Rosemount™ 8750W Magnetic Flowmeter Sensor
Quick Install Guide
May 2019
Quick Install Guide May 2019

1 Handling and Lifting Safety

To reduce the risk of personal injury or damage to equipment, follow all lifting and handling instructions.
Handle all parts carefully to prevent damage. Whenever possible,
transport the system to the installation site in the original shipping container.
PTFE-lined sensors are shipped with end covers that protect it from both
mechanical damage and normal unrestrained distortion. Remove the end covers just before installation.
Keep the shipping plugs in the conduit ports until you are ready to
connect and seal them. Appropriate care should be taken to prevent water ingress.
The sensor should be supported by the pipeline. Pipe supports are
recommended on both the inlet and outlet sides of the sensor pipeline. There should be no additional support attached to the sensor.
Use proper PPE (Personal Protection Equipment) including safety glasses
and steel toed shoes.
Do not lift the meter by holding the electronics housing or junction box.
The sensor liner is vulnerable to handling damage. Never place anything
through the sensor for the purpose of lifting or gaining leverage. Liner damage can render the sensor useless.
Do not drop the device from any height.
2 Rosemount™ 8750W Magnetic Flowmeter Sensor
May 2019 Quick Install Guide

1.1 Lifting lugs

If provided, use the lifting lugs on each flange to handle the Magnetic Flowmeter when it is transported and lowered into place at the installation site. If lifting lugs are not provided, the Magnetic Flowmeter must be supported with a lifting sling on each side of the housing.
Standard pressure 3-in. through 48-in. flanged magnetic flowmeters
come with lifting lugs.
Figure 1-1: Example lifting without and with lifting lugs
A. Without lifting lugs B. With lifting lugs
Quick Install Guide 3
Quick Install Guide May 2019

2 Introduction

This document provides basic installation guidelines for the Rosemount 8750W Magnetic Flowmeter sensor.
For transmitter installation instructions, refer to the appropriate
document:
Product model number Document number
8750WDMTxAxxx / 8750WDMRxAxxx 00825-01xx-4444
8750WDMTxFxxx / 8750WDMRxFxxx 00825-05xx-4444
8750WDMTxMxxx / 8750WDMRxMxxx 00825-04xx-4444
8750WDMWxAxxx 00825-01xx-4445
8750WDMWxFxxx 00825-05xx-4445
8750WDMWxMxxx 00825-04xx-4445
8750WDEWxAxxx 00825-01xx-4664
(1) "xx" in the second segment of the document number indicates the language.
See Table 2-1.
Table 2-1: Document language codes
(1)
Code Language
00 English
02 Italian
03 French
05 German
06 Chinese (Simplified)
07 Russian
09 Spanish
15 Korean
22 Portuguese (Brazillian)
For additional installation information, configuration, maintenance, and
troubleshooting, refer to the appropriate reference manual.
All user documentation can be found at www.emerson.com. For more contact information see Emerson Flow customer service.
4 Rosemount™ 8750W Magnetic Flowmeter Sensor
May 2019 Quick Install Guide

2.1 Return policy

Emerson procedures must be followed when returning equipment. These procedures ensure legal compliance with government transportation agencies and help provide a safe working environment for Emerson employees. Failure to follow Emerson procedures will result in your equipment being refused delivery.
Quick Install Guide 5
Quick Install Guide May 2019

2.2 Emerson Flow customer service

Email:
Worldwide: flow.support@emerson.com
Asia-Pacific: APflow.support@emerson.com
Telephone:
North and South America Europe and Middle East Asia Pacific
United States 800 522 6277 U.K. 0870 240
Canada +1 303 527
5200
Mexico +41 (0) 41
7686 111
Argentina +54 11 4837
7000
Brazil +55 15 3413
8000
Venezuela +58 26 1731
3446
The Netherlands
France 0800 917 901 India 800 440 1468
Germany 0800 182
Italy 8008 77334 China +86 21 2892
Central & Eastern
Russia/CIS +7 495 981
Egypt 0800 000
Oman 800 70101 Thailand 001 800 441
Qatar 431 0044 Malaysia 800 814 008
Kuwait 663 299 01
South Africa 800 991 390
Saudi Arabia 800 844 9564
UAE 800 0444
1978
+31 (0) 704 136 666
5347
+41 (0) 41 7686 111
9811
0015
0684
Australia 800 158 727
New Zealand 099 128 804
Pakistan 888 550 2682
9000
Japan +81 3 5769
6803
South Korea +82 2 3438
4600
Singapore +65 6 777
8211
6426
6 Rosemount™ 8750W Magnetic Flowmeter Sensor
May 2019 Quick Install Guide

3 Location and Position

3.1 Environmental considerations

To ensure maximum transmitter life, avoid extreme temperatures and excessive vibration. Typical problem areas include the following:
High-vibration lines with integrally mounted transmitters
Tropical/desert installations in direct sunlight
Outdoor installations in arctic climates
Remote mounted transmitters may be installed in the control room to protect the electronics from the harsh environment and to provide easy access for configuration or service.
Quick Install Guide 7
Quick Install Guide May 2019

3.2 Upstream and downstream piping

To ensure specified accuracy over widely varying process conditions, install the sensor with a minimum of five straight pipe diameters upstream and two pipe diameters downstream from the electrode plane.
Figure 3-1: Upstream and downstream straight pipe diameters
A. Five pipe diameters (upstream) B. Two pipe diameters (downstream) C. Flow direction
Installations with reduced upstream and downstream straight runs are possible. In reduced straight run installations, the meter may not meet accuracy specifications. Reported flow rates will still be highly repeatable.

3.3 Flow direction

The sensor should be mounted so that the arrow points in the direction of flow.