Rosemount Quick Start Guide: Rosemount™ 3051G Pressure Transmitter with 4-20mA HART® Protocol (Revision 5 and 7) Manuals & Guides

Quick Start Guide
00825-0100-4057, Rev EA
March 2020
Rosemount™ 3051G Pressure Transmitter
with 4-20mA HART® Protocol (Revision 5 and 7)
Quick Start Guide March 2020
Note
Before installing the transmitter, confirm the correct device driver is loaded on the host systems. See
System readiness.
NOTICE
This installation guide provides basic guidelines for Rosemount 3051 transmitters. It does not provide instructions for configuration, diagnostics, maintenance, service, troubleshooting, Explosion-Proof, Flameproof, or intrinsically safe (I.S.) installations. Refer to the Rosemount 3051 Reference Manual (document number 00809-0100-5007) for more instruction. This manual is also available electronically on www.emerson.com.
WARNING
Explosions could result in death or serious injury.
Installation of this transmitter in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices. Review the approvals section of the Rosemount 3051 Reference Manual for any restrictions associated with a safe installation.
Before connecting a HART-based communicator in an explosive atmosphere, make sure the instruments in the loop are installed in accordance with intrinsically safe or non-incendive field wiring practices.
In an explosion-proof/flameproof installation, do not remove the transmitter covers when power is applied to the unit.
Process leaks could result in death or serious injury.
To avoid process leaks, only use the o-ring designed to seal with the corresponding flange adapter.
Electrical shock could cause death or serious injury.
Avoid contact with the leads and terminals. High voltage that may be present on leads can cause electrical shock.
Conduit/cable entries
Unless otherwise marked, the conduit/cable entries in the housing enclosure use a ½–14 NPT form. Only use plugs, adapters, glands, or conduit with a compatible thread form when closing these entries.
Physical access
Unauthorized personnel may potentially cause significant damage to and/or misconfiguration of end users’ equipment. This could be intentional or unintentional and needs to be protected against.
Physical security is an important part of any security program and fundamental to protecting your system. Restrict physical access by unauthorized personnel to protect end users’ assets. This is true for all systems used within the facility.
Contents
System readiness......................................................................................................................... 5
Transmitter installation................................................................................................................ 6
Safety instrumented systems installation................................................................................... 18
Product certifications................................................................................................................. 19
2 Emerson.com/Rosemount
March 2020 Quick Start Guide
Declaration of Conformity..........................................................................................................28
China RoHS table........................................................................................................................32
Quick Start Guide 3
Quick Start Guide March 2020
4 Emerson.com/Rosemount
March 2020 Quick Start Guide

1 System readiness

1.1 Confirm HART revision capability

If using HART based control or asset management systems, please
confirm the HART capability of those systems prior to transmitter installation. Not all systems are capable of communicating with HART Revision 7 protocol. This transmitter can be configured for either HART Revision 5 or 7.
For instructions on how to change the HART revision of your transmitter,
see Switch HART revision mode.

1.2 Confirm correct device driver

Verify the latest device driver (DD/DTM™) is loaded on your systems to
ensure proper communications.
Download the latest device driver at Emerson.com or FieldComm Group

1.2.1 Rosemount 3051 device revisions and drivers

Table 1-1 provides the information necessary to verify the correct device
driver and documentation for your device.
Table 1-1: Rosemount 3051 Device Revisions and Files
Identify device Find device driver Review
Software release date
Dec-11 1.0.0 01 7 10 00809-0100
Jan-98 N/A 178 5 3 00809-0100
(1) NAMUR Software Revision is located on the hardware tag of the device. HART
(2) Device driver file names use Device and DD Revision, e.g. 10_01. HART Protocol
(3) HART Revision 5 and 7 Selectable, Safety Certified, Local Operator Interface,
Quick Start Guide 5
NAMUR software revision
1)
Software Revision can be read using a HART capable configuration tool.
is designed to enable legacy device driver revisions to continue to communicate with new HART devices. To access new functionality, the new device driver must be downloaded. It is recommended to download new device driver files to ensure full functionality.
Process Alerts, Scaled Variable, Configurable Alarms, Expanded Engineering Units.
HART software
(
revision
HART universal
(1)
revision
5 9
Device revision
(2)
instructions
Manual document number
-4007
-4001
Review functionality
Changes to software
(3)
See
for list
of changes.
N/A
(3)
Quick Start Guide March 2020

2 Transmitter installation

2.1 Step 1: Mount the transmitter

2.1.1 Liquid applications

Procedure
1. Place taps to the side of the line.
2. Mount beside or below the taps.
3. Mount the transmitter so that the drain/vent valves are oriented upward.
Figure 2-1: In-Line Liquid Applications

2.1.2 Gas applications

Procedure
1. Place taps in the top or side of the line.
2. Mount beside or above the taps.
6 Emerson.com/Rosemount
March 2020 Quick Start Guide
Figure 2-2: In-Line Gas Applications

2.1.3 Steam applications

Procedure
1. Place taps to the side of the line.
2. Mount beside or below the taps.
3. Fill impulse lines with water.
Figure 2-3: In-Line Steam Applications
Quick Start Guide 7
A
Quick Start Guide March 2020
Figure 2-4: Panel and Pipe Mounting
Rosemount 3051G
Panel mount
(1)
Pipe mount
(1) 1.5 / 16 × 1 ½ Panel bolts are customer supplied.

2.2 Inline gage transmitter orientation

The low side pressure port (atmospheric reference) on the inline gage transmitter is located in the neck of the transmitter, behind the housing. The vent path is 360° around the transmitter between the housing and sensor. (See Figure 2-5).
Keep the vent path free of any obstruction, including but not limited to paint, dust, and lubrication by mounting the transmitter so that the process can drain away.
Figure 2-5: Inline Gage Low Side Pressure Port
A
Low side pressure port (atmospheric reference)
8 Emerson.com/Rosemount
March 2020 Quick Start Guide

2.3 Step 2: Set the switches

Set Alarm and Security switch configuration before installation as shown in
Figure 2-6.
The Alarm switch sets the analog output alarm to high or low.Default alarm is high.
The Security switch allows (unlocked symbol) or prevents (locked
symbol) any configuration of the transmitter.
Default security is off (unlocked symbol).
Use the following procedure to change the switch configuration:
Procedure
1.
If the transmitter is installed, secure the loop, and remove power.
Remove the housing cover opposite the field terminal side. Do not
2. remove the instrument cover in explosive atmospheres when the circuit is live.
3.
Slide the security and alarm switches into the preferred position using a small screwdriver.
4. Reattach the transmitter cover. The cover must be fully engaged to comply with explosion-proof requirements.
Figure 2-6: Transmitter Electronics Board
Without LCD display With LCD/LOI display
A B
Quick Start Guide 9
Alarm Security
A
B
C
Quick Start Guide March 2020

2.4 Step 3: Connect the wiring and power up

Figure 2-7: Transmitter Wiring Diagrams (4–20 mA)
A
B
C
24 Vdc supply
RL ≥ 250
Current meter (optional)
Shielded twisted pair cable should be used for best results. Use 24 AWG or larger wire that does not exceed 5,000 feet (1500 meters) in length. If applicable, install wiring with a drip loop. Arrange the drip loop so the bottom is lower than the conduit connections and the transmitter housing.
CAUTION
Installation of the transient protection terminal block does not provide transient protection unless the Rosemount 3051 case is properly grounded.
Do not run signal wiring in conduit or open trays with power wiring, or near heavy electrical equipment.
Do not connect the powered signal wiring to the test terminals. Power could damage the test diode in the terminal block.
Use the following steps to wire the transmitter:
Procedure
1. Remove the housing cover on the FIELD TERMINALS side.
2. Connect the positive lead to the “+” terminal (PWR/COMM) and the negative lead to the “–” terminal.
3. Ground housing to fulfill local grounding regulations.
4. Ensure proper grounding. It is important that the instrument cable shield be:
10 Emerson.com/Rosemount
DP
A
B
C
March 2020 Quick Start Guide
Trimmed close and insulated from touching the transmitter
housing
Connected to the next shield if cable is routed through a junction
box
Connected to a good earth ground at the power supply end
5. If transient protection is needed, refer to section Grounding for
transient terminal block for grounding instructions.
6. Plug and seal unused conduit connections.
7. Replace the housing cover.
Figure 2-8: Wiring
A Insulate shield and shield drain wire
B Insulate exposed shield drain wire
C Connect shield back to the power supply ground

2.4.1 Grounding for transient terminal block

Ground termination is provided on the outside of the electronics housing and inside the terminal compartment. These grounds are used when the transient protection terminal blocks are installed. It is recommended that 18 AWG or larger wire is used to connect housing ground to earth ground (internal or external).
If the transmitter is currently not wired for power up and communication, follow Step 1-Step 7 of Step 3: Connect the wiring and power up When the transmitter is properly wired, reference Figure 2-8 for internal and external transient grounding locations.
Quick Start Guide 11
Loading...
+ 25 hidden pages