Rosemount Quick Start Guide: Magnetic Flowmeter System (Transmitter and Flowtube) with FOUNDATION fieldbus - 8742C, 8700 Series | Rosemount Manuals & Guides

Quick Installation Guide
Product DiscontinuedProduct Discontinued
00825-0100-4793, Rev BA July 2003
Rosemount 8742C/8700 Series
OUNDATION
fieldbus
Start
Step 1: Pre-Installation
Step 2: Handling
Step 3: Mounting
Step 4: Installation (Flanged Flowtubes)
Step 4: Installation (Wafer Flowtubes)
Step 4: Installation (Sanitary Flowtubes)
Step 5: Grounding
Step 6: Wiring
Step 7: Basic Configuration
Step 8: Process Leak Protection (Optional)
Step 9: Power up the Transmitter
FINAL
Step 10: Check Process Connections
Step 11: Confirm Configuration
End
¢00825-0100-4793r¤
www.rosemount.com
Quick Installation Guide
00825-0100-4793, Rev BA July 2003
© 2003 Rosemount Inc. All rights reserved. All marks property of owner.
Rosemount Inc.
8200 Market Boulevard Chanhassen, MN USA 55317 T (US) (800) 999-9307 T (Intnl) (952) 906-8888 F (952) 949-7001
Rosemount 8742C/8700 Series
Emerson Process Management
Groeneveldselaan 6-8 3903 AZ Veenendaal The Netherlands Tel 31 (0) 318 549 549 Fax 31 (0) 318 549 559 Tel 0800-966 180 (U.K. only) Fax 0800-966 181 (U.K. only)
Emerson Process Management Asia Pacific Private Limited
1 Pandan Crescent Singapore 128461 T (65) 6777 8211 F (65) 6777 0947/65 6777 0743
IMPORTANT NOTICE
This installation guide provides basic guidelines for the Rosemount configuration, diagnostics, maintenance, service, troubleshooting, explosion-proof, flameproof, or intrinsically safe (I.S.) installations. Refer to the 8742C reference manual (document number 00809-0100-4793) for more instructions. The manual and this QIG are also available electronically on www.rosemount.com.
®
8742C. It does not provide instructions for detailed
WARNING
Failure to follow these installation guidelines could result in death or serious injury:
Installation and servicing instructions are for use by qualified personnel only. Do not perform any servicing other than that contained in the operating instructions, unless qualified. Verify that the operating environment of the flowtube and transmitter is consistent with the appropriate FM, CSA, or CENELEC approval.
Do not connect a 8742C to a non-Rosemount flowtube that is located in an explosive atmosphere.
FINAL
Quick Installation Guide
00825-0100-4793, Rev BA July 2003
Rosemount 8742C/8700 Series
WARNING
The flowtube liner is vulnerable to handling damage. Never place anything through the flowtube for the purpose of lifting or gaining leverage. Liner damage can render the flowtube useless.
To avoid possible damage to the flowtube liner ends, do not use metallic or spiral-wound gaskets. If frequent removal is anticipated, take precautions to protect the liner ends. Short spool pieces attached to the flowtube ends are often used for protection.
Correct flange bolt tightening is crucial for proper flowtube operation and life. All bolts must be tightened in the proper sequence to the specified torque limits. Failure to observe these instructions could result in severe damage to the flowtube lining and possible flowtube replacement.
STEP 1: PRE-INSTALLATION
Before installing the Rosemount 8742C Magnetic Flowmeter Transmitter, there are several pre-installation steps that should be completed to make the installation process easier. They include identifying the options and configurations that apply to your application, setting the hardware switches if necessary, and consideration of physical requirements.
The mounting site for the Rosemount 8742C should provide enough room for secure mounting, easy access to the conduit ports, and full opening of the transmitter covers.
To ensure maximum transmitter life, avoid excessive heat and vibration. Typical problem areas include high-vibration lines with integrally mounted transmitters, warm-climate installations in direct sunlight, and outdoor installations in cold climates. To avoid potential problems, remotely mounted transmitters may be installed in the control room. This protects the electronics from the harsh environment and provides easy access for configuration or service.
FINAL
Quick Installation Guide
00825-0100-4793, Rev BA July 2003
Hardware Switches
The Rosemount 8742C electronics board is equipped with two user-selectable hardware switches. These switches set Simulate Enable and Transmitter Security. The standard configurations for these switches when shipped from the factory are as follows:
Simulate Enable: Off
Transmitter Security: Off
The switches are located on the outerboard of the electronics transmitter stack.
Figure 1. Hardware Switches
Simulate Enable
Transmitter Security
Rosemount 8742C/8700 Series
FINAL
Changing Hardware Switch Settings
In most cases, it is not necessary to change the setting of the hardware switches. If you need to change the switch settings, complete the steps outlined in the manual.
Quick Installation Guide
00825-0100-4793, Rev BA July 2003
Rotate Transmitter Housing
The electronics housing can be rotated on the flowtube in 90° increments by loosening the four mounting bolts on the bottom of the housing, rotating the housing, and reinstalling the bolts. When the housing is returned to its original position, be sure the surface is clean and there is no gap between the housing and the flowtube.
Rosemount 8742C/8700 Series
STEP 2: HANDLING
Handle all parts carefully to prevent damage. Whenever possible, transport the system to the installation site in the original shipping containers. Teflon protect it from both mechanical damage and normal unrestrained distortion. Remove the end covers just before installation.
Figure 2. Rosemount 8705 Flowtube Support for Handling
®
-lined flowtubes are shipped with end covers that
FINAL
½- through 4-Inch
Flowtubes
6-Inch and Larger
Flowtubes
8732-0281B02A, C02A
Quick Installation Guide
00825-0100-4793, Rev BA July 2003
Rosemount 8742C/8700 Series
STEP 3: MOUNTING
Upstream/Downstream Piping
To ensure specification accuracy over widely varying process conditions, install the flowtube a minimum of five straight pipe diameters upstream and two pipe diameters downstream from the electrode plane (see Figure 3).
Figure 3. Upstream and Downstream Straight Pipe Diameters
5 Pipe Diameters
Flow
Flow Direction
The flowtube should be mounted so the FORWARD end of the flow arrow, shown on the flowtube identification tag, points in the direction of flow through the tube.
Flowtube Orientation
The flowtube should be installed in a position that ensures the flowtube remains full during operation. Vertical installation allows upward process fluid flow and keeps the cross-sectional area full, regardless of flow rate. Horizontal installation should be restricted to low piping sections that are normally full. In these cases, orient the electrode plane to within 45 degrees of horizontal.
FINAL
2 Pipe Diameters
8732-0281G02A
Quick Installation Guide
00825-0100-4793, Rev BA July 2003
Figure 4. Flowtube Orientation
A
Rosemount 8742C/8700 Series
FLOW
FLOW
The electrodes in the Rosemount 8705 flowtube are properly orientated when the two measurement electrodes are in the 3 and 9 o’clock positions, as shown on the right of Figure 4.
The electrodes in the Rosemount 8711 are properly orientated when the top of the flowtube is either vertical or horizontal, as shown in Figure 5. Avoid any mounting orientation that positions the top of the flowtube at 45° from the vertical or horizontal position.
Figure 5. Rosemount 8711 Mounting Position
45° Electrode Plane
FINAL
45° Electrode Plane
8732-0005A01A, 8732-0005A01C
8711-8711-E01A, 8711-8711-F01A
Quick Installation Guide
00825-0100-4793, Rev BA July 2003
Rosemount 8742C/8700 Series
STEP 4: INSTALLATION (FLANGED FLOWTUBE)
Gaskets
The flowtube requires a gasket at each of its connections to adjacent devices or piping. The gasket material selected must be compatible with the process fluid and operating conditions. Metallic or spiral-wound gaskets can damage the liner. Gaskets are required on each side of the grounding ring. All other applications (including flowtubes with lining protectors or a grounding electrode) require only one gasket on each end connection.
Flange Bolts
Suggested torque values by flowtube line size and liner type are listed in Table 1 for ASME B16.5 (ANSI) and Table 2 for DIN flanges. Consult the factory if the flange rating of the flowtube is not listed. Tighten flange bolts on the upstream side of the flowtube in the incremental sequence shown in Figure 6 to 20% of the suggested torque values. Repeat the process on the downstream side of the flowtube. For flowtubes with more or less flange bolts, tighten the bolts in a similar crosswise sequence. Repeat this entire tightening sequence at 40%, 60%, 80%, and 100% of the suggested torque values or until the leak between the process and flowtube flanges stop.
If leakage has not stopped at the suggested torque values, the bolts can be tightened in additional 10% increments until the joint stops leaking, or until the measured torque value reaches the maximum torque value of the bolts. Practical consideration for the integrity of the liner often leads the user to distinct torque values to stop leakage due to the unique combinations of flanges, bolts, gaskets, and flowtube liner material.
Check for leaks at the flanges after tightening the bolts. Failure to use the correct tightening methods can result in severe damage. Flowtubes require a second tightening 24 hours after the initial installation. Over time, flowtube liner materials may deform under
FINAL
Quick Installation Guide
00825-0100-4793, Rev BA July 2003
pressure.
Figure 6. Flange Bolt Torquing Sequence
Table 1. Suggested Flange Bolt Torque Values for Rosemount 8705 and 8707 High-Signal Flowtubes
Size
Code
005 010 1 inch (25 mm) 8 12 - ­015 1 020 2 inch (50 mm) 19 17 14 11 030 3 inch (80 mm) 34 35 23 23 040 4 inch (100 mm) 26 50 17 32 060 6 inch (150mm) 45 50 30 37 080 8 inch (200 mm) 60 82 42 55 100 10 inch (250 mm) 55 80 40 70 120 12 inch (300 mm) 65 125 55 105 140 14 inch (350 mm) 85 110 70 95 160 16 inch (400 mm) 85 160 65 140 180 18 inch (450 mm) 120 170 95 150 200 20 inch (500 mm) 11 0 175 90 150 240 24 inch (600 mm) 165 280 140 250 300 30 inch (750 mm) 195 415 165 375 360 36 inch (900 mm) 280 575 245 525
Line Size
1
/2-inch (15 mm) 8 8 - -
1
/2 inch (40 mm) 13 25 7 18
Rosemount 8742C/8700 Series
8-bolt
Polyurethane/Neoprene/
Teflon/Tefzel/PFA liners
Class 150
(pound-feet)
Class 300
(pound-feet)
Linatex liner
Class 150
(pound-feet)
(pound-feet)
FINAL
Class 300
8742f_01a.eps
Quick Installation Guide
00825-0100-4793, Rev BA July 2003
Rosemount 8742C/8700 Series
Table 2. Flange Bolt Torque and Bolt Load Specifications for 8705
Teflon/Tefzel liner
(Newton-
meter)
10 4400 10 4400
20 10100 20 10100
50 16100 50 16100
60 20100 60 20100
50 16800 50 16800
50 17800 70 19600
90 24700 130 28700
(Newton)
(Newton-
meter)
(Newton)
(Newton-
meter)
Size
Code
Line Size
005 0.5-inch
(15 mm)
010 1 inch
(25 mm)
015 1.5 inch
(40 mm)
020 2 inch
(50 mm)
030 3 inch
(80 mm)
040 4 inch
(100 mm)
060 6 inch
(150mm)
080 8 inch
(200 mm)
100 10 inch
(250 mm)
120 12 inch
(300 mm)
140 14 inch
(350 mm)
160 16 inch
(400 mm)
180 18 inch
(450 mm)
200 20 inch
(500 mm)
240 24 inch
(600 mm)
PN10 PN 16 PN 25 PN 40
(Newton-
meter)
(Newton)
130 35200 90 19700 130 29200 170 34400
100 28000 130 28300 190 38000 250 44800
120 32000 170 38400 190 38600 270 47700
160 43800 220 49500 320 57200 410 68100
220 50600 280 56200 410 68100 610 92900
190 43200 340 68400 330 55100 420 64000
230 51100 380 68900 440 73300 520 73900
290 58600 570 93600 590 90100 850 112000
FINAL
(Newton)
Quick Installation Guide
00825-0100-4793, Rev BA July 2003
Rosemount 8742C/8700 Series
Polyurethane, Linatex, and Neoprene Liners
(Newton-
meter)
(Newton)
(Newton)
20 7040 20 7040
30 10700 30 10700
40 13400 40 13400
30 111 00 30 11100
40 11700 50 13200
60 16400 90 19200
(Newton-
meter)
(Newton)
(Newton-
meter)
(Newton)
Size
Code
Line Size
010 1 inch
(25 mm)
015 1.5 inch
(40 mm)
020 2 inch
(50 mm)
030 3 inch
(80 mm)
040 4 inch
(100 mm)
060 6 inch
(150mm)
080 8 inch
(200 mm)
100 10 inch
(250 mm)
120 12 inch
(300 mm)
140 14 inch
(350 mm)
160 16 inch
(400 mm)
180 18 inch
(450 mm)
200 20 inch
(500 mm)
240 24 inch
(600 mm)
PN 10 PN 16 PN 25 PN 40
(Newton-
meter)
90 23400 60 13100 90 19400 110 22800
70 18600 80 1880 0 130 25400 170 29900
80 21300 110 25500 130 25800 180 319 00
110 29100 150 33000 210 38200 280 45400
150 33700 190 37400 280 45400 410 62000
130 28700 230 45600 220 36800 280 42700
150 34100 260 45900 300 48800 350 49400
200 39200 380 62400 390 60100 560 74400
FINAL
STEP 4: INSTALLATION (WAFER FLOWTUBE)
Gaskets
The flowtube requires a gasket at each of its connections to adjacent devices or piping. The gasket material selected must be compatible with the process fluid and operating conditions. Metallic or spiral-wound gaskets can damage the liner. Gaskets are required on each side of the grounding ring. All other applications (including flowtubes with lining protectors or a grounding electrode) require only one gasket on each end connection.
Loading...
+ 25 hidden pages