Step 1: Location and Orientation
Step 2: Installation Preparation
Step 4: Mount the Transmitter
Product Certifications
End
www.rosemount.com
¢00825-0300-4809k¤
Quick Installation Guide
00825-0100-4031, Rev AA
Duct Mount 285 Annubar
© 2005 Rosemount Inc. All rights reserved. All marks property of owner. Rosemount and the Rosemount logotype are registered trademarks of Rosemount Inc.
Rosemount Inc.
8200 Market Boulevard Chanhassen, MN USA 55317 T (US) (800) 999-9307 T (Intnl) (952) 906-8888 F (952) 949-7001
Emerson Process Management Asia Pacific Private Limited
1 Pandan Crescent Singapore 128461 T (65) 6777 8211 F (65) 6777 0947/65 6777 0 743
Emerson Process Management GmbH & Co. OHG
Argelsrieder Feld 3 82234 Wessling Germany T 49 (8153) 9390 F49 (8153) 939172
Beijing Rosemount Far East Instrument Co., Limited
No. 6 North Street, Hepingli, Dong Cheng District Beijing 100013, China T (86) (10) 6428 2233 F (86) (10) 6422 8586
April 2005
IMPORTANT NOTICE
This installation guide provides basic guidelines for Rosemount 285 Annubar. It does not provide instructions for configuration, diagnostics, maintenance, service, troubleshooting, Explosion-proof, Flame-Proof, or instrinsically safe (I.S.) installations. Refer to the 285 Annubar reference manual (document number 00809-0100-4028) for more instruction. This manual is also available electronically on www.rosemount.com.
WARNING
Process leaks may cause harm or result in death. To avoid process leaks, only use gaskets designed to seal with the corresponding flange and o-rings to seal process connections. Flowing medium may cause the 285 Annubar assembly to become hot and could result in burns.
STEP 1: LOCATION AND ORIENTATION
Correct location in the duct is important for accurate measurement. See Table 1 on page 3 for proper installation locations.
Straight-run Installations
The recommended straight-run duct lengths upstream are 7W or 7H; downstream, 2W or 2H. Installation across the longest dimension is preferred.
H
2W
W
7W
2
H
2H
W
7H
285/15-490024-901,
15-490025-901.eps
Quick Installation Guide
1
1
00825-0100-4031, Rev AA April 2005
Duct Mount 285 Annubar
Elbow Installations
The unit will measure accurately when installed 2 duct widths (height) downstream of a 90° elbow in plane with the elbow.
H
W
2W
H
Special Installations
For unique duct configurations, consult the factory.
Table 1. Minimum straight duct requirements for the 285 Annubar
Upstream Length Downstream Length
H
W
H
W
15W
7W
7W
2W
285/15-490028-901
2W
285/15-490029-901
H
2W
2H
W
7W 2W
7W 2W
15W 2W
285/15-490026-901,
15-490027-901.eps
W
7W
2W
285/15-490030-90
H
7W 2W
15W
W
2W
285/15-490031-90
3.864
15W 2W
DAMPER
W
285/15-490032-901
3
Quick Installation Guide
A
00825-0100-4031, Rev AA
Duct Mount 285 Annubar
April 2005
STEP 2: INSTALLATION PREPARATION
Operating Limitations
For the Annubar to produce accurate, repeatable flow measurement, the following must be considered. The maximum allowed pressure and temperature limits are:
• Annubar Type D1 (duct mount without compression fitting): 10 psig @ -40°F to 850°F.
• Annubar Type D2 (duct mount with compression fitting): 10 psig @ -40°F to 300°F.
Annubar Installation Preparation
1. Make sure there is enough clearance to insert the Annubar into the duct.
2. Mark the mounting location of the Annubar, locating it along the center line of the rectangular duct, or anywhere on the circumference of a round duct. Mark horizontal and vertical center lines through the mounting location. For duct mount Annubars without compression fitting (threaded stud welded to tip of sensor), extend the center line to the opposite duct wall (or 180° around a circular duct), as shown in Figure 1.
Figure 1.
3. Measure and mark the locations of the mount screw holes and the opposite side support
285/15-490013-903,
hole (for Annubars with threaded stud welded to sensor tip) (see Table 2).
Figure 2.
180°
H
H/2
A
Table 2. Installation dimensions inches (mm)
Annubar Model Number A
285xxxxxxxxxx1x 0.75 (19.05) 285xxxxxxxxxx2x 1.31 (33.27)
4
A
A
Ø
A
A
A
A
285/15-490013-901,