Step 1: Configure (Bench Calibration)
Step 2: Set the Switches
Step 3: Mount the Transmitter
Step 4: Wire and Apply Power
Step 5: Perform a Loop Test
Safety Instrumented Systems
Product Certifications
Star t
End
00825-0100-4021, Rev DA
November 2009
Rosemount 3144P HART
Temperature Transmitter
Rosemount 3144P
www.rosemount.com
¢00825-0100-4021e¤
Quick Installation Guide
IMPORTANT NOTICE
WARNING
Emerson Process Management
Rosemount Division
8200 Market Boulevard
Chanhassen, MN USA 55317
T (US) (800) 999-9307
T (Intnl) (952) 906-8888
F (952) 949-7001
Emerson Process Management
Temperature GmbH
Frankenstrasse 21
63791 Karlstein
Germany
T 49 (6188) 992 0
F 49 (6188) 992 112
Emerson Process Management
Asia Pacific Private Limited
1 Pandan Crescent
Singapore 128461
T (65) 6777 8211
F (65) 6777 0947
This installation guide provides basic guidelines for the Rosemount 3144P. It does not
provide instructions for detailed configuration, diagnostics, maintenance, service,
troubleshooting, explosion-proof, flameproof, or intrinsically safe (I.S.) installations. Refer to
the 3144P reference manual (document number 00809-0100-4021) for more instruction.
The manual and this QIG are also available electronically on www.rosemount.com.
Explosions could result in death or serious injury:
Installation of this transmitter in an explosive environment must be in accordance with the
appropriate local, national, and international standards, codes, and practices. Please
review the approvals section of this manual for any restrictions associated with a safe
installation.
In an Explosion-proof/Flame-proof installation, do not remove the transmitter covers
when power is applied to the unit.
Process leaks may cause harm or result in death
• Install and tighten thermowells or sensors before applying pressure.
• Do not remove the thermowell while in operation.
Electrical shock can result in death or serious injury
• Avoid contact with the leads and terminals. High voltage that may be present on leads
can cause electrical shock.
November 2009
2
Quick Installation Guide
STEP 1: CONFIGURE (BENCH CALIBRATION)
250 R
L
1100
3144-0000a04a
Power
Supply
Power/Signal Terminals
00825-0100-4021, Rev DA
November 2009
Rosemount 3144P
The Rosemount 3144P communicates using a 375 Field Communicator (communication
requires a loop resistance between 250 and 1100 ohms) or AMS. Do not operate when
power is below 12 Vdc at the transmitter terminal. Refer to the 3144P Reference Manual
(document number 00809-0100-4021) and 375 Field Communicator Reference Manual
(document number 00809-0100-4276) for more information.
Update the 375 Field Communicator Software
The 375 Field Communicator Field Device Revision Dev v4, DD v1 or greater is required to
fully communicate with the 3144P. The Device Descriptors are available with new
communicators or can be loaded into existing communicators at any Emerson Process
Management Service Center.
Perform the following steps to determine if an upgrade is required.
1. Connect the sensor (see the wiring diagram located on the inside of the housing cover)
2. Connect the bench power supply to the power terminals (“+” or “–”).
3. Connect a 375 Field Communicator to the loop across a loop resistor or at the
power/signal terminals on the transmitter.
4. The following message will appear if the communicator has a previous version of the
device descriptors (DDs).
NOTICE: Upgrade the communicator software to access new XMTR functions. Continue
with old description?
NOTE:
If this notice does not appear, the latest DD is installed.
If the latest version is not available, the communicator will communicate properly, but
when the transmitter is configured some new capabilities may not be visible.
To prevent this from happening, upgrade to the latest DD or answer NO to the question
and default to the generic transmitter functionality.
Figure 1. Connecting a Communicator to a Bench Loop.
3
Quick Installation Guide
STEP 1 CONTINUED...
00825-0100-4021, Rev DA
Rosemount 3144P
November 2009
Verify Transmitter Configuration
The HART Fast Key sequences in Table 1 may be used for transmitter configuration and
startup.
Table 1. HART Fast Key Sequences
FunctionHART Fast Keys
Active Calibrator1, 2, 2, 1, 3
Alarm Values1, 3, 4, 2, 1
Analog Output1, 1, 4
Average Temperature Setup1, 3, 3, 2
Average Temperature Configuration1, 3, 3, 2
Burst Mode1, 3, 4, 3, 3
Burst Option1, 3, 4, 3, 4
Calibration1, 2, 2
Clear Log1, 2, 1, 6
Configure Hot Backup1, 3, 3, 4
Configuration1, 3
D/A Trim1, 2, 2, 2
Damping Values 1, 3, 4, 1, 3
Date1, 3, 5, 2
Descriptor 1, 3, 5, 3
Device Information1, 3, 5
Diagnostics and Service 1, 2
Differential Temperature Setup1, 3, 3, 1
Differential Temperature Configuration1, 3, 3, 1
Drift Alert 1, 3, 3, 5
Filter 50/60 Hz 1, 3, 6, 1
First Good Temperature Setup1, 3, 3, 3
First Good Temperature Configuration1, 3, 3, 3
Hardware Revision1, 4, 1
Hart Output 1, 3, 4, 3
Intermittent Sensor Detect1, 3, 6, 2
Intermittent Threshold1, 3, 6, 3
Loop Test 1, 2, 1, 1
LRV (Lower Range Value)1, 3, 4, 1, 1
LSL (Lower Sensor Limit)1, 3, 4, 1, 5
Master Reset1, 2, 1, 3
Message1, 3, 5, 4
Meter Options1, 3, 4, 4
Open Sensor Holdoff1, 3, 6, 4
Percent Range1, 1, 5
Poll Address 1, 3, 4, 3, 1
Process Temperature1, 1
Process Variables1, 1
Range Values1, 3, 4, 1
Review1, 4
Scaled D/A Trim1, 2, 2, 3
If Transmitter-Sensor Matching is being used with this combination of a transmitter and
sensor, verify the constants input. When using two sensors, repeat Steps 1 – 5 for the
second sensor.
1. At the Home screen, select 1 Device Setup, 3 Configuration, 2 Sensor Config, 1 Change Type/Conn., 1 Sensor 1 (Select Sensor 2 two sensors). Set the control loop to manual.
Select OK
2. Select Cal VanDusen at the Enter Sensor Type prompt.
3. Select the appropriate number of wires at the Enter Sensor Connection prompt.
4. Enter the R
special-order sensor.
5. Select OK after you return the control loop to automatic control.
, Alpha, Beta, and Delta values from the stainless steel tag attached to the
o
5
Quick Installation Guide
STEP 2: SETTHE SWITCHES
STEP 3: MOUNTTHE TRANSMITTER
A
E
D
B
C
3144-0433QIG
00825-0100-4021, Rev DA
Rosemount 3144P
The Security and Failure Mode Switches are located on the top center of the electronics
module. Follow the steps below to set the switches.
November 2009
Without a LCD Display
1. Set the loop to manual (if applicable) and disconnect the power.
2. Remove the electronics housing cover.
3. Set the switches to the desired position. Reattach housing cover.
4. Apply power and set the loop to automatic control.
With a LCD Display
1. Set the loop to manual (if applicable) and disconnect the power.
2. Remove the electronics housing cover.
3. Unscrew the LCD display screws and slide the meter straight off.
4. Set the switches to the desired position.
5. Reattach the LCD display and electronics housing cover (consider LCD display
orientation – rotate in 90 degree increments).
6. Apply power and set the loop to automatic control.
Mount the transmitter at a high point in the conduit run to prevent moisture from draining into
the transmitter housing.
Typical Field Mount Installation
1. Mount the thermowell to the process container wall. Install and tighten thermowells.
Perform a leak check.
2. Attach any necessary unions, couplings, and extension fittings. Seal the fitting threads
with an approved thread sealant, such as silicone or PTFE tape (if required).
3. Screw the sensor into the thermowell or directly into the process (depending on
installation requirements).
4. Verify all sealing requirements.
5. Attach the transmitter to the thermowell/sensor assembly. Seal all threads with an
approved thread sealant, such as silicone or PTFE tape (if required).
6. Install field wiring conduit into the open transmitter conduit entry (for remote mounting)
and feed wires into the transmitter housing.
7. Pull the field wiring leads into the terminal side of the housing.
8. Attach the sensor leads to the transmitter sensor terminals (the wiring diagram is located
inside the housing cover).
9. Attach and tighten both transmitter covers.
A = ThermowellD = Conduit for Field Wiring (dc power)
B = Extension (Nipple)E = Extension Fitting Length
C = Union or Coupling
6
Quick Installation Guide
STEP 3 CONTINUED...
A
E
B
C
644-0000b05b
D
00825-0100-4021, Rev DA
November 2009
Rosemount 3144P
Typical Remote Mount Installation
1. Mount the thermowell to the process container wall. Install and tighten thermowells.
Perform a leak check.
2. Attach a connection head to the thermowell.
3. Insert sensor into the thermowell and wire the sensor to the connection head (the wiring
diagram is located inside the connection head).
4. Mount the transmitter to a 2-in. (50 mm) pipe or a panel using one of the optional
mounting bracket (B4 bracket is shown below).
5. Attach cable glands to the shielded cable running from the connection head to the
transmitter conduit entry.
6. Run the shielded cable from the opposite conduit entry on the transmitter back to the
control room.
7. Insert shielded cable leads through the cable entries into the connection head /
transmitter. Connect and tighten cable glands.
8. Connect the shielded cable leads to the connection head terminals (located inside the
connection head) and to the sensor wiring terminals (located inside the transmitter
housing).
A = Cable Gland
B = Shielded Cable from Sensor to Transmitter
C = Shielded Cable from Transmitter to Control Room
D = 2-in. (50 mm) pipe
E = B4 Mounting Bracket
7
Quick Installation Guide
STEP 4: WIREAND APPLY POWER
1240
1000
750
250
0
10
12.0 Min
18.13042.4
Supply Voltage (V dc)
HART and Analog
Operating Range
4–20 mA dc
Load (Ohms)
500
1100
Analog Only
Operating Range
“–”
“+”
Sensor Terminals (1 – 5)
Test
Ground
00825-0100-4021, Rev DA
Rosemount 3144P
• Wiring diagrams are located inside the terminal block cover.
• An external power supply is required to operate the transmitter.
• The power required across the transmitter power terminals is 12 to 42.4 V DC (the
power terminals are rated to 42.4 V DC). To prevent the possibility of damaging the
transmitter, do not allow terminal voltage to drop below 12.0 Vdc when changing the
configuration parameters.
November 2009
Load Limitations
Maximum Load = 40.8 X (Supply Voltage - 12.0)
(1) Without transient protection (optional).
Power the Transmitter
1. Remove the terminal block cover.
2. Connect the positive power lead to the “+” terminal.
Connect the negative power lead to the “–” terminal.
3. Tighten the terminal screws.
4. Reattach and tighten the cover.
5. Apply power.
(1)
8
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.