Rosemount Quick Start Guide: Rosemount™ 214C Sensor Manuals & Guides

Rosemount™ 214C Sensor
Quick Start Guide
00825-0400-2654, Rev DB
May 2021
Quick Start Guide May 2021
Contents
About this guide...........................................................................................................................3
Wiring diagram for RTDs.............................................................................................................. 5
Wiring diagram for thermocouples.............................................................................................. 6
Additional RTD specifications....................................................................................................... 7
Additional thermocouple specifications....................................................................................... 9
Product certifications................................................................................................................. 10
Declaration of Conformity..........................................................................................................23
China RoHS................................................................................................................................ 25
2 Emerson.com/Rosemount
May 2021 Quick Start Guide
This guide provides basic guidelines for Rosemount 214C Sensor models. If the sensor was ordered assembled to a temperature thermowell or transmitter, see the appropriate product literature for information on configuration and hazardous locations certifications.

1.1 Safety messages

NOTICE
Complications can arise when the sensors and the transmitters to which they are assembled are certified to compatible, but each has different approvals. Be aware of the following situations:
If an I.S. approved Rosemount 214C Sensor is ordered with a housing, a
transmitter enclosed in that housing may have a different I.S. approval rating. Refer to the transmitter IS certificate if applicable.
If a sensor and transmitter have different certifications, or if either has
more certifications than the other, installation must comply with the most restrictive requirements required by either component. This is especially (but not exclusively) relevant when combination approvals are ordered on either the sensor or transmitter. Review certifications on both the sensor and transmitter for installation requirements and ensure installation of the sensor/transmitter assembly complies with a single certification that is shared by both of these components and that meets the requirements of the application.
WARNING
Explosion
Explosions could result in death or serious injury.
Installation of sensor in an explosive environment must be in accordance with appropriate local, national, and international standards, codes, and practices.
Quick Start Guide 3
Quick Start Guide May 2021
WARNING
Conduit/cable entries
Unless marked, the conduit/cable entries in the housing use a ½–14 NPT thread form. Entries marked “M20” are M20 × 1.5 thread form. On devices with multiple conduit entries, all entries will have the same thread form. Only use plugs, adapters, glands, or conduit with a compatible thread form when closing these entries.
When installing in a hazardous location, use only appropriately listed or Ex certified plugs, glands, or adapters in cable/conduit entries.
Only use plugs, adapters, glands, or conduit with a compatible thread form when closing these entries.
Physical access
Unauthorized personnel may potentially cause significant damage to and/or misconfiguration of end users’ equipment. This could be intentional or unintentional and needs to be protected against.
Physical security is an important part of any security program and fundamental to protecting your system. Restrict physical access by unauthorized personnel to protect end users’ assets. This is true for all systems used within the facility.
CAUTION
Refer to Product Certification section of this Quick Start Guide documentation.
4 Emerson.com/Rosemount
Red
Red
White
White
Red
Red
White
Red
Red
White
Black Black
Yellow
May 2021 Quick Start Guide

2 Wiring diagram for RTDs

Figure 2-1: RTD Lead Wire Configuration per IEC 60751 - Single Element
3-wire 4-wire
Note
To configure a single element, 4-wire RTD as a 3-wire system, connect only one white lead. Insulate or terminate the unused white lead in a manner that prevents shorting to the ground. To configure a single element, 4-wire RTD as a 2-wire system, connect matching colored wires first and then connect the paired wires to the terminal.
Figure 2-2: RTD Lead Wire Configuration per IEC 60751 - Dual Element
3-wire
Quick Start Guide 5
( – )
( + )
( + )
( + )
( – )
( – )
Quick Start Guide May 2021

3 Wiring diagram for thermocouples

Figure 3-1: Thermocouple Lead Wire Configuration
Single thermocouple, 2-wire Dual thermocouple, 4-wire
Table 3-1: Thermocouple Wire Color
IEC 60584 Themocouple ASTM E230 Thermocouple
Type POS (+) NEG (-) POS (+) NEG (-)
J Black White White Red
K Green White Yellow Red
T Brown White Blue Red
Note
Dual thermocouple sensors are shipped with one pair of the wires shrink­wrapped together.
6 Emerson.com/Rosemount
May 2021 Quick Start Guide

4 Additional RTD specifications

Note
All specifications in this section apply to all RTDs unless noted otherwise. All RTDs meet and/or exceed type and routine tests for sensors/thermometers per IEC 60751:2008.

4.1 Insulation resistance

1000 MΩ minimum insulation resistance when measured at 500 VDC at room temperature.

4.2 Insulation resistance at elevated temperature

Insulation resistance at elevated temperatures for sensor types RT, RH, and RW are tested and meet requirements according to IEC 60751:2008 6.5.1.

4.3 Time response

Sensor response time tested in flowing water according to IEC 60751:2008
6.5.2.
Sensor type RT: T50 average = 8.5 seconds; T90 average = 22.9 seconds
Sensor type RH: T50 average = 9.15 seconds; T90 average = 24.1 seconds
Sensor type RW: T50 average = 9.0 seconds; T90 average = 24.4 seconds
4.4
4.5
4.6
4.7
Quick Start Guide 7

Stability

Stability at upper temperature limit tested and meets requirements according to IEC 60751:2008 6.5.3.

Effects of temperature cycling

Effect of temperature cycling tested and meets requirements according to IEC 60751:2008 6.5.5.

Hysteresis

Effect of hysteresis tested and meets requirements according to IEC 60751:2008 6.5.6.

Self heating

Self-heating tested and meets requirements according to IEC 60751:2008
6.5.7.
Quick Start Guide May 2021

4.8 Process immersion

Minimum immersion depth tested according to IEC 60751:2008 6.5.8.
Sensor type RT, single: Minimum immersion depth = 30 mm
Sensor type RT, dual: Minimum immersion depth = 45 mm
Sensor type RH, single and dual: Minimum immersion depth = 40 mm
Sensor type RW, single and dual: Minimum immersion depth = 50 mm

4.9 Vibration limits

Vibration tested according to IEC 60751:2008 6.6.4.
Sensor type RT ordered with VR1: Meets 10 g vibration between 20 and 500 Hz for 150 hours.
Sensor type RT and RH: Meets 3 g vibration between 20 and 500 Hz for 150 hours.
Sensor type RW: Meets 1 g vibration between 20 and 500 Hz for 150 hours.

4.10 Functional specifications

Power
Environmental
Overvoltage Category I
Pollution Degree 4
8 Emerson.com/Rosemount
May 2021 Quick Start Guide

5 Additional thermocouple specifications

Note
All specifications in this section apply to all thermocouple types unless noted otherwise. All thermocouples meet and/or exceed type and routine tests for sensors/thermometers per IEC 61515:2016.

5.1 Insulation resistance

1000 MΩ minimum insulation resistance when measured at 500 VDC at room temperature.

5.2 Time response

Sensor response time tested in flowing water according to IEC 61515:2016
5.3.2.8.
Grounded: T50 average = 1.9 seconds; T90 average = 4.0 seconds
Ungrounded: T50 average = 2.8 seconds; T90 average = 7.3 seconds

5.3 Process immersion

Minimum immersion depth tested according to IEC 60751:2008 6.5.8.
Grounded thermocouples: Minimum immersion depth = 5 mm
Ungrounded thermocouples: Minimum immersion depth = 10 mm
5.4
5.5
Quick Start Guide 9

Continuity

Electrical continuity and polarity are tested and meet requirements according to IEC 61515:2016 5.3.2.

Functional specifications

Power
Environmental
Overvoltage Category I
Pollution Degree 4
Loading...
+ 19 hidden pages