Rosemount™ 2051 Pressure Transmitter
and Rosemount 2051CF DP Flow Meter
with WirelessHART® Protocol
Quick Start GuideOctober 2019
Safety Messages
NOTICE
This guide provides basic guidelines for Rosemount 2051 Wireless Transmitters. It does not provide
instructions for configuration, diagnostics, maintenance, service, troubleshooting or Intrinsically Safe
(I.S.) installations. Refer to the Rosemount 2051 Wireless Reference Manual for more instruction. This
manual is also available electronically on Emerson.com/Rosemount.
Shipping considerations for wireless products:
The unit was shipped to you without the power module installed. Remove the power module prior to
shipping the unit.
Each power module contains one “D” size primary lithium-thionyl chloride battery. Primary lithium
batteries are regulated in transportation by the U.S. Department of Transportation, and are also
covered by IATA (International Air Transport Association), ICAO (International Civil Aviation
Organization), and ARD (European Ground Transportation of Dangerous Goods). It is the responsibility
of the shipper to ensure compliance with these or any other local requirements. Consult current
regulations and requirements before shipping.
WARNING
Explosions could result in death or serious injury.
Installation of this transmitter in an explosive environment must be in accordance with the appropriate
local, national, and international standards, codes, and practices. Review the approvals section of the
Rosemount Reference Manual for any restrictions associated with a safe installation.Before connecting
a handheld communicator in an explosive atmosphere, ensure that the instruments in the loop are
installed in accordance with intrinsically safe or non-incendive field wiring practices.
Process leaks could result in death or serious injury.
To avoid process leaks, only use the O-ring designed to seal with the corresponding flange adapter.
Electrical shock could cause death or serious injury.
Avoid contact with the leads and terminals. High voltage that may be present on leads can cause
electrical shock.
Physical access
Unauthorized personnel may potentially cause significant damage to and/or misconfiguration of end
users’ equipment. This could be intentional or unintentional and needs to be protected against.
Physical security is an important part of any security program and fundamental to protecting your
system. Restrict physical access by unauthorized personnel to protect end users’ assets. This is true for
all systems used within the facility.
The power module should not be installed on any wireless device until the
Emerson Wireless Gateway (Gateway) is installed and functioning properly.
This transmitter uses the green power module (order model number
701PGNKF). Wireless devices should also be powered up in order of
proximity from the Gateway, beginning with the closest. This will result in a
simpler and faster network installation. Enable active advertising on the
Gateway to ensure new devices join the network faster. For more
information, see the Emerson Wireless Gateway Reference Manual.
1.2Connecting the transmitter with a Field Communicator
In order for the Field Communicator to interface with the Rosemount 2051
Wireless, the power module must be connected. This transmitter uses the
green power module (order model number 701PGNKF). Figure 1-1 shows
how to connect the Field Communicator to the transmitter. Open the power
module compartment to hook up the leads.
Figure 1-1: Field Communicator Connections
Quick Start Guide5
Quick Start GuideOctober 2019
2Mount the transmitter
2.1Liquid applications
Procedure
1. Place taps to the side of the line.
2. Mount beside or below the taps.
3. Mount the transmitter so the drain/vent valves are oriented upward.
2.2Gas applications
Procedure
1. Place taps in the top or side of the line.
2. Mount beside or above the taps.
6Quick Start Guide
October 2019Quick Start Guide
2.3Steam applications
Procedure
1. Place taps to the side of the line.
2. Mount beside or below the taps.
3. Fill impulse lines with water.
Figure 2-1: Panel and Pipe Mounting
Panel mount
Coplanar flange
Traditional flange
Quick Start Guide7
(1)
Pipe mount
Quick Start GuideOctober 2019
Rosemount 2051T
2.4
(1) × 1 panel bolts are customer supplied.
Bolting considerations
If the transmitter installation requires assembly of the process flanges,
manifolds, or flange adapters, follow the assembly guidelines to ensure a
tight seal for optimal performance characteristics of the transmitters. Use
only bolts supplied with the transmitter or sold by Emerson as spare parts.
Figure 2-2 illustrates common transmitter assemblies with the bolt length
required for proper transmitter assembly.
8Quick Start Guide
A
4 × 1.75-in.
(44 mm)
D
4 × 1.75-in.
(44 mm)
4 × 2.25-in.
(57 mm)
C
4 × 1.75-in.
(44 mm)
4
× 1.50-in.
(38 mm)
B
4 × 2.88-in.
(73 mm)
October 2019Quick Start Guide
Figure 2-2: Common Transmitter Assemblies
A. Transmitter with coplanar flange
B. Transmitter with coplanar flange and optional flange adapters
C. Transmitter with traditional flange and optional flange adapters
D. Transmitter with coplanar flange and optional manifold and flange
adapters
Bolts are typically carbon steel (CS) or stainless steel (SST). Confirm the
material by viewing the markings on the head of the bolt and referencing
Table 2-1. If bolt material is not shown in Table 2-1, contact a local Emerson
representative for more information.
Carbon steel bolts do not require lubrication and the stainless steel bolts are
coated with a lubricant to ease installation. However, no additional lubricant
should be applied when installing either type of bolt.
Use the following bolt installation procedure:
Procedure
1. Finger tighten the bolts.
2. Torque the bolts to the initial torque value using a crossing pattern.
See Table 2-1 for initial torque value.
3. Torque the bolts to the final torque value using the same crossing
pattern. See Table 2-1 for final torque value.
4. Verify the flange bolts are protruding through the sensor module
Quick Start Guide9
bolt holes before applying pressure.
B7M
316
316
316
SW
316
STM
316
R
B8M
Quick Start GuideOctober 2019
Table 2-1: Torque Values for the Flange and Flange Adapter Bolts
Bolt materialHead markingsInitial
CS
SST
2.5O-rings
The two styles of Rosemount flange adapters (Rosemount 1151 and
Rosemount 3051/2051/2024/3095) each require a unique O-ring (see
Figure 2-3). Use only the O-ring designed for the corresponding flange
adapter.
WARNING
Failure to install proper flange adapter O-rings may cause process leaks,
which can result in death or serious injury. The two flange adapters are
distinguished by unique O-ring grooves. Only use the O-ring that is designed
for its specific flange adapter, as shown below. When compressed, PTFE Orings tend to cold flow, which aids in their sealing capabilities.
torque
Final torque
300 in-lb650 in-lb
150 in-lb300 in-lb
10Quick Start Guide
Loading...
+ 22 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.