Rosemount Quick Start Guide: Rosemount 3100 Series Ultrasonic Level Transmitter External Temperature Sensor Manuals & Guides

Quick Installation Guide
00825-0100-4842, Rev. BA November 2010
Level
Rosemount 3100 Series Ultrasonic Level Transmitter External Temperature Sensor
Part No : 03100-0001-0001 For use with ultrasonic transmitters 3102 and 3105
For transmitter installations where the integral temperature sensor is not representative of the air / medium temperature in the process, the use of the external temperature sensor improves accuracy.
Sensor Specifi cation
316 Stainless steel body with two locknuts, M8 thread, 6 mm maximum panel thickness. Sensor working temperature -40 to 85 °C, cable working temperature -20 to 80 °C. Cable 5 m long, single twisted pair.
www.rosemount.com
Note :
When connected to a 3105 intrinsically safe transmitter, this sensor is classifi ed as ‘simple apparatus’ according to EN 50020 paragraph 5.4. Temperature class T6,
-20 °C < Ta < 80 °C
Level

Installation

Quick Installation Guide
00825-0100-4842, Rev. BA
November 2010
1. Connect the two sensor wires to terminals 7 and 8 of the transmitter; polarity is not important. See diagram below; also refer to Transmitter Installation Manual. Ensure use of a suitably IP rated cable gland to maintain the IP rating of the transmitter.
2. Mount the sensor between the transmitter and the liquid level, to measure the air / medium temperature at a representative point.
3. Avoid allowing the sensor to become submerged.
4. Do not mount the sensor near a heat source or in direct sunlight.
5. For the optimum response to temperature change, do not mount directly onto a large thermal mass.
6. To avoid false echoes, do not mount the sensor directly in the path of the transmitter beam.
7. The transmitter will automatically detect and enable the sensor. Fine adjustments to the temperature calibration may be made; refer to the Installation Manual supplied with the transmitter.
7
Temp
Wiring Diagram External temperature sensor
8
3100 Series Transmitter
The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount and the Rosemount logotype are registered trademarks of Rosemount Inc. All other marks are the property of their respective owners. Standard Terms and Conditions of Sale can be found at www.rosemount.com\terms_of_sale
© 2010 Rosemount, Inc. All rights reserved.
Emerson Process Management Rosemount Division
8200 Market Boulevard Chanhassen, MN USA 55317 T (U.S.) 1-800-999-9307 T (Intnl) (952) 906-8888 F (952) 949-7001 www.rosemount.com
www.rosemount.com
Emerson Process Management
Bleigistrasse 23 P.O. Box 1046 CH 6341 Baar Switzerland T +41 (0) 41 768 6111 F +41 (0) 41 768 630
Emerson FZE
P.O. Box 17033 Jebel Ali Free Zone Dubai UAE T +971 4 883 5235 F +971 4 883 5312
Emerson Process Management Asia Pacifi c Private Limited
1 Pandan Crescent Singapore 128461 T (65) 6777 8211 F (65) 6777 0947 / (65) 6777 0743 Enquiries@AP.EmersonProcess.com
Loading...