Rosemount™ 2051 Pressure Transmitter
and Rosemount 2051CF Series Flow
Meter
with PROFIBUS® PA Protocol
Quick Start GuideMay 2021
Safety messages
This guide provides basic guidelines for the Rosemount 2051HT Transmitter. It does not provide
instructions for configuration, diagnostics, maintenance, service, troubleshooting, Explosion-proof,
Flameproof, or intrinsically safe (I.S.) installations.
CAUTION
The products described in this document are NOT designed for nuclear-qualified applications. Using
non-nuclear qualified products in applications that require nuclear-qualified hardware or products may
cause inaccurate readings. For information on Rosemount nuclear-qualified products, contact your
local Emerson Sales Representative.
WARNING
Explosions could result in death or serious injury.
Installation of this transmitter in an explosive environment must be in accordance with the appropriate
local, national, and international standards, codes, and practices. Review the approvals section of this
manual for any restrictions associated with a safe
• Before connecting a Field Communicator in an explosive atmosphere, ensure the instruments in
the loop are installed in accordance with intrinsically safe or non-incendive field wiring practices.
• In an explosion-proof/flameproof installation, do not remove the transmitter covers when power
is applied to the unit.
Process leaks may cause harm or result in death.
• Install and tighten process connectors before applying pressure.
• Do not attempt to loosen or remove flange bolts while the transmitter is in service.
Electrical shock can result in death or serious injury.
• Avoid contact with the leads and terminals. High voltage that may be present on leads can cause
electrical shock.
• Before connecting a handheld communicator in an explosive atmosphere, ensure the instruments
in the loop are installed in accordance with intrinsically safe or non-incendive field wiring
practices.
• In an Explosion-Proof/Flameproof installation, do not remove the transmitter covers when power
is applied to the unit.
Process leaks may cause harm or result in death.
• Install and tighten process connectors before applying pressure.
Physical access
• Unauthorized personnel may potentially cause significant damage to and/or misconfiguration of
end users’ equipment. This could be intentional or unintentional and needs to be protected
against.
• Physical security is an important part of any security program and fundamental to protecting your
system. Restrict physical access by unauthorized personnel to protect end users’ assets. This is
true for all systems used within the facility.
2 Rosemount 2051 Pressure Transmitter and Rosemount 2051CF Series Flow Meter Quick Start Guide
May 2021Quick Start Guide
WARNING
Replacement equipment or spare parts not approved by Emerson for use as spare parts could
reduce the pressure retaining capabilities of the transmitter and may render the instrument
dangerous.
• Use only bolts supplied or sold by Emerson as spare parts.
Improper assembly of manifolds to traditional flange can damage sensor module.
For safe assembly of manifold to traditional flange, bolts must break back plane of flange web (i.e., bolt
hole) but must not contact sensor module housing.
Physical access
• Unauthorized personnel may potentially cause significant damage to and/or misconfiguration of
end users’ equipment. This could be intentional or unintentional and needs to be protected
against.
• Physical security is an important part of any security program and fundamental to protecting your
system. Restrict physical access by unauthorized personnel to protect end users’ assets. This is
true for all systems used within the facility.
Contents
Mount the transmitter..................................................................................................................5
4 Rosemount 2051 Pressure Transmitter and Rosemount 2051CF Series Flow Meter Quick Start Guide
May 2021Quick Start Guide
1Mount the transmitter
1.1Liquid applications
Procedure
1. Place taps to the side of the line.
2. Mount beside or below the taps.
3. Mount the transmitter so the drain/vent valves are oriented upward.
1.2Gas applications
Procedure
1. Place taps in the top or side of the line.
2. Mount beside or above the taps.
Quick Start Guide5
Quick Start GuideMay 2021
1.3Steam applications
Procedure
1. Place taps to the side of the line.
2. Mount beside or below the taps.
3. Fill impulse lines with water.
6 Rosemount 2051 Pressure Transmitter and Rosemount 2051CF Series Flow Meter Quick Start Guide
May 2021Quick Start Guide
Figure 1-1: Panel and Pipe Mounting
Panel mount
Coplanar flange
Traditional flange
(1)
Pipe mount
Rosemount 2051T
(1) × 1 panel bolts are customer supplied.
Quick Start Guide7
A
4 × 1.75-in.
(44 mm)
D
4 × 1.75-in.
(44 mm)
4 × 2.25-in.
(57 mm)
C
4 × 1.75-in.
(44 mm)
4
× 1.50-in.
(38 mm)
B
4 × 2.88-in.
(73 mm)
Quick Start GuideMay 2021
1.4Bolting considerations
If the transmitter installation requires assembly of the process flanges,
manifolds, or flange adapters, follow the assembly guidelines to ensure a
tight seal for optimal performance characteristics of the transmitters. Use
only bolts supplied with the transmitter or sold by Emerson as spare parts.
Figure 1-2 illustrates common transmitter assemblies with the bolt length
required for proper transmitter assembly.
Figure 1-2: Common Transmitter Assemblies
A. Transmitter with coplanar flange
B. Transmitter with coplanar flange and optional flange adapters
C. Transmitter with traditional flange and optional flange adapters
D. Transmitter with coplanar flange and optional manifold and flange
adapters
Bolts are typically carbon steel (CS) or stainless steel (SST). Confirm the
material by viewing the markings on the head of the bolt and referencing
Table 1-1. If bolt material is not shown in Table 1-1, contact a local Emerson
representative for more information.
Carbon steel bolts do not require lubrication and the stainless steel bolts are
coated with a lubricant to ease installation. However, no additional lubricant
should be applied when installing either type of bolt.
Use the following bolt installation procedure:
Procedure
1. Tighten the bolts by hand.
2. Torque the bolts to the initial torque value using a crossing pattern.
8 Rosemount 2051 Pressure Transmitter and Rosemount 2051CF Series Flow Meter Quick Start Guide
See Table 1-1 for initial torque value.
B7M
316
316
316
SW
316
STM
316
R
B8M
May 2021Quick Start Guide
3. Torque the bolts to the final torque value using the same crossing
pattern. See Table 1-1 for final torque value.
4. Verify the flange bolts are protruding through the sensor module
bolt holes before applying pressure.
Table 1-1: Torque Values for the Flange and Flange Adapter Bolts
Bolt material Head markingsInitial torque Final torque
CS
SST
300 in-lb650 in-lb
150 in-lb300 in-lb
1.5O-rings
The two styles of Rosemount flange adapters (Rosemount
3051/2051/2024/3095) each require a unique O-ring (see Figure 1-3). Use
only the O-ring designed for the corresponding flange adapter.
WARNING
Failure to install proper flange adapter O-rings may cause process leaks,
which can result in death or serious injury. The two flange adapters are
distinguished by unique O-ring grooves. Only use the O-ring that is designed
for its specific flange adapter, as shown below. When compressed, PTFE Orings tend to cold flow, which aids in their sealing capabilities.
Quick Start Guide9
Quick Start GuideMay 2021
Figure 1-3: O-rings
A. Flange adapter
B. O-ring
C. PFTE based
D. Elastomer
Note
You should replace PTFE O-rings if you remove the flange adapter.
1.6Environmental seal for housing
Thread sealing (PTFE) tape or paste on male threads of conduit is required to
provide a water/dust tight conduit seal and meets requirements of NEMA
Type 4X, IP66, and IP68. Consult factory if other Ingress Protection ratings
are required.
For M20 threads, install conduit plugs to full thread engagement or until
mechanical resistance is met.
®
1.7
10 Rosemount 2051 Pressure Transmitter and Rosemount 2051CF Series Flow Meter Quick Start Guide
In-line gage transmitter orientation
The low side pressure port (atmospheric reference) on the in-line gage
transmitter is located in the neck of the transmitter, behind the housing. The
vent path is 360° around the transmitter between the housing and sensor.
(See Figure 1-4.)
Keep the vent path free of any obstruction, including but not limited to
paint, dust, and lubrication by mounting the transmitter so fluids can drain
away.
A
May 2021Quick Start Guide
Figure 1-4: In-line Gage Low Side Pressure Port
A. Pressure port location
Quick Start Guide11
A
Quick Start GuideMay 2021
2Housing rotation
To improve field access to wiring or to better view the optional LCD display
follow the procedure steps.
Figure 2-1: Housing Rotation
A. Housing rotation set screw (5/64-in.)
Procedure
1. Loosen the housing rotation set screw using a 5/64 -in. hex wrench.
2. Rotate the housing clockwise to the desired location.
3. If the desired location cannot be achieved due to thread limit, rotate
the housing counterclockwise to the desired location (up to 360°
from thread limit).
4. Retighten the housing rotation set screw to no more than 7 in-lbs
when desired location is reached.
12 Rosemount 2051 Pressure Transmitter and Rosemount 2051CF Series Flow Meter Quick Start Guide