This document provides basic installation guidelines for the Rosemount 1195 Integral Orifice
Assembly. For comprehensive instructions for detailed configuration, diagnostics, maintenance,
service, installation, or troubleshooting refer to the Rosemount 1195 Reference Manual. The manual
and this guide are also available electronically on www.emerson.com.
If the Rosemount 1195 Integral Orifice was ordered assembled to a Rosemount Pressure Transmitter,
refer to the following Quick Start Guides for information on configuration and hazardous locations
certifications:
1. Rosemount 3051S Quick Start Guide
2. Rosemount 3051SMV Quick Start Guide
3. Rosemount 3051 Quick Start Guide
WARNING
Process leaks could result in death or serious injury.
To avoid process leaks, only use the gasket designed to seal with the corresponding flange adapter. To
avoid process leaks, only use the O-ring designed to seal with the corresponding flange adapter.
Contents
Rosemount 1195 Integral Orifice Assembly View......................................................................... 3
Location and orientation.............................................................................................................. 4
Primary element orientation........................................................................................................ 6
Primary element installation.........................................................................................................9
Preparing for operation.............................................................................................................. 12
E. Transmitter
F. Rosemount 1195 enhanced support body
G. Enhanced support orifice plate
(1)
(1)
Transmitter and housing are shown for clarity purposes - only supplied if ordered.
Quick Start Guide3
UD
UD
U
D
Quick Start GuideApril 2021
2Location and orientation
Install the Rosemount 1195 Integral Orifice in the correct location within the
piping branch to prevent inaccurate measurement caused by flow
disturbances.
2.1Straight pipe length
Use the upstream (U) and downstream (D) lengths provided below in
conjunction with figures below to determine the appropriate upstream (U)
and downstream (D) pipe lengths. For example, for a 1-in. line size with a
beta ratio (×) of 0.4 using installation of , the straight length of upstream
piping required is 25 x 1 = 25-in., and downstream 10 x 1 = 10-in.
Note
The Rosemount 1195 Integral Orifice comes with the associated pipe
lengths (18D upstream and 8D downstream) when ordered with process
pipe-end connections.
Straight run requirements
Figure 2-1: Reducer
(2 d to d over a length of 1.5 d to 3 d)
Figure 2-2: Single 90° Bend Flow from One Branch
Figure 2-3: Two or More 90° Bends in Same Planes
(2)
(2)
For dimensions, see Table 2-1
4www.emerson.com
UD
UD
UD
April 2021Quick Start Guide
Figure 2-4: Two or More 90° Bends in Different Planes
Figure 2-5: Expander
(0.5 d to d over a length of d to 2 d)
Figure 2-6: Ball/Gate Valve Fully Open
Table 2-1: Straight Run Requirements (in Pipe Diameters)
(1)
β
Figure
2-1
upstream
(U)
Figure
2-2
upstream
(U)
Figure
2-3
upstream
(U)
Figure
2-4
upstream
(U)
Figure
2-5
upstream
(U)
Figure
2-6
upstream
(U)
Figures
2-1
through
2-6
On
downstream
(2)
(D)
0.20 20242530222210
0.40 20252731222210
0.50 20252833232310
0.60 20273137252510
0.70 23323542282810
0.75 25353845303010
(1) Interpolation of intermediate β values can be used.
(2) All straight lengths are expressed as multiples of the pipe inside diameter (d) and
shall be measured from the upstream face of orifice plate.
Quick Start Guide5
A
B
C
D
FLOW
A
C
B
D
Quick Start GuideApril 2021
3Primary element orientation
Figure 3-1: Rosemount 1195 Flowmeter Orientation with Traditional
Style Manifold
Gas (horizontal)Gas (vertical)
Liquid (horizontal)Liquid (vertical)
Steam (horizontal)Steam (vertical)
6www.emerson.com
A
C
B
FLOW
F
E
D
A
B
C
D
FLOW
April 2021Quick Start Guide
1. 90° recommended zone
2. Vertical plane
3. Horizontal plane
1. 360° recommended zone
2. Block valves
3. Vent valves
Figure 3-2: Rosemount 1195 Flowmeter Orientation with Flange by
Flange Manifold
Gas (horizontal)Gas (vertical)
Liquid (horizontal)Liquid (vertical)
Quick Start Guide7
A
B
C
D
A
B
C
FLOW
F
E
D
Quick Start GuideApril 2021
Gas (horizontal)Gas (vertical)
Steam (horizontal)Steam (vertical)
1. A. 120° recommended zone
2. B. Horizontal plane
3. C. Vertical plane
1. D. 360° recommended zone
2. E. Block valves
3. F. Vent valves
Note
For saturated steam that is not high quality, it is recommended to mount in
8www.emerson.com
a vertical line to avoid damming effect of the liquid.