Rosemount Perpetua Power Puck Solutions Quick Start Guide

00825-0100-4404, Rev AA
Perpetua® Power Puck® Solutions
Quick Start Guide
October 2015
Quick Start Guide
This guide provides basic guidelines for the Power Puck. It does not provide instructions for detailed configuration, diagnostics, maintenance, service, troubleshooting, or installation of wireless devices. Refer to the wireless device manuals and respective Quick Start Guides for more information.
Explosions could result in death or serious injury.
Installation of this Power Puck or intelligent power module (IPM) or both in an explosive environment must
be in accordance with the appropriate local, national, and international standards, codes, and practices. Review the Product Certifications section for any restric tions associated with a safe installation.
Before connecting a Field Communicator in an explosive atmosphere, ensure the instruments are installed
in accordance with intrinsically safe or non-incendive field wiring practices.
Electrical shock can result in death or serious injury.
Avoid contact with the leads and terminals. High voltage that may be present on leads can cause electrical
shock.
Power Pucks and IPMs may be replaced in hazardous areas. The IPM has surface resistivity greater than one
gigaohm and must be properly installed in the wireless device enclosure.
Care must be taken during transportation to and from the point of installation to prevent electrostatic
charge build-up.
The Power Puck is designed for use on warm or hot surfaces and will generate heat itself; a burn hazard may exist. Wear thermal gloves for protection during installation or when handling the Power Puck after installation.
Each IPM contains two “C” size primary lithium batteries. Primary lithium batteries are regulated in transportation by the U.S. Department of Transportation, and are also covered by IATA (International Air Transport Association), ICAO (International Civil Aviation Organization), and ARD (European Ground Transportation of Dangerous Goods). It is the responsibility of the shi pper to e nsure c omplian ce with these o r any othe r local requ irements. Cons ult current r egulations a nd requirements before ship ping.
Contents
What’s in the box? . . . . . . . . . . . . . . . . . . . page 3
Attach to heat source . . . . . . . . . . . . . . . . page 4
Connect to transmitter . . . . . . . . . . . . . . . page 6
2
Verify voltage and base temperature . . . page 7
Troubleshooting . . . . . . . . . . . . . . . . . . . . page 8
Product Certifications . . . . . . . . . . . . . . . page 10
October 2015
Quick Start Guide

What’s in the box?

Power Pucks for magnetic mount applications include four basic components.
Figure 1. Magnetic Mount Components
A. Power Puck B. Power cable C. IPM (interface to the transmitter) D. Cable gland
Power Pucks for pipe mount applications also include pipe adapters with sizes ranging from 1- to 12-in. nominal pipe size (NPS), and temperature-reducing heat extenders to accommodate higher pipe temperatures (see
Figure 2).
Figure 2. Pipe Mount Components
A. Pipe adapter (1- to 12-in. NPS pipe) B. High temperature heat extender (3- or 6-in.)
Note
The following equipment may be needed for installation:
Protective thermal gloves Wire stripper/cutter
3
/8- in. Allen wrench
Small, slotted screw driver
1
/2- and 9/16-in. wrench
Adjustable wrenchWire br ush or emery clothPTFE tape
3
Quick Start Guide

Step 1: Attach to heat source

Power Pucks are mounted in two primary configurations:
Magnetic mount Pipe mount
Magnetic mount Power Pucks
1. Attach the connector (4-pin M12) end of the cable to the Power Puck
Figure 3).
(see
2. Place the Power Puck on a flat metal surface that is less than 105 °C (220 °F) (Figure 3). A surface that is smooth, clean, and vertical, with the Power Puck mounted horizontally, provides the most efficient operation.
3. Proceed to
Figure 3. Connect Cable and Attach Power Puck to Flat Metal Surface
Connect to transmitter.
Pipe mount Power Pucks
Pipe mount Power Pucks include four configurations, based on the maximum variable temperature of the heat source (see Tab l e 1).
Table 1. Pipe Mount Configurations by Temperature Category
Heat source category
(maximum variable temperature)
-45 °C to 105 °C
(-50 °F to 220 °F)
106 °C to 175 °C
(221 °F to 350 °F)
176 °C to 290 °C
(351 °F to 550 °F)
-291 °C to 450 °C (551 °F to 845 °F)
1. If the pipe is insulated, remove approximately six inches of insulation where the Power Puck will be installed.
2. Using a wire brush, emery cloth, or compressed air, create a clean, smooth area on the pipe where the Power Puck will be mounted.
3. (if using 6-in. heat extender) With the included Allen wrench, loosen the set screw in the heat extender and configure the extender using
Ta bl e 2.
4
Pipe mount configuration
Pipe mount with adapter only
(no heat extender)
Pipe mount with 3-in. heat extender
(no extension, insulated)
Pipe mount with 6-in. heat extender
(extended, insulated)
Pipe mount with 6-in. heat extender
(extended, no insulation)
Figure 4 and
October 2015
4. Remove the U-bolts and combination hex/lock nuts from the pipe adapter. Place the Power Puck and adapter assembly on the pipe in a vertical position.
5. Reinstall the U-bolts and lightly tighten the hex/lock nuts.
6. Rotate the Power Puck and adapter assembly to a horizontal position and tighten the hex/lock nuts to about 10 foot-pounds.
7. Connect the M12 connector end of the cable to the Power Puck.
8. Reinsulate the pipe, adapter base, and heat extender.
Note
With heat sources above 290 °C, do not insulate the heat extender.
9. Proceed to Connect to transmitter.
Figure 4. 6-in. Heat Extender Base-to-Base Measurement
A. Base-to-base measurement
Quick Start Guide
Table 2. 6-in. Heat Extender Lengths for Temperature Ranges
Heat source range
(maximum variable temperature)
Celsius Farenheit Centimeters Inches
190 or less 375 or less Fully collaps ed Fully collapsed
191-210 376-410 18.4 7.25
211-230 411-445 20.3 8.00
231-250 446-480 22.9 9.00
251-270 481-520 24.8 9.75
271-290 521-550 26.7 10.50
Heat source range
(maximum variable temperature)
Celsius Farenheit Centimeters Inches
291-320 551-610 20.3 8.00
321-350 611-660 21.6 8.50
351-380 661-715 22.9 9.00
381-410 716-770 24.1 9.50
411-440 771-825 25.4 10.00
441-450 826-845 26.0 10.25
Base-to-base extension (insulated)
Base-to-base extension
(not insulated)
5
Quick Start Guide

Step 2: Connect to transmitter

1. Cut the flying lead end of the supplied cable to the desired length and trim
2. Remove the port screw and battery cover from the transmitter.
3. Wrap the cable gland with PTFE tape and thread into port screw opening;
1
/4 inch of insulation from the blue and brown leads.
about
lightly tighten the gland.
4. Feed the cable from the outside of the gland until the leads emerge inside the transmitter housing. Fold the black and white leads back on the cable and secure with electrical tape.
6
October 2015
5. With a small screwdriver, secure the blue and brown leads to the IPM (blue to positive [+] and brown to negative [0V]).
6. Install the IPM in the transmitter’s battery compartment, while pulling the cable through the gland to remove slack.
7. Tighten the cable gland and replace the battery cover.
Quick Start Guide

Step 3: Verify voltage and base temperature

It is important to verify the Power Puck’s voltage and base temperature is within specification and validate the Power Puck is operating correctly. There are two ways to verify operation and two ways to verify base temperature.
Note
Power Pucks will heat fully within 30 minutes of installation.
Validating voltage
Using the transmitter’s LCD display
The easiest way to validate Power Puck operation is to check the supply voltage on the transmitter LCD display. The LCD display indicates the value of several process variables, including supply voltage, shown as SUPLY VOLTS. Supply voltages at 6.8V or greater indicate the Power Puck is fully powering the transmitter.
Using the AMS® Device Manager
The supply voltage can also be monitored remotely with AMS Device Manager under Device Variables. Supply voltages at 6.8V or greater indicate the Power Puck is fully powering the transmitter.
7
Quick Start Guide
Verifying base temperature
Using reusable temperature strips (pipe mount only)
Pipe mounts include two reusable temperature strips. The base temperature is indicated by the point on the scale glowing bright green. Verify the base temperature is below 105 °C (220 °F). If the temperature exceeds this value, the Power Puck must be reconfigured with a heat extender or moved to a lower temperature.
Using IR sensor or thermocouple (magnetic and pipe mount)
The base temperature of either a pipe or magnetic mount Power Puck may be verified using an IR sensor or thermocouple probe. Always take the temperature reading in close proximity to the base of the Power Puck. Verify the base temperature is below 105 °C (220 °F). If the temperature exceeds this value, the Power Puck must be reconfigured with a heat extender or moved to a lower temperature.

Troubleshooting

Once the Power Puck is connected, the transmitter’s supply voltage should read
6.8 volts or greater, indicating the Power Puck is fully powering the transmitter. If
the supply voltage is below 6.8 volts, check the following:
Determine whether sufficient, consistent process heat is available for the
desired update rate (reference power source lifetime tables in Power Puck
Solutions Product Data Sheet).
Check cable connections between Power Puck and wireless device. Check mounting surface; clean and smooth is best.

Warning on product labels

Power Puck solutions connect to Emerson transmitters using an IPM. The IPM includes a printed warning label, as shown in
The text of the warning is as follows: “WARNING Potential Static Hazard. Use
Caution when Handling. Risk of Fire, Explosion or Severe Burn Hazard. DO NOT Recharge, Disassemble, Heat above 100°C, Incinerate or Expose Contents to Water. Li metal content approx 5g.
Figure 5. IPM Warning Label
8
Figure 5.
October 2015
Quick Start Guide

Disposal/recycling of depleted IPMs

Dispose in accordance with applicable laws and regulations in your country and state.
Disposal should only be performed by authorized professionals in accordance with applicable requirements for hazardous waste transportation and disposal.
Shipping regulations
Primary lithium batteries are regulated in transportation by the U.S. Department of Transportation, and are also covered by IATA (International Air Transport Association), ICAO (International Civil Aviation Organization), and ARD (European Ground Transportation of Dangerous Goods). It is the responsibility of the shipper to ensure compliance with these or any other local requirements. Consult current regulations and requirements before shipping.
Handling considerations
Each IPM contains two “C” size primary lithium batteries.
Under normal conditions, the battery materials are self-contained and not reactive as long as the batteries and the battery pack integrity are maintained. Care should be taken to prevent thermal, electrical, or mechanical damage. Contacts should be protected to prevent premature discharge.
Use caution when handling the IPM. It may be damaged if dropped onto a hard surface. Battery hazards remain when cells are discharged.
Environmental considerations
As with any battery, local environmental rules and regulations should be consulted for proper management of spent batteries. If no specific requirements exist, recycling through a qualified recycler is encouraged. Consult the material safety data sheet for specific battery information.
9
Quick Start Guide
μ

Product Certifications

Power Puck Certifications
Approved Manufacturing Locations
Perpetua Power Source Technologies, Inc.— Corvallis, Oregon USA
U.S.A.
UL Intrinisically Safe
Certificate: E464513 Class I, Division 1, Groups A, B, C, and D; Class II, Division 1, Groups E, F, and G; Class III, Division 1; Class I, Zone 0, AEx ia IIC T4
Canada
UL Intrinisically Safe
Class I, Division 1, Groups A, B, C, and D; Class II, Division 1, Groups E, F, and G; Class III, Division 1; Class I, Zone 0, Ex ia IIC T4
Europe
ATE X Int rins ic Sa fet y Certificate: DEMKO 14 ATEX 1303X Standards: EN 60079-0:2012+A11:2013
EN 60079-11:2012 EN 60079-26:2007
II1G Ex ia IIC T4 II1D Ex ia IIIC T135 °C
International
Certificate: IECEx UL 14.0083X Standards: IEC 60079-0:2011 Ex ia IIC T4 Ga Ex ia IIIC T135 °C Da T4: -45 °C Ta +65 °C
UL File Number: e464513
Table 3. Power Puck Safety Parameters
U
o
I
o
P
o
C
o
L
o
10
12.6V
19mA
59mW
1.15 F
98mH
October 2015
μ
μ
IPM Certifications
Approved Manufacturing Locations
Perpetuum Ltd—Southampton, United Kingdom
North America
FM Approvals Intrinsically Safe
Certificate: 3047349
Europe
ATE X Int rin sic Saf ety
Certificate: Baseefa 13ATEX0062X Standards: EN 60079-0:2009
EN 60079-11:2007
ATE X Int rin sic Saf ety
Certificate: Baseefa 13ATEX0062X Standards: EN 60079-0:2009
EN 60079-11:2007
Ex ia IICT4 Ga (-40 °C to +85 °C)
International
IECEx Intrinsic Safety
Certificate: IECEx BAS 13.0036X Standards: IEC 60079-0:2004
IEC 60079-0:2007-10 IEC 60079-11:2006
Ex ia IICT4 Ga (-40 °C to +85 °C)
Quick Start Guide
Table 4. IPM Safety Parameters
Parameter
U
o
I
o
P
o
C
o
L
o
Input (from
power source)
20V 7.8V
20mA 1.84A
0.165W 0.77W
0 9.3 F
0 14.9 H
Output (to WSN)
11
Quick Start Guide
Figure 6. Perpetua Declaration of Conformity
12
October 2015
Figure 7. Perpetuum Declaration of Conformity
Quick Start Guide
13
Quick Start Guide
00825-0100-4404, Rev AA
October 2015
AMS is a registered trademark of Emerson Electric Co. Perpetua and Power Puck are registered trademarks of Perpetua Power Source Technologies, Inc. All other marks are the proper ty of their respec tive owners. © 2015 All rights reserved.