Fast Key Sequences
Function HART Fast Keys
Active Calibrator 1, 2, 2, 1, 3 Alarm Values 1, 3, 4, 2, 1 Analog Output 1, 1, 4 Average Temperature Setup 1, 3, 3, 2 Average Temperature Configuration 1, 3, 3, 2 Burst Mode 1, 3, 4, 3, 3 Burst Option 1, 3, 4, 3, 4 Calibration 1, 2, 2 Clear Log 1, 2, 1, 6 Configure Hot Backup 1, 3, 3, 4 Configuration 1, 3 D/A Trim 1, 2, 2, 2 Damping Values 1, 3, 4, 1, 3 Date 1, 3, 5, 2 Descriptor 1, 3, 5, 3 Device Information 1, 3, 5 Diagnostics and Service 1, 2 Differential Temperature Setup 1, 3, 3, 1 Differential Temperature Configuration 1, 3, 3, 1 Drift Alert 1, 3, 3, 5 Filter 50/60 Hz 1, 3, 6, 1 First Good Temperature Setup 1, 3, 3, 3 First Good Temperature Configuration 1, 3, 3, 3 Hardware Revision 1, 4, 1 Hart Output 1, 3, 4, 3 Intermittent Sensor Detect 1, 3, 6, 2 Intermittent Threshold 1, 3, 6, 3 Loop Test 1, 2, 1, 1 LRV (Lower Range Value) 1, 3, 4, 1, 1 LSL (Lower Sensor Limit) 1, 3, 4, 1, 5 Master Reset 1, 2, 1, 3 Message 1, 3, 5, 4 Meter Options 1, 3, 4, 4 Open Sensor Holdoff 1, 3, 6, 4 Percent Range 1, 1, 5 Poll Address 1, 3, 4, 3, 1 Process Temperature 1, 1 Process Variables 1, 1 Range Values 1, 3, 4, 1 Review 1, 4 Scaled D/A Trim 1, 2, 2, 3
4
Quick Installation Guide
00825-0100-4021, Rev DA November 2009
Function HART Fast Keys
Sensor 1 Configuration 1, 3, 2, 3 Sensor 2 Configuration 1, 3, 2, 4 Sensor Limits 1, 3, 2, 2 Sensor 1 Serial Number 1, 3, 2, 3, 3 Sensor 2 Serial Number 1, 3, 2, 4, 3 Sensor 1 Setup 1, 3, 2, 3 Sensor 2 Setup 1, 3, 2, 4 Sensor Trim 1, 2, 2, 1, 1 Sensor Type 1, 3, 2, 1 Sensor 1 Unit 1, 3, 2, 3, 1 Sensor 2 Unit 1, 3, 2, 4, 1 Software Revision 1, 4, 1 Status 1, 2, 1, 4 Ta g 1, 3, 5, 1 Terminal Temperature Setup 1, 3, 2, 5 Test Device 1, 2, 1 Transmitter-Sensor Matching 1, 3, 2, 1 URV (Upper Range Value) 1, 3, 4, 1, 2 USL (Upper Sensor Limit) 1, 3, 4, 1, 6 Variable Mapping 1, 3, 1 View Log 1, 2, 1, 5 Wires 1, 3, 2, 1 2-wire Offset Sensor 1 1, 3, 2, 3, 6 2-wire Offset Sensor 2 1, 3, 2, 4, 6
Rosemount 3144P
Input/Verify Callendar Van-Dusen Constants
If Transmitter-Sensor Matching is being used with this combination of a transmitter and sensor, verify the constants input. When using two sensors, repeat Steps 1 – 5 for the second sensor.
1. At the Home screen, select 1 Device Setup, 3 Configuration, 2 Sensor Config, 1 Change Type/Conn., 1 Sensor 1 (Select Sensor 2 two sensors). Set the control loop to manual. Select OK
2. Select Cal VanDusen at the Enter Sensor Type prompt.
3. Select the appropriate number of wires at the Enter Sensor Connection prompt.
4. Enter the R special-order sensor.
5. Select OK after you return the control loop to automatic control.
, Alpha, Beta, and Delta values from the stainless steel tag attached to the
o
5
Quick Installation Guide

STEP 2: SET THE SWITCHES

STEP 3: MOUNT THE TRANSMITTER

A
E
D
B
C
3144-0433QIG
00825-0100-4021, Rev DA
Rosemount 3144P
The Security and Failure Mode Switches are located on the top center of the electronics module. Follow the steps below to set the switches.
November 2009
Without a LCD Display
1. Set the loop to manual (if applicable) and disconnect the power.
2. Remove the electronics housing cover.
3. Set the switches to the desired position. Reattach housing cover.
4. Apply power and set the loop to automatic control.
With a LCD Display
1. Set the loop to manual (if applicable) and disconnect the power.
2. Remove the electronics housing cover.
3. Unscrew the LCD display screws and slide the meter straight off.
4. Set the switches to the desired position.
5. Reattach the LCD display and electronics housing cover (consider LCD display orientation – rotate in 90 degree increments).
6. Apply power and set the loop to automatic control.
Mount the transmitter at a high point in the conduit run to prevent moisture from draining into the transmitter housing.
Typical Field Mount Installation
1. Mount the thermowell to the process container wall. Install and tighten thermowells. Perform a leak check.
2. Attach any necessary unions, couplings, and extension fittings. Seal the fitting threads with an approved thread sealant, such as silicone or PTFE tape (if required).
3. Screw the sensor into the thermowell or directly into the process (depending on installation requirements).
4. Verify all sealing requirements.
5. Attach the transmitter to the thermowell/sensor assembly. Seal all threads with an approved thread sealant, such as silicone or PTFE tape (if required).
6. Install field wiring conduit into the open transmitter conduit entry (for remote mounting) and feed wires into the transmitter housing.
7. Pull the field wiring leads into the terminal side of the housing.
8. Attach the sensor leads to the transmitter sensor terminals (the wiring diagram is located inside the housing cover).
9. Attach and tighten both transmitter covers.
A = Thermowell D = Conduit for Field Wiring (dc power) B = Extension (Nipple) E = Extension Fitting Length C = Union or Coupling
6
Quick Installation Guide
STEP 3 CONTINUED...
A
E
B
C
644-0000b05b
D
00825-0100-4021, Rev DA November 2009
Rosemount 3144P
Typical Remote Mount Installation
1. Mount the thermowell to the process container wall. Install and tighten thermowells. Perform a leak check.
2. Attach a connection head to the thermowell.
3. Insert sensor into the thermowell and wire the sensor to the connection head (the wiring diagram is located inside the connection head).
4. Mount the transmitter to a 2-in. (50 mm) pipe or a panel using one of the optional mounting bracket (B4 bracket is shown below).
5. Attach cable glands to the shielded cable running from the connection head to the transmitter conduit entry.
6. Run the shielded cable from the opposite conduit entry on the transmitter back to the control room.
7. Insert shielded cable leads through the cable entries into the connection head / transmitter. Connect and tighten cable glands.
8. Connect the shielded cable leads to the connection head terminals (located inside the connection head) and to the sensor wiring terminals (located inside the transmitter housing).
A = Cable Gland B = Shielded Cable from Sensor to Transmitter C = Shielded Cable from Transmitter to Control Room D = 2-in. (50 mm) pipe E = B4 Mounting Bracket
7
Quick Installation Guide

STEP 4: WIRE AND APPLY POWER

1240
1000
750
250
0
10
12.0 Min
18.1 30 42.4
Supply Voltage (V dc)
HART and Analog Operating Range
4–20 mA dc
Load (Ohms)
500
1100
Analog Only Operating Range
“–” “+”
Sensor Terminals (1 – 5)
Test
Ground
00825-0100-4021, Rev DA
Rosemount 3144P
• Wiring diagrams are located inside the terminal block cover.
• An external power supply is required to operate the transmitter.
• The power required across the transmitter power terminals is 12 to 42.4 V DC (the power terminals are rated to 42.4 V DC). To prevent the possibility of damaging the transmitter, do not allow terminal voltage to drop below 12.0 Vdc when changing the configuration parameters.
November 2009
Load Limitations
Maximum Load = 40.8 X (Supply Voltage - 12.0)
(1) Without transient protection (optional).
Power the Transmitter
1. Remove the terminal block cover.
2. Connect the positive power lead to the “+” terminal. Connect the negative power lead to the “–” terminal.
3. Tighten the terminal screws.
4. Reattach and tighten the cover.
5. Apply power.
(1)
8
Loading...
+ 16 hidden pages