Rosemount Quick Start Guide: 8732EM with Modbus Manuals & Guides

Quick Start Guide
00825-0400-4444, Rev AC
November 2017
Rosemount® 8732EM Transmitter with Modbus Protocol
Quick Start Guide

1 Safety

Failure to follow these installation guidelines could result in serious injury
or death.
Installation and servicing instructions are for use by qualified personnel
only. Do not perform any servicing other than that contained in the operating instructions, unless qualified.
Rosemount Magnetic Flowmeters ordered with non-standard paint
options or non-metallic labels may be subject to electrostatic discharge. To avoid electrostatic charge build-up, do not rub the flowmeter with a dry cloth or clean with solvents.
Verify that the operating environment of the sensor and transmitter is
consistent with the appropriate Agency Approval.
If installed in an explosive atmosphere, verify that the device certification
and installation techniques are suitable for that particular environment.
To prevent ignition of flammable or combustible atmosphere, disconnect
power before servicing circuits.
Explosion hazard—Do not disconnect equipment when a flammable or
combustible atmosphere is present.
Do not connect a Rosemount Transmitter to a non-Rosemount sensor
when installed in an “Ex” environment, explosive atmosphere, hazardous area, or classified area.
Follow national, local, and plant standards to properly earth ground the
transmitter and sensor. The earth ground must be separate from the process reference ground.
November 2017
CAUTION!
In cases where high voltage/high current are present near the meter
installation, ensure proper protection methods are followed to prevent stray voltage/current from passing through the meter. Failure to adequately protect the meter could result in damage to the transmitter and lead to meter failure.
Completely remove all electrical connections from both sensor and
transmitter prior to welding on the pipe. For maximum protection of the sensor, consider removing it from the pipeline.
2 Rosemount 8732EM Transmitter with Modbus Protocol
November 2017

2 Introduction

This document provides basic installation guidelines for the Rosemount 8732EM field-mount transmitter.
For sensor installation refer to the Rosemount® 8700 Magnetic Flowmeter
Sensor Quick Installation Guide
For additional installation information, configuration, maintenance, and
troubleshooting, refer to the Rosemount® 8732EM Transmitter with
Modbus Protocol Reference Manual
All user documentation can be found at www.emerson.com. For more contact information see Section 2.2.

2.1 Return policy

Emerson procedures must be followed when returning equipment. These procedures ensure legal compliance with government transportation agencies and help provide a safe working environment for Emerson employees. Failure to follow Emerson procedures will result in your equipment being refused delivery.
Quick Start Guide
Quick Start Guide 3
Quick Start Guide November 2017

2.2 Emerson Flow customer service

Email:
Worldwide: flow.support@emerson.com
Asia-Pacific: APflow.support@emerson.com
Telephone:
North and South America Europe and Middle East Asia Pacific
United States 800 522 6277 U.K. 0870 240 1978 Australia 800 158 727
Canada +1 303 527
Mexico +41 (0) 41 7686
Argentina +54 11 4837
Brazil +55 15 3413
Venezuela +58 26 1731
5200
111
7000
8000
3446
The Nether­lands
France 0800 917 901 India 800 440 1468
Germany 0800 182 5347 Pakistan 888 550 2682
Italy 8008 77334 China +86 21 2892
Central & East­ern
Russia/CIS +7 495 981
Egypt 0800 000 0015 Singapore +65 6 777 8211
Oman 800 70101 Thailand 001 800 441
Qatar 431 0044 Malaysia 800 814 008
Kuwait 663 299 01
South Africa 800 991 390
Saudi Arabia 800 844 9564
UAE 800 0444 0684
+31 (0) 704 136 666
+41 (0) 41 7686 111
9811
New Zealand 099 128 804
9000
Japan +81 3 5769
South Korea +82 2 3438
6803
4600
6426
4 Rosemount 8732EM Transmitter with Modbus Protocol
November 2017

3 Pre-installation

Before installing the transmitter, there are several pre-installation steps that should be completed to make the installation process easier:
Identify options and configurations that apply to your application
Set the hardware switches if necessary
Consider mechanical, electrical, and environmental requirements
Note
Refer to the product reference manual for more detailed requirements.
Identify options and configurations
The typical transmitter installation includes a device power connection, a Modbus RS-485 output connection, and sensor coil and electrode connections. Other applications may require one or more of the following configurations or options:
Pulse output
Discrete input/discrete output
Hardware switches
Quick Start Guide
The transmitter has two user-selectable hardware switches. These switches set the internal/external pulse power and transmitter security. The standard configuration for these switches when shipped from the factory is as follows:
Hardware switch default settingsTable 3-1:
Setting Factory configuration
Internal/external pulse power External
Transmitter security Off
The internal/external pulse power switch is not available when ordered with intrinsically safe output, ordering code B.
In most cases, it is not necessary to change the setting of the hardware switches. If the switch settings need to be changed, refer to the product reference manual.
Be sure to identify any additional options and configurations that apply to the installation. Keep a list of these options for consideration during the installation and configuration procedures.
Quick Start Guide 5
Quick Start Guide
Mechanical considerations
The mounting site for the transmitter should provide enough room for secure mounting, easy access to conduit entries, full opening of the transmitter covers, and easy readability of the Local Operator Interface (LOI) screen (if equipped).
Rosemount 8732EM dimensional drawingFigure 3-1:
10.5 [130]
5.0
[128]
1.94
[49,0]
3.00
[76,2]
7.49
[190,0]
6.48
[164,6]
A
3.07
[78,0]
8.81
[224,0]
B
November 2017
2.71
[76,2]
5.0
[128]
A
11.02
[280.0]
6.48
[164,6]
5.82
[148,0]
1.97
[50,0]
2.71 [68,8]
C
A. Conduit entry ½–14 NPT or M20 B. LOI cover C. Mounting screws
Electrical considerations
Before making any electrical connections to the transmitter, consider national, local, and plant electrical installation requirements. Be sure to have the proper power supply, conduit, and other accessories necessary to comply with these standards.
6 Rosemount 8732EM Transmitter with Modbus Protocol
November 2017
The transmitter requires external power. Ensure access to a suitable power source.
Rosemount 8732EM Flow Transmitter
Power input AC power:
Pulsed circuit Internally powered (Active): Outputs up to
Modbus output circuit Internally powered (Active): Outputs up to
Termination resisters Typically 120 ohms. Refer to the MODBUS over
Um 250V
Coil excitation output 500mA, 40V max, 9W max
Quick Start Guide
Electrical dataTable 3-2:
90–250VAC, 0.45A, 40VA
Standard DC power: 12–42VDC, 1.2A, 15W
Low power DC: 12–30VDC, 0.25A, 4W
12VDC, 12.1mA, 73mW Externally powered (Passive): Input up to
28VDC, 100mA, 1W
3.3VDC, 100mA, 100mW
Serial Line Specification & Implementation Guide (http://www.modbus.org) for more de­tails.
Environmental considerations
To ensure maximum transmitter life, avoid extreme temperatures and excessive vibration. Typical problem areas include the following:
High-vibration lines with integrally mounted transmitters
Tropical or desert installations in direct sunlight
Outdoor installations in arctic climates
Remote mounted transmitters may be installed in the control room to protect the electronics from the harsh environment and to provide easy access for configuration or service.
Quick Start Guide 7
Quick Start Guide

4 Mounting

Remote-mount transmitters are shipped wth a mounting bracket for use on a 2-in. pipe or a flat surface.
Procedure
1. Orient the transmitter on the mounting bracket.
2. Attach the mounting bracket to the instrument pole and securely tighten the fasteners.
A
November 2017
Mounting bracketFigure 4-1:
C
B
D
A. U-bolt B. Mounting bracket C. Transmitter D. Fasteners (example configuration)
3. To enable correct orientation, the LOI can be rotated in 90 degree increments up to 180 degrees. Do not rotate more than 180 degrees in any one direction.
8 Rosemount 8732EM Transmitter with Modbus Protocol
November 2017

5 Wiring

5.1 Conduit entries and connections

Transmitter conduit entry ports can be ordered with ½"-14NPT or M20 female threaded connections. Conduit connections should be made in accordance with national, local, and plant electrical codes. Unused conduit entries should be sealed with the appropriate certified plugs. The plastic shipping plugs do not provide ingress protection.

5.2 Conduit requirements

For installations with an intrinsically safe electrode circuit, a separate
conduit for the coil cable and the electrode cable may be required. Refer to the product reference manual.
For installations with non-intrinsically safe electrode circuit, or when
using the combination cable, a single dedicated conduit run for the coil drive and electrode cable between the sensor and the remote transmitter may be acceptable. Removal of the barriers for intrinsic safety isolation is permitted for non-intrinsically safe electrode installations.
Bundled cables from other equipment in a single conduit are likely to
create interference and noise in the system. See Figure 5-1.
Electrode cables should not be run together in the same cable tray with
power cables.
Output cables should not be run together with power cables.
Select conduit size appropriate to feed cables through to the flowmeter.
Quick Start Guide
Quick Start Guide 9
Quick Start Guide
A
B
B
November 2017
Best practice conduit preparationFigure 5-1:
E
E
C
D
E
A. Power B. Output C. Coil D. Electrode E. Safety ground
5.3
10 Rosemount 8732EM Transmitter with Modbus Protocol

Sensor to transmitter wiring

Integral mount transmitters
Integral mount transmitters ordered with a sensor will be shipped assembled and wired at the factory using an interconnecting cable. Use only the factory supplied cable provided with the instrument. For replacement transmitters use the existing interconnecting cable from the original assembly. Replacement cables, if applicable, are available (see Figure 5-2).
Loading...
+ 22 hidden pages