Rosemount Quick Start Guide: Magnetic Flow Meter System for Utility, Water, and Wastewater Applications - Model 8750WB | Rosemount Manuals & Guides

Quick Start Guide
00825-0200-4750, Rev AA
February 2014
Rosemount 8750WB Magnetic Flowmeter System
for Utility, Water, and Wastewater Applications
Quick Start Guide
February 2014
This document provides basic installation guidelines for the Rosemount® 8750W Magnetic Flowmeter System. For comprehensive instructions, for detailed configuration, diagnostics, maintenance, service, installation or troubleshooting, refer to the Rosemount 8750W reference manual (document number 00809-0100-4750 Rev. BA). The manual and this QSG are also available electronically on www.rosemount.com.
Failure to follow these installation guidelines could result in death or serious injury:
Installation and servicing instructions are for use by qualified personnel only. Do not perform
any servicing other than that contained in the operating instructions, unless qualified.
Verify that the operating environment of the sensor and transmitter is consistent with the
operating environment.
Do not connect a Rosemount transmitter to a non-Rosemount sensor that is located in an
explosive atmosphere.
The sensor liner is vulnerable to handling damage. Never place anything through the sensor
for the purpose of lifting or gaining leverage. Liner damage may render the sensor inoperable.
Metallic or spiral-wound gaskets should not be used as they will damage the liner face of the
sensor.
If frequent removal is anticipated, take precautions to protect the liner ends. Short spool
pieces attached to the sensor ends are often used for protection.
Rosemount Magnetic Flowmeters ordered with non-standard paint options may be subject to
electrostatic discharge. To avoid electrostatic charge build-up, do not rub the flowmeter with a dry cloth or clean with solvents.
Correct flange bolt tightening is crucial for proper sensor operation and life. All bolts must be
tightened in the proper sequence to the specified torque specifications. Failure to observe these instructions could result in severe damage to the sensor lining and possible sensor replacement.
Contents
Pre-installation . . . . . . . . . . . . . . page 3
Handling . . . . . . . . . . . . . . . . . . . page 7
Mounting . . . . . . . . . . . . . . . . . .page 8
Installation . . . . . . . . . . . . . . . . page 10
Grounding . . . . . . . . . . . . . . . .page 15
Wiring . . . . . . . . . . . . . . . . . . . . page 17
Basic configuration . . . . . . . . .page 28
2
February 2014
Quick Start Guide

Step 1: Pre-installation

Before installing the Rosemount 8750W Flowmeter, there are several pre-installation steps that should be completed to make the installation process easier:
Identify the options and configurations that apply to your application Set the hardware switches if necessary Consider mechanical, electrical, and environmental requirements

Mechanical considerations

The mounting site for the Rosemount 8750W transmitter should provide enough room for secure mounting, easy access to conduit ports, full opening of the transmitter covers, and easy readability of the LOI screen (see
Figure 2).
If the Rosemount 8750W transmitter is mounted separately from the sensor, it may not be subject to the same limitations that apply to the sensor.

Figure 1. Field mount transmitter dimensional drawing

7.49 (190)
6.48 (165)
LOI Cover
Figure 1 and
1
/2”-14 NPT (3 places)*
1
/2”-14 NPT (2 places)*
5.82
(148)
8.81
(224)
4.97
(126)
3.00 (76)
3.07 (78)
4.97
(126)
*Non- standard conduit entry thread. M20 connections are available with the use of threaded
conduit adapters.
3
Quick Start Guide

Figure 2. Wall mount transmitter dimensional drawing

WITH STANDARD COVER
February 2014
4.31
(109)
2.96 (75)
9.01
(229)
2.81 (71)
WITH LOI COVER
3.11 (79)
11.15 (283)
0.44 (11)
12.02 (305)
4
Ground Lug
NOTE
Dimensions are in inches (millimeters)
1
/2–14 NPT
Conduit
Connection
(4 Places)
LOI Keypad
Cover
February 2014
Quick Start Guide

Environmental considerations

To ensure maximum transmitter life, avoid extreme temperature and excessive vibration. Typical problem areas:
high-vibration lines with integrally mounted transmitters warm-climate installations in direct sunlight outdoor installations in cold climates.
Remote-mounted transmitters may be installed in the control room to protect the electronics from the harsh environment and provide easy access for configuration or service.
Both remotely and integrally mounted Rosemount 8750W transmitters require external power so there must be access to a suitable power source.
Installation procedures
Rosemount 8750W installation includes both detailed mechanical and electrical installation procedures.

Mount the transmitter

At a remote site the transmitter may be mounted on a pipe up to two inches in diameter or against a flat surface.

Pipe mounting

To mount the transmitter on a pipe:
1. Attach the mounting bracket to the pipe using the mounting hardware.
2. Attach the Rosemount 8750W transmitter to the mounting bracket using the mounting screws.

Identify options and configurations

The standard application of the 8750W includes a 4–20 mA output and control of the sensor coils and electrodes. Other applications may require one or more of the following configurations or options:
HART Multidrop Configuration Discrete Output Discrete Input Pulse Output
Be sure to identify any additional options and configurations that apply to the installation. Keep a list of these options nearby for consideration during the installation and configuration procedures.
5
Quick Start Guide

Hardware jumpers/switches

The 8750W electronics board is equipped with user-selectable hardware switches depending on the transmitter model ordered. These switches set the Failure Alarm Mode, Internal/External Analog Power, Internal/External Pulse Power and Transmitter Security. The standard configuration for these switches when shipped from the factory is as follows:
Failure Alarm Mode: HIGH
Internal/External Analog Power: INTERNAL
Internal/External Pulse Power: EXTERNAL (Field Mount only)
Transmitter Security: OFF

Changing hardware switch settings

In most cases, it will not be necessary to change the setting of the hardware switches. If the switch settings need to be changed, follow the steps outlined in the manual.
Use a non-metallic tool to move switch positions.

Electrical considerations

Before making any electrical connections to the Rosemount 8750W, consider national, local and plant electrical installation requirements. Be sure to have the proper power supply, conduit, and other accessories necessary to comply with these standards.
February 2014

Rotate transmitter housing

The Field Mount transmitter housing can be rotated on the sensor in 90° increments by removing the four mounting bolts on the bottom of the housing. Do not rotate the housing more than 180 ° in any one direction. Prior to tightening, be sure the mating surfaces are clean, the O-ring is seated in the groove, and there is no gap between the housing and the sensor.
6
February 2014
Quick Start Guide

Step 2: Handling

Handle all parts carefully to prevent damage. Whenever possible, transport the system to the installation site in the original shipping containers. Rosemount flow sensors are shipped with end covers that protect it from mechanical damage. For PTFE lined sensors the cover also prevents normal liner relaxation. Remove the end covers just before installation.

Figure 3. Rosemount 8750W flanged sensor support for handling

½- through 4-Inch Sensors
5-Inch and Larger Sensors
7
Quick Start Guide

Step 3: Mounting

Upstream/downstream piping

To ensure specification accuracy over widely varying process conditions, install the sensor a minimum of five straight pipe diameters upstream and two pipe diameters downstream from the electrode plane (see

Figure 4. Upstream and downstream straight pipe diameters

5 Pipe Diameters
Flow
Installations with reduced upstream and downstream straight runs are possible. In reduced straight run installations, absolute performance may shift. Reported flow rates will still be highly repeatable.
The sensor should be mounted so the FORWARD end of the flow arrow points in the direction of flow through the sensor (see
Figure 5).
Figure 4).
2 Pipe Diameters
February 2014

Figure 5. Flow direction

8
February 2014
The sensor should be installed in a location that ensures it remains full during operation. Vertical installation with upward process fluid flow keeps the cross-sectional area full, regardless of flow rate. Horizontal installation should be restricted to low piping sections that are normally full.

Figure 6. Sensor orientation

FLOW
FLOW
Quick Start Guide
Mounting position
The electrodes in the sensor are properly orientated when the two measurement electrodes are in the 3 and 9 o’clock position or within 45 ° from the vertical, as shown on the right of measurement electrodes are in the 6 and 12 o’clock position as shown on the left of
Figure 7.
Figure 7. Avoid any mounting orientation where the two

Figure 7. Sensor mounting position

Incorrect Correct
9
Quick Start Guide
February 2014

Step 4: Installation

Flanged sensors

Gaskets

The sensor requires a gasket at each of its connections to adjacent devices or piping. The gasket material selected must be compatible with the process fluid and operating conditions. Gaskets are required on each side of a grounding ring. All other applications (including sensors with lining protectors or a grounding electrode) require only one gasket on each end connection.
Metallic or spiral-wound gaskets should not be used as they will damage the liner face of the sensor. If spiral wound or metallic gaskets are required for the application, lining protectors must be used.

Figure 8. Flanged gasket placement

10
February 2014
Quick Start Guide

Flange bolts

Do not bolt one side at a time. Tighten each side simultaneously. Example:
1. Snug upstream
2. Snug downstream
3. Tighten upstream
4. Tighten downstream
Do not snug and tighten the upstream side and then snug and tighten the downstream side.
Failure to alternate between the upstream and downstream flanges when tightening bolts may result in liner damage. Suggested torque values by sensor line size and liner type are listed in
page 12. Consult the factory if the flange rating of the sensor is not listed.
Tighten flange bolts on the upstream side of the sensor in the incremental sequence shown in Repeat the process on the downstream side of the sensor. For sensors with more or less flange bolts, tighten the bolts in a similar crosswise sequence. Repeat this entire tightening sequence at 40%, 60%, 80%, and 100% of the suggested torque values or until the leak between the process and sensor flanges stop.
If leakage has not stopped at the suggested torque values, the bolts can be tightened in additional 10% increments until the joint stops leaking, or until the measured torque value reaches the maximum torque value of the bolts. Practical consideration for the integrity of the liner often leads the user to distinct torque values to stop leakage due to the unique combinations of flanges, bolts, gaskets, and sensor liner material.
Check for leaks at the flanges after tightening the bolts. Failure to use the correct tightening methods can result in severe damage. Sensors require a second tightening 24 hours after the initial installation. Over time, sensor liner materials may deform under pressure.
Figure 9 on page 11 to 20% of the suggested torque values.
Table 1 on

Figure 9. Flange bolt torquing sequence

For torque values not listed in Table 1, Table 2, or Table 3, contact technical support.
11
Quick Start Guide
Table 1. Suggested flange bolt torque values for ASME
PTFE liner Neoprene liner
Size code Line size
005 0.5 inch (15 mm) 8 8 - -
010 1 inch (25 mm) 8 12 - -
015 1.5 inch (40 mm) 13 25 7 18
020 2 inch (50 mm) 19 17 14 11
025 2.5 inch (65 mm) 22 24 17 16
030 3 inch (80 mm) 34 35 23 23
040 4 inch (100 mm) 26 50 17 32
050 5 inch (125 mm) 36 60 25 35
060 6 inch (150 mm) 45 50 30 37
080 8 inch (200 mm) 60 82 42 55
100 10 inch (250 mm) 55 80 40 70
120 12 inch (300 mm) 65 125 55 105
140 14 inch (350 mm) 85 110 70 95
160 16 inch (400 mm) 85 160 65 140
180 18 inch (450 mm) 120 170 95 150
200 20 inch (500 mm) 110 175 90 150
240 24 inch (600 mm) 165 280 140 250
300 30 inch (750 mm) 195 415 165 375
360 36 inch (900 mm) 280 575 245 525
Class 150
(pound-feet)
Class 300
(pound-feet)
Class 150
(pound-feet)
February 2014
Class 300
(pound-feet)
12
February 2014
Table 2. Suggested flange bolt torque values for EN1092-1
PTFE liner
Size
code
005
010
015
020
025
030
040
050
060
080
100
120
140
160
180
200
240
Line size
0.5-inch
(15 mm)
1 inch
(25 mm)
1.5 inch
(40 mm)
2 inch
(50 mm)
2.5 inch
(65 mm)
3 inch
(80 mm)
4 inch
(100 mm)
5.0 inch
(125 mm)
6 inch
(150mm)
8 inch
(200 mm)
10 inch
(250 mm)
12 inch
(300 mm)
14 inch
(350 mm)
16 inch
(400 mm)
18 inch
(450 mm)
20 inch
(500 mm)
24 inch
(600 mm)
PN10 PN 16 PN 25 PN 40
(Newton-meter) (Newton-meter) (Newton-meter) (Newton-meter)
50 70
70 100
90 130
130 90 130 170
100 130 190 250
120 170 190 270
160 220 320 410
220 280 410 610
190 340 330 420
230 380 440 520
290 570 590 850
Quick Start Guide
10
20
50
60
50
50
13
Quick Start Guide
February 2014
Table 2. (cont) Suggested flange bolt torque values for EN1092-1
Neoprene liner
Size
code
010
015
020
025
030
040
050
060
080
100
120
140
160
180
200
240
Line size
1 inch
(25 mm)
1.5 inch
(40 mm)
2 inch
(50 mm)
2.5 inch
(65 mm)
3 inch
(80 mm)
4 inch
(100 mm)
5.0 inch
(125 mm)
6 inch
(150 mm)
8 inch
(200 mm)
10 inch
(250 mm)
12 inch
(300 mm)
14 inch
(350 mm)
16 inch
(400 mm)
18 inch
(450 mm)
20 inch
(500 mm)
24 inch
(600 mm)
PN 10 PN 16 PN 25 PN 40
(Newton-meter) (Newton-meter) (Newton-meter) (Newton-meter)
40 50
50 70
60 90
90 60 90 110
70 80 130 170
80 110 130 180
110 150 210 280
150 190 280 410
130 230 220 280
150 260 300 350
200 380 390 560
20
30
40
35
30
Table 3. Flange bolt torque and load specifications for large line sizes
AWWA C207 (Ft-Lbs) EN1092-1 (N-m)
40-in. (1000 mm)
42-in. (1050 mm)
48-in. (1200 mm)
AS2129 (N-m) AS4087 (N-m)
40-in. (1000 mm)
48-in. (1200 mm)
Class D
Class E
Class D
Class E
Class D
Class E
Table D
Table E
Table D
Table E
757
757 PN10 413
839 PN16 478
839
872 PN10 622
872
614
652 PN21 515
786
839 PN21 840
40-in. (1000 mm)
48-in. (1200 mm)
40-in. (1000 mm)
48-in. (1200 mm)
14
PN6 208
PN6 375
PN16 612
PN16 785
Loading...
+ 30 hidden pages