Rosemount Quick Start Guide: Magnetic Flowmeter System (Transmitter and Flowtube) with FOUNDATION fieldbus - 8742C, 8700 Series | Rosemount Manuals & Guides
8200 Market Boulevard
Chanhassen, MN USA
55317
T (US) (800) 999-9307
T (Intnl) (952) 906-8888
F (952) 949-7001
Rosemount 8742C/8700 Series
Emerson Process
Management
Groeneveldselaan 6-8
3903 AZ Veenendaal
The Netherlands
Tel 31 (0) 318 549 549
Fax 31 (0) 318 549 559
Tel 0800-966 180 (U.K. only)
Fax 0800-966 181 (U.K. only)
Emerson Process
Management Asia Pacific
Private Limited
1 Pandan Crescent
Singapore 128461
T (65) 6777 8211
F (65) 6777 0947/65 6777 0743
IMPORTANT NOTICE
This installation guide provides basic guidelines for the
Rosemount
configuration, diagnostics, maintenance, service, troubleshooting,
explosion-proof, flameproof, or intrinsically safe (I.S.) installations.
Refer to the 8742C reference manual (document number
00809-0100-4793) for more instructions. The manual and this QIG
are also available electronically on www.rosemount.com.
®
8742C. It does not provide instructions for detailed
WARNING
Failure to follow these installation guidelines could result in
death or serious injury:
Installation and servicing instructions are for use by qualified
personnel only. Do not perform any servicing other than that
contained in the operating instructions, unless qualified. Verify that
the operating environment of the flowtube and transmitter is
consistent with the appropriate FM, CSA, or CENELEC approval.
Do not connect a 8742C to a non-Rosemount flowtube that is
located in an explosive atmosphere.
FINAL
Quick Installation Guide
00825-0100-4793, Rev BA
July 2003
Rosemount 8742C/8700 Series
WARNING
The flowtube liner is vulnerable to handling damage. Never place
anything through the flowtube for the purpose of lifting or gaining
leverage. Liner damage can render the flowtube useless.
To avoid possible damage to the flowtube liner ends, do not use
metallic or spiral-wound gaskets. If frequent removal is anticipated,
take precautions to protect the liner ends. Short spool pieces
attached to the flowtube ends are often used for protection.
Correct flange bolt tightening is crucial for proper flowtube operation
and life. All bolts must be tightened in the proper sequence to the
specified torque limits. Failure to observe these instructions could
result in severe damage to the flowtube lining and possible flowtube
replacement.
STEP 1: PRE-INSTALLATION
Before installing the Rosemount 8742C Magnetic Flowmeter
Transmitter, there are several pre-installation steps that should be
completed to make the installation process easier. They include
identifying the options and configurations that apply to your
application, setting the hardware switches if necessary, and
consideration of physical requirements.
The mounting site for the Rosemount 8742C should provide enough
room for secure mounting, easy access to the conduit ports, and full
opening of the transmitter covers.
To ensure maximum transmitter life, avoid excessive heat and
vibration. Typical problem areas include high-vibration lines with
integrally mounted transmitters, warm-climate installations in direct
sunlight, and outdoor installations in cold climates. To avoid potential
problems, remotely mounted transmitters may be installed in the
control room. This protects the electronics from the harsh environment
and provides easy access for configuration or service.
FINAL
Quick Installation Guide
00825-0100-4793, Rev BA
July 2003
Hardware Switches
The Rosemount 8742C electronics board is equipped with two
user-selectable hardware switches. These switches set Simulate
Enable and Transmitter Security. The standard configurations for
these switches when shipped from the factory are as follows:
Simulate Enable: Off
Transmitter Security: Off
The switches are located on the outerboard of the electronics
transmitter stack.
Figure 1. Hardware Switches
Simulate
Enable
Transmitter
Security
Rosemount 8742C/8700 Series
FINAL
Changing Hardware Switch Settings
In most cases, it is not necessary to change the setting of the
hardware switches. If you need to change the switch settings,
complete the steps outlined in the manual.
Quick Installation Guide
00825-0100-4793, Rev BA
July 2003
Rotate Transmitter Housing
The electronics housing can be rotated on the flowtube in 90°
increments by loosening the four mounting bolts on the bottom of the
housing, rotating the housing, and reinstalling the bolts. When the
housing is returned to its original position, be sure the surface is clean
and there is no gap between the housing and the flowtube.
Rosemount 8742C/8700 Series
STEP 2: HANDLING
Handle all parts carefully to prevent damage. Whenever possible,
transport the system to the installation site in the original shipping
containers. Teflon
protect it from both mechanical damage and normal unrestrained
distortion. Remove the end covers just before installation.
Figure 2. Rosemount 8705 Flowtube Support for Handling
®
-lined flowtubes are shipped with end covers that
FINAL
½- through 4-Inch
Flowtubes
6-Inch and Larger
Flowtubes
8732-0281B02A, C02A
Quick Installation Guide
00825-0100-4793, Rev BA
July 2003
Rosemount 8742C/8700 Series
STEP 3: MOUNTING
Upstream/Downstream Piping
To ensure specification accuracy over widely varying process
conditions, install the flowtube a minimum of five straight pipe
diameters upstream and two pipe diameters downstream from the
electrode plane (see Figure 3).
Figure 3. Upstream and Downstream Straight Pipe Diameters
5 Pipe Diameters
Flow
Flow Direction
The flowtube should be mounted so the FORWARD end of the flow
arrow, shown on the flowtube identification tag, points in the direction
of flow through the tube.
Flowtube Orientation
The flowtube should be installed in a position that ensures the
flowtube remains full during operation. Vertical installation allows
upward process fluid flow and keeps the cross-sectional area full,
regardless of flow rate. Horizontal installation should be restricted to
low piping sections that are normally full. In these cases, orient the
electrode plane to within 45 degrees of horizontal.
FINAL
2 Pipe Diameters
8732-0281G02A
Quick Installation Guide
00825-0100-4793, Rev BA
July 2003
Figure 4. Flowtube Orientation
A
Rosemount 8742C/8700 Series
FLOW
FLOW
The electrodes in the Rosemount 8705 flowtube are properly
orientated when the two measurement electrodes are in the 3 and 9
o’clock positions, as shown on the right of Figure 4.
The electrodes in the Rosemount 8711 are properly orientated when
the top of the flowtube is either vertical or horizontal, as shown in
Figure 5. Avoid any mounting orientation that positions the top of the
flowtube at 45° from the vertical or horizontal position.
Figure 5. Rosemount 8711 Mounting Position
45° Electrode Plane
FINAL
45° Electrode Plane
8732-0005A01A, 8732-0005A01C
8711-8711-E01A, 8711-8711-F01A
Quick Installation Guide
00825-0100-4793, Rev BA
July 2003
Rosemount 8742C/8700 Series
STEP 4: INSTALLATION (FLANGED FLOWTUBE)
Gaskets
The flowtube requires a gasket at each of its connections to adjacent
devices or piping. The gasket material selected must be compatible with the
process fluid and operating conditions. Metallic or spiral-wound gaskets
can damage the liner. Gaskets are required on each side of the
grounding ring. All other applications (including flowtubes with lining
protectors or a grounding electrode) require only one gasket on each
end connection.
Flange Bolts
Suggested torque values by flowtube line size and liner type are listed
in Table 1 for ASME B16.5 (ANSI) and Table 2 for DIN flanges.
Consult the factory if the flange rating of the flowtube is not listed.
Tighten flange bolts on the upstream side of the flowtube in the
incremental sequence shown in Figure 6 to 20% of the suggested
torque values. Repeat the process on the downstream side of the
flowtube. For flowtubes with more or less flange bolts, tighten the bolts
in a similar crosswise sequence. Repeat this entire tightening
sequence at 40%, 60%, 80%, and 100% of the suggested torque
values or until the leak between the process and flowtube flanges
stop.
If leakage has not stopped at the suggested torque values, the bolts
can be tightened in additional 10% increments until the joint stops
leaking, or until the measured torque value reaches the maximum
torque value of the bolts. Practical consideration for the integrity of the
liner often leads the user to distinct torque values to stop leakage due
to the unique combinations of flanges, bolts, gaskets, and flowtube
liner material.
Check for leaks at the flanges after tightening the bolts. Failure to use
the correct tightening methods can result in severe damage.
Flowtubes require a second tightening 24 hours after the initial
installation. Over time, flowtube liner materials may deform under
FINAL
Quick Installation Guide
00825-0100-4793, Rev BA
July 2003
pressure.
Figure 6. Flange Bolt Torquing Sequence
Table 1. Suggested Flange Bolt Torque Values for
Rosemount 8705 and 8707 High-Signal Flowtubes
Size
Code
005
0101 inch (25 mm)812-015 1
0202 inch (50 mm)19171411
0303 inch (80 mm)34352323
040 4 inch (100 mm)26501732
0606 inch (150mm)45503037
080 8 inch (200 mm)60824255
100 10 inch (250 mm)55804070
120 12 inch (300 mm)6512555105
140 14 inch (350 mm)851107095
160 16 inch (400 mm)8516065140
180 18 inch (450 mm)12017095150
200 20 inch (500 mm)11 017590150
240 24 inch (600 mm)165280140250
300 30 inch (750 mm)195415165375
360 36 inch (900 mm)280575245525
Line Size
1
/2-inch (15 mm)88--
1
/2 inch (40 mm)1325718
Rosemount 8742C/8700 Series
8-bolt
Polyurethane/Neoprene/
Teflon/Tefzel/PFA liners
Class 150
(pound-feet)
Class 300
(pound-feet)
Linatex liner
Class 150
(pound-feet)
(pound-feet)
FINAL
Class 300
8742f_01a.eps
Quick Installation Guide
00825-0100-4793, Rev BA
July 2003
Rosemount 8742C/8700 Series
Table 2. Flange Bolt Torque and Bolt Load Specifications for 8705
Teflon/Tefzel liner
(Newton-
meter)
104400104400
20101002010100
50161005016100
60201006020100
50168005016800
50178007019600
902470013028700
(Newton)
(Newton-
meter)
(Newton)
(Newton-
meter)
Size
Code
Line Size
005 0.5-inch
(15 mm)
0101 inch
(25 mm)
015 1.5 inch
(40 mm)
0202 inch
(50 mm)
0303 inch
(80 mm)
0404 inch
(100 mm)
0606 inch
(150mm)
0808 inch
(200 mm)
100 10 inch
(250 mm)
120 12 inch
(300 mm)
140 14 inch
(350 mm)
160 16 inch
(400 mm)
180 18 inch
(450 mm)
200 20 inch
(500 mm)
240 24 inch
(600 mm)
PN10PN 16PN 25PN 40
(Newton-
meter)
(Newton)
1303520090197001302920017034400
10028000130283001903800025044800
12032000170384001903860027047700
16043800220495003205720041068100
22050600280562004106810061092900
19043200340684003305510042064000
23051100380689004407330052073900
290586005709360059090100850112000
FINAL
(Newton)
Quick Installation Guide
00825-0100-4793, Rev BA
July 2003
Rosemount 8742C/8700 Series
Polyurethane, Linatex, and Neoprene Liners
(Newton-
meter)
(Newton)
(Newton)
207040207040
30107003010700
40134004013400
30111 003011100
40117005013200
60164009019200
(Newton-
meter)
(Newton)
(Newton-
meter)
(Newton)
Size
Code
Line Size
0101 inch
(25 mm)
015 1.5 inch
(40 mm)
0202 inch
(50 mm)
0303 inch
(80 mm)
0404 inch
(100 mm)
0606 inch
(150mm)
0808 inch
(200 mm)
100 10 inch
(250 mm)
120 12 inch
(300 mm)
140 14 inch
(350 mm)
160 16 inch
(400 mm)
180 18 inch
(450 mm)
200 20 inch
(500 mm)
240 24 inch
(600 mm)
PN 10PN 16PN 25PN 40
(Newton-
meter)
90234006013100901940011022800
7018600801880 01302540017029900
80213001102550013025800180319 00
11029100150330002103820028045400
15033700190374002804540041062000
13028700230456002203680028042700
15034100260459003004880035049400
20039200380624003906010056074400
FINAL
STEP 4: INSTALLATION (WAFER FLOWTUBE)
Gaskets
The flowtube requires a gasket at each of its connections to adjacent
devices or piping. The gasket material selected must be compatible with the
process fluid and operating conditions. Metallic or spiral-wound gaskets
can damage the liner. Gaskets are required on each side of the
grounding ring. All other applications (including flowtubes with lining
protectors or a grounding electrode) require only one gasket on each
end connection.
Loading...
+ 25 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.