Quick Installation Guide
Step 1: Mount the Transmitter
Step 2: Connect the Battery
Step 3: Trim the Transmitter
Step 4: Verify Operation
Step 5: Reference Information
Product Certifications
Star t
End
Product Discontinued. Click here for the new WirelessHART document.
00825-0100-4802, Rev BA
June 2007
Rosemount 3051S Wireless
Rosemount 3051S Series Pressure Transmitter with
Wireless Enabled HART® Solutions
Rosemount 3051SF Series Flowmeter Transmitter
with Wireless Enabled HART
®
Solutions
www.rosemount.com
¢00825-0100-4809[¤

Quick Installation Guide
Product Discontinued. Click here for the new WirelessHART document.
00825-0100-4802, Rev BA
Rosemount 3051S Wireless
© 2007 Rosemount Inc. All rights reserved. All marks property of owner. Rosemount and the Rosemount logotype are
registered trademarks of Rosemount Inc.
Rosemount Inc.
8200 Market Boulevard
Chanhassen, MN USA 55317
T (US) (800) 999-9307
T (Intnl) (952) 906-8888
F (952) 949-7001
Emerson Process Management
Asia Pacific Private Limited
1 Pandan Crescent
Singapore 128461
T (65) 6777 8211
F (65) 6777 0947/65 6777 0743
This installation guide provides basic guidelines for Rosemount 3051S Wireless Transmitters
(reference manual document number 00809-0100-4802). It does not provide instructions for
diagnostics, maintenance, service, or troubleshooting. Refer to the Rosemount 3051S Wireless
reference manual (document number 00809-0100-4802) for more instruction. The manual and
this QIG are also available electronically on www.rosemount.com.
Explosions could result in death or serious injury:
Installation of this transmitter in an explosive environment must be in accordance with the appropriate
local, national, and international standards, codes, and practices. Please review the product
certifications section for any restrictions associated with a safe installation.
• Before connecting a 375 Field Communicator in an explosive atmosphere, ensure the instruments
are installed in accordance with intrinsically safe or non-incendive field wiring practices.
Process leaks may cause harm or result in death.
• Install and tighten process connectors before applying pressure.
Electrical shock can result in death or serious injury.
• Avoid contact with the leads and terminals. High voltage that may be present on leads can cause
electrical shock.
Emerson Process Management
GmbH & Co. OHG
Argelsrieder Feld 3
82234 Wessling
Germany
T 49 (8153) 9390, F49 (8153) 939172
Beijing Rosemount Far East Instrument Co.,
Limited
No. 6 North Street, Hepingli, Dong Cheng District
Beijing 100013, China
T (86) (10) 6428 2233
F (86) (10) 6422 8586
June 2007
The Rosemount 3051S and all other wireless devices should be installed only after the 1420 Wireless
Gateway has been installed and is functioning properly. Wireless devices should also be powered up
in order of proximity from the 1420 Wireless Gateway, beginning with the closest. This will result in a
simpler and faster network installation.
Shipping considerations for wireless products (Lithium Batteries):
The unit was shipped to you without the battery installed. Please remove the battery pack prior to
shipping the unit.
Primary lithium batteries are regulated in transportation by the U. S. Department of Transportation,
and are also covered by IATA (International Air Transport Association), ICAO (International Civil
Aviation Organization), and ARD (European Ground Transportation of Dangerous Goods). It is the
responsibility of the shipper to ensure compliance with these or any other local requirements. Please
consult current regulations and requirements before shipping.
2

Quick Installation Guide
STEP 1: MOUNT THE TRANSMITTER
Product Discontinued. Click here for the new WirelessHART document.
00825-0100-4802, Rev BA
June 2007
Liquid Flow Applications
1. Place taps to the side of the line.
2. Mount beside or below the taps.
3. Mount the transmitter so that the drain/vent
valves are oriented upward.
Gas Flow Applications
1. Place taps in the top or side of the line.
2. Mount beside or above the taps.
Rosemount 3051S Wireless
Steam Flow Applications
1. Place taps to the side of the line.
2. Mount beside or below the taps.
3. Fill impulse lines with water.
3

Rosemount 3051S Wireless
Product Discontinued. Click here for the new WirelessHART document.
Quick Installation Guide
00825-0100-4802, Rev BA
June 2007
Panel Mount Pipe Mount
Coplanar™ Flange
Traditional Flange
In-line
NOTE:
Position the antenna such that it is VERTICAL, either straight up or straight down.
4