OXYMITTER 5000
OXYGEN TRANSMITTER
WITH FOUNDATION
FIELDBUS COMMUNICATIONS
NOTICE
Read this manual before working with the product. For personal and system safety, and for optimum
product performance, make sure you thoroughly understand the contents before installing, using, or
maintaining this product.
The products described in this document are NOT designed for nuclear-qualified applications.
Using non-nuclear-qualified products in applications that require nuclear-qualified hardware or
products may cause inaccurate readings.
For information on Fisher-Rosemount nuclear-qualified products, contact your local FisherRosemount Sales Representative.
Rosemount is a registered trademark of Rosemount Inc.
Delta V, the Delta V logotype, PlantWeb, and the PlantWeb logotype are trademarks of Fisher-Rosemount.
OUNDATION
F
is a trademark of the Fieldbus Foundation.
Rosemount satisfies all obligations coming from legislation to harmonize the product requirements
in the European Union.
ROSEMOUNT WARRANTY
Rosemount warrants that the equipment manufactured and sold by it will, upon shipment, be free of defects in workmanship or material. Should any failure to conform to this
warranty become apparent during a peri od of on e year after the date of s h ipment, Rosemou n t
shall, upon prompt written notice from the purchaser, correct such nonconformity by repair
or replacement, F.O.B. factory of the defective part or parts. Correction in the manner
provided above shall constitute a fulfillment of all liabilities of Rosemount with respect to
the quality of the equipment.
THE FOREGOING WARRANTY IS EXCLUSIVE AND IN LIEU OF
ALL OTHER WARRANTIES OF QUALITY WHETHER WRITTEN, ORAL,
OR IMPLIED (INCLUDING ANY WARRANTY OF MERCHANTABILITY OF
FITNESS FOR PURPOSE).
The remedy(ies) provided above s h all be pu rch as er's sole remedy(ies ) f or an y failure of
Rosemount to comply with the warranty provisions, whether claims by the purchaser are
based in contract or in tort (including negligence).
Rosemount does not warrant equipment against normal deteriora tion due to environment. Factors such as corrosive gases and solid particulates can be detrimental and can
create the need for repair or replacement as part of normal wear and tear during the warranty
period.
Equipment supplied by Rosemount Analytical Inc. but not manufactured by it will be
subject to the same warran t y as is extended to Rosemoun t by the original manu f actu rer.
At the time of installation it is important that the required services are supplied to the
system and that the electronic controller is set up at least to the point where it is controlling
the sensor heater. This will ensure, that should there be a delay between installation and full
commissioning that the sensor being supplied with ac power and reference air will not be
subjected to component deterioration.
IB-106-350
i
PURPOSE
The purpose of this manual is to provide a comprehensive understanding of the Oxymitter 5000
components, functions, installation, and maintenance.
This manual is designed to provide information about the Oxymitter 5000. We recommend that you
thoroughly familiarize yourself with the Description and Installation sections before installing your transmitter.
The description presents the basic principles of the transmitter along with its performance characteristics
and components. The remaining sections contain detailed procedures and information necessary to install and
service the transmitter.
Before contacting Rosemount concerning any questions, first consult this manual. It describes most
situations encountered in your equipment’s operation and details necessary action.
DEFINITIONS
The following definitions apply to WARNINGS, CAUTIONS, and NOTES found throughout this
publication.
Highlights an operation or maintenance
procedure, practice, condition, statement,
etc. If not strictly observed, could result
in injury, death, or long-term health
hazards of personnel.
Highlights an essential operating procedure,
condition, or statemen t.
: EARTH (GROUND) TERMINAL
: PROTECTIVE CONDUCTOR TERMINAL
: RISK OF ELECTRICAL SHOCK
: WARNING: REFER TO INSTRUCTION BULLETIN
NOTE TO USERS
Highlights an operation or maintenance
procedure, practice, condition, statement,
etc. If not strictly observed, could result
in damage to or destruction of equipment,
or loss of effectiveness.
NOTE
The number in the low er rig h t corn er of each illu stration in th is pu blication is a manual illustration number.
It is not a part number, and is not related to the illustration in any technical manner.
IB-106-35
ii
IMPORTANT
SAFETY INSTRUCTIONS FOR THE WIRING AND
INSTALLATION OF THIS APPARATUS
The following safety instructions apply specifically to all EU member
states. They should be strictly adhered to in order to assure
compliance with the Low Voltage Directive. Non-EU states should
also comply with the following unless superseded by local or National
Standards.
1. Adequate earth connections shou ld be made to all earthing points, in tern al an d ex tern al, where provided.
2. After installation or troubleshooting, all safety covers and safety grounds must be replaced. The integrity
of all earth terminals must be maintained at all tim es.
3. Mains supply cords s h ou ld comply w it h t h e requ irements of IEC227 or IEC 245.
4. All wiring shall be su itable f or us e in an ambient temperature of greater than 75°C .
5. All cable glands used shou ld be of s u ch in tern al dimensions as to provide adequ ate cable an ch orag e.
6. To ensure safe operation of this equipment, connection to the mains supply should only be made through
a circuit breaker which will disconnect all circuits carrying conductors during a fault situation. The circuit
breaker may also include a mechanically operated isolating switch. If not, then another means of
disconnecting the equipment from the supply must be provided and clearly marked as such. Circuit
breakers or switches must comply with a recognized standard such as IEC947. All wiring must conform
with any local s tan dards.
7. Where equipment or covers are marked with the symbol to the right,
hazardous voltages are likely to be present beneath. These covers should only
be removed when power is removed from the equipment — and then only by
trained service personnel.
8. Where equipment or covers are mark ed with the symbol to the right, there is a
danger from hot surfaces beneath. These covers should only be removed by
trained service personnel when power is removed from the equipment.
Certain surfaces may remain hot to the touch .
9. Where equipment or covers are marked with the symbol to the right, refer to
the Operator Manual for instructions .
10. All graphical symbols used in this product are from one or more of the following standards: EN61010-1,
IEC417, and ISO3864.
IB-106-350
iii
BELANGRIJK
Veiligheidsvoorschriften voor de aansluiting en installatie van dit toestel.
De hierna volgende veiligheidsvoorschriften zijn vooral bedoeld voor de EU lidstaten. Hier moet aan
gehouden worden om de onderworpenheid aan de Laag Spannings Richtlijn (Low Voltage Directive) te
verzekeren. Niet EU staten zouden deze richtlijnen moeten volgen tenzij zij reeds achterhaald zouden zijn
door plaatselijke of nationale voorschriften.
1.Degelijke aardingsaansluitingen moeten gemaakt worden naar alle voorziene aardpunten, intern en extern.
2.Na installatie of controle moeten alle veiligheidsdeksels en -aardingen terug geplaatst worden. Ten alle tijde
moet de betrouwbaarheid van de aarding behouden blijven.
3.Voedingskabels moeten onderworpen zijn aan de IEC227 of de IEC245 voorschriften.
4.Alle bekabeling moet geschikt zijn voor het gebruik in omgevingstemperaturen, hoger dan 75°C.
5.Alle wartels moeten zo gedimensioneerd zijn dat een degelijke kabel bevestiging verzekerd is.
6.Om de veilige werking van dit toestel te verzekeren, moet de voeding door een stroomonderbreker gevoerd
worden (min 10A) welke alle draden van de voeding moet onderbreken. De stroomonderbreker mag een
mechanische schakelaar bevatten. Zoniet moet een andere mogelijkheid bestaan om de voedingsspanning
van het toestel te halen en ook duidelijk zo zijn aangegeven. Stroomonderbrekers of schakelaars moeten onderworpen zijn aan een erkende standaard zoals IEC947.
7.Waar toestellen of deksels aangegeven staan met het symbool is er meestal hoogspanning aanwezig. Deze deksels mogen enkel verwijderd worden nadat de
voedingsspanning werd afgelegd en enkel door getraind onderhoudspersoneel.
8.Waar toestellen of deksels aangegeven staan met het symbool is er gevaar
voor hete oppervlakken. Deze deksels mogen enkel verwijderd worden door
getraind onderhoudspersoneel nadat de voedingsspanning verwijderd werd. Sommige oppper-vlakken kunnen 45 minuten later nog steeds heet aanvoelen.
9.Waar toestellen of deksels aangegeven staan met het symbool gelieve het handboek te raadplegen.
10. Alle grafische symbolen gebruikt in dit produkt, zijn afkomstig uit een of meer van devolgende standaards:
EN61010-1, IEC417 en ISO3864.
IB-106-350
iv
VIGTIGT
Sikkerhedsinstruktion for tilslutning og installering af dette udstyr.
Følgende sikkerhedsinstruktioner gælder specifikt i alle EU-medlemslande. Instruktionerne skal nøje
følges for overholdelse af Lavsspændingsdirektivet og bør også følges i ikke EU-lande medmindre andet er
specificeret af lokale eller nationale standarder.
1.Passende jordforbindelser skal tilsluttes alle jordklemmer, interne og eksterne, hvor disse forefindes.
2.Efter installation eller fejlfinding skal alle sikkerhedsdæksler og jordforbindelser reetableres.
3.Forsyningskabler skal opfylde krav specificeret i IEC227 eller IEC245.
4.Alle ledningstilslutninger skal være konstrueret til omgivelsestemperatur højere end 75° C.
5.Alle benyttede kabelforskruninger skal have en intern dimension, så passende kabelaflastning kan etableres.
6.For opnåelse af sikker drift og betjening skal der skabes beskyttelse mod indirekte berøring gennem afbryder
(min. 10A), som vil afbryde alle kredsløb med elektriske ledere i fejlsitua-tion. Afbryderen skal indholde en
mekanisk betjent kontakt. Hvis ikke skal anden form for afbryder mellem forsyning og udstyr benyttes og
mærkes som sådan. Afbrydere eller kontakter skal overholde en kendt standard som IEC947.
7.Hvor udstyr eller dæksler er mærket med dette symbol, er farlige spændinger normalt
forekom-mende bagved. Disse dæksler bør kun afmonteres, når forsyningsspændingen
er frakoblet - og da kun af instrueret servicepersonale.
8.Hvor udstyr eller dæksler er mærket med dette symbol, forefindes meget varme overflader bagved. Disse dæksler bør kun afmonteres af instrueret servicepersonale, når
forsyningsspænding er frakoblet. Visse overflader vil stadig være for varme at berøre i
op til 45 minutter efter frakobling.
9.Hvor udstyr eller dæksler er mærket med dette symbol, se da i betjeningsmanual for
instruktion.
10. Alle benyttede grafiske symboler i dette udstyr findes i én eller flere af følgende standarder:- EN61010-1,
IEC417 & ISO3864.
IB-106-350
v
BELANGRIJK
Veiligheidsinstructies voor de bedrading en installatie van dit apparaat.
Voor alle EU lidstaten zijn de volgende veiligheidsinstructies van toepassing. Om aan de geldende richtlijnen voor laagspanning te voldoen dient men zich hieraan strikt te houden. Ook niet EU lidstaten dienen
zich aan het volgende te houden, tenzij de lokale wetgeving anders voorschrijft.
1.Alle voorziene interne- en externe aardaansluitingen dienen op adequate wijze aangesloten te worden.
2.Na installatie,onderhouds- of reparatie werkzaamheden dienen alle beschermdeksels /kappen en aardingen
om reden van veiligheid weer aangebracht te worden.
3.Voedingskabels dienen te voldoen aan de vereisten van de normen IEC 227 of IEC 245.
4.Alle bedrading dient geschikt te zijn voor gebruik bij een omgevings temperatuur boven 75°C.
5.Alle gebruikte kabelwartels dienen dusdanige inwendige afmetingen te hebben dat een adequate verankering
van de kabel wordt verkregen.
6.Om een veilige werking van de apparatuur te waarborgen dient de voeding uitsluitend plaats te vinden via
een meerpolige automatische zekering (min.10A) die
foutconditie optreedt. Deze automatische zekering mag ook voorzien zijn van een mechanisch bediende
schakelaar. Bij het ontbreken van deze voorziening dient een andere als zodanig duidelijk aangegeven mogelijkheid aanwezig te zijn om de spanning van de apparatuur af te schakelen. Zekeringen en schakelaars dienen te voldoen aan een erkende standaard zoals IEC 947.
alle
spanningvoerende geleiders verbreekt indien een
7.Waar de apparatuur of de beschermdeksels/kappen gemarkeerd zijn met het volgende
symbool, kunnen zich hieronder spanning voerende delen bevinden die gevaar op kunnen leveren. Deze beschermdeksels/kappen mogen uitsluitend verwijderd worden door
getraind personeel als de spanning is afgeschakeld.
8.Waar de apparatuur of de beschermdeksels/kappen gemarkeerd zijn met het volgende
symbool, kunnen zich hieronder hete oppervlakken of onderdelen bevinden. Bepaalde
delen kunnen mogelijk na 45 min. nog te heet zijn om aan te raken.
9.Waar de apparatuur of de beschermdeksels/kappen gemarkeerd zijn met het volgende
symbool, dient men de bedieningshandleiding te raadplegen.
10. Alle grafische symbolen gebruikt bij dit produkt zijn volgens een of meer van de volgende standaarden: EN
61010-1, IEC 417 & ISO 3864.
IB-106-350
vi
TÄRKEÄÄ
Turvallisuusohje, jota on noudatettava tämän laitteen asentamisessa ja kaapeloinnissa.
Seuraavat ohjeet pätevät erityisesti EU:n jäsenvaltioissa. Niitä täytyy ehdottomasti noudattaa jotta täytettäisiin EU:n matalajännitedirektiivin (Low Voltage Directive) yhteensopivuus. Myös EU:hun kuulumattomien valtioiden tulee nou-dattaa tätä ohjetta, elleivät kansalliset standardit estä sitä.
1.Riittävät maadoituskytkennät on tehtävä kaikkiin maadoituspisteisiin, sisäisiin ja ulkoisiin.
2.Asennuksen ja vianetsinnän jälkeen on kaikki suojat ja suojamaat asennettava takaisin pai-koilleen.
Maadoitusliittimen kunnollinen toiminta täytyy aina ylläpitää.
3.Jännitesyöttöjohtimien täytyy täyttää IEC227 ja IEC245 vaatimukset.
4.Kaikkien johdotuksien tulee toimia >75°C lämpötiloissa.
5.Kaikkien läpivientiholkkien sisähalkaisijan täytyy olla sellainen että kaapeli lukkiutuu kun-nolla kiinni.
6.Turvallisen toiminnan varmistamiseksi täytyy jännitesyöttö varustaa turvakytkimellä (min 10A), joka kytkee
irti kaikki jännitesyöttöjohtimet vikatilanteessa. Suojaan täytyy myös sisältyä mekaaninen erotuskytkin. Jos
ei, niin jännitesyöttö on pystyttävä katkaisemaan muilla keinoilla ja merkittävä siten että se tunnistetaan
sellaiseksi. Turvakytkimien tai kat-kaisimien täytyy täyttää IEC947 standardin vaatimukset näkyvyydestä.
7.Mikäli laite tai kosketussuoja on merkitty tällä merkillä on merkinnän takana tai
alla hengenvaarallisen suuruinen jännite. Suojaa ei saa poistaa jänniteen ollessa
kytkettynä laitteeseen ja poistamisen saa suorittaa vain alan asian-tuntija.
8.Mikäli laite tai kosketussuoja on merkitty tällä merkillä on merkinnän takana tai
alla kuuma pinta. Suojan saa poistaa vain alan asiantuntija kun jännite-syöttö on
katkaistu. Tällainen pinta voi säilyä kosketuskuumana jopa 45 mi-nuuttia.
9.Mikäli laite tai kosketussuoja on merkitty tällä merkillä katso lisäohjeita käyttöohjekirjasta
10. Kaikki tässä tuotteessa käytetyt graafiset symbolit ovat yhdestä tai useammasta seuraavis-ta standardeista:
EN61010-1, IEC417 & ISO3864.
IB-106-350
vii
IMPORTANT
Consignes de sécurité concernant le raccordement et l’installation de cet appareil.
Les consignes de sécurité ci-dessous s’adressent particulièrement à tous les états membres de la communauté européenne. Elles doivent être strictement appliquées afin de satisfaire aux directives concernant
la basse tension. Les états non membres de la communauté européenne doivent également appliquer ces
consignes sauf si elles sont en contradiction avec les standards locaux ou nationaux.
1.Un raccordement adéquat à la terre doit être effectuée à chaque borne de mise à la terre, interne et externe.
2.Après installation ou dépannage, tous les capots de protection et toutes les prises de terre doivent être remis
en place, toutes les prises de terre doivent être respectées en permanence.
3.Les câbles d’alimentation électrique doivent être conformes aux normes IEC227 ou IEC245
4.Tous les raccordements doivent pouvoir supporter une température ambiante supérieure à 75°C.
5.Tous les presse-étoupes utilisés doivent avoir un diamètre interne en rapport avec les câbles afin d’assurer
un serrage correct sur ces derniers.
6.Afin de garantir la sécurité du fonctionnement de cet appareil, le raccordement à l’alimentation électrique
doit être réalisé exclusivement au travers d’un disjoncteur (minimum 10A.) isolant tous les conducteurs en
cas d’anomalie. Ce disjoncteur doit également pouvoir être actionné manuellement, de façon mécanique.
Dans le cas contraire, un autre système doit être mis en place afin de pouvoir isoler l’appareil et doit être
signalisé comme tel. Disjoncteurs et interrupteurs doivent être conformes à une norme reconnue telle
IEC947.
7.Lorsque les équipements ou les capots affichent le symbole suivant, cela signifie que
des tensions dangereuses sont présentes. Ces capots ne doivent être démontés que lorsque l’alimentation est coupée, et uniquement par un personnel compétent.
8.Lorsque les équipements ou les capots affichent le symbole suivant, cela signifie que
des surfaces dangereusement chaudes sont présentes. Ces capots ne doivent être
démontés que lorsque l’alimentation est coupée, et uniquement par un personnel compétent. Certaines surfaces peuvent rester chaudes jusqu’à 45 mn.
9.Lorsque les équipements ou les capots affichent le symbole suivant, se reporter au
manuel d’instructions.
10. Tous les symboles graphiques utilisés dans ce produit sont conformes à un ou plusieurs des standards suivants: EN61010-1, IEC417 & ISO3864.
IB-106-350
viii
Wichtig
Sicherheitshinweise für den Anschluß und die Installation dieser Geräte.
Die folgenden Sicherheitshinweise sind in allen Mitgliederstaaten der europäischen Gemeinschaft gültig.
Sie müssen strickt eingehalten werden, um der Niederspannungsrichtlinie zu genügen.
Nichtmitgliedsstaaten der europäischen Gemeinschaft sollten die national gültigen Normen und
Richtlinien einhalten.
1.Alle intern und extern vorgesehenen Erdungen der Geräte müssen ausgeführt werden.
2.Nach Installation, Reparatur oder sonstigen Eingriffen in das Gerät müssen alle Sicherheitsabdeckungen und
Erdungen wieder installiert werden. Die Funktion aller Erdverbindungen darf zu keinem Zeitpunkt gestört
sein.
3.Die Netzspannungsversorgung muß den Anforderungen der IEC227 oder IEC245 genügen.
4.Alle Verdrahtungen sollten mindestens bis 75 °C ihre Funktion dauerhaft erfüllen.
5.Alle Kabeldurchführungen und Kabelverschraubungen sollten in Ihrer Dimensionierung so gewählt werden,
daß diese eine sichere Verkabelung des Gerätes ermöglichen.
6.Um eine sichere Funktion des Gerätes zu gewährleisten, muß die Spannungsversorgung über mindestens 10
A abgesichert sein. Im Fehlerfall muß dadurch gewährleistet sein, daß die Spannungsversorgung zum Gerät
bzw. zu den Geräten unterbrochen wird. Ein mechanischer Schutzschalter kann in dieses System integriert
werden. Falls eine derartige Vorrichtung nicht vorhanden ist, muß eine andere Möglichkeit zur Unterbrechung der Spannungszufuhr gewährleistet werden mit Hinweisen deutlich gekennzeichnet werden. Ein solcher Mechanismus zur Spannungsunterbrechung muß mit den Normen und Richtlinien für die allgemeine
Installation von Elektrogeräten, wie zum Beispiel der IEC947, übereinstimmen.
7.Mit dem Symbol sind Geräte oder Abdeckungen gekennzeichnet, die eine gefährliche (Netzspannung) Spannung führen. Die Abdeckungen dürfen nur entfernt
werden, wenn die Versorgungsspannung unterbrochen wurde. Nur geschultes Personal darf an diesen Geräten Arbeiten ausführen.
8.Mit dem Symbol sind Geräte oder Abdeckungen gekennzeichnet, in bzw. unter
denen heiße Teile vorhanden sind. Die Abdeckungen dürfen nur entfernt werden,
wenn die Versorgungsspannung unterbrochen wurde. Nur geschultes Personal
darf an diesen Geräten Arbeiten ausführen. Bis 45 Minuten nach dem Unterbrechen der Netzzufuhr können derartig Teile
noch über eine erhöhte Temperatur verfügen.
9.Mit dem Symbol sind Geräte oder Abdeckungen gekennzeichnet, bei denen vor
dem Eingriff die entsprechenden Kapitel im Handbuch sorgfältig durchgelesen
werden müssen.
10. Alle in diesem Gerät verwendeten graphischen Symbole entspringen einem oder mehreren der nachfolgend
aufgeführten Standards: EN61010-1, IEC417 & ISO3864.
IB-106-350
ix
IMPORTANTE
Norme di sicurezza per il cablaggio e l’installazione dello strumento.
Le seguenti norme di sicurezza si applicano specificatamente agli stati membri dell’Unione Europea, la cui
stretta osservanza è richiesta per garantire conformità alla Direttiva del Basso Voltaggio. Esse si applicano
anche agli stati non appartenenti all’Unione Europea, salvo quanto disposto dalle vigenti normative l ocali
o nazionali
1.Collegamenti di terra idonei devono essere eseguiti per tutti i punti di messa a terra interni ed esterni, dove
2.Dopo l’installazione o la localizzazione dei guasti, assicurarsi che tutti i coperchi di protezione siano stati
3.I cavi di alimentazione della rete devono essere secondo disposizioni IEC227 o IEC245.
4.L’intero impianto elettrico deve essere adatto per uso in ambiente con temperature superiore a 75°C.
5.Le dimensioni di tutti i connettori dei cavi utilizzati devono essere tali da consentire un adeguato ancoraggio
.
previsti.
collocati e le messa a terra siano collegate. L’integrità di ciscun morsetto di terra deve essere costantemente
garantita.
al cavo.
6.Per garantire un sicuro funzionamento dello strumento il collegamento alla rete di alimentazione principale
dovrà essere eseguita tramite interruttore automatico (min.10A), in grado di disattivare tutti i conduttori di
circuito in caso di guasto. Tale interruttore dovrà inoltre prevedere un sezionatore manuale o altro dispositivo di interruzione dell’alimentazione, chiaramente identificabile. Gli interruttori dovranno essere conformi
agli standard riconosciuti, quali IEC947.
7.Il simbolo riportato sullo strumento o sui coperchi di protezione indica probabile
presenza di elevati voltaggi. Tali coperchi di protezione devono essere rimossi esclusivamente da personale qualificato, dopo aver tolto alimentazione allo strumento.
8.Il simbolo riportato sullo strumento o sui coperchi di protezione indica rischio di
contatto con superfici ad alta temperatura. Tali coperchi di protezione devono essere
rimossi esclusivamente da personale qualificato, dopo aver tolto alimentazione allo
strumento. Alcune superfici possono mantenere temperature elevate per oltre 45 minuti.
9.Se lo strumento o il coperchio di protezione riportano il simbolo, fare riferimento alle istruzioni del manuale Operatore.
10. Tutti i simboli grafici utilizzati in questo prodotto sono previsti da uno o più dei seguenti standard:
EN61010-1, IEC417 e ISO3864.
IB-106-350
x
VIKTIG
Sikkerhetsinstruks for tilkobling og installasjon av dette utstyret.
Følgende sikkerhetsinstruksjoner gjelder spesifikt alle EU medlemsland og land med i EØS-avtalen.
Instruksjonene skal følges nøye slik at installasjonen blir i henhold til lavspenningsdirektivet. Den bør
også følges i andre land, med mindre annet er spesifisert av lokale- eller nasjonale standarder.
1.Passende jordforbindelser må tilkobles alle jordingspunkter, interne og eksterne hvor disse forefinnes.
2.Etter installasjon eller feilsøking skal alle sikkerhetsdeksler og jordforbindelser reetableres. Jordingsforbindelsene må alltid holdes i god stand.
3.Kabler fra spenningsforsyning skal oppfylle kravene spesifisert i IEC227 eller IEC245.
4.Alle ledningsforbindelser skal være konstruert for en omgivelsestemperatur høyere en 750C.
5.Alle kabelforskruvninger som benyttes skal ha en indre dimensjon slik at tilstrekkelig avlastning oppnåes.
6.For å oppnå sikker drift og betjening skal forbindelsen til spenningsforsyningen bare skje gjennom en
strømbryter (minimum 10A) som vil bryte spenningsforsyningen til alle elektriske kretser ved en feilsituasjon. Strømbryteren kan også inneholde en mekanisk operert bryter for å isolere instrumentet fra spenningsforsyningen. Dersom det ikke er en mekanisk operert bryter installert, må det være en annen måte å
isolere utstyret fra spenningsforsyningen, og denne måten må være tydelig merket. Kretsbrytere eller kontakter skal oppfylle kravene i en annerkjent standard av typen IEC947 eller tilsvarende.
7.Der hvor utstyr eller deksler er merket med symbol for farlig spenning, er det sannsynlig at disse er tilstede bak dekslet. Disse dekslene må bare fjærnes når spenningsforsyning er frakoblet utstyret, og da bare av trenet servicepersonell.
8.Der hvor utstyr eller deksler er merket med symbol for meget varm overflate, er det
sannsynlig at disse er tilstede bak dekslet. Disse dekslene må bare fjærnes når spenningsforsyning er frakoblet utstyret, og da bare av trenet servicepersonell. Noen overflater kan være for varme til å berøres i opp til 45 minutter etter spenningsforsyning
frakoblet.
9.Der hvor utstyret eller deksler er merket med symbol, vennligst referer til instruksjonsmanualen for instrukser.
10. Alle grafiske symboler brukt i dette produktet er fra en eller flere av følgende standarder: EN61010-1,
IEC417 & ISO3864.
IB-106-350
xi
IMPORTANTE
Instruções de segurança para ligação e instalação deste aparelho.
As seguintes instruções de segurança aplicam-se especificamente a todos os estados membros da UE. Devem ser observadas rigidamente por forma a garantir o cumprimento da Directiva sobre Baixa Tensão.
Relativamente aos estados que não pertençam à UE, deverão cumprir igualmente a referida directiva,
exceptuando os casos em que a legislação local a tiver substituído.
1.Devem ser feitas ligações de terra apropriadas a todos os pontos de terra, internos ou externos.
2.Após a instalação ou eventual reparação, devem ser recolocadas todas as tampas de seg urança e terras de
protecção. Deve manter-se sempre a integridade de todos os terminais de terra.
3.Os cabos de alimentação eléctrica devem obedecer às exigências das normas IEC227 ou IEC245.
4.Os cabos e fios utilizados nas ligações eléctricas devem ser adequados para utilização a uma temperatura
ambiente até 75º C.
5.As dimensões internas dos bucins dos cabos devem ser adequadas a uma boa fixação dos cabos.
6.Para assegurar um funcionamento seguro deste equipamento, a ligação ao cabo de alimentação eléctrica
deve ser feita através de um disjuntor (min. 10A) que desligará todos os condutores de circuitos durante uma
avaria. O disjuntor poderá também conter um interruptor de isolamento accionado manualmente. Caso
contrário, deverá ser instalado qualquer outro meio para desligar o equipamento da energia eléctrica, devendo ser assinalado convenientemente. Os disjuntores ou interruptores devem obedecer a uma norma reconhecida, tipo IEC947.
7.Sempre que o equipamento ou as tampas contiverem o símbolo, é provável a existência de tensões perigosas. Estas tampas só devem ser retiradas quando a energia
eléctrica tiver sido desligada e por Pessoal da Assistência devidamente treinado.
8.Sempre que o equipamento ou as tampas contiverem o símbolo, há perigo de existência de superfícies quentes. Estas tampas só devem ser retiradas por Pessoal da Assistência devidamente treinado e depois de a energia eléctrica ter sido desligada.
Algumas superfícies permanecem quentes até 45 minutos depois.
9.Sempre que o equipamento ou as tampas contiverem o símbolo, o Manual de Funcionamento deve ser consultado para obtenção das necessárias instruções.
10. Todos os símbolos gráficos utilizados neste produto baseiam-se em uma ou mais das seguintes normas:
EN61010-1, IEC417 e ISO3864.
IB-106-350
xii
IMPORTANTE
Instrucciones de seguridad para el montaje y cableado de este aparato.
Las siguientes instrucciones de seguridad , son de aplicacion especifica a todos los miembros de la UE y se
adjuntaran para cumplir la normativa europea de baja tension.
1.Se deben preveer conexiones a tierra del equipo, tanto externa como internamente, en aquellos terminales
previstos al efecto.
2.Una vez finalizada las operaciones de mantenimiento del equipo, se deben volver a colocar las cubiertas de
seguridad aasi como los terminales de tierra. Se debe comprobar la integridad de cada terminal.
3.Los cables de alimentacion electrica cumpliran con las normas IEC 227 o IEC 245.
4.Todo el cableado sera adecuado para una temperatura ambiental de 75ºC.
5.Todos los prensaestopas seran adecuados para una fijacion adecuada de los cables.
6.Para un manejo seguro del equipo, la alimentacion electrica se realizara a traves de un interruptor magnetotermico ( min 10 A ), el cual desconectara la alimentacion electrica al equipo en todas sus fases durante un
fallo. Los interruptores estaran de acuerdo a la norma IEC 947 u otra de reconocido prestigio.
7.Cuando las tapas o el equipo lleve impreso el simbolo de tension electrica peligrosa, dicho alojamiento solamente se abrira una vez que se haya interrumpido la
alimentacion electrica al equipo asimismo la intervencion sera llevada a cabo por
personal entrenado para estas labores.
8.Cuando las tapas o el equipo lleve impreso el simbolo, hay superficies con alta
temperatura, por tanto se abrira una vez que se haya interrumpido la alimentacion
electrica al equipo por personal entrenado para estas labores, y al menos se esperara unos 45 minutos para enfriar las superficies calientes.
9.Cuando el equipo o la tapa lleve impreso el simbolo, se consultara el manual de
instrucciones.
10. Todos los simbolos graficos usados en esta hoja, estan de acuerdo a las siguientes normas EN61010-1,
IEC417 & ISO 3864.
IB-106-350
xiii
VIKTIGT
Säkerhetsföreskrifter för kablage och installation av denna apparat.
Följande säkerhetsföreskrifter är tillämpliga för samtliga EU-medlemsländer. De skall följas i varje avseende för att överensstämma med Lågspännings direktivet. Icke EU medlemsländer skall också följa
nedanstående punkter, såvida de inte övergrips av lokala eller nationella föreskrifter.
1. Tillämplig jordkontakt skall utföras till alla jordade punkter, såväl internt som externt där så erfordras.
2. Efter installation eller felsökning skall samtliga säkerhetshöljen och säkerhetsjord återplaceras. Samtliga
jordterminaler måste hållas obrutna hela tiden.
3. Matningsspänningens kabel måste överensstämma med föreskrifterna i IEC227 eller IEC245.
4. Allt kablage skall vara lämpligt för användning i en omgivningstemperatur högre än 75ºC.
5. Alla kabelförskruvningar som används skall ha inre dimensioner som motsvarar adekvat kabelförankring.
6. För att säkerställa säker drift av denna utrustning skall anslutning till huvudströmmen endast göras genom en
säkring (min 10A) som skall frånkoppla alla strömförande kretsar när något fel uppstår. Säkringen kan även
ha en mekanisk frånskiljare. Om så inte är fallet, måste ett annat förfarande för att frånskilja utrustningen
från strömförsörjning tillhandahållas och klart framgå genom markering. Säkring eller omkopplare måste
överensstämma med en gällande standard såsom t ex IEC947.
7. Där utrustning eller hölje är markerad med vidstående symbol föreliggerisk för
livsfarlig spänning i närheten. Dessa höljen får endast avlägsnas när strömmen ej är
ansluten till utrustningen - och då endast av utbildad servicepersonal.
8. När utrustning eller hölje är markerad med vidstående symbol föreligger risk för
brännskada vid kontakt med uppvärmd yta. Dessa höljen får endast avlägsnas av utbildad servicepersonal, när strömmen kopplats från utrustningen. Vissa ytor kan vara
mycket varma att vidröra även upp till 45 minuter efter avstängning av strömmen.
9. När utrustning eller hölje markerats med vidstående symbol bör instruktionsmanualen
studeras för information.
10.
Samtliga grafiska symboler som förekommer i denna produkt finns angivna i en eller flera av följande
föreskrifter:- EN61010-1, IEC417 & ISO3864.
Vitreous Aluminosilicate Fibers with Silicon Dioxide.
CHEMICAL NAME
N.A.
CHEMICAL FORMULA
N.A.
MANUFACTURER’S NAME AND ADDRESS
Watlow Columbia 573-474-9402
2101 Pennsylvania Drive 573-814-1300, ext. 5170
Columbia, MO 65202
HEALTH HAZARD SUMMARY
WARNING
• Possible cancer hazard based on tests with laboratory animals.
• May be irritating to skin, eyes and respiratory tract.
• May be harmful if inhaled.
• Cristobalite (crystalline silica) formed at high temperatures (above 1800ºF) can cause severe respiratory disease.
IB-106-350
xvi
SECTION II. PHYSICAL DATA
APPEARANCE AND ODOR
Cream to white colored fiber shapes. With or without optional white to gray granular surface coating and/or optional
black surface coating.
SPECIFIC WEIGHT: 12-25 lb./cubic footBOILING POINT: N.A.
VOLATILES (% BY WT.): N.A.WATER SOLUBILITY: N.A.
SECTION III. HAZARDOUS INGREDIENTS
MATERIAL, QUANTITY, AND THRESHOLD/EXPOSURE LIMIT VALUES
Aluminosilicate (vitreous) 99+ %1 fiber/cc TWA
CAS. No. 142844-00-0610 fibers/cc CL
Zirconium Silicate0-10% 5 mg/cubic meter (TLV)
Black Surface Coating**0 - 1% 5 mg/cubic meter (TLV)
Armorphous Silica/Silicon Dioxide0-10% 20 mppcf (6 mg/cubic meter)
**Composition is a trade secret.
PEL (OSHA 1978) 3 gm cubic meter
(Respirable dust): 10 mg/cubic meter,
Intended TLV (ACGIH 1984-85)
SECTION IV. FIRE AND EXPLOSION DATA
FLASH POINT: NoneFLAMMABILITY LIMITS: N.A.
EXTINGUISHING MEDIA
Use extinguishing agent suitable for type of surrounding fire.
UNUSUAL FIRE AND EXPLOSION HAZARDS/SPECIAL FIRE FIGHTING
PROCEDURES
N.A.
IB-106-350
xvii
SECTION V. HEALTH HAZARD DATA
THRESHOLD LIMIT VALUE
(See Section III)
EFFECTS OF OVER EXPOSURE
EYE
Avoid contact with eyes. Slightly to moderately irritating. Abrasive action may cause damage to outer surface of eye.
INHALATION
May cause respiratory tract irritation. Repeated or prolonged breathing of particles of respirable size may cause inflammation of the lung leading to chest pain, difficult breathing, coughing and possible fibrotic change in the lung
(Pneumoconiosis). Pre-existing medical conditions may be aggravated by exposure: specifically, bronchial hyperreactivity and chronic bronc hia l or lung disease.
INGESTION
May cause gastrointestinal disturbances. Symptoms may include irritation and nausea, vomiting and diarrhea.
SKIN
Slightly to moderate irritating. May cause irritation and inflammation due to mechanical reaction to sharp, broken ends
of fibers.
EXPOSURE TO USED CERAMIC FIBER PRODUCT
Product which has been in service at elevated temperatures (greater than 1800ºF/982ºC) may undergo partial conversion
to cristobalite, a form of crystalline silica which can cause severe respiratory disease (Pneumoconiosis). The amount of
cristobalite present will depend on the temperature and length of time in service. (See Section IX for permissible exposure levels).
SPECIAL TOXIC EFFECTS
The existing toxicology and epidemiology data bases for RCF’s are still preliminary. Information will be updated as
studies are completed and reviewed. The following is a review of the results to date:
EPIDEMIOLOGY
At this time there are no known published reports demonstrating negative health outcomes of workers exposed to refractory ceramic fiber (RCF). Epidemiologic investigations of RCF production workers are ongoing.
1) There is no evidence of any fibrotic lung disease (interstitial fibrosis) whatsoever on x-ray.
2) There is no evide nce of any lung disease among those employees exposed to RCF that had never smoked.
3) A statistical “trend” was observed in the exposed population between the duration of exposure to RCF and a
decrease in some measures of pulmonary function. These observations are clinically insignificant. In other words, if
these observations were made on an individual employee, the results would be interpreted as being within the normal
range.
4) Pleural plaques (thickening along the chest wall) have been observed in a small number of employees who had a
long duration of employment. There are several occupational and non-occupational causes for pleural plaque. It
should be noted that plaques are not “pre-cancer” nor are they associated with any measurable effect on lung
function.
IB-106-350
xviii
TOXICOLOGY
A number of studies on the health effects of inhalation exposure of rats and hamsters are available. Rats were exposed
to RCF in a series of life-time nose-only inhalation studies. The animals were exposed to 30, 16, 9, and 3 mg/m
corresponds with approximately 200, 150, 75, and 25 fibers/cc.
Animals exposed to 30 and 16 mg/m
posed to 9 mg/m
3
had developed a mild parenchymal fibrosis; animals exposed to the lowest dose were found to have
3
were observed to have developed a pleural and parenchymal fibroses; animals ex-
the response typically observed any time a material is inhaled into the deep lung. While a statistica lly significant increase in lung tumors was observed following exposure to the highest dose, there was no excess lung cancers at the other
doses. Two rats exposed to 30 mg/m
The International Agency for Research on Cancer (IARC) reviewed the carcinogenicity data on man-made vitreous fi-
3
and one rat exposed to 9 mg/m3 developed masotheliomas.
bers (including ceramic fiber, glasswool, rockwool, and slagwool) in 1987. IARC classified ceramic fiber, fibrous
glasswool and mineral wool (rockwool and slagwool) as possible human carcinogens (Group 2B).
EMERGENCY FIRST AID PROCEDURES
EYE CONTACT
Flush eyes immediately with large amounts of water for approximately 15 minutes. Eye lids should be held away from
the eyeball to insure thorough r insing. Do not rub eyes. Get medical attention if irritation persists.
INHALATION
Remove person from source of exposure and move to fresh air. Some people may be sensitive to fiber induced irritation
of the respiratory tract. If symptoms such as shortness of breath, coughing, wheezing or chest pain develop, seek medical attention. If person experiences continued breathing difficulties, administer oxygen until medical assistance can be
rendered.
3
, which
INGESTION
Do not induce vomiting. Get medical attention if irritation persists.
SKIN CONTACT
Do not rub or scra tch exposed skin. Wash area of contact thoroughly with soap and water. Using a skin cream or lotion
after washing may be helpful. Get medical attention if irritation persists.
SECTION VI. REACTIVITY DATA
STABILITY/CONDITIONS TO AVOID
Stable under normal conditions of use.
HAZARDOUS POLYMERIZATION/CONDITIONS TO AVOID
N.A.
IB-106-350
xix
INCOMPATIBILITY/MATERIALS TO AVOID
Incompatible with hydrofluoric acid and concentrated alkali.
HAZARDOUS DECOMPOSITION PRODUCTS
N.A.
SECTION VII. SPILL OR LEAK PROCEDURES
STEPS TO BE TAKEN IF MATERIAL IS RELEASED OR SPILLED
Where possible, use vacuum suction with HEPA filters to clean up spilled material. Use dust suppressant where sweeping if necessary. Avoid clean up procedure which may result in water pollution. (Observe Special Protection Information Section VIII.)
WASTE DISPOSAL METHODS
The transportation, treatment, and disposal of this waste material must be conducted in compliance with all applicable
Federal, State, and Local regulations.
SECTION VIII. SPECIAL PROTECTION INFORMATION
RESPIRATORY PROTECTION
Use NIOSH or MSHA approved equipment when airborne exposure limits may be exceeded. NIOSH/MSHA approved
breathing equipment may be required for non-routine and emergency use. (See Section IX for suitable equipment).
Pending the results of long term health effects studies, engineering control of airborne fibers to the lowest levels attainable is advised.
VENTILATION
Ventilation should be used whenever possible to control or reduce airborne concentrations of fiber and dust. Carbon
monoxide, carbon dioxide, oxides of nitrogen, reactive hydrocarbons and a small amount of formaldehyde may accompany binder burn-off during first heat. Use adequate ventilation or other precautions to eliminate vapors resulting from
binder burn-off. Exposure to burn-off fumes may cause respiratory tract irritation, bronchial hyper-reactivity and asthmatic response.
SKIN PROTECTION
Wear gloves, hats and full body clothing to prevent skin contact. Use separate lockers for work clothes to prevent fiber
transfer to street cl othes. Wash work clothes separ ately from other clothing and rinse washing machine thoro ughly after
use.
EYE PROTECTION
Wear safety glasses or chemical worker’s goggles to prevent eye contact. Do not wear contact lenses when working
with this substance. Have eye baths readily available where eye contact can occur.
IB-106-350
xx
SECTION IX. SPECIAL PRECAUTIONS
PRECAUTIONS TO BE TAKEN IN HANDLING AND STORING
General cleanliness should be followed.
The Toxicology data indicate that ceramic fiber should be handled with caution. T he handling practices described in this
MSDS must be strictly followed. In particular, when handling refractory ceramic fiber in any application, special caution should be taken to avoid unnecessary cutting and tearing of the material to minimize generation of airborne dust.
It is recommended that full body clothing be worn to reduce the potential for skin irritation. Washable or disposable
clothing may be used. Do not ta ke unwashed work clothing home. Work clothes should be washed separately from
other clothing. Rinse washing machine thor oughly after use. If clothing is to be launde red by someone else, inform
launderer of proper procedure. Work clothes and street clothes should be kept separate to prevent contamination.
Product which has been in service at elevated temperatures (greater than 1800ºF/982ºC) may undergo partial conversion
to cristobalite, a form of crystalline silica. This reaction occurs at the furnace lining hot face. As a consequence, this
material becomes more friable; special caution must be taken to minimize generation of airborne dust. The amount of
cristobalite present will depend on the temperature and length in service.
IARC has recently reviewed the animal, human, and other relevant experimental data on silica in order to critically
evaluate and classify the cancer causing potential. Based on its review, IARC classified crystalline silica as a group 2A
carcinogen ( probable human carcinogen).
The OSHA permissible exposure limit (PEL for cristobalite is 0.05 mg/m
value (TLV) for cristobalite is 0.05 mg/m
3
(respirable dust) (ACGIH 1991-92). Use NIOSH or MSHA approved
equipment when airborne exposure limits may be exceeded. The minimum respiratory protection recommended for
given airborne fiber or cristobalite concentrations are:
3
(respirable dust). The ACGIH threshold limit
CONCENTRATION
3
0-1 fiber/cc or 0-0.05 mg/m
(the OSHA PEL)9970 or equivalent).
Up to 5 fibers/cc or up to 10 times theHalf face, air-purifying respirator equipped
OSHA PEL for cristobalitewith high efficiency particulate air (HEPA)
Up to 25 fibers/cc or 50 times the OSHAFull face, air-purifying respirator with high
PEL for cristobalite (2.5 mg/m
Greater than 25 fibers/cc or 50 times theFull face, positive pressure supplied air respiraOSHA PEL for cristobalite (2.5 mg/m
filter cartridges (e.g. 3M 6000 series with
2040 filter or equivalent).
3
)efficiency particulate air (HEPA) filter cart-
ridges (e.g. 3M 7800S with 7255 filters or
equivalent) or powered air-purifying respirator
(PARR) equipped with HEPA filter cartridges
(e.g. 3M W3265S with W3267 filters or
equivalent).
3
)tor (e.g. 3M 7800S with W9435 hose & W3196
low pressure regulator kit connected to clean
air supply or equivalent).
IB-106-350
xxi
If airborne fiber or cristobalite concentrations are not known, as minimum protection, use NIOSH/MSHA approved half
face, air-purifying respirator with HEPA filter cartridges.
Insulation surface should be lightly sprayed with water before removal to suppress airborne dust. As water evaporates
during removal, additional water should be sprayed on surfaces as needed. Only enough water should be sprayed to
suppress dust so that water does not run onto the floor of the work area. To aid the wetting process, a surfactant can be
used.
After RCF removal is completed, dust-suppressing cleaning methods, such as wet sweeping or vacuuming, should be
used to clean the work area. If dry vacuuming is used, the vacuum must be equipped with HEPA filter. Air blowing or
dry sweeping should not be used. Dust-suppressing components can be used to clean up light dust.
Product packaging may contain product residue. Do not reuse except to reship or return Ceramic Fiber products to the
factory.
APPENDIX B.ANALOG INPUT (AI) FUNCTION BLOCK.................................................... B-1
APPENDIX C.PID FUNCTION BLOCK......................................................................................C-1
INDEX ........................................................................................................................................................I-1
IB-106-350
xxiv
LIST OF ILLUSTRATIONS
FigurePage
1-1Typical System Package......................................................................................................... 1-0
1-2Oxymitter 5000 Autocalibration System Options .................................................................. 1-2
1-3Oxymitter 5000 F
OUNDATION
1-4Typical System Installation.................................................................................................... 1-5
7-1Replacement Parts for Probe..................................................................................................7-1
7-2Replacement Parts for Electronics.........................................................................................7-5
7-3Replacement Parts for SPS 4000............................................................................................ 7-7
7-4Replacement Parts for Calibration Gas Bottles...................................................................... 7-7
IB-106-350
xxvii
1 1
1
6
2
3
5
4
1. Instruction Bulletin
2. IMPS 4000 Intelligent MultiprobeTest Gas Sequencer (Optional)
3. Oxymitter 5000 with Integral Electronics
4. SPS 4000 Single Probe Autocalibration Sequencer (Optional) - (Shown with reference air option)
5. Adaptor Plate with Mounting Hardware and Gasket
6. Reference Air Set (used if SPS 4000 without reference air option or IMPS 4000 not supplied)
Figure 1-1. Typical System Package
IB-106-350
1-0
28550004
SECTION I. INTRODUCTION
1-1. COMPONENT CHECKLIST OF TYPICAL
SYSTEM (PACKAGE CONTENTS) . A typical
Rosemount Oxymitter 5000 Oxygen Transmitter
should contain the items shown in Figure 1-1. Record
the part number, serial number, and order number for
each component of your system in the table located
on the first page of this manual.
Use the product matrix in Table 1-1 at the end of this
section to compare your order number against your
unit. The first part of the matrix defines the model.
The last part defines the various options and features
of the Oxymitter 5000. Ensure the features and options specified by your order number are on or included with the unit.
1-2. SYSTEM OVERVIEW.
a. Scope. This Instruction Bulletin is designed to
supply details needed to install, start up, o perate,
and maintain the Oxymitter 5000. Integral signal
conditioning electronics outputs a digital
OUNDATION
F
fieldbus signal representing an O
value and provides a membrane keypad for setup,
calibration, and diagnostics. This same information, plus additional details, can be accessed via
fieldbus digital communications.
OUNDATION
b. F
OUNDATION
F
fieldbus Technology.
fieldbus is an all digital, serial,
two-way communication system that interconnects field equipment such as sensors, actuators,
and controllers. Fieldbus is a Local Area Network (LAN) for instruments used in both process
and manufacturing automation with built-in capacity to distribute the control application across
the network. The fieldbus environment is the
base level group of digital networks in the hierarchy of planet networks.
The fieldbus retains the desirable features of the
4-20 mA analog system, including a standardized
physical interface to the wire, bus powered devices on a single wire, and intrinsic safety options, and enables additional capabilities, such as:
• Increased capabilities due to full digital com-
munications
• Reduced wiring and wire terminations due to
multiple devices on one set of wires
• Increased selection of suppliers due to
interoperability
• Reduced loading on control room equipment
with the distribution of some control and input/
output functions to field de vices
• Speed options for process control and manu-
facturing applications
c. System Description. The Oxymitter 5000 is de-
signed to measure the net concentration of oxygen in an industrial process; i.e., the oxygen
remaining after all fuels have been oxidized. The
probe is permanently positioned within an exhaust duct or stack and performs its task without
the use of a sampling system.
The equipment measures oxygen percentage by
reading the voltage developed across a heated
electrochemical cell, which consists of a small
yttria-stabilized, zirconia disc. Both sides of the
disc are coated with porous metal electrodes.
When operated at the proper temperature, the
millivolt output voltage of the cell is given by the
following Nernst equation:
2
EMF = KT log
10(P1/P2
) + C
Where:
1. P
is the partial pressure of the oxygen in the
2
measured gas on one side of the cell.
2. P
is the partial pressure of the oxygen in the
1
reference air on the opposite side of the cell.
3. T is the absolute temperature.
4. C is the cell constant.
5. K is an arithmetic constant.
NOTE
For best results, use clean, dry, instrument
air (20.95% oxygen) as the reference air.
When the cell is at operating temperature and
there are unequal oxygen concentrations across
the cell, oxygen ions will travel from the high
oxygen partial pressure side to the low oxygen
partial pressure side of the cell. The resulting
logarithmic output voltage is approximately
50 mV per decade. The output is proportional to
the inverse logarithm of the oxygen concentration. Therefore, the output signal increases as the
oxygen concentration of the sample gas decreases. This characteristic enables the Oxymitter
5000 to provide exceptional sensitivity at low
oxygen concentrations.
IB-106-350
1-1
The Oxymitter 5000 measures net oxygen concentration in the presence of all the products of
combustion, including water vapor . Therefore, it
may be considered an analysis on a “wet” basis.
In comparison with older methods, such as the
portable apparatus, which provides an analysis on
a “dry” gas basis, the “wet” analysis will, in general, indicate a lower percentage of oxygen. The
difference will be proportional to the water content of the sampled gas stream.
d. System Configuration. Oxymitter 5000 units are
available in five length op tions, giving the use r the
flexibility to use an in situ penetration appropriate
to the size of the stack or duct. The options on
length are 18 in. (457 mm), 3 ft (0.91 m), 6 ft
(1.83 m), 9 ft (2.7 m ), or 12 f t (3.66 m).
e. System Features.
The CALIBRATION RECOMMENDED
1.
feature detects when the sensing cell is
likely out of limits. This may eliminate the
need to calibrate on a “time since last cal”
basis.
The cell output voltage and sensitivity
2.
increase as the oxygen concentration
decreases.
Membrane keypad and F
3.
bus communication are standard.
Field replaceable cell, heater, thermocou-
4.
ple, and diffusion element.
OUNDATION
field-
The integral electronics control probe temperature and provide an output that represents the
measured oxygen concentration. The power supply can accept voltages of 90-250 VAC and
50/60 Hz; therefore, no setup procedures are required. The oxygen sensing cell is maintained at
a constant temperature by modulating the duty
cycle of the probe heater portion of the integral
electronics. The integral electronics accepts millivolt signals generated by the sensing cell and
produces the outputs to be used by remotely connected devices. The output is a F
OUNDATION
fieldbus digital communication signal.
Two calibration gas sequencers are available to
the Oxymitter 5000: the IMPS 4000 and the SPS
4000 (Figure 1-2).
Systems with multiprobe applications may employ
an optional IMPS 4000 Intelligent Multiprobe Test
Gas Sequencer. The IMPS 4000 provides automatic calibration gas sequencing for up to four
Oxymitter 5000 units and accommodates autocalibrations based on the CALIBRATION RECOMMENDED signal from the Oxymitter 5000, a
timed interval set up via fieldbus or the IMPS
4000, or when a calibration requ es t is i n it ia ted.
The Oxymitter 5000 is constructed of rug-
5.
ged 316 L stainless steel for all wetted
parts.
For systems with one or two Oxymitter 5000 units
per combustion process, an optional SPS 4000
Single Probe Autocalibration Sequencer can be
used with each Oxymitter 5000 to provide
automatic calibration gas sequencing. The SPS
4000 can be mounted directly to the Oxymitter
5000 or in a remote location if space is limited.
The sequencer performs autocalibrations based on
the CALIBRATION RECOMMENDED signal
from the Oxymitter 5000, a timed interval set up in
fieldbus, or whenever a calibration request is
initiated.
IB-106-350
Figure 1-2. Oxymitter 5000 Autocalibration
System Options
1-2
Integral electronics eliminates traditional
6.
wiring between probe and electronics.
The integral electronics are adaptable for
7.
line voltages from 90-250 VAC; therefore,
no configuration is nece ssary.
The Oxymitter 5000 membrane keypad is
8.
available in five languages:
English
French
German
Italian
Spanish
An operator can calibrate and diagnostically
9.
troubleshoot the Oxymitter 5000 in one of
three ways:
(c) Optional IMPS 4000. The Program-
mable Logic Controller (PLC) in the
IMPS 4000 provides fault indications
using flashing LEDs and LCD display
messages. Refer to the IMPS 4000
Intelligent Multiprobe Test Gas
Sequencer Instruction Bulletin for
more information.
f. Handling the Oxymitter 5000.
It is important that printed circuit
boards and integrated circuits are
handled only when adequate antistatic
precautions have been taken to prevent
possible equipment damage.
(a) Membrane Keypad. The membrane
keypad, housed within the right side
of the electronics housing, provides
fault indication by way of flashing
LEDs. Calibration can be performed
from the membrane keypad.
OUNDATION
(b) F
fieldbus Interface. The
Oxymitter 5000’s output carries a signal containing the oxygen level encoded in digital format. This digital
output can also be used to communicate with the Oxymitter and access all
of the Oxymitter’s status information.
The Oxymitter 5000 is designed for
industrial applications. Treat each
component of the system with care to
avoid physical damage. Some probe
components are made from ceramics,
which are susceptible to shock when
mishandled.
g. System Considerations. Prior to installing your
Oxymitter 5000, make sure you have all the
components necessary to make the system installation. Ensure all the components are prop e rly
integrated to make the system functional.
IB-106-350
1-3
After verifying that you have all the components,
select mounting locations and determine how
each component will be placed in terms of available line voltage, ambient temperatures, environmental considerations, convenience, and
serviceability. Figure 1-3 shows a typical system
wiring. A typical system installation is illustrated
in Figure 1-4.
A source of instrument air is optional at the
Oxymitter 5000 for reference air use. Since the
unit is equipped with an in-place calibration feature, provisions can be made to permanently
connect calibration gas tanks to the Oxymitter
5000.
If the calibration gas bottles will be permanently
connected, a check valve is required next to the
calibration fittings on the integral electronics.
This check valve is to prevent breathing of the
calibration gas line and subsequent flue gas co ndensation and corrosion. The check valve is in
addition to the stop valve in the calibration gas
kit or the solenoid valves in the IMPS 4000 or
SPS 4000.
NOTE
The integral electronics is rated NEMA 4X
(IP66) and is capable of operation at temperatures up to 149°F (65°C).
Retain the packaging in which the
Oxymitter 5000 arrived from the factory in
case any components are to be shipped to
another site. This packaging has been
designed to protect the product.
1-3. IMPS 4000 (OPTIONAL). Information on the
IMPS 4000 is available in the IMPS 4000 Intelligent
Multiprobe Test Gas Sequencer Instruction Bulletin.
OXYMITTER 5000
WITH INTEGRAL ELECTRONICS
2 CALIBRATION GAS LINES
BY CUSTOMER
[300 FT (90 M) MAX]
Figure 1-3. Oxymitter 5000 F
LINE VOLTAGE
OUNDATION
FIELDBUS DIGITAL
SIGNAL
Fieldbus Connections
FIELDBUS COMPUTER
TERMINAL
28550005
IB-106-350
1-4
GASES
STACK
STANDARD
DUCT
OXYMITTER
5000
LINE
VOLTAGE
LOGIC I/O
FIELDBUS
DIGITAL
SIGNAL
FLOWMETER
CALIBRATION
GAS
ADAPTOR
PLATE
PRESSURE
REGULATOR
VOLTAGE
INSTRUMENT
AIR SUPPLY
(REFERENCE AIR)
STACK
ADAPTOR
PLATE
OXYMITTER
5000
LINE
GASES
IMPS 4000 OPTION
DUCT
CALIBRATION
GAS
CALIBRATION GAS 2
CALIBRATION GAS 1
INST. AIR
SUPPLY
(WITH REFERENCE AIR OPTION)
SPS 4000 OPTION
GASES
DUCT
STACK
OXYMITTER
5000
INSTRUMENT
AIR SUPPLY
CALIBRATION
CALIBRATION
(LOWGAS)
LINE
VOLTAGE
FIELDBUS DIGITAL SIGNAL,
RELAY OUTPUTS, AND
REMOTE CONTACT INPUT
Figure 1-4. Typical System Installation
FIELDBUS
DIGITAL
SIGNAL
ADAPTOR
PLATE
CALIBRATION GAS 1
(HIGHGAS)CALIBRATION
GAS 2
LOGIC I/O
REFERENCE
AIR
IMPS 4000
28550006
IB-106-350
1-5
CALIBRATION GAS
FLOWMETER
FRONT VIEW
REFERENCE GAS
FLOWMETER
REAR VIEW (OF MANIFOLD ONLY)
CALIBRATION GAS 1
INTERFACE
BOARD
(HIGH CALIBRATION GAS)
SOLENOID
REFERENCE AIR
PRESSURE
REGULATOR
(OPTIONAL)
NOTE:
MANIFOLD COVER IS
REMOVED TO SHOW
INTERNAL COMPONENTS.
ALSO, BOARD COMPONENTS
ARE NOT SHOWN FOR
CLARITY.
TERMINAL
COVER
POWER
SUPPLY BOARD
CALIBRATION GAS 2
(LOW CALIBRATION GAS)
Figure 1-5. SPS 4000
1-4. SPS 4000 (OPTIONAL). The SPS 4000 Single
Probe Autocalibration Sequencer provides the capability of performing automatic, timed or on demand,
calibrations of a single Oxymitter 5000 without
sending a technician to the installation site.
a. Mounting. The SPS 4000 can be mounted ei-
ther directly to an Oxymitter 5000 or at a remote
location if space is limited. In addition, the integrally mounted SPS 4000 can be configured for a
horizontally or vertically mounted Oxymitter
5000 (Figure 2-2). The information in this instruction bulletin will cover the integrally
mounted units only. For information on remote
mounted units, refer to the SPS 4000 Single
consists of a manifold and a calibration gas
flowmeter. The manifold provides electrical
feedthroughs and calibration gas ports to route
power and signal connections and calibration
gases to and from the sequencer. In addition, the
manifold houses two calibration gas solenoids
that sequence the gases to the Oxymitter 5000, a
pressure switch that detects low calibration gas
pressure, and two PC boards. A terminal strip
housed within the terminal cover provides
convenient access for all user connections.
IB-106-350
1-6
Components optional to the SPS 4000 include a
reference air flowmeter and pressure regulator.
The reference air flowmeter indicates the flow
rate of reference air continuously flowing to the
Oxymitter 5000. The reference air pressure
regulator ensures the instrument air (reference
air) flowing to the Oxymitter 5000 is at a constant pressure [20 psi (138 kPa)]. The regulator
also has a filter to remove particulates in the reference air and a drain valve to bleed the moisture
that collects in the filter bowl.
Brass fittings and Teflon tubing are standard.
Stainless steel fittings and tubing are optional.
Also, disposable calibration gas bottles are avail-
able as an option or ca n be purchased through a
local supplier.
c. Operation. The SPS 4000 works in conjunction
with the Oxymitter 5000’s CALIBRATION
RECOMMENDED feature to perform an autocalibration. This feature automatically performs a
gasless calibration check every hour on the Oxymitter 5000. If a calibration is recommended and
its contact output signal is set for “handshaking”
with the sequencer, the Oxymitter 5000 sends a
signal to the sequencer. The sequencer automatically performs a calibration upon receiving the
signal. Thus, no human interface is required for
the automatic calibration to take place.
IB-106-350
1-7
1-5. SPECIFICATIONS.
Table 1-1. Specifications
Oxymitter 5000
O2 Range:
Standard ....................................................................0 to 10% O
0 to 25% O
0 to 40% O2 (via F
Accuracy ...........................................................................±0.75% of reading or 0.1% O
2
2
OUNDATION
fieldbus)
, whichever is greater
2
System Response to Calibration Gas ..............................Initial response in less than 3 seconds T90 in less than
8 seconds
Temperature Limits:
Process .......................................................................32° to 1300°F (0° to 704°C) up to 2400°F (1300°C) with
optional accessories
Electronics .................................................................-40° to 149°F (-40° to 65°C) Ambient
Probe Lengths ...................................................................18 in. (457 mm)
3 ft (0.91 m)
6 ft (1.83 m)
9 ft (2.74 m)
12 ft (3.66 m)
Mounting and M ounting Position ...................................Vertical or horizontal
Materials:
Probe ..........................................................................Wetted or welded parts - 316L stainless steel
Non-wetted parts - 304 stainless steel, low-copper aluminum
Calibration ........................................................................Manual, semi-automatic, or automatic
Calibration Gas Mixtures Recommended ......................0.4% O
8% O2, Balance N
, Balance N
2
2
2
Calibration Gas Flow .......................................................5 scfh (2.5 l/m)
Reference Air ....................................................................2 scfh (1 l/m), clean, dry, instrument-quality air
(20.95% O
), regulated to 5 psi (34 kPa)
2
Electronics ........................................................................NEMA 4X, IP66 with fitting and pipe on reference exhaust
port to clear dry atmosphere
Electronic Noise ................................................................Meets EN 50082-2 Generic Immunity Std. Part II.
Includes EN 61000-4-2 for Electrostatic Discharge
4 KV contact, 8 KV in air
Includes IEC 801-4 for fast transients; 2 KV on power supply
and control lines
Line Voltage ......................................................................90-250 VAC, 50/60 Hz. No configuration necessary
3/4 in. - 14 NPT conduit port
Signals:
Digital Output ...........................................................F
OUNDATION
fieldbus compatible
Logic I/O ....................................................................Two-terminal logic contact configurable as either an alarm
output or as a bi-directional calibration handshake signal to
IMPS 4000 or SPS 4000
..............................................................................Self-powered (+5 V), in series with 340 ohms
..............................................................................Conduit ports — 3/4 in.-14 NPT (one threaded hole for both
analog output and logic I/O)
IB-106-350
1-8
Table 1-1. Specifications (Continued)
Power Requirements:
Probe Heater .............................................................175 W nominal
Electronics .................................................................10 W nominal
Maximum ...................................................................500 W
SPS 4000
Mounting ..........................................................................Integral to Oxymitter 5000
to/from Oxymitter 5000 (self-powered) ..................5 V (5 mA maximum)
Cal Initiate Contact Input from Control Room ............5 VDC (self-powered)
Relay Outputs to Control Room .....................................5 to 30 VDC, Form A (SPST)
(one “In-Cal”, one “Cal Failed”)
Cabling Distance between
SPS 4000 and Oxymitter 5000 .................................Maximum 1000 ft (303 m)
Piping Distance between SPS 4000
and Oxymitter 5000 ..................................................Maximum 300 ft (91 m)
Approximate Shipping Weight .......................................10 lbs (4.5 kg)
Fisher-Rosemount has satisfied all obligations coming from the European legislation to harmonize the product
requirements in Europe.
IB-106-350
1-9
OXT5A Oxymitter 5000 In Situ Oxygen Transmitter
Oxygen Transmitter - Instruction Book
CodeSensing Probe Type
1ANSI (N. American Std.) Probe with Ceramic Diffuser
2ANSI Probe with Flame Arrestor and Ceramic Dif fuser
3ANSI Probe with Snubber Diffuser
4DIN (European Std.) Probe with Ceramic Diffuser
5DIN Probe with Flame Arrestor and Snubber Diffuser
6DIN Probe with Snubber Diffuser
7JIS (Japanese Std.) Probe with Ceramic Diffuser
8JIS Probe with Flame Arrestor and Ceramic Diffuser
9JIS Probe with Snubber Diffuser
CodeProbe Assembly
018 in. (457 mm) Probe
118 in. (457 mm) Probe with Abrasive Shield
23 ft (0.91 m) Probe
33 ft (0.91 m) Probe with Abrasive Shield
46 ft (1.83 m) Probe
56 ft (1.83 m) Probe with Abrasive Shield
69 ft (2.74 m) Probe
79 ft (2.74 m) Probe with Abrasive Shield
812 ft (3.66 m) Probe
(1)
912 ft (3.66 m) Probe with Abrasive Shield
Table 1-2. Product Ma t rix
(1)
(1)
(1)
(1)
(1)
CodeMounting Hardware - Stack Side
0No Mounting Hardware (“0” must be chosen under “Mounting Hardware - Probe Side” below)
1New Installation - Square weld plate with studs
2Mounting to Model 218 Mounting Plate (with M odel 218 Shield Removed)
3Mounting to Existing Model 218 Support Shield
4Mounting to Other Mounting
(2)
5Mounting to Model 132 Adaptor Plate
CodeMounting Hardware - Probe Side
0No Mounting Hardware
1Probe Only (ANSI) (N. American Std.)
2New Bypass or Abrasive Shield (ANSI)
4Probe Only (DIN) (European Std.)
5New Bypass or Abrasive Shield (DIN)
7Probe Only (JIS) (Japanese Std.)
8New Bypass or Abrasive Shield (JIS)
CodeElectronics Housing & Filtered Customer Termination - NEMA 4X, IP66
00No Hardware
01Calibration Gas Flowmeter and Reference Air Set
02Intelligent Multiprobe S equencer (Refer to Table 1-4)
XXSingle Probe Sequencer – mounted to Oxy m i tter 5000 (Refer to Table 1-6)
Cont’d100XXExample
NOTES:
(1)
Recommended usages: High velocity particulates in flue s tream, installation within 11.5 f t (3.5 m) of soot blowers or heavy salt cake
buildup. Applications: Pulverized coal, recovery boil ers, lime kiln. Regardless of appli cation, abrasive shields with support brackets are
recommended for 9 ft (2.74 m) and 12 ft (3.66 m) probe installations, particularly horizontal installati ons.
(2)
Where possible, specify SPS number; otherwise, prov ide details of the existing mounting plate as follows:
Plate with studsBolt circle diameter, num ber, and arrangement of studs, stud thread, s tud height above mounting plate.
Plate without studsBolt circle diameter, number, and arrangement of holes, thread, depth of stud mounting plate with accessori es.
Table 1-3. Calibration Gas Bottles
PART
NUMBERDESCRIPTION
1A99119G01Two disposable calibration gas bottles — 0.4% and 8% O2,
balance nitrogen — 550 liters each, includes bottle rack *
1A99119G02Two flow regulators f or calibration g as bottles
*Calibration gas bottles cannot be shipped via airfreight.
When the bottles are used with “CALIBRATION RECOMMENDED” features,
the bottles should provide 2 to 3 years of calibrations in normal service.
IB-106-350
1-11
Table 1-4. Intelligent Multiprobe Test Gas Sequencer Versions
NUMBER
PART
NUMBERDESCRIPTION
OF OXYMITTER
5000 UNITS
3D39695G01IMPS1
3D39695G02IMPS2
3D39695G03IMPS3
3D39695G04IMPS4
3D39695G05IMPS w/115 V Heater1
3D39695G06IMPS w/115 V Heater2
3D39695G07IMPS w/115 V Heater3
3D39695G08IMPS w/115 V Heater4
3D39695G09IMPS w/220 V Heater1
3D39695G10IMPS w/220 V Heater2
3D39695G11IMPS w/220 V Heater3
3D39695G12IMPS w/220 V Heater4
Table 1-5. Z-Purge Option for Use with IMPS 4000
PART
NUMBERDESCRIPTION
4513C24G03Z-Purge System for IMPS used with Oxymitter 5000
4513C24G03Z-Purge System for IMPS used with Oxymitter 5000,
includes loss of purge switch (WPS)
Table 1-6. Single Probe Autocalibration Sequencer Coding
OXYMITTER
REF AIR
SET
FITTINGS/
TUBING
5000
MOUNTING
BRASS/
CODENOYES
TEFLONSTSTEELHORVERT
03XXX
04XXX
05XXX
06XXX
07XXX
08XXX
09XXX
10XXX
IB-106-350
1-12
SECTION II. INSTALLATION
Before installing this equipment, read
the “Safety instructions for the wiring
and installation of this apparatus” at the
front of this Instruction Bulletin. Failure
to follow the safety instructions could
result in serious injury or death.
2-1. MECHANICAL INSTALLATION.
a. Selecting Location.
The location of the Oxymitter 5000 in the
1.
stack or flue is most important for maximum accuracy in the oxygen analyzing process. The Oxymitter 5000 must be
positioned so the gas it measures is representative of the process. Best results are
normally obtained if the Oxymitter 5000 is
positioned near the center of the duct (40 to
60% insertion). Longer ducts may require
several Oxymitter 5000 units since the O
can vary due to stratification. A point too
near the wall of the duct, or the inside radius of a bend, may not provide a representative sample because of the very low
flow conditions. The sensing point should
be selected so the process gas temperature
falls within a range of 32° to 1300°F (0° to
704°C). Figure 2-1 through Figure 2-6 provide mechanical installation references. The
ambient temperature of the integral electronics housing must not exceed 149°F
(65°C).
Check the flue or stack for holes and air
2.
leakage. The presence of this condition will
substantially affect the accuracy of the oxygen reading. Therefore, either make the
necessary repairs or install the Oxymitter
5000 upstream of any leakage.
2 2
2
Ensure the area is clear of internal and ex-
3.
ternal obstructions that will interfere with
installation and maintenance access to the
membrane keypad. Allow adequate clearance for removal of the Oxymitter 5000
(Figure 2-1 or Figure 2-2).
Do not allow the temperature of the
Oxymitter 5000 integral electronics to
exceed 149°F (65°C) or damage to the
unit may result.
b. Installation.
Ensure all components are available to in-
1.
stall the Oxymitter 5000. If equipped with
the optional ceramic diffusor element, ensure it is not damaged.
The Oxymitter 5000 may be installed intact
2.
as it is received.
NOTE
An abrasive shield is recommended for high
velocity particulates in the flue stream (such
as those in coal-fired boilers, kilns, and recovery boilers). Vertical and horizontal
brace clamps are provided for 9 ft and 12 ft
(2.75 m and 3.66 m) probes to provide mechanical support for the Oxymitter 5000.
Refer to Figure 2-6.
Weld or bolt adaptor plate (Figure 2-5) onto
3.
the duct.
IB-106-350
2-1
E
R
E
H
P
S
O
-
M
T
G
A
N
I
N
E
R
V
A
I
W
S
O
-
L
P
X
E
N
R
SMART FAMILY
Rosemount Analytical Inc.
R
E
R
E
H
P
S
O
M
-
T
G
A
N
I
N
E
R
V
A
I
W
S
O
-
ALL DIMENSIONS ARE IN
INCHES WITH MILLIMETERS
IN PARENTHESES.
INSULATE IF EXPOSEDTO
NOTE:
AMBIENT WEATHER CONDITIONS
L
P
X
E
N
-
I
TM
HART
800-433-6076
Orrville,OH 44667-0901
TM
OXYMITTER 4000
-
I
85.8
49.8
31.8
(808)
16
(406)
18 IN.
34
3 FT
(1265)
70
(864)
6 FT
DIM "B"
REF.
GAS
DIM "A"
E
V
I
L
A
T
I
U
C
R
I
C
N
E
H
W
T
H
G
I
T
P
-
E
E
K
500VA
5 Amps
3/4 NPT
ELEC CONN
REF AIR
PROBE
TABLE 2 INSTALLATION/REMOVAL
121.8
(2179)
106
(1778)
(3094)
(2692)
9 FT
157.8
(4008)
142
(3607)
12 FT
6 mm TUBEJIS
4-20 mA
85-264VAC 48-62 Hz
SERIAL NO.
TAG NO.
VOLTS:WATTS:
OUTPUT: LINE FUSE:
E
V
I
L
A
T
I
U
C
R
I
C
N
E
H
W
T
H
G
I
T
P
-
E
E
K
CAL GAS
ANSI 1/4 (6.35) TUBE
DIN 6 mm TUBE
12
(305)
6.52
(39)
1.55
(166)
2.89
(73)
COVER REMOVAL & ACCESS
12
(305)
.062 THK GASKET
PROCESS FLOW MUST BE IN
THIS DIRECTION WITH RESPECT
TO DEFLECTOR 3534B48G01
3535B18H02
3535B46H01
3535B45H01
DIN
JIS
ANSI
2.27 (58)
DIA MAX
CAL.
GAS
3.80(96)
ADD TO DIM “A”
FOR PROBE
DIM "B"
12.50 (318)
6.02 (153)
4.77 (121)
WITH
DIM "A"
STANDARD
DIFFUSER
5.14(131)
WITH CERAMIC
ADD TO DIM “A”
FOR PROBE WITH
REMOVAL ENVELOPE
JIS
SNUBBER
DIFFUSER
4512C18H01
DIN
4512C19H01
ARRESTOR
AND FLAME
CERAMIC DIFFUSER
ANSI
TABLE 1 MOUNTING FLANGE
4512C17H01
0.59
6.10
(155)
0.71
7.28
(185)
0.75
6.00
(153)
HOLE
FLANGE
DIA
(15)
5.12
5.71
(18)
(20)
4.75
(4) HOLES
DIA
(130)
(145)
(121)
EQ SP
ON BC
BOTTOMVIEW
26170013
Figure 2-1. Oxymitter 5000 Installation
IB-106-350
2-2
1/4 IN. TUBE
FITTING FOR
HIGH CAL
GAS IN
HORIZONTAL MOUNTED SPS 4000 A
1/4 IN. TUBE FITTING FOR
INSTRUMENT AIR IN (OPTIONAL)
11.00
(279.40)
NOMINAL
0.94
(23.88)
TERMINAL
COVER
1/4 IN. TUBE
FITTING
TO CAL GAS
FLOWMETER
1/4 IN. TUBE
FITTING FOR
LOW CAL
GAS IN
0.94
(23.88)
2.00 (50.80)
1/2 NPT SIGNAL
CONDUIT PORT
(CUSTOMER TO
SUPPLY FITTING)
14.00 (355.60)
NOMINAL
12.00 (304.80)
NOMINAL
VERTICAL MOUNTED SPS 4000 A
13.00
(330.20)
NOMINAL
1/2 IN. CONDUIT
FITTING FOR
LINE VOLTAGE
10 (254)
NOMINAL
2.00 (50.80)
NOMINAL
CLEARANCE TO
REMOVE COVER
NOTE:
DIMENSIONS ARE IN INCHES
WITH MILLIMETERS IN PARENTHESES.
(BOTH BRACE CLAMP ASSEMBLIES ARE THE SAME.
INSTALLATION AND LOCATION OF CLAMP ASSEMBLIES
AND BRACE BARS TO BE DONE IN FIELD.)
5.62
(143)
ABRASIVE SHIELD
BY ROSEMOUNT
}
4.12
(105)
NOTE: BRACING IS FOR VERTICAL AND HORIZONTAL OXYMITTER 4000
INSTALLATION. EXTERNAL BRACING REQUIRED FOR 9 FT AND 12 FT
(2.75 M AND 3.66 M) PROBES AS SHOWN ABOVE.
0.375
1.00
(25) MAX
Figure 2-6. Oxymitter 5000 Bracing Installation
If using the optional ceramic diffusor ele-
4.
ment, the vee deflector must be correctly
oriented. Before inserting the Oxymitter
5000, check the direction of flow of the gas
in the duct. Orient the vee deflector so the
apex points upstream toward the flow
(Figure 2-7). This may be done by loosening the setscrews and rotating the vee deflector to the desired position. Retighten the
setscrews.
In vertical installations, ensure the system
5.
cable drops vertically from the Oxymitter
5000 and the conduit is routed below the
level of the electronics housing. This drip
loop minimizes the possibility that moisture
will damage the electronics (Figure 2-8).
(10)
36.00 (914)
5.62
(143)
GAS FLOW
DIRECTION
VEE
DEFLECTOR
APEX
DIFFUSION
FILTER
ELEMENT
Figure 2-7. Orienting the Optional Vee Deflector
26170034
SETSCREW
DEFLECTOR
VEE
22220020
IB-106-350
2-7
REPLACE INSULATION
AFTER INSTALLING
OXYMITTER 5000
INSULATION
LINE
VOLT AGE
FIELDBUS
DIGIT AL
SIGNAL
E
V
I
-
L
A
E
R
T
E
I
H
P
S
O
-
M
T
G
A
N
I
N
E
R
V
A
I
W
S
O
L
P
X
U
C
R
I
C
N
E
H
W
-
T
H
E
G
I
T
N
I
P
-
E
E
K
DRIP
LOOP
CAL.
GAS
ADAPTOR
PLATE
Figure 2-8. Installation with Drip Loop and Insulation Removal
If the system has an abrasive shield, check
6.
the dust seal gaskets. The joints in the two
gaskets must be staggered 180°. Also, make
sure the gaskets are in the hub grooves as
the Oxymitter 5000 slides into the 15°
forcing cone in the abrasive shield.
NOTE
If process temperatures will exceed 392°F
(200°C), use anti-seize compound on stud
threads to ease future removal of Oxymitter
5000.
Insert probe through the opening in the
7.
mounting flange and bolt the unit to the
flange. When probe lengths selected are 9
STACK OR DUCT
METALWALL
28550007
or 12 ft (2.74 or 3.66 m), special brackets
are supplied to provide additional support
for the probe inside the flue or stack (Figure
2-6).
Uninsulated stacks or ducts may cause
ambient temperatures around the electronics to exceed 149°F (65°C), which
may cause overheating damage to the
electronics.
If insulation is being removed to access the
8.
duct work for Oxymitter 5000 mounting,
make sure the insulation is replaced afterward (Figure 2-8).
IB-106-350
2-8
2-2. ELECTRICAL INSTALLATION (FOR OXY-
MITTER 5000 WITHOUT SPS 4000). All wir-
ing must conform to local and national codes.
Disconnect and lock out power before
connecting the unit to the power supply.
Install all protective equipment covers
and safety ground leads after installation. Failure to install covers and
ground leads could result in serious injury or death.
To meet the Safety Requirements of IEC
1010 (EC requirement), and ensure safe
operation of this equipment, connection
to the main electrical power supply must
be made through a circuit breaker (min
10 A) which will disconnect all currentcarrying conductors during a fault
situation. This circuit breaker should
also include a mechanically operated
isolating switch. If not, then another external means of disconnecting the supply
from the equipment should be located
close by. Circuit breakers or switches
must comply with a recognized standard
such as IEC 947.
NOTE
To maintain CE compliance, ensure a good
connection exists between the mounting
flange bolts and earth.
wire to the L1 terminal and the neutral, or L2
wire, to the N terminal (Figure 2-9). The Oxymitter 5000 automatically will configure itself for
90-250 VAC line voltage and 50/60 Hz. The
power supply requires no setup.
c. Connect fieldbus Digital Signal and Logic I/O/
Calibration Handshake Leads (Figure 2-9).
Fieldbus Digital Signal. The fieldbus digital
1.
signal carries the O
value. This digital sig-
2
nal can also be used to communicate with
the Oxymitter.
Logic I/O/Calibration Handshake. The out-
2.
put can either be an alarm or provide the
handshaking to interface with an IMPS
4000. For more information, refer to paragraph 5-3 and the IMPS 4000 Intelligent
Multiprobe Test Gas Sequencer Instruction
Bulletin.
If autocalibration is not utilized, a common
3.
bi-directional logic contact is provided for
any of the diagnostic alarms listed in Table
5-1. The assignment of alarms which
Figure 2-9. Terminal Block
IB-106-350
2-9
can actuate this contact can be modified to
one of seven additional groupings listed in
Table 3-1.
The logic contact is self-powered, +5 VDC,
340 ohm series resistance. An interposing
relay will be required if this contact is to be
utilized to annunciate a higher voltage device, such as a light or horn, and may also
be required for certain DCS input cards. A
Potter & Brumfield R10S-E1Y1-J1.0K 3.2
MA DC or an equal interposing relay will
be mounted where the contact wires terminate in the control/relay room.
Install all protective equipment covers
and safety ground leads after installation. Failure to install covers and
ground leads could result in serious injury or death.
Disconnect and lock out power before
connecting the unit to the power supply.
d. Install terminal block cover (31, Figure 6-1) and
secure with cover lock (38), gasket (37), and
screw (36).
2-3. ELECTRICAL INSTALLATION (FOR OXY-
MITTER 5000 WITH SPS 4000). All wiring
must conform to local and national codes.
To meet the Safety Requirements of IEC
1010 (EC requirement), and ensure safe
operation of this equipment, connection
to the main electrical power supply must
be made through a circuit breaker (min
10 A) which will disconnect all currentcarrying conductors during a fault
situation. This circuit breaker should
also include a mechanically operated
isolating switch. If not, then another external means of disconnecting the supply
from the equipment should be located
close by. Circuit breakers or switches
must comply with a recognized standard
such as IEC 947.
a. Autocalibration Connections.
Autocalibration systems will inject gases into the
probe and make electronic adjustments with no
operator attention required. The SPS 4000 provides solenoid valves and circuitry for calibrating
a single Oxymitter 5000 unit.
The SPS 4000 autocalibration system utilizes the
Oxymitter 5000’s bidirectional logic contact as a
“handshake” signal; therefore, this signal is not
available for alarming purposes.
The following contacts ar e provided through the
autocalibration system:
One contact closure per probe from the
1.
control room to the SPS 4000 for “calibration initiate”.
One contact output per probe from SPS
2.
4000 to the control room for “in calibration” notification.
One contact per probe from SPS 4000 to
3.
the control room for “calibration failed”
notification, which includes output from
pressure switch indicating “cal gas bottles
empty”.
IB-106-350
2-10
NOTE
The fieldbus digital signal can be
configured to respond normally during a ny
calibration, or can be configured to hold the
last O
value upon the intitiation of
2
calibration. Factory default is for the
fieldbus signal to operate normally
throughout calibration. Holding the last O
value may be useful if several probes are
being averaged for the purpose of
automatic control. Unless several probes
are being averaged, always place any
control loops using the O
signal into
2
manual prior to calibrating.
b. Other Electrical Connections.
Remove screws (26, Figure 6-11) securing
1.
terminal cover (27). Remove the cover to
expose terminal strip (25).
Connect Line Voltage. Ro ute the line volt-
2.
age leads into the manifold through the
1/2 in. line voltage conduit fitting (Figure
2-2) and out through the bottom of the
manifold. Connect the LINE IN and NEUTRAL leads to terminals L and N, respectively, as shown in Figure 2-10. Also, be
2
sure to connect the ground wire to the
ground lug. The unit automatically will configure itself for 90 to 250 VAC line voltage
and 50/60 Hz. The power supply requires
no setup.
Connect Remote Contact Inp ut Wiring. To
3.
set up the SPS 4000 to initiate a calibration
from a remote location, route the 5 VDC
calibration initiate contact input leads
through the 1/2 in. NP T signal conduit port
(Figure 2-2) and out thr ough the bottom of
the manifold. Connect the (+) and (-) CAL
INITIATE leads to terminals 1 and 2, respectively, as shown in Figure 2-10.
Figure 2-10. SPS 4000 Electrical Connections
IB-106-350
2-11
Figure 2-11. Air Set, Plant Air Connection
Connect Relay Output Wiring. Relay con-
4.
nections are available to signal when the
Oxymitter 5000 is in calibration or when
calibration failed. Relay outputs can be
connected to either indicator lights or a
computer interface. The relay contacts are
capable of handling a 5 to 30 VDC maximum power source. The cabling requirement is 1000 ft (303 m) maximum. Route
the relay output leads through the 1/2 in.
NPT signal conduit port (Figure 2-2) and
out through the bottom of the manifold.
Connect the (+) and (-) CAL FAIL leads
and the (+) and (-) IN CAL leads to terminals 7, 8, 9, and 10, respectively, as shown
in Figure 2-10.
Connect fieldbus Digital Signal Wiring.
5.
Route the signal wiring into the manifold
through the 1/2 in. NP T signal conduit port
(Figure 2-2) and out thr ough the bottom of
the manifold. Connect the (+) and (-) signal
leads to terminals 3 and 4, respectively, as
shown in Figure 2-10.
Once all connections are made, install ter-
6.
minal cover (27, Figure 6-11) and secure
with screws (26).
2-4. PNEUMATIC INSTALLATION (FOR OXY-
MITTER 5000 WITHOUT SPS 4000).
a. Reference Air Package. After the Oxymitter
5000 is installed, connect the reference air set to
the Oxymitter 5000. The reference air set should
be installed in accordance with Figure 2-11.
Instrument Air (Reference Air): 10 psig
(68.95 kPag) minimum, 225 psig (1551.38 kPag)
maximum at 2 scfh (56.6 L/hr) maximum; less
than 40 parts-per-million total hydrocarbons.
Regulator outlet pressure should be set at 5 psi
(35 kPa). Reference air can be supplied by the
reference air set of the IMPS 4000.
If using an IMPS 4000, refer to the IMPS 4000
Intelligent Multiprobe Test Gas Sequencer Instruction Bulletin for the proper reference air
connections.
IB-106-350
2-12
Do not use 100% nitrogen as a low gas
(zero gas). It is suggested that gas for the
low (zero) be between 0.4% and 2.0%
O2. Do not use gases with hydrocarbon
concentrations of more than 40 parts
per million. Failure to use proper gases
will result in erroneous readings.
b. Calibration Gas. Two calibration gas concen-
trations are used with the Oxymitter 5000, Low
Gas - 0.4% O
and High Gas - 8% O2. See Figure
2
2-12 for the Oxymitter 5000 connections.
2-5. PNEUMATIC INSTALLATION (FOR OXY-
MITTER 5000 WITH SPS 4000).
Do not use 100% nitrogen as a low gas
(zero gas). It is suggested that gas for the
low (zero) be between 0.4% and 2.0%
O2. Do not use gases with hydrocarbon
concentrations of more than 40 parts
per million. Failure to use proper gases
will result in erroneous readings.
a. Calibration Gas Connections. Locate the
1/4 in. calibration gas fittings on the SPS 4000
manifold (Figure 2-2). Connect O
calibration
2
gas 1 (high calibration gas) to the HIGH CALGAS IN fitting and O
calibration gas 2 (low
2
calibration gas) to the LOW CAL GAS IN fitting. Ensure the calibration gas pressure is set at
20 psi (138 kPa).
b. Reference Air Connection (Optional). If the
reference air option (which includes the reference
air flowmeter, pressure regulator, and necessary
tubing and fittings) is used, connect the instrument air to the 1/4 in. fitting on the reference air
pressure regulator (Figure 2-2). The pressure
regulator is factory set at 20 psi (138 kPa). Readjust by turning the knob on the top of the
regulator to obtain the desired pressure.
If the SPS 4000 does not have the reference air
option, connect the reference air to the Oxymitter
5000 as instructed in paragraph 2-4.
R
R
Rosemount Analytical Inc.
SMART FAMILY
Orrville,OH 44667-0901
TM
HART
800-433-6076
TM
OXYMITTER 4000
SERIAL NO.
CALIBRATION GAS
TAG NO.
VOLTS:WATTS:
85-264VAC 48-62 Hz
4-20 mA
OUTPUT: LINE FUSE:
500VA
5 Amps
REFERENCE AIR
Figure 2-12. Oxymitter 5000 Gas Connections
26170025
NOTE
Upon completing installation, make sure that the Oxymitter 5000 is turned
on and operating prior to firing up the combustion process. Damage can
result from having a cold Oxymitter 5000 exposed to the process gases.
During outages, and if possible, leave all Oxymitter 5000 units running to
prevent condensation and premature aging from thermal cycling.
If the ducts will be washed down during outage, MAKE SURE to power
down the Oxymitter 5000 units and remove them from the wash area.
IB-106-350
2-13/2-14
Install all protective equipment covers
and safety ground leads before equipment startup. Failure to install covers
and ground leads could result in serious
injury or death.
NOTE
Refer to Appendices A, B, and C for fieldbus information concerning the Oxymitter
5000.
3-1. GENERAL.
a. Verify Mechanical Installation.
Oxymitter 5000 is installed correctly (Section II,
INSTALLAT ION) .
b. Verify Terminal Block Wiring.
1.
Remove screw (36, Figure 6-1), gasket
(37), and cover lock (38) that secure the
3 3
SECTION III. STARTUP
2.
3.
4.
Ensure the
5.
terminal block cover. Remove the cover to
expose the terminal block (Figure 3-1).
Check the terminal block wiring. Be sure
the power, fieldbus signal, and logic outputs
are properly connected and secure.
Install the housing cover on the terminal
block and secure with cover lock (38,
Figure 6-1), gasket (37), and screw (36).
For an Oxymitter 5000 with an integrally
mounted SPS 4000, remove screws (26,
Figure 6-11) and terminal cover (27).
Check that the power and signal terminations are properly connected to terminal
strip (25) and secure according to instructions in Section II, INSTALLATION.
Install terminal cover (27) and secure with
screws (26).
Figure 3-1. Integral Electronics
IB-106-350
3-1
c. Verify Oxymitter 5000 Configuration (Figure
3-2). Located on the microprocessor board, the
top board, is a switch that controls the simulate
enable status of the Oxymitter 5000. To allow the
Oxymitter to be placed in simulation mode, place
position two of SW2 in the ON position. Once
the Oxymitter has been set to the simulate mode,
switch position two of SW2 to the OFF position
to remove the Oxymitter from simulate mode.
Note that SW2 does not actually place the Oxymitter in simulate mode, it only allows the Oxymitter to be placed into simulate mode through
the fieldbus interface.
Positions 1, 3, and 4 o f SW 2 are not used, and
should remain in the OFF position.
Refer to Appendix A for more information on
using the AI block.
e. Once the cell is up to operating temperature, the
O
percentage can be read:
2
Access TP5 and TP6 next to the membrane
1.
keypad. Attach a multimeter across TP5 and
TP6. The calibration and process gases can
now be monitored. Pressing the INC or
DEC once will cause the output to switch
from the process gas to the calibration gas.
Pressing INC or DEC a second time will increase or decrease the calibration gas parameter. If the keys have been inactive for
one minute, the output reverts to the process
gas. When a calibration has been initiated,
the value at TP5 and TP6 is the % O
seen
2
by the cell. Oxygen levels, as seen on the
multimeter, are:
Typically, the probe’s sensing cell,
which is in direct contact with the process gases, is heated to approximately
1357°F (736°C), and the external temperature of the probe body may exceed
842°F (450°C). If operating conditions
also contain high oxygen levels and
combustible gases, the Oxymitter 5000
may self-ignite.
d. O2 Range. The O2 range of the Oxymitter is set
through the fieldbus interface using the AI block.
8.0% O2 = 8.0 VDC
0.4% O2 = 0.4 VDC
NOTE
The maximum reading available at TP5 and
TP6 is 30 VDC. While the Oxymitter will
measure oxygen concentrations up to 40%,
the test point output will reach a maximum
of 30 VDC at a 30% oxygen concentration.
OUNDATION
F
2.
fieldbus.
IB-106-350
3-2
SIMULATE
ENABLE
HEATERT/C
DIAGNOSTIC
ALARMS
HEATER
O2 CELL
CALIBRATION
CALIBRATION RECOMMENDED
O2 CELL mV +
TEST
POINTS
O2 CELL mV -
HEATERT/C +
HEATERT/C -
INCINC
HIGH
GAS
LOW
GAS
DECDEC
CAL
TEST GAS +
PROCESS -
% O2
TP1
TP2
TP3
TP4
TP5
TP6
1
2
3
4
NOT USED
OFF
NOT USED
NOT USED
SW2
ON
J1
RED
DEFAULT
POSITION
(EX-FACTORY)
YEL
GRN
ORG
NOT USED
ON
NOT USED
NOT USED
Figure 3-2. Oxymitter 5000 Defaults
IB-106-350
3-3
28550011
3-2. LOGIC I/O.T his two-terminal logic contact can
be configured either as a solid-state relay-activated
alarm or as a bi-directional calibration handshake
signal to an IMPS 4000 or SPS 4000. The configuration of this signal depends on the setting of the
IO_PIN_MODE parameter via fieldbus. The different
modes available are described in Table 3-1. The
IO_PIN_MODE and IO_PIN_STATE parameters are
described in Table 3-2.
a. Alarm. When configured as an alarm, this signal
alerts you to an out-of-spec condition. The output
is 5 V in series with a 340 ohm resistor. For optimum performance, Rosemount recommends
connecting the output to a Potter & Bromfield
3.2 mA DC relay (P/N R10S-E1Y1-J1.0K).
Of the ten modes in Table 3-1, modes 0 through
7 are the alarm modes. The factory default is
Table 3-1. Logic I/O Configuration
ModeConfiguration
mode 5 for Oxymitter 5000 units without an
IMPS 4000 or SPS 4000. In this mode, the output will signal when a unit alarm or a
CALIBRATION RECOMMENDED indication
occurs.
b. Calibration Handshake Signal. If using an op-
tional IMPS 4000 or SPS 4000, the logic I/O
must be configured for calibration handshaking.
Of the ten modes in Table 3-1, only modes 8 and
9 are configured fo r calibr ation handshaking. For
an Oxymitter 5000 with an IMPS 4000 or an SPS
4000, the factory sets the default to mode 8. In
this mode, the logic I/O will be used to communicate between the Oxymitter 5000 and sequencer and to signal the sequencer when a
CALIBRATION RECOMMENDATION indication occurs.
0The unit is not configured for any alarm condition.
1The unit is configured for a Unit Alarm.
2The unit is configured for Low O2.
3The unit is configured for both a Unit Alarm and Lo w O2.
4The unit is configured for a High AC Impeda nce/CALIBRATION RECOMMENDED.
5*The unit is configured for both a Unit Alarm and a High AC Impedance/CALIBRATION
RECOMMENDED.
6The unit is configured for both a Low O2 and High AC Impedance/CALIBRATION RECOMMENDED.
7The unit is configured for a Unit Alarm, a Low O2, and a High AC Impedance/CALIBRATION
RECOMMENDED.
8**The unit is configured for a calibration handshake with IMPS 4000 or SPS 4000. CALIBRATION
RECOMMENDED will initiate the calibration cycle.
9The unit is configured for a calibration handshake. CALIBRATION RECOMMENDED will not initiate the
calibration cycle with the IMPS 4000 or SPS 4000.
* The default condition f or an Ox ymitter 5000 with ou t an IMPS 4000 or SPS 4000.
** The defau lt con dition for an Oxymitter 5000 with an IMPS 4000 or SPS 4000.
IB-106-350
3-4
Table 3-2. Logic I/O Parameters
ParameterDefinitionRange
Parameter
Number
IO_PIN_MODEThis parameter represents the operating mode of the
discrete IO pin of the transmitter.
IO_PIN_STATEThis parameter represents the current state of the
transmitter’s discrete IO pin. 0=FALSE, 1=TRUE.
3-3. RECOMMENDED CONFIGURATION.
a. Fieldbus Signal Upon Critical Alarm. When a
critical alarm occurs which causes the O2 reading
to become unstable or unreliable, the Oxymitter
will flag the O
reading. All further O2 readings
2
will be flagged as Out Of Service until the problem has been corrected.
If the O
measurement is being utilized as part of
2
an automatic control loop, the loop should be
placed in manual upon this failure event, or other
appropriate action should be taken.
b. Calibration. Rosemount recommends utilizing
an autocalibration system, actuated by the “calibration recommended” diagnostic. New O
may operate for more than a year, but older cells
may require recalibration every few weeks as
they near the end of their life. This strategy ensures that the O
reading is always accurate, and
2
eliminates many unnecessary calibrations based
on calendar days or weeks since previous calibration. When utilizing the SPS 4000 or the
IMPS 4000, consider wiring some or all associated alarm contacts.
cells
2
1-1040
0-141
CALIBRATION INITIATE. Contact from
1.
the control room to an SPS 4000 or IMPS
4000 (one per probe) provides the ability to
manually initiate a calibration at any time
from the control room. Note that calibrations can also be initiated via fieldbus or
from the keypad on the Oxymitter 5000.
IN CALIBRATION. One contact per
2.
probe provides notification to the control
room that the “calibration recommended”
diagnostic has initiated an automatic calibration through the SPS 4000 or IMPS
4000. If the O
signal is being utilized in an
2
automatic control loop, this contact should
be utilized to place the control loop into
manual during calibration.
CALIBRATION FAILED. One contact
3.
per probe from and SPS 4000 or IMPS
4000 to the control room for notification
that the calibration procedure failed.
Grouped with this alarm is an output from a
pressure switch that indicates when the
calibration gas bottles are empty.
IB-106-350
3-5
3-4. POWER UP.
a. Startup Display. When power is applied to the
probe, the cell heater turns on. It takes approximately one half hour for the cell to heat to operating temperature. This condition is indicated by
the top four LEDs (DIAGNOSTIC ALARMS)
on the membrane keypad (Figure 3-3). Starting
with the CALIBRATION LED, the LEDs light
in ascending order until all four LEDs are on. At
this point, all four turn off and the cycle starts
again. This ramp cycle continues until the cell is
up to operating tempe rature.
b. Operating Display. The ramp cycle turns into a
cycle where the diagnostic LEDs light in sequence from the top to the bottom, one at a time.
HEA TERT/C
DIAGNOSTIC
ALARMS
CALIBRATION RECOMMENDED
TEST
POINTS
INC INC
HIGH
LOW
GAS
GAS
DEC DEC
HEA TER
O2 CELL
CALIBRATION
O2 CELL mV +
O2 CELL mv -
HEATERT/C +
HEATERT/C -
CAL
TEST GAS +
PROCESS -
% O2
TP1
TP2
TP3
TP4
TP5
TP6
SW2
After the bottom LED turns on, the sequence
starts again at the top with the HEATER T/C
LED (Figure 3-3).
Error. If there is an error condition at
1.
startup, one of the diagnostics LEDs will be
blinking. Refer to Section V, TROUBLESHOOTING, to determine the cause of the
error. Clear the error, cycle power, and the
operating display should return.
Keypad. The five membrane keys on the
2.
membrane keypad are only used during
calibration to adjust the high and low gas
and to initiate the calibration sequence
(Figure 3-4).
HEATER T/C
HEATER
O CELL
2
ON
J1
YEL
RED
GRN
ORG
CALIBRATION
HEATER T/C
HEATER
O CELL
2
CALIBRATION
1
2341234
LIGHTING SEQUENCE DURING NORMAL OPERATION
1
2341234
LIGHTING SEQUENCE DURING WARM-UP
Figure 3-3. Startup and Normal Operation
IB-106-350
3-6
28550012
HEATER T/C
DIAGNOSTIC
ALARMS
CALIBRATION
CALIBRATION REQUIRED
02 CELL mV +
TEST
POINTS
02 CELL mv HEATER T/C +
HEATER T/C -
HEATER
02 CELL
3-5. START UP OXYMITTER 5000 CALIBRA-
TION. Refer to Section VI, MAINTENANCE AND
SERVICE, for calibration instructions.
3-6. IMPS 4000 CONNECTIONS. See the IMPS 4000
Intelligent Multiprobe Test Gas Sequencer Instruction Bulletin for wiring and pneumatic connections.
INCINC
HIGH
DECDEC
GAS
LOW
GAS
TEST GAS +
PROCESS -
Figure 3-4. Calibration Keys
CAL
%02
IB-106-350
3-7/3-8
4 4
SECTION IV. OPERATION FROM LOCAL KEYPAD
4-1. GENERAL.
a. Overview.
normal operation. The diagnostic LEDs will display the operating cycle. All other LEDs should
be off (Figure 4-1).
1.
DIAGNOSTIC ALARM LEDS. If there
is an error in the system, one of these LEDs
will flash various blink codes (Section V,
TROUBLESHOOTING). In the case of
multiple errors, only one will be displayed
based on a priority system. Correct the
problem and cycle power. The operating
display will return or the next error will be
displayed. The alarms are:
2.
CALIBRATION
Turns on when the system determines a
calibration is recommended.
3.
TEST POINTS. Test points 1 through 6
will allow you to monitor with a multimeter:
the heater thermocouple, O
and the process O
Ensure the Oxymitter 5000 is at
HEATER T/C
HEATER
O2 CELL
CALIBRATION
RECOMMENDED
cell millivolt,
2
.
2
LED.
(a) TP1 and TP2 monitor the oxygen cell
millivolt output which equates to the
percentage of oxygen present.
(b) TP3 and TP4 monitor the heater
thermocouple.
(c) TP5 and TP6 monitor the process gas
or the calibration gas parameter. The
maximum reading available from
these test points is 30 VDC. This
corresponds to 30% oxygen
concentrations.
4.
CAL LED. The CAL LED is on steady or
flashing during calibration. Further information is available in Section VI, MAINTENANCE AND SERVICE.
5.
Keys.
(a) INC and DEC. The INC and DEC
keys are used to set the values of the
calibration gases. Attach a multimeter
across TP5 and TP6. The calibration
and process gases can now be monitored. Pressing the INC or DEC once
will cause the output to switch from
the process gas to the calibration gas.
HEA TERT/C
DIAGNOSTIC
ALARMS
CALIBRATION RECOMMENDED
TEST
POINTS
INC INC
HIGH
LOW
GAS
GAS
DEC DEC
HEA TER
O2 CELL
CALIBRA TION
O2 CELL mV +
O2 CELL mv -
HEATERT/C +
HEATERT/C -
CAL
TEST GAS +
PROCESS -
% O2
HEATER T/C
CALIBRATION
HEATER
O CELL
2
TP1
TP2
TP3
TP4
TP5
TP6
SW2
ON
J1
YEL
RED
GRN
ORG
CAL LED
Figure 4-1. Normal Operation
IB-106-350
4-1
2341234
1
LIGHTING SEQUENCE DURING NORMAL OPERATION
28550013
Pressing INC or DEC a second time
will increase or decrease the calibration gas parameter. If the keys have
been inactive for one minute, the output reverts to the process gas. When a
calibration has been initiated, the
value at TP5 and TP6 is the % O
seen by the cell. Oxygen levels, as
seen on the multimeter, are:
8.0% O
0.4% O
= 8.0 volts DC
2
= 0.4 volts DC
2
(b) CAL. The CAL key can:
1 Initiate a calibration.
2 Sequence through calibration.
2
3 Abort the calibration.
b. Model 751 Remote Powered Loop LCD Dis-
play (Optional). Refer to Remote Powered
Loop LCD manual for calibration and operation.
IB-106-350
4-2
SECTION V. TROUBLESHOOTING
Install all protective equipment covers
and safety ground leads after troubleshooting. Failure to install covers and
ground leads could result in serious injury or death.
5 5
will flash a code that will correspond to an error
message. Only one LED will blink at a time. An
alarm code guide is provided inside the screw cover
for the electronics. All alarm indications will be
available via fieldbus. When the error is corrected
and/or power is cycled, the diagnostic alarms will
clear or the next error on the priority list will appear.
5-1. GENERAL. The troubleshooting section describes
how to identify and isolate faults that may develop in
the Oxymitter 5000. Also, additional troubleshooting
information is provided in paragraph 5-5 for those
units with the optional SPS 4000. When troubleshooting the Oxymitter 5000, reference the following
information.
a. Grounding. It is essential that adequate
grounding precautions are taken when installing
the system. Thoroughly check both the pr obe and
electronics to ensure the grounding quality has
not degraded during fault finding. The system
provides facilities for 100% effective grounding
and the total elimination of ground loops.
b. Electrical Noise. The Oxymitter 5000 has been
designed to operate in the type of environment
normally found in a boiler room or control room.
Noise suppression circuits are employed on all
field terminations and main inputs. When fault
finding, evaluate the electrical noise being generated in the immediate circuitry of a faulty system.
Also, ensure all cable shields are connected to
earth.
c. Loose Integrated Circuits. The Oxymitter
5000 uses a microprocessor and supporting integrated circuits (IC). If the electronics are handled
roughly during installation or located where
subjected to severe vibration, the ICs could work
loose. Before troubleshooting the system, ensure
all ICs are fully seated.
d. Electrostatic Discharge. Electrostatic discharge
can damage the ICs used in the electronics. Before removing or ha ndling the p roc essor boa rd or
the ICs, ensure you are at ground potential.
5-2. ALARM INDICATIONS. The majority of the
fault conditions for the Oxymitter 5000 will be indicated by one of the four LEDs referred to as diagnostic, or unit, alarms on the operator’s keypad. An LED
5-3. ALARM CONTACTS.
a.
If autocalibration is not utilized, a common bidirectional logic contact is provided for any of
the diagnostic alarms listed in Table 5-1. The assignment of alarms which can actuate this contact
can be modified to one of seven additional
groupings listed in Table 7-1.
The logic contact is self-powered, +5 VDC,
340 ohm series resistance. An interposing relay
will be required if this contact is to be utilized to
annunciate a higher voltage device, such as a
light or horn, and may also be required for certain DCS input cards. A Potter & Brumfield
R10S-E1Y1-J1.0K 3.2 MA DC or an equal interposing relay will be mounted where the contact wires terminate in the control/relay room.
b. If autocalibration systems are utilized, the bidi-
rectional logic contact is utilized as a “handshake” signal between the autocalibration system
(SPS 4000 or IMPS 4000) and is unavailable for
alarming purposes. The following additional
contacts are pro vided through the auto calibration
systems:
SPS 4000 and IMPS 4000, 1-4 probes.
1.
(a) One contact closure per probe from
the control room to the SPS 4000 or
IMPS 4000 for “calibration initiate”.
(b) One contact output per probe from
SPS 4000 or IMPS 4000 to the control room for “in calibration” notification.
(c) Once contact output per probe from
the SPS 4000 or IMPS 4000 to the
control room for “calibration failed”
notification. (Includes output from
pressure switch indicating “cal gas
bottles empty”.)
IB-106-350
5-1
Additional IMPS Alarm Contacts.
2.
indicated using the four diagnostic, or unit, alarms.
The pattern of repeating blinks will define the prob-
(a) One contact per IMPS 4000 for “low
calibration gas flowing”.
(b) One contact per IMPS 4000 for “high
calibration gas flowing”.
5-4. IDENTIFYING AND CORRECTING ALARM
INDICATIONS. Faults in the Oxymitter 5000 are
lem. A condensed table of the errors and the corresponding blink codes can be found on the inside right
cover of the electronics housing. Table 5-1 also identifies the blink code and fault status of each LED as
well as the output of the fieldbus digital signal line
and a fault number that corresponds to the troubleshooting instructions provided in this sectio n.
2HIGH HIGH TEMPBAD5YES
3HIGH CASE TEMPBAD6YES
4LOW TEMPBAD7NO
5HIGH TEMPBAD8YES
O2 CELL1HIGH mVBAD9YES
3BADUNCERTAIN10YES
4EEPROM CORRUPTBAD11NO
CALIBRATION1INVALID SLOPEUNCERTAIN12YES
2INVALID CONSTANTUNCERTAIN13YES
3LAST CALIBRATION
UNCERTAIN14YES
FAILED
**CALIBRATION RECOM-
GOODYES
MENDED
* Critical alarm conditions will render the O2 measurement as unusable, and any of these events will cause the PV values to
be tagged Out of Service. Alarms which are not “self-clearing” will require recycling of power to the electronics.
**The CALIBRATION RECOMMENDED alarm flashes the Calibration Recommended alarm LED on the operator’s
keypad.
IB-106-350
5-2
a. Fault 1, Open Thermocouple. The HEATER
T/C LED flashes once, pauses for three seconds,
and repeats (Figure 5-1).
HEATERT/C
DIAGNOSTIC
ALARMS
CALIBRA TION RECOMMENDED
TEST
POINTS
INCINC
HIGH
LOW
GAS
GAS
DEC DEC
HEATER
O2 CELL
CALIBRATION
O2 CELL mV +
O2 CELL mv -
HEATERT/C +
HEATERT/C -
CAL
TEST GAS +
PROCESS -
% O2
SW2
TP1
TP2
TP3
TP4
TP5
TP6
Figure 5-1. Fault 1, Open Thermocouple
ON
J1
YEL
RED
28550014
GRN
ORG
Check connector J1. Ensure the connector
1.
is properly seated.
Using a multimeter, measure TP3+ to TP4-.
2.
If the reading is 1.2 VDC ±0.1 VDC, the
thermocouple is open.
Remove power. Disconnect J1. Measure
3.
continuity across the red and yellow thermocouple leads.
The measurement should read approxi-
4.
mately 1 ohm.
If the thermocouple is open, see para-
5.
graph 6-7, Heater Strut Replacement.
IB-106-350
5-3
b. Fault 2, Shorted Thermocouple. The HEATER
T/C LED flashes twice, pauses for three seconds,
and repeats (Figure 5-2).
HEATERT/C
DIAGNOSTIC
ALARMS
CALIBRA TION RECOMMENDED
TEST
POINTS
INCINC
HIGH
LOW
GAS
GAS
DEC DEC
HEATER
O2 CELL
CALIBRATION
O2 CELL mV +
O2 CELL mv -
HEATERT/C +
HEATERT/C -
CAL
TEST GAS +
PROCESS -
% O2
SW2
TP1
TP2
TP3
TP4
TP5
TP6
Figure 5-2. Fault 2, Shorted Thermocouple
ON
J1
YEL
RED
GRN
28550015
ORG
Using a multimeter, measure across TP3+
1.
and TP4-.
If the reading is 0 ±0.5 mV, then a shorted
2.
thermocouple is likely.
Remove power and disconnect J1.
3.
Measure from TP3+ to TP4-. The reading
4.
should be approximately 20 Kohms.
If so, the short is not on the PC board. See
5.
paragraph 6-7, Heater Strut Replacement.
IB-106-350
5-4
c. Fault 3, Reversed Thermocouple. The
HEATER T/C LED flashes three times, pauses
for three seconds, and repeats (Figure 5-3).
HEATERT/C
DIAGNOSTIC
ALARMS
CALIBRA TION RECOMMENDED
TEST
POINTS
INCINC
HIGH
LOW
GAS
GAS
DEC DEC
HEATER
O2 CELL
CALIBRATION
O2 CELL mV +
O2 CELL mv HEATERT/C +
HEATERT/C -
CAL
TEST GAS +
PROCESS -
% O2
TP1
TP2
TP3
TP4
TP5
TP6
SW2
ON
Figure 5-3. Fault 3, Reversed Thermocouple
J1
YEL
RED
GRN
28550016
ORG
Using a multimeter, measure TP3+ to TP4-.
1.
If the reading is negative, the thermocouple
2.
wiring is reversed.
Check red and yellow wires in the J1 con-
3.
nector for the proper placement.
If the wiring is correct, the fault is in the PC
4.
board. See paragraph 6-5b, Electronic Assembly Replacement.
IB-106-350
5-5
d. Fault 4, Open Heater. The HEATER LED
flashes once, pauses for three seconds, and repeats (Figure 5-4).
HEATERT/C
DIAGNOSTIC
ALARMS
CALIBRA TION RECOMMENDED
TEST
POINTS
INCINC
HIGH
LOW
GAS
GAS
DEC DEC
HEATER
O2 CELL
CALIBRATION
O2 CELL mV +
O2 CELL mv -
HEATERT/C +
HEATERT/C -
CAL
TEST GAS +
PROCESS -
% O2
.
TP1
TP2
TP3
TP4
TP5
TP6
SW2
ON
RED
J1
YEL
GRN
28550017
ORG
Remove power. Remove the electronic as-
1.
sembly per paragraph 6-5b, Electronic Assembly Replacement.
Using a multimeter, measure across the
2.
heater connector J8.
The measurement should be approximately
3.
72 ohms. If the heater is open, see paragraph 6-7, Heater Strut Replacement.
Figure 5-4. Fault 4, Open Heater
IB-106-350
5-6
e. Fault 5, High High Heater Temp. The
HEATER LED flashes twice, pauses for three
seconds, and repeats (Figure 5-5).
HEATERT/C
DIAGNOSTIC
ALARMS
CALIBRA TION RECOMMENDED
TEST
POINTS
INCINC
HIGH
LOW
GAS
GAS
DEC DEC
HEATER
O2 CELL
CALIBRA TION
O2 CELL mV +
O2 CELL mv HEATERT/C +
HEATERT/C -
CAL
TEST GAS +
PROCESS -
% O2
TP1
TP2
TP3
TP4
TP5
TP6
SW2
ON
Figure 5-5. Fault 5, High High Heater Temp
J1
YEL
RED
GRN
28550018
ORG
The high high heater temp alarm will acti-
1.
vate when the thermocouple produces a
voltage of 37.1 mV (1652°F/900°C).
The triac and the temperature control may
2.
be at fault.
Remove power. Allow Oxymitter 5000 to
3.
cool for five minutes. Restore power.
If the condition repeats, replace the
4.
electronic assembly per paragraph 6-5b,
Electronic Assembly Replacement.
IB-106-350
5-7
f. Fault 6, High Case Temp. The HEATER LED
flashes three times, pauses for three seconds, and
repeats (Figure 5-6).
HEATERT/C
DIAGNOSTIC
ALARMS
CALIBRA TION RECOMMENDED
TEST
POINTS
INCINC
HIGH
LOW
GAS
GAS
DEC DEC
HEATER
O2 CELL
CALIBRA TION
O2 CELL mV +
O2 CELL mv -
HEATERT/C +
HEATERT/C -
CAL
TEST GAS +
PROCESS -
% O2
TP1
TP2
TP3
TP4
TP5
TP6
Figure 5-6. Fault 6, High Case Temp
SW2
ON
RED
28550019
If the case temperature exceeds 185°F
1.
(85°C), the temperature control will shut off
and a fieldbus alarm will be sent.
J1
This signifies that the environment where
2.
the Oxymitter 5000 is installed exceeds the
ambient temperature requirements or that
YEL
GRN
ORG
heat due to convection is causing case temperature to rise above the limit.
Placing a spool piece between the stack
3.
flange and the Oxymitter 5000 flange may
eliminate this problem.
If a spool piece does not solve the problem,
4.
relocation is the only solution.
IB-106-350
5-8
g. Fault 7, Low Heater Temp. The HEATER
LED flashes four times, pauses for three seconds,
and repeats (Figure 5-7).
HEATERT/C
DIAGNOSTIC
ALARMS
CALIBRA TION RECOMMENDED
TEST
POINTS
INCINC
HIGH
LOW
GAS
GAS
DEC DEC
HEATER
O2 CELL
CALIBRATION
O2 CELL mV +
O2 CELL mv HEATERT/C +
HEATERT/C -
CAL
TEST GAS +
PROCESS -
% O2
SW2
TP1
TP2
TP3
TP4
TP5
TP6
Figure 5-7. Fault 7, Low Heater Temp
ON
RED
28550020
The low heater temperature alarm is active
1.
when the thermocouple reading has dropped
below 28.6 mV.
J1
If the thermocouple reading continues to
2.
ramp downward for one minute and does
not return to the temperature set point of
YEL
GRN
ORG
approximately 29.3 mV, then an Open
Heater fault will be displayed.
Power down the electronics. Remove the
3.
electronic assembly per paragraph 6-5b,
Electronic Assembly Replacement. Using a
multimeter, measure across the heater connector, J8.
If the heater is good, the reading will be
4.
aproximately 70 ohms. If the heater is open,
see paragraph 6-7, Heater Strut
Replacement.
IB-106-350
5-9
h. Fault 8, High Heater Temp. The HEATER
LED flashes five times, pauses for three seconds,
and repeats (Figure 5-8).
HEATERT/C
DIAGNOSTIC
ALARMS
CALIBRA TION RECOMMENDED
TEST
POINTS
INCINC
HIGH
LOW
GAS
GAS
DEC DEC
HEATER
O2 CELL
CALIBRATION
O2 CELL mV +
O2 CELL mv -
HEATERT/C +
HEATERT/C -
CAL
TEST GAS +
PROCESS -
% O2
SW2
TP1
TP2
TP3
TP4
TP5
TP6
Figure 5-8. Fault 8, High Heater Temp
ON
RED
J1
YEL
GRN
28550021
ORG
If the thermocouple produces a voltage in
1.
excess of approximately 30.7 mV, the high
heater temp alarm activates.
An alarm is sent via fieldbus.
2.
This alarm is self-clearing. When tempera-
3.
ture control is restored and the thermocouple voltage returns to the normal range, the
alarm clears.
If the temperature continues to rise, the next
4.
alarm will be the high high heater temp
alarm.
IB-106-350
5-10
i. Fault 9, High Cell mV. The O2 CELL flashes
once, pauses for three seconds, and repeats
(Figure 5-9).
HEATERT/C
DIAGNOSTIC
ALARMS
CALIBRA TION RECOMMENDED
TEST
POINTS
INCINC
HIGH
LOW
GAS
GAS
DEC DEC
HEATER
O2 CELL
CALIBRA TION
O2 CELL mV +
O2 CELL mv HEATERT/C +
HEATERT/C -
CAL
TEST GAS +
PROCESS -
% O2
TP1
TP2
TP3
TP4
TP5
TP6
Figure 5-9. Fault 9, High Cell mV
SW2
ON
RED
J1
YEL
GRN
28550022
ORG
Using a multimeter, measure across TP1+
1.
to TP2-.
If you measure 1.2 VDC, the cell wires, ei-
2.
ther orange or green, have become detached
from the input.
One possible cause is connector J1. The or-
3.
ange or green wire has come loose from the
crimped connection.
The platinum pad could also be at fault. The
4.
pad could have broken free from the back
of the cell.
Replace heater strut per paragraph 6-7,
5.
Heater Strut Replacement. If necessary, replace the cell flange assembly per paragraph 6-8, Cell Replacement.
IB-106-350
5-11
j. Fault 10, Bad Cell. The O2 CELL flashes three
times, pauses for three seconds, and repeats
(Figure 5-10).
HEATERT/C
DIAGNOSTIC
ALARMS
CALIBRA TION RECOMMENDED
TEST
POINTS
INCINC
HIGH
LOW
GAS
GAS
DEC DEC
HEATER
O2 CELL
CALIBRA TION
O2 CELL mV +
O2 CELL mv -
HEATERT/C +
HEATERT/C -
CAL
TEST GAS +
PROCESS -
% O2
Figure 5-10. Fault 10, Bad Cell
TP1
TP2
TP3
TP4
TP5
TP6
SW2
ON
RED
28550023
J1
YEL
GRN
ORG
The bad cell alarm activates when the cell
1.
exceeds the maximum resistance value.
The cell should be replaced. See paragraph
2.
6-8, Cell Replacement, for cell replacement
instructions.
IB-106-350
5-12
k. Fault 11, EEPROM Corrupt. The O2 CELL
LED flashes four times, pauses for three seconds,
and repeats (Figure 5-11).
HEATERT/C
DIAGNOSTIC
ALARMS
CALIBRA TION RECOMMENDED
TEST
POINTS
INCINC
HIGH
LOW
GAS
GAS
DEC DEC
HEATER
O2 CELL
CALIBRATION
O2 CELL mV +
O2 CELL mv HEATERT/C +
HEATERT/C -
CAL
TEST GAS +
PROCESS -
% O2
SW2
TP1
TP2
TP3
TP4
TP5
TP6
Figure 5-11. Fault 11, EEPROM Corrupt
ON
RED
28550024
This alarm can occur if the EEPROM is
1.
changed for a later version. At power up,
the EEPROM is not updated.
J1
To correct this problem, power down and
2.
then restore power. The alarm should clear.
If the alarm occurs while the unit is running,
YEL
GRN
ORG
3.
there is a hardware problem on the microprocessor board.
If cycling the power does not clear the
4.
alarm, see paragraph 6-5b, Electronic
Assembly Replacement.
IB-106-350
5-13
l. Fault 12, Invalid Slope. The CALIBRATION
LED flashes once, pauses for three seconds, and
repeats (Figure 5-12).
HEATERT/C
DIAGNOSTIC
ALARMS
CALIBRA TION RECOMMENDED
TEST
POINTS
INCINC
HIGH
LOW
GAS
GAS
DEC DEC
HEATER
O2 CELL
CALIBRA TION
O2 CELL mV +
O2 CELL mv -
HEATERT/C +
HEATERT/C -
CAL
TEST GAS +
PROCESS -
% O2
TP1
TP2
TP3
TP4
TP5
TP6
Figure 5-12. Fault 12, Invalid Slope
SW2
ON
RED
28550025
During a calibration, the electronics calcu-
1.
lates a slope value. If the value of the slope
is less than 35 mV/deg or more than 52
J1
YEL
GRN
ORG
mV/deg, the slope alarm will be active until
the end of the purge cycle.
See paragraph 6-2, Calibration. Verify the
2.
calibration by carefully repeating it. Ensure
the calibration gases match the calibration
gas parameters. If you attach a multimeter
to TP1+ and TP2-, sample gas measurements are:
8% O
≈ 23 mV
2
0.4% O
Power down the Oxymitter 5000 and re-
3.
≈ 85 mV
2
move it from the stack.
Replace the cell per paragraph 6-8, Cell
4.
Replacement.
IB-106-350
5-14
m. Fault 13, Invalid Constant. The CALIBRA-
TION LED flashes twice, pauses for three seconds, and repeats (Figure 5-13).
HEATERT/C
DIAGNOSTIC
ALARMS
CALIBRA TION RECOMMENDED
TEST
POINTS
INCINC
HIGH
LOW
GAS
GAS
DEC DEC
HEATER
O2 CELL
CALIBRATION
O2 CELL mV +
O2 CELL mv HEATERT/C +
HEATERT/C -
CAL
TEST GAS +
PROCESS -
% O2
SW2
TP1
TP2
TP3
TP4
TP5
TP6
Figure 5-13. Fault 13, Invalid Constant
ON
J1
YEL
RED
GRN
28550026
ORG
After a calibration has been performed, the
1.
electronics calculates a cell constant value.
If the cell constant value is outside of the
2.
range, -4 mV to 10 mV, the alarm will activate. See paragraph 6-2, Calibration, and
verify the last calibration was performed
correctly.
Power down the Oxymitter 5000 and re-
3.
move it from the stack.
Replace the cell per paragraph 6-8, Cell
4.
Replacement.
IB-106-350
5-15
n. Fault 14, Last Calibration Failed. The CALI-
BRATION LED flashes three times, pauses for
three seconds, and repeats (Figure 5-14).
HEATERT/C
DIAGNOSTIC
ALARMS
CALIBRA TION RECOMMENDED
TEST
POINTS
INCINC
HIGH
LOW
GAS
GAS
DEC DEC
HEATER
O2 CELL
CALIBRA TION
O2 CELL mV +
O2 CELL mv -
HEATERT/C +
HEATERT/C -
CAL
TEST GAS +
PROCESS -
% O2
TP1
TP2
TP3
TP4
TP5
TP6
SW2
ON
RED
28550027
Figure 5-14. Fault 14, Last Calibration Failed
The last calibration failed alarm activates
1.
when the slope and constant values calculated are out of range and the unit reverts to
J1
using the previous calibration values.
The cell should be replaced. See paragraph
2.
6-8, Cell Replacement, for cell replacement
YEL
GRN
ORG
instructions.
IB-106-350
5-16
Install all protective equipment covers
and safety ground leads after troubleshooting. Failure to replace covers and
ground leads could result in serious
injury or death.
5-5. SPS 4000 TROUBLESHOOTING. Use the CAL
FAIL and IN CAL relay outputs to identify possible
SPS 4000 faults.
a. If a calibration was not successfully completed,
the SPS 4000 sends a CAL FAIL contact indication to the control room. To determine if the SPS
4000 caused the failed calibration, go to the
Oxymitter 5000 site to view the keypad. Or, access the Oxymitter via fieldbus.
If no alarms are indicated on the keypad or
1.
via fieldbus, the calibration did not fail
because of an Oxymitter 5000 fault.
Therefore, a calibration gas flow problem
occurred. Refer to Table 5-2 or Figure 5-15
to troubleshoot the SPS 4000.
TENANCE AND SERVICE, Also,
verify your calibration gas setup.
(b) Perform another calibration and
monitor the process. If the calibration
fails before both calibration gases
finish sequencing, a gas flow problem
exists. Refer to Table 5-2 or Figure
5-15 to troubleshoot the SPS 4000.
If the calibration setup is correct and
the Oxymitter 5000 indicates an
invalid slope fault (fault 12) before
the gases are purged and a last
calibration failed fault (fault 14) after
the gases are purged, replace the
Oxymitter 5000 cell per paragraph 6-8
in Section VI, MAINTENANCE
AND SERVICE.
b. If a semi-automatic or manual calibration is be-
ing performed but no 5-30 VDC relay output
contact (IN CAL or CAL FAIL) is being received by the control room, the interface board
relays are malfunctioning. Replace the interface
board per paragraph 6-10b.
If the LAST CAL FAILED alarm is indi-
2.
cated on the keypad or via fieldbus, the
failure is due to either a bad Oxymitter
5000 cell or a calibration gas flow problem.
(a) Verify your calibration setup per
paragraph 6-2 in Section VI, MAIN-
NOTE
If the unit is performing frequent
autocalibrations, investigate at the
Oxymitter 5000 site or via fieldbus. This
condition may indicate an aging cell in the
Oxymitter 5000.
IB-106-350
5-17
Table 5-2. SPS 4000 Fault Finding
SYMPTOMCHECKFAULTREMEDY
No calibration gas flow
WiringImproper wire connections,
loose connections, or damaged wiring
Logic I/OOxymitter 5000 logic I/O
not set for calibration hand-
Properly connect wiring or secure
loose wiring connections; replace
damaged wiring if necessary.
Set logic I/O to mode 8 via fieldbus
using the IO_PIN_MODE parameter.
shaking with SPS 4000
Calibration gas lines be-
Clogged calibration gas lineReplace clogged calibration gas line.
tween cylinders and manifold
Calibration gas flowmeter
knob
Calibration gas line between
Flowmeter knob not turned
counterclockwise to allow
flow
Turn calibration gas flowmeter knob
counterclockwise to allow calibration
gas to flow.
Clogged calibration gas lineReplace clogged calibration gas line.
manifold and calibration gas
flowmeter
Fuse on power supply boardBlown fuseReplace fuse per paragraph 6-10a.
Interface board operationInterface board not sending
signals
Replace interface board per paragraph
6-10b.
Check valveClogged check valveReplace check valve per paragraph
6-10e.
Calibration gas line between
Clogged calibration gas lineReplace calibration gas line.
calibration gas flowmeter
and check valve
Calibration gas flowmeterClogged flowmeterReplace flowmeter per paragraph
6-10h.
Power supply outputPower supply failureReplace power supply board per para-
graph 6-10b.
SolenoidSolenoid failureReplace solenoid per paragraph 6-10c.
Pressure switchPressure switch failureReplace pressure switch per paragraph
6-10d.
IB-106-350
5-18
Figure 5-15. SPS 4000 Troubleshooting Flowchart (Sheet 1 of 2)
IB-106-350
5-19
SYMPTOM — NO TEST GAS FLOW (CONTINUED)
CONTINUED
FROM SHEET
1OF2
PLACE JUMPER BETWEEN CAL
RET TERMINAL AND EITHER HI
GAS OR LO GAS TERMINAL OF J3.
SEE NOTE 1.
IS THERE
FLOW?
NO
USE METER (SEE NOTE 2)
TO CHECK FOR SHORT
BETWEEN CAL RET AND NO GAS
TERMINALS OF J3.
IS THERE
A SHORT?
YES
YES
INTERFACE BOARD IS
NOT SENDING SIGNAL.
REPLACE INTERFACE
BOARD PER PARAGRAPH
6-10b.
DISCONNECT CAL GAS
LINE AT CHECK VALVE.
NOTE 1:
NOTE 2:
NOTE 3:
NOTE 4:
SECURELY TIGHTEN ALL J3 SCREW TERMINALS ON
POWER SUPPLY BOARD TO MAKE CONNECTIONS.
USE A SIMPSON MODEL 260 OR EQUIVALENT
MULTIMETER.
IF REPLACING THE CHECK VALVE DOES NOT
CORRECT THE PROBLEM, A CLOG COULD EXIST IN
THE RED SILICON GAS TUBE WITHIN THE PROBE.
IF CHECKING CAL GAS 1 SOLENOID CONNECTOR J5,
ENSURE CAL RET TERMINAL IS JUMPERED TO HI GAS
TERMINAL OF J3. IF CHECKING CAL GAS 2 SOLENOID
CONNECTOR J4, ENSURE CAL RET TERMINAL IS
JUMPERED TO LO GAS TERMINAL OF J3.
IS THERE
FLOW?
YES
REPLACE CHECK VALVE
PER PARAGRAPH 6-10e.
SEE NOTE 3.
NO
DISCONNECT SOLENOID FROM
POWER SUPPLY BOARD AND USE
METER TO MEASURE ACROSS
TWO OUTER PINS OF BOARD
CONNECTOR. SEE NOTE 4.
CHECK BOTH SOLENOIDS.
IS THERE
+30VDC?
YES
DISCONNECT CAL GAS LINE
AT MANIFOLD OUTPUT PORT.
IS THERE
FLOW?
YES
REPLACE PRESSURE SWITCH
PER PARAGRAPH 6-10d.
NO
NO
REPLACE POWER
SUPPLY BOARD PER
PARAGRAPH 6-10b.
REPLACE SOLENOID
PER PARAGRAPH 6-10c.
NO
DISCONNECT CAL GAS LINE
AT TOP FITTING OF CAL GAS
FLOWMETER.
IS THERE
FLOW?
NO
REPLACE FAULTY CAL GAS
FLOWMETER PER PARAGRAPH
6-10h.
YES
REPLACE CLOGGED
CAL GAS LINE BETWEEN
CAL GAS FLOWMETER
AND CHECK VALVE.
Figure 5-15. SPS 4000 Troubleshooting Flowchart (Sheet 2 of 2)
IB-106-350
5-20
27610002
6
SECTION VI. MAINTENANCE AND SERVICE
6-1. OVERVIEW. This section identifies the calib ration
methods available and provides the procedures to
maintain and service the Oxymitter 5000 and optional
integrally mounted SPS 4000.
Install all protective equipment covers
and safety ground leads after equipment
repair or service. Failure to install
covers and ground leads could result in
serious injury or death.
6-2. CALIBRATION.
a. During a calibration, two calibration gases with
known O
concentrations are applied to the
2
Oxymitter 5000. Slope and constant values calculated from the two calibration gases determine
if the Oxymitter 5000 is correctly measuring the
net concentration of O
in the industrial process.
2
Before calibrating the Oxymitter 5000, verify
that the calibration gas parameters are correct by
setting the gas concentrations used when calibrating the unit (See paragraph 4-1a5) and by
setting the calibration gas flowmeter.
The calibration gas flowmeter regulates the calibration gas flow and must be set to 5 scfh. However, only adjust the flowmeter to 5 scfh after
placing a new diffusion element on the end of the
Oxymitter 5000. Adjusting the flowmeter at any
other time can pressurize the cell and bias the
calibration.
In applications with a heavy dust loading, the O
probe diffusion element may become plugged
over time, causing a slower speed of response.
The best way to detect a plugged diffusion element is to note the time it takes the Oxymitter
5000 to return to the normal process reading after
the last calibration gas is removed and the calibration gas line is blocked off. A plugged element also can be indicated by a slightly lower
reading on the flowmeter.
Change the diffusion element when the
calibration gas flowmeter reads slightly lower
during calibration or when the response time to
the process flue gases becomes very slow. Each
time the diffusion element is changed, reset the
calibration gas flowmeter to 5 scfh and calibrate
the Oxymitter 5000. To change the diffusion
element, refer to paragraph 6-8.
b.
Three types of calibration methods are available:
automatic, semi-automatic, and manual.
NOTE
A calibration can be aborted any time during the process by pressing the CAL key
(Figure 6-2) on the Oxymitter 5000 keypad
three times in a three second interval or via
OUNDATION
F
fieldbus or an IMPS 4000. An
aborted calibration will retain the values of
the previous good calibration.
Automatic Calibration.Automatic calibra-
1.
tions require no operator action. However,
the calibration gases must be permanently
piped to the Oxymitter 5000, an SPS 4000
or IMPS 4000 must be installed to sequence
the gases, and the Oxymitter 5000’s logic
I/O must be set to mode 8 via fieldbus using
the IO_PIN_MODE parameter so the
sequencer and Oxymitter 5000 can
communicate.
Depending on your system setup, an automatic calibration can be initiated by the
2
following methods:
(a) The Oxymitter 5000’s CALIBRATION
RECOMMENDED alarm signals that
a calibration is required.
(b) Enter a time to next calibration using
the TIME_TO_NEXT_CAL parameter via fieldbus. Calibrations will then
occur regularly at this interval.
IB-106-350
6-1
Note: The Electronic Assembly, item 12,
consists of items 13 through 24.
24
25
26
27
28
29
30
37
36
31
12
13
14
DIAGNOSTIC
ALARMS
HEATERT/C
CALIBRATION RECOMMENDED
HEATER
CALIBRATION
TEST
POINTS
02 CELL mV +
02 CELL mv -
HEATERT/C +
INC
HEATERT/C -
INC
HIGH
GAS
LOW
GAS
DEC
DEC
TEST GAS +
PROCESS -
02 CELL
CAL
% 02
11
Note: Not all parts shown.
16
17
20
18
10
21
19
22
23
15
36
38
1. Heater Strut Assembly
38
37
2. Diffusion Assembly (Snubber)
3. Retainer Screw
4. Cell and Flange Assembly
5. Corrugated Seal
6. Probe Tube Assembly
7. Screw
8. Tube Connector
9. Gas Port
10. O-ring
11. Right Housing Cover
12. Electronic Assembly
13. Screw
7
14. Membrane Keypad
15. Snap Connector
16. Captive Screw
17. Microprocessor Board
18. Screw
19. Washer
20. Fieldbus Output Board
21. Fieldbus Isolator Board
22. Fuse Cap
6
23. Fuse
24. Power Supply Board
25. Electronic Housing
26. Screw
32
33
34
35
9
8
1
Figure 6-1. Oxymitter 5000 Exploded View
IB-106-350
6-2
5
4
27. Lock Washer
28. Cable Clamp
29. Terminal Block
30. Captive Screw
31. Left Housing Cover
32. SiliconTube
33. Tube Clamp
34. Screw
35. Washer
36. Screw
37. Gasket
38. Cover Lock
3
28550001
2
HEATERT/C
DIAGNOSTIC
ALARMS
CALIBRATION RECOMMENDED
TEST
POINTS
HEATER
O2 CELL
CALIBRATION
O2 CELL mV +
O2 CELL mv -
HEATERT/C +
HEATERT/C -
to sequence the gases, and the Oxymitter
5000’s logic I/O must be set to mode 8 or 9
via fieldbus so the sequencer and Oxymitter
5000 can communicate.
Depending on your system setup, a semiautomatic calibration can be initiated by the
following methods:
(a) Oxymitter 5000. Press the CAL key
on the Oxymitter 5000 keypad.
INCINC
HIGH
LOW
GAS
GAS
DEC DEC
CAL
TEST GAS +
PROCESS -
% O2
22220067
Figure 6-2. Membrane Keypad
(c) If using an IMPS 4000, enter a time
interval via the IMPS 4000 keypad
that will initiate an automatic
calibration at a scheduled time
interval (in hours). To set the
CalIntvX parameter of the CHANGE
PRESETS display mode, refer to the
IMPS 4000 Intelligent Multiprobe
Test Gas Sequencer Instruction
Bulletin for more information.
Once an automatic calibration is initiated,
by any of the methods previously described,
the Oxymitter 5000’s CALIBRATION
RECOMMENDED alarm signals an IMPS
4000 or SPS 4000 to initiate a calibration.
The sequencer sends an “in cal” signal to
the control room so that any automatic control loops can be placed in manual. Then,
the sequencer begins to sequence the calibration gases.
Semi-Automatic Calibration. Semi-automatic
2.
calibrations only require operator initiation.
However, the calibration gases must be permanently piped to the Oxymitter 5000, an
SPS 4000 or IMPS 4000 must be installed
(b) IMPS 4000. Use the IMPS 4000 key-
pad to change the InitCalX parameter
of the CHANGE PRESETS display
mode from 0000 to 0001. Refer to the
IMPS 4000 Intelligent Multiprobe
Test Gas Sequencer Instruction Bulletin for more information.
OUNDATION
(c) F
to perform the O
fieldbus. Use fieldbus
CAL method.
2
(d) Remote Contact. Initiate a calibration
from a remote location via the remote
contact input connection provided by
an IMPS 4000 or SPS 4000. Refer to
the documentation available for the
control system in use for more
information.
Once a semi-automatic calibration is
initiated, by any of the methods previously
described, the Oxymitter 5000’s
CALIBRATION RECOMMENDED alarm
signals an IMPS 4000 or SPS 4000 to
initiate a calibration. The sequencer sends
an “in cal” signal to the control room so that
any automatic control loops can be placed
in maual. Then, the sequencer begins to
sequence the calibration gases.
Manual Calibration. Manual calibrations
3.
must be performed at the Oxymitter 5000
site and require operator intervention
throughout the proc ess.
Manual calibration instructions can also be
found, in condensed form, on the inside of
the right electronics housing cover (Figure
6-3).
IB-106-350
6-3
ALARMS
LED
HEATER T/C
HEATER
O2 CELL
CALIBRATION
MANUAL
CALIBRATION
PLACE CONTROL LOOP
*
IN MANUAL
IF CAL LED ON
FLASHES
1
2
3
1
2
3
4
5
1
3
4
1
2
3
STATUS
OPEN
SHORTED
REVERSED
OPEN
HIGH HIGH
TEMP
HIGH CASE
TEMP
LOW TEMP
HIGH TEMP
OPEN
BAD
EPROM
CORRUPT
INVALID SLOPE
INVALID
CONSTANT
LAST CAL
FAILED
*
GO TO STEP 2
PUSH CAL
1
CAL LED ON
PUSH CAL
2
CAL LED FLASH
APPLY TG1
3
PUSH CAL
CAL LED ON SOLID
4
WAIT FOR FLASH
REMOVE TG1 & APPLY TG2
5
PUSH CAL
CAL LED ON SOLID
WAIT FOR FLASH
6
2 FLASH VALID CAL
3 FLASH INVALID CAL
7
REMOVE TG2
PUSH CAL
CAL LED ON FOR
8
PURGE TIME
CAL LED OFF
SW2 DIP SWITCH
NOT USED
OFF
NOT USED
NOT USED
NOT USED
ON
NOT USED
NOT USED
Figure 6-3. Inside Right Cover
28550029
Use the following procedure to perform a
manual calibration:
(a) Place control loop in manual.
(b) Verify the calibration gas parameters
are correct per paragraph 6-2.a.
(c) If performing a manual calibration with
CALIBRATION RECOMMENDED
LED off and the CAL LED off, start
at step 1.
(d) If performing a manual calibration with
CALIBRATION RECOMMENDED
LED on and the CAL LED on, start at
step 2.
1 Push the CAL key. The CALI-
BRATION RECOMMENDED
LED will come on and the CAL
LED will be on solid. If a multimeter is attached across TP5 and
TP6, the reading will display the
percentage of oxygen seen by the
cell.
2 Push the CAL key. The CALI-
BRATION RECOMMENDED
LED will turn off and the CAL
LED will flash continuously. The
flashing LED indicates that the
Oxymitter 5000 is ready to accept
the first calibration gas.
3 Apply the first calibration gas.
(Electronics will abort the calibration if step 4 is not done within
30 minutes).
4 Push the CAL key; the CAL LED
will be on solid. A timer is
activated to allow the calibration
gas adequate time to flow (default
time of five minutes). When the
timer times out, the Oxymitter
5000 has taken the readings using
the first calibration gas and the
CAL LED will flash continuously.
The flashing indicates the
Oxymitter 5000 is ready to take
readings using the second
calibration gas.
IB-106-350
6-4
5 Remove the first calibration gas
and apply the second calibration
gas. (Electronics will abort the
calibration if step 6 is not done
within 30 minutes).
(e) Place control loop in automatic.
OUNDATION
c. F
fieldbus O2 CAL METHOD.
To perform a calibration using F
fieldbus, use the following procedure.
OUNDATION
6 Push the CAL key; the CAL LED
will be on solid. The timer is activated for the second calibration
gas flow. When the timer times
out, the CAL LED will flash a 2
pattern flash or a 3 pattern flash (2
pattern flash equals a valid calibration, 3 pattern flash equals an
invalid calibration).
If the slope or the constant is out
of specification, a diagnostic
alarm LED will be flashing. The
diagnostic alarm will remain active until the purge cycle is over.
If the three pattern flash occurs
without a diagnostic alarm, the
calibration gases could be the
same or the calibration gas was
not turned on.
The CAL LED flashing indicates
the calibration is done. (See Section V, TROUBLESHOOTING,
for an explanation of the 2 pattern
and 3 pattern flashes).
7 Remove the second calibration
gas and cap off the calibration gas
port.
From the computer running the fieldbus
1.
control program, run the O
Cal Method.
2
Failure to remove the Oxymitter 5000
from automatic control loops prior to
performing this procedure may result in
a dangerous operating condition.
In the first O
2.
CAL screen, a “Loop should
2
be removed from automatic control” warning appears. Remove the Oxymitter 5000
from any automatic control loops to avoid a
potentially dangerous operating condition
and press OK.
From this point, follow the on-screen
3.
prompts to complete the calibration
procedure. When a step is complete, select
Proceed to Next Step and press the Next
button.
During the wait periods, such as during a
4.
purge, the Time Remaining display may be
updated by selecting Update and pressing
the Next button.
8 Push the CAL key; the CAL LED
will be on solid as the unit purges.
(Default purge time is three minutes). When the purge is complete, the CAL LED will turn off.
If the calibration was valid, the
DIAGNOSTIC ALARMS LEDs will
indicate normal operation. If the new
calibration values, slope or constant,
is not within the parameters, the
DIAGNOSTIC ALARMS LED will
indicate an alarm. (See Section V,
TROUBLESHOOTING, for alarm
codes). If the calibration was invalid,
the Oxymitter 5000 will return to
normal operation, as it was before a
calibration was initiated, and the
parameters will not be updated.
IB-106-350
6-3. LED STATUS INDICATORS.
a. Diagnostic/Unit Alarms. Table 6-1 lists the
types and status of alarms that will be encountered. (See Section V, TROUBLESHOOTING,
for a detailed description of each fault).
b. When the electronics determines a calibration is
recommended, the CALIBRATION RECOMMENDED LED is on solid.
c. The CAL LED turns on when a calibration is
recommended and is on during the calibration
process. During calibration, the CAL LED can be
flashing, which would indicate operator ac tion is
requested, or on solid, which indicates calculations and measurements are in progress.
6-5
Table 6-1. Diagnostic/Unit Alarms
LEDFLASHESSTATUSFAULT
1OPEN
HEATER T/C2SHORTED
3REVERSED
1OPEN
2HIGH HIGH
TEMP
HEATER3HIGH CASE
TEMP
4LOW TEMP
5HIGH TEMP
1HIGH mV
O2 CELL3BAD
4EEPROM
CORRUPT
CALIBRATION1INVALID
SLOPE
2INVALID
CONSTANT
3LAST
CALIBRA-
TION
FAILED
It is recommended that the Oxymitter
5000 be removed from the stack for all
service activities. The unit should be
allowed to cool and be t aken to a clean
work area. Failure to comply may cause
severe burns.
10
11
12
13
14
(b) Shut off the calibration gases at the
cylinders and the instrument air.
1
2
3
4
5
6
(c) Disconnect the calibration gas and in-
strument air lines from the Oxymitter
5000.
(d) While facing the Oxymitter 5000 and
looking at the Rosemount label, r e m o ve
screw (36, Figure 6-1), gasket (37)
and cover lock (38) securing left
housing cover (31) . Remove the c over
to expose the terminal block Figure
6-4.
7
8
(e) Loosen the screw on the AC terminal
cover and slide the cover back to ac-
9
cess the neutral and line terminals.
Loosen the AC line and neutral terminal screws and remove the leads.
Loosen the ground lug scre ws and remove the leads. Slide the line power
leads out of the AC line voltage port.
(f) Loosen the logic I/O and the fieldbus
signal terminal screws. Remove the
leads from the terminals and slide the
wires out of the signal port.
(g) Remove insulation to access the
mounting bolts. Unbolt the Oxymitter
5000 from the stack and take it to a
clean work area.
(h) Allow the unit to cool to a comfort-
able working temperature.
Replace.
2.
(a) Bolt the Oxymitter 5000 to the stack
and install insulation.
Disconnect and lock out power before
working on any electrical components.
There is voltage up to 115 VAC.
6-4. OXYMITTER 5000 REMOVAL/REPLACEMENT.
a. Oxymitter 5000 (without Integrally Mounted
SPS 4000).
Remove.
1.
(a) Turn off power to the system.
IB-106-350
(b) Insert the logic I/O and fieldbus signal
leads in the signal port and connect to
the logic I/O and fieldbus digital signal screw terminals (Figure 6-4).
(c) Insert the power leads in the AC line
voltage port and connect to the AC
line screw terminals. Connect the line,
or L1, wire to the L1 terminal, and the
neutral, or L2, wire to the N terminal.
Slide the AC terminal cover over the
terminal connection and tighten the
cover screw.
6-6
Figure 6-4. Terminal Block
(d) Install left housing cover (31, Figure
6-1) and ensure it is tight. Secure the
cover using cover lock (38), gasket
(37), and screw (36).
(e) Connect the calibration gas and in-
strument air lines to the Oxymitter
5000.
(f) Turn on the calibration gases at the
cylinders and turn on instrument air.
(g) Restore power to the system.
b. Oxymitter 5000 (with Integrally Mounted
SPS 4000).
Remove.
1.
(a) Turn off power to the system.
(b) Shut off the calibration gases at the
cylinders and the instrument air.
(c) Disconnect the instrument air and
calibration gas lines from the SPS
4000. If the instrument air does not
flow through the SPS 4000, disconnect the instrument air directly at the
Oxymitter 5000.
fold. Remove the terminal cover to
expose the terminal strip.
(e) Tag all customer-wired leads that are
connected to the terminal strip before
removing.
(f) On the terminal strip, loosen the
screws securing the customer-wired
LINE IN and NEUTRAL leads to
terminals L and N (Figure 2-10). Also,
remove the customer-wired ground
lead from the ground lug. Remove the
leads from the terminal strip and slide
them from the manifold through the
line voltage conduit port.
(g) Next, loosen the screws of remote
contact input terminals 1 and 2; fieldbus digital signal terminals 3 and 4; and
relay output terminals 7, 8, 9, and 10.
Remove the leads from the terminal
strip and slide them from the manifold
through the signal conduit port.
(h) Remove insulation to access the
mounting bolts. Unbolt the Oxymitter
5000/SPS 4000 assembly from the
stack and take the entire assembly to a
clean work area.
(d) Remove the screws securing the ter-
minal cover to the SPS 4000 mani-
IB-106-350
(i) Allow the unit to cool to a comfort-
able working temperature.
6-7
MOUNTING SCREW
R
Rosemount Analytical Inc.
Orrville,OH 44667-0901
800-433-6076
TM
OXYMITTER 4000
SERIAL NO.
TAG NO.
VOLTS:WATTS:
85-264VAC 48-62 Hz
4-20 mA
OUTPUT: LINE FUSE:
MOUNTING
R
SMART FAMILY
TM
HART
500VA
5 Amps
Figure 6-5. Electronic Assembly
Replace.
2.
(a) Bolt the Oxymitter 5000/SPS 4000
assembly to the stack and install
insulation.
SCREW
HEA TERT/C
LOW
GAS
HEA TER
O2 CELL
CALIBRATION
O2 CELL mV +
O2 CELL mv HEA TERT/C +
HEA TERT/C -
CAL
TEST GAS +
PROCESS -
% O2
DIAGNOSTIC
ALARMS
CALIBRATION RECOMMENDED
TEST
POINTS
INC INC
HIGH
GAS
DEC DEC
TP1
TP2
TP3
TP4
TP5
TP6
SW2
ON
J1
YEL
RED
GRN
ORG
MOUNTING SCREW
Follow the instructions in paragraph 6-4.a.1
1.
to remove the Oxymitter 5000 from the
stack or duct. If removing an Oxymitter
5000/SPS 4000 assembly, follow the instructions in paragraph 6-4.b.1.
J1
28550031
(b) Follow the instructions in paragraph
2-3 to connect the line voltage and
signal leads to an Oxymitter 5000/
SPS 4000 assembly.
(c) Follow the instructions in paragraph
2-5 to connect the calibration gases
and instrument air to an Oxymitter
5000/SPS 4000 assembly. Turn on the
calibration gases at the cylinders and
turn on instrument air.
(d) Restore power to the system.
6-5. ELECTRONICS REPLACEMENT. Each of the
following procedures details how to remove and
replace a specific electronic component of the
Oxymitter 5000.
a. Entire Electronics Replacement (with
Housing).
NOTE
Only perform this procedure on Oxymitter
5000 units without integrally mounted SPS
4000 units. If it is necessary to replace the
entire electronics on an Oxymitter 5000/
SPS 4000 assembly, contact Rosemount for
further instructions.
Remove the right housing cover unco vering
2.
the electronic assembly (Figure 6-5).
Depress and remove the J1 (cell and T/C)
3.
connector from the J1 socket. Loosen the
three captive mounting screws on the
microprocessor board (top board).
The J8 connector (heater leads) can be ac-
4.
cessed by moving the J1 connector leads
out of the slot on the microprocessor board
and sliding the electronic assembly partially
out of the housing (Figure 6-6).
Squeeze the J8 connector on the sides and
5.
carefully remove. The electronic assembly
can now be completely removed from the
housing.
Remove the four screws (7, Figure 6-1)
6.
from the probe finned housing. The probe
and the electronic housing can now be
separated.
When reinstalling or replacing the elec-
7.
tronic housing, make sure that o-ring ( 10) is
in good condition. Place the J1 and J8 connectors in the hole on the flat side of the
electronic ho using.
IB-106-350
6-8
250VAC
TIME LAG
3D39619G
1
+
POWER
SUPPLY
+
+
+
5A
+
+
+
1
+
REV
+
BOARD
J8
13. Follow the instructions in paragraph 6-4a2
to install the Oxymitter 5000 into the stack
or duct. If installing an Oxymitter 5000/
SPS 4000 assembly, follow the instructions
in paragraph 6-4b2.
b. Electronic Assembly Replacement.
(Figure 6-5).
Remove the right housing cover unco vering
1.
the electronic assembly.
Depress and remove the J1 (cell and T/C)
2.
connector from the J1 socket. Loosen the
three captive mounting screws on the mi-
22220061
croprocessor board (top board).
Figure 6-6. J8 Connector
Hold the J1 and J8 connectors out and to
8.
the probe side of the electronic housing.
Make sure that the conduit port of the electronic housing is on the same side as the
CAL and REF gas ports. Replace the four
screws and tighten.
Reconnect the J8 connector to the power
9.
supply board. Make sure the connector is
secure.
10. Holding the J1 connector leads, slide the
electronic assembly the rest of the way into
the housing. Align the electronic assembly
so that it fits flush on the pins. To ensure
that it is flush, gently try to rotate the electronics. If the electronics rotates, repeat the
alignment.
11. Reconnect the J1 connector to the microprocessor board. Ensure the connector is
secure and tighten the three captive screws
on the microprocessor board (top board).
The J8 connector (heater leads) can be ac-
3.
cessed by moving the J1 connector leads
out of the slot on the microprocessor board
and sliding the electronic assembly partially
out of the housing (Figure 6-6).
Squeeze the J8 connector on the sides and
4.
carefully remove. The electronic assembly
can now be completely removed from the
housing.
Reconnect the J8 connector to the power
5.
supply board. Make sure the connector is
secure.
Holding the J1 connector leads, slide the
6.
electronic assembly the rest of the way into
the housing. Align the electronic assembly
so that it fits flush on the pins. To ensure
that it is flush, gently try to rotate the electronics. If the electronics rotates, repeat the
alignment.
Reconnect the J1 connector to the micro-
7.
processor board. Ensure the connector is
secure and tighten the three captive screws
on the microprocessor board (top board).
12. Replace the housing cover and ensure it is
tight.
IB-106-350
6-9
Replace the housing cover and ensure it is
8.
tight.
c. Terminal Block Replacement (Figure 6-4).
Loosen the mounting screws on the terminal
1.
block and carefully lift the block out of the
housing.
POWER
SUPPLY
BOARD
1
+
Carefully align the new terminal block on
2.
the pins so that it sits flat in the housing.
The round end of the terminal block should
be on the opposite side of the housing conduit ports and should not be able to rotate.
Tighten the three mounting screws and en-
3.
sure the terminal block is secure in the
housing.
d. Fuse Replacement (Figure 6-5).
Remove the right housing cover unco vering
1.
the electronic assembly.
Depress and remove the J1 (cell and T/C)
2.
connector from the J1 socket. Loosen the
three captive mounting screws on the microprocessor board (top board).
The J8 connector (heater leads) can be ac-
3.
cessed by moving the J1 connector leads
out of the slot on the microprocessor board
and sliding the electronic assembly partially
out of the housing (Figure 6-6).
Squeeze the J8 connector on the sides and
4.
carefully remove. The electronic assembly
can now be completely removed from the
housing.
FUSE
+
+
+
5A
250VAC
TIME LAG
3D39619G
1
+
REV
+
+
+
22220058
Figure 6-7. Fuse Location
Completely remove the three mounting
5.
screws on the microprocessor board.
Turn the electronic assembly over so that
6.
you are looking at the bottom of the power
supply printed circuit board. Gently depress
the two white posts one at a time. Carefully
separate the power supply board from the
microprocessor board.
Remove the fuse and replace it with a new
7.
one (Figure 6-7).
+
IB-106-350
6-10
Align the white posts with the post holes on
8.
the power supply board and the pin connector on the power supply board with the
connector port on the back of the microprocessor board. Gently push the boards together until the white posts snap in place.
Ensure the assembly is secure by gently
trying to separate the boards.
Reconnect connector J8 to the power supply
9.
board. Make sure the connector is secure.
10. Holding the J1 connector leads, slide the
electronic assembly the rest of the way into
the housing. Align the electronic assembly
so that it fits flush on the pins. To ensure
that it is flush, gently try to rotate the electronics. If the electronics rotates, repeat the
alignment.
6-7. HEATER STRUT REPLACEMENT. This
paragraph covers heater strut replacement. Do not
attempt to replace the heater strut until all other possibilities for poor performance have been considered.
If heater strut replacement is needed, order a replacement heater strut. (Table 7-1).
Use heat resistant gloves and clothing
when removing probe. Do not attempt to
work on the probe until it has cooled to
room temperature. The probe can be as
hot as 800°F (427°C). This can cause
severe burns.
NOTE
11. Reconnect the J1 connector to the microprocessor board. Ensure the connector is
secure and tighten the three captive screws
on the microprocessor board (top board).
12. Replace the housing cover and ensure that it
is tight.
6-6. ENTIRE PROBE REPLACEMENT (EX-
CLUDING ELECTRONICS). Do not attempt to
replace the probe until all other possibilities for poor
performance have been considered. If probe replacement is needed, see Table 7-1 for part numbers.
a. Follow the instructions in paragraph 6-4.a.1to
remove the Oxymitter 5000 from the stack or
duct. If removing an Oxymitter 5000 with an integrally mounted SPS 4000, follow the instructions in paragraph 6-4.b.1.
b. Separate the probe and the electronics housing
per paragraph 6-5.a, steps 2 through 6.
c. Reinstall electronics on the new probe per para-
graph 6-5.a, steps 7 through 13.
If the Oxymitter 5000 has an integrally
mounted SPS 4000, it is not necessary to
remove the sequencer when replacing the
heater strut.
a. Follow the instructions in paragraph 6-4a1 to
remove the Oxymitter 5000 from the stack or
duct. If removing an Oxymitter 5000/SPS 4000
assembly, follow the instructions in paragraph
6-4.b.1.
b. Remove entire electronics per paragraph 6-5.a,
steps 2 through 6.
NOTE
If the Oxymitter 5000 is equipped with an
integrally mounted SPS 4000 and installed
in corrosive conditions, stainless steel gas
tubes are used instead of silicon or Teflon
tubes.
c. Carefully remove the CAL and REF gas silicon
tubes by pulling them off the CAL and REF gas
ports. Pull the silicon tubes off the CAL and REF
gas lines.
IB-106-350
6-11
V-DEFLECTOR
CERAMIC
DIFFUSER
ASSEMBLY
WIRE
LOOP
CERAMIC SUPPORT ROD
CELL FLANGE
HEATER
22220050
Figure 6-8. Heater Strut Assembly
d. Loosen, but do not remove, the three screws (34,
Figure 6-1) on the strut in the finned housing.
The spring tension should release and the strut
moves up.
e. Grasp the wire loop and carefully slide the strut
out of the probe tube (Figure 6-8).
f. When replacing the strut, align the slot on the
heater plate with the calibration gas line in the
probe tube. Slide the strut into the p robe tube. It
will turn to align the hole on the back plate of the
strut with the calibration gas line. When the hole
and the calibration gas line are aligned correctly,
the strut will slide in the rest of the way.
g. Push down on the back plate of the strut to make
sure you have spring tension and then tighten the
three screws on the back plate.
h. Replace the CAL and REF gas silicon tubes.
i. Install the entire electronics per paragraph 6-5.a,
steps 7 through 13.
j. Follow the instructions in paragraph 6-4.a.2to in-
stall the Oxymitter 5000 into the stack or duct. If
installing an Oxymitter 5000/SPS 4000 assembly,
follow the instructions in paragraph 6-4.b.2.
IB-106-350
6-12
PROBETUBE
(NOT INCLUDED
IN KIT)
CORRUGATED
SEAL
CELL AND
FLANGE
ASSEMBLY
SOCKET HEAD
CAP SCREWS
CALIBRATION GAS
PASSAGE
22220028
Figure 6-9. Cell Replacement Kit
6-8. CELL REPLACEMENT. This par agraph covers
oxygen sensing cell replacement. Do not attempt to
replace the cell until all other possibilities for poor
performance have been considered. If cell replacement is needed, order the cell replacement kit (Table
7-1).
The cell replacement kit (Figure 6-9) contains a cell
and flange assembly, corrugated seal, setscrews,
socket head cap screws, and anti-seize compound.
The items are carefully packaged to preserve precise
surface finishes. Do not remove items from the packaging until they are ready to be used. Spanner
wrenches and hex wrenches needed for this procedure
are part of an available special tools kit (Table 7-1).
Use heat-resistant gloves and clothing
when removing the probe. Do not attempt to work on these components until
they have cooled to room temperature.
Probe components can be as hot as
800°F (427°C). This can cause severe
burns.
Disconnect and lock out power before
working on any electrical components.
There is voltage of up to 115 VAC.
Do not remove the cell unless certain it
needs to be replaced. Removal may
damage the cell and platinum pad. Go
through the complete troubleshooting
procedure to make sure the cell needs to
be replaced before removing it.
a. Follow the instructions in paragraph 6-4.a.1 to
remove the Oxymitter 5000 from the stack or
duct. If removing an Oxymitter 5000/SPS 4000
assembly, follow the instructions in paragraph
6-4.b.1.
b. If the probe uses the standard diffusion element,
use a spanner wrench to remove the diffusion
element.
IB-106-350
6-13
NOTE
To determine if the diffusion element
needs to be replaced, refer to paragraph
6-2.
c.
If equipped with the optional ceramic diffusor
assembly, remove and discard the setscrews and
remove the vee deflector (Figure 6-10). Use
spanner wrenches from the probe disassembly kit
(Table 7-1), to turn the hub free from the retainer.
Inspect the diffusion element. If damaged, replace the element.
d. Loosen the four socket head cap screws from the
cell and flange assembly and remove the assembly and the corrugated seal. The cell flange has a
notch that may be used to gently pry the flange
away from the probe. Note that the contact pad
inside of the probe will sometimes fuse to the
oxygen sensing cell. If the cell is fused to the
contact pad, push the cell assembly back into the
probe (against spring pressure) and quickly twist
the cell assembly. The cell and contact pad
should separate. If the contact pa d stays fusedto the cell, a new contact/thermocouple assembly
must be installed. Disconnect the cell and the
thermocouple wires at the probe electronics and
withdraw the cell with the wires still attached.
e. Remove entire electronics per paragraph 6-5.a,
steps 2 through 6.
j. Install the entire electronics per paragraph 6-5.a,
steps 7 through 13.
k. Apply anti-seize compound to the threads of the
cell assembly, hub, and setscrews. Reinstall the
hub on the cell assembly. Using pin spanner
wrenches, torque to 10 ft-lbs (14 N·m). If applicable, reinstall the vee deflector, orienting apex
toward gas flow. Secure with the setscrews and
anti-seize compound. Torque to 25 in-lbs
(2.8 N·m).
l. On systems equipped with an abrasive shield, in-
stall the dust seal gaskets, with joints 180° apart.
m.
Reinstall the probe and gasket on the stack
flange.
n. Follow the instructions in paragraph 6-4.a.2 to
install the Oxymitter 5000 into the stack or duct.
If installing an Oxymitter 5000/SPS 4000 assembly, follow the instructions in paragraph 6-4.b.2.
If there is an abrasive shield in the stack, make
sure the dust seal gaskets are in place as they enter the 15° reducing cone.
o. Turn on power and monitor thermocouple output.
It should stabilize at 29.3+0.2 mV. Set reference
air flow at 2 scfh (56.6 l/hr). After the Oxymitter
5000 stabilizes, calibrate the unit. If new components have been installed, repeat calibration after
24 hours of operation.
f. If the contact assembly is damaged, replace the
strut or the contact pad. Instructions for replacing
the contact pad are in the cell replacement kit.
g. Remove and discard the corrugated seal. Clean
the mating faces of the probe tube and retainer.
Remove burrs and raised surfaces with a block of
wood and crocus cloth. Clean the threads on the
retainer and hub.
h. Rub a small amount of anti-seize compound on
both sides of the new corrugated seal.
i. Assemble the cell and flange assembly, corru-
gated seal, and probe tube. Make sure the calibration tube lines up with the calibration gas pa ssage in each component. Apply a small amount
of anti-seize compound to the screw threads and
use the screws to secure assembly. Torque to 35
in-lbs (4 N·m).
PIN
WRENCH
OPTIONAL CERAMIC
DIFFUSION ELEMENT
FILLET
SETSCREW
VEE
DEFLECTOR
22220029
CEMENT
PORT
RETAINER
HUB
CEMENT
Figure 6-10. Ceramic Diffusion Element Replacement
IB-106-350
6-14
6-9. CERAMIC DIFFUSION ELEM ENT
REPLACEMENT.
NOTE
This refers to ceramic diffuser element only.
a. General. The diffusion element protects the cell
from particles in process gases. It does not
normally need to be replaced because the vee
deflector protects it from particulate erosion. In
severe environments, the filter may be broken or
subject to excessive erosion. Examine the
ceramic diffusion element whenever removing
the probe for any purpose. Replace if damaged.
Damage to the ceramic diffusion element may
become apparent during calibration. Compare
probe response with previous response. A broken
diffusion element will cause a slower response to
calibration gas.
Hex wrenches needed to remove setscrews and
socket head screws in the following procedure
are available as part of a Probe Disassembly Kit,
Table 7-1.
b. Replacement Procedure.
Follow the instructions in paragraph 6-4.a
1.
to remove the Hazardous Area Oxymitter
5000 from the stack or duct.
Loosen setscrews, Figure 6-10, using hex
2.
wrench from Probe Disassembly Kit, Table
7-1, and remove vee deflector. Inspect
setscrews. If damaged, replace with
stainless setscrews coated with anti-seize
compound.
On systems equipped with abrasive shield,
3.
remove dual dust seal gaskets.
Use spanner wrenches from Probe
4.
Disassembly Kit, Table 7-1, to turn hub free
from retainer.
Replace ceramic diffusion element using the
7.
ceramic diffusion element replacement kit
in Table 7-1. This consists of a diffusion
element, cement, setscrews, anti-seize compound, and instructions.
Test fit replacement ceramic diffusion ele-
8.
ment to be sure seat is clean.
Do not get cement on ceramic diffusion
element except where it touches the hub.
Any cement on ceramic diffusion element
blocks airflow through element. Wiping
wet cement off of ceramic only forces
cement into pores. Also, do not get any
cement onto the flame arrester element.
Thoroughly mix cement and insert tip of
9.
squeeze bottle into cement port. Tilt bo ttle
and squeeze while simultaneously turning
ceramic diffusion element into seat. Do not
get any cement on upper part of ceramic
diffusion element. Ensure complete penetration of cement around 3 grooves in hub.
Cement should extrude from opposite hole.
Wipe excess material back into holes and
wipe top fillet of cement to form a uniform
fillet. (A cotton swab is useful for this.)
Clean any excess cement from hub with
water.
10. Allow filter to dry at room temperature
overnight or 1 to 2 hours at 200°F (93°C).
11. Wipe a heavy layer of anti-seize compound
onto the threads and mating surfaces of the
flame arrester, diffusion hub, and probe
tube.
12. Assemble flame arrester and diffusion hub
with two pin spanner wrenches. Torque to
10 ft-lbs (14 N·m). Secure with hub retaining setscrew.
Put hub in vise. Break out old ceramic dif-
5.
fusion element with chisel along cement
line. Use a 3/8 in. (9.5 mm) pin punch and
clean fillet from the cement port.
Break out remaining ceramic diffusion ele-
6.
ment by tapping lightly around hub with
hammer. Clean grooves with pointed tool if
necessary.
IB-106-350
6-15
13. On systems equipped with abrasive shield,
install dust seal gaskets with joints 180(
apart.
14. Reinstall vee deflector, orienting apex toward gas flow. Apply anti-seize compound
to setscrews and tighten with hex wrench.
15. Reinstall probe on stack flange.
6-10. SPS 4000 MAINTENANCE AND COMPONENT
REPLACEMENT. These paragraphs describe SPS
4000 maintenance and component replacement
procedures. Replacement parts referenced are
available from Rosemount. Refer to Section VIII,
REPLACEMENT PARTS, for part numbers and
ordering information.
Install all protective equipment covers
and safety ground leads af ter equipment
repair or service. Failure to install covers
and ground leads could result in serious
injury or death.
a. Fuse Replacement. The SPS 4000 has a fuse
(17, Figure 6-11) on the power supply board
(18). Refer to Table 7-3 for replacement fuse
specifications. Perform the following procedure
to check or replace the fuse.
Disconnect and lock out power before
working on any electrical components.
Turn off power to the system.
1.
Remove screw (7, Figure 6-11) securing
2.
manifold cover lock (6) an d remove the lock.
Remove manifold cover ( 14).
3.
Remove fuseholder (16) by pushing in the
4.
top and turning 1/4 turn counterclockwise.
Remove fuse (17).
Remove screw (7) securing manifold c over
2.
lock (6) and remove the lock.
Remove manifold cover ( 14).
3.
Remove two screws (11) attaching spacers
4.
(9) to manifold (5).
Being careful not to disconnect the board
5.
wiring, carefully lift power supply board
(18) and interface board (19) from manifold
(5) and set aside. Do not lose o-rings (8)
from the bottom of spacers (9).
Tag all leads on the board to be replaced to
6.
simplify installation.
See Figure 6-12. If removing the power
7.
supply board, remove the line voltage input
leads from connector J7. Also, unplug calibration gas 1 solenoid leads from connector
J5, calibration gas 2 solenoid leads from
connector J4, and pressure switch leads
from connector J2.
See Figure 6-12. If removing the interface
board, remove the CAL INITIATE leads
from connector J3, CAL FAIL and IN CAL
leads from connector J4, and logic I/O
handshake connection from connector J5.
Remove stop nuts (22, Figure 6-11), wash-
8.
ers (21), and screws (10) securing power
supply board (18) and interface board (19)
to spacers (9).
Carefully separate boards (18 and 19).
9.
10. Connect replacement board to board (18 or
19).
After checking or replacing fuse (17), in-
5.
stall fuseholder (16) by pushing in the top
and turning 1/4 turn clockwise.
Install manifold cover (14), and secure with
6.
manifold cover lock (6) and screw (7).
b. Board Replacement. Perform the following
procedure to replace power supply board (18,
Figure 6-11) or interface board (19).
Disconnect and lock out power before
working on any electrical components.
Turn off power to the system.
1.
IB-106-350
6-16
11. Install screws (10), washers (21), and stop
nuts (22) to secure power supply board (18)
and interface board (19) to spacers (9).
12. Install all applicable leads in the appropriate
locations on the power supply board or interface board as shown in Figure 6-12.
13. Install power supply board (18, Figure
6-11) and interface board (19) into manifold
(5). Align spacers (9) with the mounting
holes on the manifold and secure with
screws (11). Ensure o-rings (8) are installed
between the spacers and the manifold
surface.
14. Install manifold cover (14) and secure with
manifold cover lock (6) and screw (7).
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.