MODEL OPM 2000R
TRANSMISSOMETER
OPACITY/DUST DENSITY
TRANSMITTER
Instruction Bulletin IB-106-200RRevision 1.1
Page 2
HIGHLIGHTS OF CHANGES
Effective April, 1998 Rev. 1.0
PAGESUMMARY
AllThe revision level changed from Original Issue to Revision 1.0 to distinguish between instruction
bulletins released in a preliminary state and the finalized instruction bulletin.
Effective February, 1999 Rev. 1.1
PAGESUMMARY
ThroughoutChanged NEMA 4X to Type 4X.
iiAdd electrical symbols.
1-5Modified the user-definable pathlength range.
2-7Indicated that power supply 2 (PS2) also supplies power to a status LED. Modified Figure 2-9 to
show that JM1 represents the low gain and JM2 represents the high gain.
2-9Changed the pathlength range of 20 to 40 ft (6.1 to 12.2 m) to 20 to 26 ft (6.1 to 7.9 m) in
Figure 2-12.
3-1Illustrated fuse F1 on the IG-1 software board in Figure 3-1.
3-2Listed relay jumper blocks in paragraph 3-2.b as components on the HART daughter board.
Illustrated fuse F1 on the IG-1 software board in Figure 3-2 and added paragraph 3-2.a.6
discussing the fuse.
3-3Modified Figure 3-3 to identify the relay jumper blocks and switches. Added paragraph 3-2.b.8 to
discuss the switches.
3-4Added paragraph 3-2.b.9 to explain the relay jumper blocks.
3-5Added new Figure 3-4 to illustr ate the HART daughter boa rd relay contact configurations.
3-6Listed relay jumper blocks in paragraph 3-3.b as components on the HART daughter board.
Updated figure number and figure number references. Illustrated fuse F1 on the IG-1 software
board in Figure 3-5.
3-7Updated figure numbers and figure number references.
4-0Added note 5 concerning the purge air failure flow switch cable connection.
4-3Added the B16.5 designation to the ANSI flange in Figure 4-3.
4-5Added four holes (and their dimensions) for customer wiring and add ed wiring conduit to
Figure 4-5.
4-8Added temperatures to Figure 4-8 at which the thermostat opens and closes. Corrected the
specification reference in paragraph 4-9.a.
4-9Added a no te concerning the relay jumper blocks on the HART da ughter board.
4-10Added note 1 to Figure 4-9 (Sheet 1 of 2) concerning the transceiver and retroreflector purge air
failure flow switch wiring.
IB-106-200R
Page 3
HIGHLIGHTS OF CHANGES (Continued)
Effective February, 1999 Rev. 1.1 (Continued)
PAGESUMMARY
4-12Added note 1 to Figure 4-10 (Sheet 1 of 2) concerning the transceiver and retroreflector purge air
failure flow switch wiring.
4-13Modified the HART daughter board to identify the relay jumpers and modified the IG-1 software
board to identify fuse F1 in Figure 4-10 (sheet 2 of 2).
4-14Added a note concerning the relay jumper blocks on the H ART daughter boar d.
6-9Added the default setting column to Table 6-6.
6-11Updated figure reference in paragraph 6-7.b.1.(c). Added new step 6-7.b.3 and modified new
paragraphs 7 and 8 concer ning zero jig usage. Renumbered subsequent steps.
6-12Added step 6-7.b.12 concerning zero jig usage. Added OCRF information to Table 6-7.
6-15Changed the number of neutral density filters from 20 to 30.
6-16Changed the number of neutral density filters from 20 to 30.
6-18Added a note concerning HART variables assigned the same process variables.
6-19Added the
6-20Updated the relay 4 and relay 5 default setting information in Table 6-12.
6-21Added the default setting column to Table 6-13.
6-23Added the default setting column to Table 6-15.
6-24Added the default setting column to Table 6-16.
6-25Added the default setting column to Table 6-17.
6-26Added OCRF to the REF. VOLTAGES menu in Figure 6-10 (sheet 1 of 3).
7-5Added item 12 to Table 7-2 concerning the stack LON board status LED.
8-10Updated the figure number and item number references in paragraphs 8-5.e.2, 3, and 5.
9-1Modified the pathlength LF and zero jig ranges in the encode matrix.
9-3Updated the pathlength LF, zero jig, and certification and labeling portions of the decode matrix.
9-4Updated the figure number references in Table 9-2.
9-5Added a second LCW 2 and added descriptive information to the existing LCW 2 in Table 9-4.
Also modified the objective lens and zero jig ranges in Table 9-4 and the retroreflector range in
Table 9-5.
9-6Updated figure number reference for part number 1A97913H03 in Table 9-6.
C-2Added OCRF at the end of the REF. VOLTAGES parameter list.
lx/lt
default setting information to paragraph 6-8.c.
IB-106-200R
Page 4
ROSEMOUNT WARRANTY
Rosemount warrants that the equipment manufactured and sold by it will, upon shipment, be free of defects in workmanship or material. Should any failure to conform to this
warranty become apparent during a peri od of on e year after the date of s h ipment, Rosemou n t
shall, upon prompt written notice from the purchaser, correct such nonconformity by repair
or replacement, F.O.B. factory of the defective part or parts. Correction in the manner
provided above shall constitute a fulfillment of all liabilities of Rosemount with respect to
the quality of the equipment.
THE FOREGOING WARRANTY IS EXCLUSIVE AND IN LIEU OF
ALL OTHER WARRANTIES OF QUALITY WHETHER WRITTEN, ORAL,
OR IMPLIED (INCLUDING ANY WARRANTY OF MERCHANTABILITY OF
FITNESS FOR PURPOSE).
The remedy(ies) provided above s h all be pu rch as er's sole remedy(ies ) f or an y failure of
Rosemount to comply with the warranty provisions, whether claims by the purchaser are
based in contract or in tort (including negligence).
Rosemount does not warrant equipment against normal deteriora tion due to environment. Factors such as corrosive gases and solid particulates can be detrimental and can
create the need for repair or replacement as part of normal wear and tear during the warranty
period.
Equipment supplied by Rosemount Analytical Inc. but not manufactured by it will be
subject to the same warran t y as is extended to Rosemoun t by the original manu f actu rer.
At the time of installation it is important that the required services are supplied to the
system and that the electronic controller is set up at least to the point where it is controlling
the sensor heater. This will ensure, that should there be a delay between installation and full
commissioning that the sensor being supplied with ac power and reference air will not be
subjected to component deterioration.
IB-106-200R
i
Page 5
PURPOSE
The purpose of this manual is to provide a comprehensive understanding of the OPM 2000R
Opacity/Dust Density Transmitter components, function, installation, startup, and maintenance. Opacity
Transmitter and Dust Density Transmitter both refer to the OPM 2000R instrument. The designation for U.S.
applications is Opacity Transmitter and for European applications is Dust Density Transmitter.
The overview presents the basic principles of the Opacity/Dust Density Transmitter along with the
system's performance characteristics and components. The remaining sections contain detailed procedures and
information necessary for the installation , startup, and servicing of the system.
Before contacting Rosemount concerning any questions, first consult this manual. It describes most
situations encountered in your system's operation and details necessary action.
DEFINITIONS
The following definitions apply to WARNINGS, CAUTIONS, and NOTES found throughout this
publication.
Highlights an operation or maintenance
procedure, practice, condition, statement,
etc. If not strictly observed, could result
in injury, death, or long-term health
hazards of personnel.
Highlights an essential operating procedure,
condition, or statemen t.
: EARTH (GROUND) TERMINAL
: PROTECTIVE CONDUCTOR TERMINAL
: RISK OF ELECTRICAL SHOCK
: WARNING: REFER TO INSTRUCTION BULLETIN
NOTE TO USERS
NOTE
Highlights an operation or maintenance
procedure, practice, condition, statement,
etc. If not strictly observed, could result
in damage to or destruction of equipment,
or loss of effectiveness
.
The number in the low er rig h t corn er of each illu stration in th is pu blication is a manual illustration number.
It is not a part number, and is not related to the illustration in any technical manner.
IB-106-200R
ii
Page 6
IMPORTANT
SAFETY INSTRUCTIONS FOR THE WIRING AND
INSTALLATION OF THIS APPARATUS
The following safety instructions apply specifically
to all EU member states. They should be strictly
adhered to in order to assure compliance with the
Low Voltage Directive. Non-EU states should also
comply with the following unless superseded by
local or National Standards.
1. Adequate earth connections should be made to all earthing points, internal and
external, where provided.
2. After installation or troubleshooting, all safety covers and safety grounds must be
replaced. The integrity of all earth terminals must be maintained at all times.
3. Mains supply cords should com pl y with th e requ i rements of IEC227 or IEC245.
4. All wiring sh all be s u itable f or us e in an ambient temperature of greater than 75°C .
5. All cable glands used should be of such internal dimensions as to provide adequate
cable anchorage.
6. To ensure safe operation of this equipment, connection to the mains supply should only
be made through a circuit breaker which will disconnect all circuits carrying
conductors during a fault situation. The circuit breaker may also include a
mechanically operated isolating switch. If not, then another means of disconnecting the
equipment from the supply must be provided and clearly marked as such. Circuit
breakers or switches must comply with a recognized standard such as IEC947. All
wiring mu s t con f orm with any local standards.
7. Where equipment or covers are marked with the symbol to the right,
hazardous voltages are likely to be present beneath. These covers
should only be removed when power is removed from the
equipment — and then on ly by trained service pers on n el.
8. Where equipment or covers are marked with the symbol to the right,
there is a danger from hot surfaces beneath. These covers should
only be removed by trained service personnel when power is
removed from the equipment. Certain surfaces may remain hot to
the touch.
9. Where equipment or covers are marked with the symbol to the right,
refer to the Operator Manual for instructions.
10. All graphical symbols used in this product are from one or more of the following
standards: EN61010-1, IEC417, and IS O3864.
IB-106-200R
iii
Page 7
BELANGRIJK
Veiligheidsvoorschriften voor de aansluiting en installatie van dit toestel.
De hierna volgende veiligheidsvoorschriften zijn vooral bedoeld voor de EU lidstaten. Hier
moet aan gehouden worden om de onderworpenheid aan de Laag Spannings Richtlijn (Low
Voltage Directive) te verzekeren. Niet EU staten zouden deze richtlijnen moeten volgen
tenzij zij reeds achterhaald zouden zijn door plaatselijke of nationale voorschriften.
1.Degelijke aardingsaansluitingen moeten gemaakt worden naar alle voorziene aardpunten,
intern en extern.
2.Na installatie of controle moeten alle veiligheidsdeksels en -aardingen terug geplaatst
worden. Ten alle tijde moet de betrouwbaarheid van de aarding behouden blijven.
3.Voedingskabels moeten onderworpen zijn aan de IEC227 of de IEC245 voorschriften.
4.Alle bekabeling moet geschikt zijn voor het gebruik in omgevingstemperaturen, hoger dan
75°C.
5.Alle wartels moeten zo gedimensioneerd zijn dat een degelijke kabel bevestiging verzekerd
is.
6.Om de veilige werking van dit toestel te verzekeren, moet de voeding door een
stroomonderbreker gevoerd worden (min 10A) welke alle draden van de voeding moet
onderbreken. De stroomonderbreker mag een mechanische schakelaar bevatten. Zoniet moet
een andere mogelijkheid bestaan om de voedingsspanning van het toestel te halen en ook
duidelijk zo zijn aangegeven. Stroomonderbrekers of schakelaars moeten onderworpen zijn
aan een erkende standaard zoals IEC947.
7.Waar toestellen of deksels aangegeven staan met het symbool is er
meestal hoogspanning aanwezig. Deze deksels mogen enkel verwijderd
worden nadat de voedingsspanning werd afgelegd en enkel door getraind
onderhoudspersoneel.
8.Waar toestellen of deksels aangegeven staan met het symbool is er gevaar
voor hete oppervlakken. Deze deksels mogen enkel verwijderd worden
door getraind onderhoudspersoneel nadat de voedingsspanning
verwijderd werd. Sommige oppper-vlakken kunnen 45 minuten later nog
steeds heet aanvoelen.
9.Waar toestellen of deksels aangegeven staan met het symbool gelieve het
handboek te raadplegen.
10. Alle grafische symbolen gebruikt in dit produkt, zijn afkomstig uit een of meer van
devolgende standaards: EN61010-1, IEC417 en ISO3864.
IB-106-200R
iv
Page 8
VIGTIGT
Sikkerhedsinstruktion for tilslutning og installering af dette udstyr.
Følgende sikkerhedsinstruktioner gælder specifikt i alle EU-medlemslande.
Instruktionerne skal nøje følges for overholdelse af Lavsspændingsdirektivet og bør også
følges i ikke EU-lande medmindre andet er specificeret af lokale eller nationale standarder.
1.Passende jordforbindelser skal tilsluttes alle jordklemmer, interne og eksterne, hvor disse
forefindes.
2.Efter installation eller fejlfinding skal alle sikkerhedsdæksler og jordforbindelser
reetableres.
3.Forsyningskabler skal opfylde krav specificeret i IEC227 eller IEC245.
4.Alle ledningstilslutninger skal være konstrueret til omgivelsestemperatur højere end 75° C.
5.Alle benyttede kabelforskruninger skal have en intern dimension, så passende
kabelaflastning kan etableres.
6.For opnåelse af sikker drift og betjening skal der skabes beskyttelse mod indirekte berøring
gennem afbryder (min. 10A), som vil afbryde alle kredsløb med elektriske ledere i fejlsituation. Afbryderen skal indholde en mekanisk betjent kontakt. Hvis ikke skal anden form for
afbryder mellem forsyning og udstyr benyttes og mærkes som sådan. Afbrydere eller
kontakter skal overholde en kendt standard som IEC947.
7.Hvor udstyr eller dæksler er mærket med dette symbol, er farlige spændinger
normalt forekom-mende bagved. Disse dæksler bør kun afmonteres, når
forsyningsspændingen er frakoblet - og da kun af instrueret servicepersonale.
8.Hvor udstyr eller dæksler er mærket med dette symbol, forefindes meget
varme overflader bagved. Disse dæksler bør kun afmonteres af instrueret
servicepersonale, når forsyningsspænding er frakoblet. Visse overflader vil
stadig være for varme at berøre i op til 45 minutter efter frakobling.
9.Hvor udstyr eller dæksler er mærket med dette symbol, se da i
betjeningsmanual for instruktion.
10. Alle benyttede grafiske symboler i dette udstyr findes i én eller flere af følgende standarder:EN61010-1, IEC417 & ISO3864.
IB-106-200R
v
Page 9
BELANGRIJK
Veiligheidsinstructies voor de bedrading en installatie van dit apparaat.
Voor alle EU lidstaten zijn de volgende veiligheidsinstructies van toepassing. Om aan de
geldende richtlijnen voor laagspanning te voldoen dient men zich hieraan strikt te houden.
Ook niet EU lidstaten dienen zich aan het volgende te houden, tenzij de lokale wetgeving
anders voorschrijft.
1.Alle voorziene interne- en externe aardaansluitingen dienen op adequate wijze aangesloten
te worden.
2.Na installatie,onderhouds- of reparatie werkzaamheden dienen alle beschermdeksels
/kappen en aardingen om reden van veiligheid weer aangebracht te worden.
3.Voedingskabels dienen te voldoen aan de vereisten van de normen IEC 227 of IEC 245.
4.Alle bedrading dient geschikt te zijn voor gebruik bij een omgevings temperatuur boven
75°C.
5.Alle gebruikte kabelwartels dienen dusdanige inwendige afmetingen te hebben dat een
adequate verankering van de kabel wordt verkregen.
6.Om een veilige werking van de apparatuur te waarborgen dient de voeding uitsluitend plaats
te vinden via een meerpolige automatische zekering (min.10A) die
alle
spanningvoerende
geleiders verbreekt indien een foutconditie optreedt. Deze automatische zekering mag ook
voorzien zijn van een mechanisch bediende schakelaar. Bij het ontbreken van deze
voorziening dient een andere als zodanig duidelijk aangegeven mogelijkheid aanwezig te
zijn om de spanning van de apparatuur af te schakelen. Zekeringen en schakelaars dienen te
voldoen aan een erkende standaard zoals IEC 947.
7.Waar de apparatuur of de beschermdeksels/kappen gemarkeerd zijn met het
volgende symbool, kunnen zich hieronder spanning voerende delen bevinden
die gevaar op kunnen leveren. Deze beschermdeksels/kappen mogen
uitsluitend verwijderd worden door getraind personeel als de spanning is
afgeschakeld.
8.Waar de apparatuur of de beschermdeksels/kappen gemarkeerd zijn met het
volgende symbool, kunnen zich hieronder hete oppervlakken of onderdelen
bevinden. Bepaalde delen kunnen mogelijk na 45 min. nog te heet zijn om aan
te raken.
9.Waar de apparatuur of de beschermdeksels/kappen gemarkeerd zijn met het
volgende symbool, dient men de bedieningshandleiding te raadplegen.
10. Alle grafische symbolen gebruikt bij dit produkt zijn volgens een of meer van de volgende
standaarden: EN 61010-1, IEC 417 & ISO 3864.
IB-106-200R
vi
Page 10
TÄRKEÄÄ
Turvallisuusohje, jota on noudatettava tämän laitteen asentamisessa ja kaapeloinnissa.
Seuraavat ohjeet pätevät erityisesti EU:n jäsenvaltioissa. Niitä täytyy ehdottomasti
noudattaa jotta täytettäisiin EU:n matalajännitedirektiivin (Low Voltage Directive)
yhteensopivuus. Myös EU:hun kuulumattomien valtioiden tulee nou-dattaa tätä ohjetta,
elleivät kansalliset standardit estä sitä.
1.Riittävät maadoituskytkennät on tehtävä kaikkiin maadoituspisteisiin, sisäisiin ja ulkoisiin.
2.Asennuksen ja vianetsinnän jälkeen on kaikki suojat ja suojamaat asennettava takaisin paikoilleen. Maadoitusliittimen kunnollinen toiminta täytyy aina ylläpitää.
3.Jännitesyöttöjohtimien täytyy täyttää IEC227 ja IEC245 vaatimukset.
4.Kaikkien johdotuksien tulee toimia >75°C lämpötiloissa.
5.Kaikkien läpivientiholkkien sisähalkaisijan täytyy olla sellainen että kaapeli lukkiutuu kunnolla kiinni.
6.Turvallisen toiminnan varmistamiseksi täytyy jännitesyöttö varustaa turvakytkimellä (min
10A), joka kytkee irti kaikki jännitesyöttöjohtimet vikatilanteessa. Suojaan täytyy myös
sisältyä mekaaninen erotuskytkin. Jos ei, niin jännitesyöttö on pystyttävä katkaisemaan
muilla keinoilla ja merkittävä siten että se tunnistetaan sellaiseksi. Turvakytkimien tai katkaisimien täytyy täyttää IEC947 standardin vaatimukset näkyvyydestä.
7.Mikäli laite tai kosketussuoja on merkitty tällä merkillä on merkinnän
takana tai alla hengenvaarallisen suuruinen jännite. Suojaa ei saa poistaa
jänniteen ollessa kytkettynä laitteeseen ja poistamisen saa suorittaa vain
alan asian-tuntija.
8.Mikäli laite tai kosketussuoja on merkitty tällä merkillä on merkinnän
takana tai alla kuuma pinta. Suojan saa poistaa vain alan asiantuntija kun
jännite-syöttö on katkaistu. Tällainen pinta voi säilyä kosketuskuumana
jopa 45 mi-nuuttia.
9.Mikäli laite tai kosketussuoja on merkitty tällä merkillä katso lisäohjeita
käyt-töohjekirjasta
10. Kaikki tässä tuotteessa käytetyt graafiset symbolit ovat yhdestä tai useammasta seuraavis-ta
standardeista: EN61010-1, IEC417 & ISO3864.
IB-106-200R
vii
Page 11
IMPORTANT
Consignes de sécurité concernant le raccordement et l’installation de cet appareil.
Les consignes de sécurité ci-dessous s’adressent particulièrement à tous les états membres
de la communauté européenne. Elles doivent être strictement appliquées afin de satisfaire
aux directives concernant la basse tension. Les états non membres de la communauté
européenne doivent également appliquer ces consignes sauf si elles sont en contradiction
avec les standards locaux ou nationaux.
1.Un raccordement adéquat à la terre doit être effectuée à chaque borne de mise à la terre,
interne et externe.
2.Après installation ou dépannage, tous les capots de protection et toutes les prises de terre
doivent être remis en place, toutes les prises de terre doivent être respectées en permanence.
3.Les câbles d’alimentation électrique doivent être conformes aux normes IEC227 ou IEC245
4.Tous les raccordements doivent pouvoir supporter une température ambiante supérieure à
75°C.
5.Tous les presse-étoupes utilisés doivent avoir un diamètre interne en rapport avec les câbles
afin d’assurer un serrage correct sur ces derniers.
6.Afin de garantir la sécurité du fonctionnement de cet appareil, le raccordement à
l’alimentation électrique doit être réalisé exclusivement au travers d’un disjoncteur
(minimum 10A.) isolant tous les conducteurs en cas d’anomalie. Ce disjoncteur doit
également pouvoir être actionné manuellement, de façon mécanique. Dans le cas contraire,
un autre système doit être mis en place afin de pouvoir isoler l’appareil et doit être signalisé
comme tel. Disjoncteurs et interrupteurs doivent être conformes à une norme reconnue telle
IEC947.
7.Lorsque les équipements ou les capots affichent le symbole suivant, cela
signifie que des tensions dangereuses sont présentes. Ces capots ne doivent
être démontés que lorsque l’alimentation est coupée, et uniquement par un
personnel compétent.
8.Lorsque les équipements ou les capots affichent le symbole suivant, cela
signifie que des surfaces dangereusement chaudes sont présentes. Ces capots
ne doivent être démontés que lorsque l’alimentation est coupée, et uniquement
par un personnel compétent. Certaines surfaces peuvent rester chaudes jusqu’à
45 mn.
9.Lorsque les équipements ou les capots affichent le symbole suivant, se
reporter au manuel d’instructions.
10. Tous les symboles graphiques utilisés dans ce produit sont conformes à un ou plusieurs des
standards suivants: EN61010-1, IEC417 & ISO3864.
IB-106-200R
viii
Page 12
Wichtig
Sicherheitshinweise für den Anschluß und die Installation dieser Geräte.
Die folgenden Sicherheitshinweise sind in allen Mitgliederstaaten der europäischen
Gemeinschaft gültig. Sie müssen strickt eingehalten werden, um der
Niederspannungsrichtlinie zu genügen. Nichtmitgliedsstaaten der europäischen
Gemeinschaft sollten die national gültigen Normen und Richtlinien einhalten.
1.Alle intern und extern vorgesehenen Erdungen der Geräte müssen ausgeführt werden.
2.Nach Installation, Reparatur oder sonstigen Eingriffen in das Gerät müssen alle
Sicherheitsabdeckungen und Erdungen wieder installiert werden. Die Funktion aller
Erdverbindungen darf zu keinem Zeitpunkt gestört sein.
3.Die Netzspannungsversorgung muß den Anforderungen der IEC227 oder IEC245 genügen.
4.Alle Verdrahtungen sollten mindestens bis 75 °C ihre Funktion dauerhaft erfüllen.
5.Alle Kabeldurchführungen und Kabelverschraubungen sollten in Ihrer Dimensionierung so
gewählt werden, daß diese eine sichere Verkabelung des Gerätes ermöglichen.
6.Um eine sichere Funktion des Gerätes zu gewährleisten, muß die Spannungsversorgung über
mindestens 10 A abgesichert sein. Im Fehlerfall muß dadurch gewährleistet sein, daß die
Spannungsversorgung zum Gerät bzw. zu den Geräten unterbrochen wird. Ein mechanischer
Schutzschalter kann in dieses System integriert werden. Falls eine derartige Vorrichtung
nicht vorhanden ist, muß eine andere Möglichkeit zur Unterbrechung der Spannungszufuhr
gewährleistet werden mit Hinweisen deutlich gekennzeichnet werden. Ein solcher
Mechanismus zur Spannungsunterbrechung muß mit den Normen und Richtlinien für die
allgemeine Installation von Elektrogeräten, wie zum Beispiel der IEC947, übereinstimmen.
7.Mit dem Symbol sind Geräte oder Abdeckungen gekennzeichnet, die eine
gefährliche (Netzspannung) Spannung führen. Die Abdeckungen dürfen
nur entfernt werden, wenn die Versorgungsspannung unterbrochen wurde.
Nur geschultes Personal darf an diesen Geräten Arbeiten ausführen.
8.Mit dem Symbol sind Geräte oder Abdeckungen gekennzeichnet, in bzw.
unter denen heiße Teile vorhanden sind. Die Abdeckungen dürfen nur
entfernt werden, wenn die Versorgungsspannung unterbrochen wurde.
Nur geschultes Personal darf an diesen Geräten Arbeiten ausführen. Bis
45 Minuten nach dem Unterbrechen der Netzzufuhr können derartig Teile
noch über eine erhöhte Temperatur verfügen.
9.Mit dem Symbol sind Geräte oder Abdeckungen gekennzeichnet, bei
denen vor dem Eingriff die entsprechenden Kapitel im Handbuch
sorgfältig durchgelesen werden müssen.
10. Alle in diesem Gerät verwendeten graphischen Symbole entspringen einem oder mehreren
der nachfolgend aufgeführten Standards: EN61010-1, IEC417 & ISO3864.
IB-106-200R
ix
Page 13
IMPORTANTE
Norme di sicurezza per il cablaggio e l’installazione dello strumento.
Le seguenti norme di sicurezza si applicano specificatamente agli stati membri dell’Unione
Europea, la cui stretta osservanza è richiesta per garantire conformità alla Direttiva del
Basso Voltaggio. Esse si applicano anche agli stati non appartenenti all’Unione Europea,
salvo quanto disposto dalle vigenti normative locali o nazionali
1.Collegamenti di terra idonei devono essere eseguiti per tutti i punti di messa a terra interni
ed esterni, dove previsti.
2.Dopo l’installazione o la localizzazione dei guasti, assicurarsi che tutti i coperchi di
protezione siano stati collocati e le messa a terra siano collegate. L’integrità di ciscun
morsetto di terra deve essere costantemente garantita.
3.I cavi di alimentazione della rete devono essere secondo disposizioni IEC227 o IEC245.
4.L’intero impianto elettrico deve essere adatto per uso in ambiente con temperature superiore
a 75°C.
5.Le dimensioni di tutti i connettori dei cavi utilizzati devono essere tali da consentire un
adeguato ancoraggio al cavo.
.
6.Per garantire un sicuro funzionamento dello strumento il collegamento alla rete di
alimentazione principale dovrà essere eseguita tramite interruttore automatico (min.10A), in
grado di disattivare tutti i conduttori di circuito in caso di guasto. Tale interruttore dovrà
inoltre prevedere un sezionatore manuale o altro dispositivo di interruzione
dell’alimentazione, chiaramente identificabile. Gli interruttori dovranno essere conformi
agli standard riconosciuti, quali IEC947.
7.Il simbolo riportato sullo strumento o sui coperchi di protezione indica
probabile presenza di elevati voltaggi. Tali coperchi di protezione devono
essere rimossi esclusivamente da personale qualificato, dopo aver tolto
alimentazione allo strumento.
8.Il simbolo riportato sullo strumento o sui coperchi di protezione indica rischio
di contatto con superfici ad alta temperatura. Tali coperchi di protezione
devono essere rimossi esclusivamente da personale qualificato, dopo aver tolto
alimentazione allo strumento. Alcune superfici possono mantenere
temperature elevate per oltre 45 minuti.
9.Se lo strumento o il coperchio di protezione riportano
il simbolo, fare riferimento alle istruzioni del manuale
Operatore.
10. Tutti i simboli grafici utilizzati in questo prodotto sono previsti da uno o più dei seguenti
standard: EN61010-1, IEC417 e ISO3864.
IB-106-200R
x
Page 14
VIKTIG
Sikkerhetsinstruks for tilkobling og installasjon av dette utstyret.
Følgende sikkerhetsinstruksjoner gjelder spesifikt alle EU medlemsland og land med i
EØS-avtalen. Instruksjonene skal følges nøye slik at installasjonen blir i henhold til
lavspenningsdirektivet. Den bør også følges i andre land, med mindre annet er spesifisert
av lokale- eller nasjonale standarder.
1.Passende jordforbindelser må tilkobles alle jordingspunkter, interne og eksterne hvor disse
forefinnes.
2.Etter installasjon eller feilsøking skal alle sikkerhetsdeksler og jordforbindelser reetableres.
Jordingsforbindelsene må alltid holdes i god stand.
3.Kabler fra spenningsforsyning skal oppfylle kravene spesifisert i IEC227 eller IEC245.
4.Alle ledningsforbindelser skal være konstruert for en omgivelsestemperatur høyere en 750C.
5.Alle kabelforskruvninger som benyttes skal ha en indre dimensjon slik at tilstrekkelig
avlastning oppnåes.
6.For å oppnå sikker drift og betjening skal forbindelsen til spenningsforsyningen bare skje
gjennom en strømbryter (minimum 10A) som vil bryte spenningsforsyningen til alle
elektriske kretser ved en feilsituasjon. Strømbryteren kan også inneholde en mekanisk
operert bryter for å isolere instrumentet fra spenningsforsyningen. Dersom det ikke er en
mekanisk operert bryter installert, må det være en annen måte å isolere utstyret fra
spenningsforsyningen, og denne måten må være tydelig merket. Kretsbrytere eller
kontakter skal oppfylle kravene i en annerkjent standard av typen IEC947 eller tilsvarende.
7.Der hvor utstyr eller deksler er merket med symbol for farlig spenning, er det
sannsynlig at disse er tilstede bak dekslet. Disse dekslene må bare fjærnes når
spenningsforsyning er frakoblet utstyret, og da bare av trenet servicepersonell.
8.Der hvor utstyr eller deksler er merket med symbol for meget varm overflate,
er det sannsynlig at disse er tilstede bak dekslet. Disse dekslene må bare
fjærnes når spenningsforsyning er frakoblet utstyret, og da bare av trenet
servicepersonell. Noen overflater kan være for varme til å berøres i opp til 45
minutter etter spenningsforsyning frakoblet.
9.Der hvor utstyret eller deksler er merket med symbol, vennligst referer til
instruksjonsmanualen for instrukser.
10. Alle grafiske symboler brukt i dette produktet er fra en eller flere av følgende standarder:
EN61010-1, IEC417 & ISO3864.
IB-106-200R
xi
Page 15
IMPORTANTE
Instruções de segurança para ligação e instalação deste aparelho.
As seguintes instruções de segurança aplicam-se especificamente a todos os estados
membros da UE. Devem ser observadas rigidamente por forma a garantir o cumprimento
da Directiva sobre Baixa Tensão. Relativamente aos estados que não pertençam à UE,
deverão cumprir igualmente a referida directiva, exceptuando os casos em que a legislação
local a tiver substituído.
1.Devem ser feitas ligações de terra apropriadas a todos os pontos de terra, internos ou externos.
2.Após a instalação ou eventual reparação, devem ser recolocadas todas as tampas de seg urança
e terras de protecção. Deve manter-se sempre a integridade de todos os terminais de terra.
3.Os cabos de alimentação eléctrica devem obedecer às exigências das normas IEC227 ou
IEC245.
4.Os cabos e fios utilizados nas ligações eléctricas devem ser adequados para utilização a uma
temperatura ambiente até 75º C.
5.As dimensões internas dos bucins dos cabos devem ser adequadas a uma boa fixação dos
cabos.
6.Para assegurar um funcionamento seguro deste equipamento, a ligação ao cabo de
alimentação eléctrica deve ser feita através de um disjuntor (min. 10A) que desligará todos
os condutores de circuitos durante uma avaria. O disjuntor poderá também conter um
interruptor de isolamento accionado manualmente. Caso contrário, deverá ser instalado
qualquer outro meio para desligar o equipamento da energia eléctrica, devendo ser
assinalado convenientemente. Os disjuntores ou interruptores devem obedecer a uma norma
reconhecida, tipo IEC947.
7.Sempre que o equipamento ou as tampas contiverem o símbolo, é provável a
existência de tensões perigosas. Estas tampas só devem ser retiradas quando a
energia eléctrica tiver sido desligada e por Pessoal da Assistência devidamente
treinado.
8.Sempre que o equipamento ou as tampas contiverem o símbolo, há perigo de
existência de superfícies quentes. Estas tampas só devem ser retiradas por
Pessoal da Assistência devidamente treinado e depois de a energia eléctrica ter
sido desligada. Algumas superfícies permanecem quentes até 45 minutos
depois.
9.Sempre que o equipamento ou as tampas contiverem o símbolo, o Manual de
Funcionamento deve ser consultado para obtenção das necessárias instruções.
10. Todos os símbolos gráficos utilizados neste produto baseiam-se em uma ou mais das
seguintes normas: EN61010-1, IEC417 e ISO3864.
IB-106-200R
xii
Page 16
IMPORTANTE
Instrucciones de seguridad para el montaje y cableado de este aparato.
Las siguientes instrucciones de seguridad , son de aplicacion especifica a todos los
miembros de la UE y se adjuntaran para cumplir la normativa europea de baja tension.
1.Se deben preveer conexiones a tierra del equipo, tanto externa como internamente, en
aquellos terminales previstos al efecto.
2.Una vez finalizada las operaciones de mantenimiento del equipo, se deben volver a colocar
las cubiertas de seguridad aasi como los terminales de tierra. Se debe comprobar la
integridad de cada terminal.
3.Los cables de alimentacion electrica cumpliran con las normas IEC 227 o IEC 245.
4.Todo el cableado sera adecuado para una temperatura ambiental de 75ºC.
5.Todos los prensaestopas seran adecuados para una fijacion adecuada de los cables.
6.Para un manejo seguro del equipo, la alimentacion electrica se realizara a traves de un
interruptor magnetotermico ( min 10 A ), el cual desconectara la alimentacion electrica al
equipo en todas sus fases durante un fallo. Los interruptores estaran de acuerdo a la norma
IEC 947 u otra de reconocido prestigio.
7.Cuando las tapas o el equipo lleve impreso el simbolo de tension electrica
peligrosa, dicho alojamiento solamente se abrira una vez que se haya
interrumpido la alimentacion electrica al equipo asimismo la intervencion
sera llevada a cabo por personal entrenado para estas labores.
8.Cuando las tapas o el equipo lleve impreso el simbolo, hay superficies
con alta temperatura, por tanto se abrira una vez que se haya interrumpido
la alimentacion electrica al equipo por personal entrenado para estas
labores, y al menos se esperara unos 45 minutos para enfriar las
superficies calientes.
9.Cuando el equipo o la tapa lleve impreso el simbolo, se consultara el
manual de instrucciones.
10. Todos los simbolos graficos usados en esta hoja, estan de acuerdo a las siguientes normas
EN61010-1, IEC417 & ISO 3864.
IB-106-200R
xiii
Page 17
VIKTIGT
Säkerhetsföreskrifter för kablage och installation av denna apparat.
Följande säkerhetsföreskrifter är tillämpliga för samtliga EU-medlemsländer. De skall
följas i varje avseende för att överensstämma med Lågspännings direktivet. Icke EU
medlemsländer skall också följa nedanstående punkter, såvida de inte övergrips av lokala
eller nationella föreskrifter.
1. Tillämplig jordkontakt skall utföras till alla jordade punkter, såväl internt som externt där så
erfordras.
2. Efter installation eller felsökning skall samtliga säkerhetshöljen och säkerhetsjord
återplaceras. Samtliga jordterminaler måste hållas obrutna hela tiden.
3. Matningsspänningens kabel måste överensstämma med föreskrifterna i IEC227 eller
IEC245.
4. Allt kablage skall vara lämpligt för användning i en omgivningstemperatur högre än 75ºC.
5. Alla kabelförskruvningar som används skall ha inre dimensioner som motsvarar adekvat
kabelförankring.
6. För att säkerställa säker drift av denna utrustning skall anslutning till huvudströmmen endast
göras genom en säkring (min 10A) som skall frånkoppla alla strömförande kretsar när något
fel uppstår. Säkringen kan även ha en mekanisk frånskiljare. Om så inte är fallet, måste ett
annat förfarande för att frånskilja utrustningen från strömförsörjning tillhandahållas och
klart framgå genom markering. Säkring eller omkopplare måste överensstämma med en
gällande standard såsom t ex IEC947.
7. Där utrustning eller hölje är markerad med vidstående symbol föreliggerisk för
livsfarlig spänning i närheten. Dessa höljen får endast avlägsnas när strömmen
ej är ansluten till utrustningen - och då endast av utbildad servicepersonal.
8. När utrustning eller hölje är markerad med vidstående symbol föreligger risk
för brännskada vid kontakt med uppvärmd yta. Dessa höljen får endast
avlägsnas av utbildad servicepersonal, när strömmen kopplats från
utrustningen. Vissa ytor kan vara mycket varma att vidröra även upp till 45
minuter efter avstängning av strömmen.
9. När utrustning eller hölje markerats med vidstående symbol bör
instruktionsmanualen studeras för information.
10.
Samtliga grafiska symboler som förekommer i denna produkt finns angivna i en eller flera
av följande föreskrifter:- EN61010-1, IEC417 & ISO3864.
X.RETURNING EQUIPMENT TO THE FACTORY........................................................10-1
INDEX ................................................................................................................................................I-1
APPENDIX A. OPACITY CROSS-REFERENCE TABLE ............................................................A-1
APPENDIX B. OPACITY MONITORING SYSTEM OPM 2000R SERVICE SCHEDULE.........B-1
APPENDIX C. ROSEMOUNT OPACITY VALUES WORKSHEET.............................................C-1
IB-106-200R
xviii
Page 22
LIST OF ILLUSTRATIONS
FigurePage
1-1Standard Model OPM 2000R Transmissometer Opacity/Dust Density Transmitter.......1-0
Communications Package (optional)
4Optical Alignment Sight (optional) 12Instruction Bulletin
56 in. Optical Extension (optional) 13Power Test Cable
6LON Communication Test Cable14Zero Jig (optional)
7Power Supply (optional)
Figure 1-1. Standard Model OPM 2000R Transmi s s ometer Opacity/Dust Dens ity T r ans mitter
24670004
IB-106-200R
1-0
Page 26
SECTION I. SYSTEM OVERVIEW
1-1.COMPONENT CHECKLIST OF TYPICAL
SYSTEM (PACKAGE CONTENTS).
Rosemount Model OPM 2000R Transmissometer
Opacity/Dust Density Transmitter should contain the
items shown in Figure 1-1.
1-2.SYSTEM OVERVIEW.
a. Scope
b. Reason for Measuring Opacity.
. This instruction bulletin is designed to
supply details needed to install, operate, and
maintain an OPM 2000R.
to the amount of light being scattered or absorbed
by particles in the light beam path. An opacity or
dust density transmitter (also called a transmissometer) measures the particulate level of stack
emissions. One of the most common reasons for
measuring opacity is to comply with Environmental Protection Agency (EPA) or other
national requirements. Federal regulations for
new emission sources and many state regulations
for both new and existing sources specify
maximum limits for stack emission opacity.
A transmissometer can be used in a variety of
applications. Those applications include monitoring the efficiency of emission control systems,
detecting broken bags in baghouses, and determining the time rapping cycles for electrostatic
precipitators. Another application is to gauge the
effectiveness of injecting flue gas conditioning
agents used to improve electrostatic precipitator
performance.
Opacity data can also serve a s a rough indicator
of combustion efficiency. Extreme changes in
opacity may indicate inefficient combustion or
A typical
Opacity refers
boiler problems. Because the transmitter gives
accurate, immediate-response data, corrective
actions can be taken as soon as problems occur.
This data serves not only the compliance
requirement of pollution regulation standards b ut
also as a means to achieve improved efficiency
and operating profit.
Originally, a trained smoke reader determined the
particulate level of stack emissions solely by
observation. The opacity of the plume was
judged in reference to a standard Ringelmann
scale of 0 to 5. These determinations tended to be
influenced by several sources of error such as sky
haze, sun position, and the subjective determination of the observer. These sources of error,
especially at lower opacity levels, can produce
highly variable readings even when performed by
a trained observer.
c.System Description.
situ optical transmitter that uses a visible light
beam in the photopic region (peak and mean
responses in the 500 to 600 nm range) to measure
opacity in stack emissions. The OPM 2000R
contains no moving parts except for blower
motors, which eliminates sources of wear and
possible failure.
Federal regulations and many state and local laws
use visual observation as a reference. Thus, for a
true correlation, it is important that transmissometers use the same spectral response range as
the human eye. This portion of the spectrum is
called the photopic response range. Since visual
readings are taken at the stack exit, the OPM
2000R compensates for the difference between
stack diameter at the exit and stack diameter at
the installation site.
The OPM 2000R is an in
IB-106-200R
1-1
Page 27
The OPM 2000R consists of a transmitter/
receiver (transceiver) module, a retroreflector
module, and intelligent electronics. The
transceiver and retroreflector modules are
mounted directly opposite of each other on the
stack (Figure 1-2). The transceiver projects a
controlled beam of light across the stack. The
corner cube bounces the light back along a
parallel path to the transceiver. Particles in the
gas stream cause a certain amount of the light
to be scattered and absorbed. This amount
varies depending upon the particulate content
of the gas stream and the particle type and
size.
TRANSCEIVER
MODULE
LAMP
OBJECTIVE
LENS
The light then strikes a detector, which converts
the light into a voltage that can be processed. The
detector signal is amplified by an independently
powered detector/amplifier board. The amplified
signal is then digitized and transmitted to the
intelligent electronics. The intelligent electronics
calculates opacity, sends commands to the
transceiver, and provides an operator interface
via HART communications.
Because the beam passes through the stack twice
(once in each direction), the resulting value is a
double-pass transmittance measurement. By
passing through the smoke twice, sensitivity to
low opacity levels is increased.
WINDOW
RETROREFLECTOR
STACK
EXHAUST
CORNER
CUBE
BEAM
SPLITTER
NOTES: BLOWER MOTORS ARE NOT SHOWN.
COMMUNICATIONS CABLE MAY BE UP TO 1 MILE LONG.
DETECTOR
Figure 1-2. Component Relationships
COMMUNICATIONS
CABLE TO AND
FROM TRANSCEIVER
WINDOW
ACCESS
PLATE
INTELLIGENT
ELECTRONICS
HART
COMMUNICATOR
24670005
IB-106-200R
1-2
Page 28
The measurement value is compared to a
reference value previously determined with no
smoke in the light path. The resulting ratio is the
transmittance value for the measurement path.
This ratio can then be converted to units of
optical density, stack exit opacity, and dust
concentration.
The reference value depends on the lf dimension
shown in Figure 1-3. Also illustrated are dimensions lx and lt, which are necessary for OPM
2000R calibration and setup. These dimensions
are defined as follows:
lx
lt
lf
The LX/LT parameter is entered in the BASIC
SETUP sub-menu of the HART Communicator.
See paragraph 6-8.c for more information.
Opacity is a complementary function of transmittance. It is a measurement of the amount of light
that is blocked or absorbed by the flue gases. The
measurement of smoke opacity is also sometimes
referred to in Ringelmann numbers. By definition,
Ringelmann No. 1 is equivalent to 20% opacity
with the opacity increasing 20% for each subsequent number. This scale is based on a single-pass
value as would be read by a human obs erv er.
TRANSCEIVER
MODULE
Figure 1-3. Calibration Dimensions
= inside stack diameter at stack exit.
= inside stack diameter at the transmitter
location.
= flange to flange distance between the
transceiver and retroreflector unit. It is
also the distance that must be used to
calibrate the unit offline.
lx
STACK
RETROREFLECTOR
MODULE
lt
lf
24670006
2.0
1.9
1.8
1.7
D = -log(Tr/100)
OPTICAL DENSITY
(EXTINCTION)
NOTE: THIS INFORMATION IS PROVIDED
IN TABLE FORM IN APPENDIX A.
1.6
1.5
1.4
1.3
1.2
1.1
1.0
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0
0% OPACITY
10 20 30 40 50 60 70 80 90 100
100% TRANSMITTANCE90 80 70 60 50 40 30 20 10 0
Figure 1-4. Relationship of Opacity,
Transmittance, and Optical Density
The relationship between opacity, transmittance,
and optical density (or extinction) is shown
graphically in Figure 1-4 and in the table in
Appendix A. One hundred pe rcent transmittance
is equivalent to 0% opacity or zero optical
density. Opacity and optical density are
logarithmically related in such a way that zero
optical density equals zero opacity; an optical
density of one is equal to 90% opacity; an op tical
density of two is equal to 99% opacity, etc.
The OPM 2000R automatically compensates for
the effects of ambient light, zero drift, and
component aging with every measurement cycle.
Four separate voltages produced in each
measurement cycle are compared against two sets
of reference voltages taken either off stack or in a
clear stack. The first set is taken in 0% opacity
conditions, and the second set is taken in
simulated 100% opacity conditions. The resulting
reference zero and span voltages produce a
reference point by which the transmitter judges
current operation.
24670007
IB-106-200R
1-3
Page 29
d. System Considerations.
All procedures in this
manual must be performed carefully in order to
gain the maximum benefit from the OPM 2000R.
Proper maintenance is important for maintaining
signal accuracy and will greatly increase
instrument life.
e.Dust Concentration Measurements.
The OPM
2000R uses an optical technique to measure
opacity and extinction. Equating this to a dust
concentration measurement requires additional
iso-kinetic sampling in order to calibrate the unit.
Iso-kinetic sampling involves taking a series of
actual dust concentration measurements in the
flue and comparing these with the extinction
reading from the OPM 2000R. From this
comparison, a graph can be plotted (Figure 1-5)
that shows the relationship between extinction
and dust measurement exclusive to that particular
application. This method takes into account the
variation in dust sizes and densities in different
applications. The procedure is described in the
following standards:
1. ISO 9096 Stationary Source Emissions.
Determination of mass concentration and
mass flow rate of particulate matter in gascarrying ducts - manual gravimetric method.
linearized and represented by the following
equation:
DC = kE + c
Where:
DC = dust concentration
k= slope of dust concentration by extinction
(determined from stack dust sampling
test data)
c= y intercept of dust concentration (deter-
mined from stack dust sampling test
data)
E= Extinction (measured variable by OPM
2000R)
The values for k and c are then entered in the
DUST SETUP sub-menu of the HART
Communicator to calculate the dust concentration
(DC) from the extinction value. Refer to
paragraph 6-9.e for more information.
90
3
80
70
2. ISO/DIS 10155 Stationary Source Emissions.
Automated monitoring of mass concentration
of particles - performance characteristics, test
methods, and specifi cation s.
1-3.METHOD OF M EASUREMENT
. The following
sequence of steps determines the relationship of dust
concentration to extinction readings:
After the OPM 2000R has been installed and is
a.
functioning properly, a series of gravimetric
measurements are taken using a standard method
as outlined in ISO 9096. As each measurement is
taken, the equivalent extinction reading on the
OPM 2000R is recorded.
The recorded data is plotted and presented in
b.
accordance with methods outlined in ISO 10155
or a relevant local standard. This information is
used to calculate the “extinction coefficient” that
determines the relationship between extinction
and dust concentration measurement.
A typical graph and dust concentration
c.
calculation (Figure 1-5) shows a linear
relationship between extinction and dust
concentration. The calibration curve can be
60
50
40
95% CONFIDENCE
INTERVAL
0.03
0.04 0.05
= 1940
0.06
24670008
DUST CONCENTRATION (DC) mg/m
16.5
-2.9
30
20
10
0.02
0.01
-10
k=
DC=kE+C
DC = 1940E - 2.9
WHERE:
DC = DUST CONCENTRATION
k = EXTINCTION COEFFICIENT = 1940
c = -2.9
k=
EXTINCTION (E)
DC-C
E
16.5 - (-2.9)
0.01
Figure 1-5. Example Relationship of Extinction
and Dust Concentration
IB-106-200R
1-4
Page 30
1-4.SPECIFICATIONS.
Electrical:
Input Voltage Requirements.............................100/115/220/240 VAC, 50/60 Hz
Power Requirements.........................................400 watts to transceiver, including 300 watt heater. The
Wiring...............................................................Two twisted pair (Belden 8162, 8163, or equivalent);
Electrical Classification....................................Category II
Environmental:
Ambient Operating Temperature......................-40° to 130°F (-40° to 55°C)
Flue Gas Temperature.......................................Maximum 1000°F (538°C); Minimum 220°F (104°C);
Flue Gas Pressure.............................................Maximum 10 in. (254 mm) WC with supplied blowers
Pathlength.........................................................User-definable from 3 to 26 ft (0.9 to 7.9 m)
Physical:
Optical System..................................................Double-pass multiple lens optical system with solid state
Light Source .....................................................Gas-filled incandescent bulb; expected life greater than
System Shipping Weight...................................356 lbs (161.5 kg)
blowers are separately powered and rated at 1/2 HP @
60 Hz or 1/3 HP @ 50 Hz (5.6 A @ 115 VAC or 3.1 A @
240 VAC, 50 Hz).
maximum 5000 ft (1524 m) of cable between transceiver
and intelligent electronics
Non-condensing
electronic light modulation; utilizes liquid crystal windows
30,000 hours
Transceiver and Retroreflector:
Enclosure Type.................................................Weather housings are moisture-proof. The transceiver
assembly is designed for Type 4X environments.
Dimensions.......................................................Height: 28.77 in. (731 mm)
Width: 12.5 in. (318 mm)
Depth: 33.94 in. (862 mm)
Weight ..............................................................Transceiver: 80 lbs (36.3 kg)
Operational:
The OPM 2000R meets EPA design and performance requirements as specified in 40 CFR, Part 60, Appendix B,
Performance Specification 1. The OPM 2000R also meets the performance audit requirements of EPA Method 203.
Vibration Frequency Magnitude.......................<0.0025 in. at 60 Hz
IB-106-200R
1-6
Page 32
1-5.SYSTEM STARTUP PROCEDURE.
following steps to start the OPM 2000R. If the
opacity transmitter is installed to meet the
requirements of EPA regulation 40 CFR, Part 60,
Appendix B, Specification 1, follow this procedure
prior to installing the opacity transmitter on the stack
(see 40 CFR, Part 60, Appendix B, Specification 1,
Section 7, PERFORMANCE SPECIFICATION
VERIFICATION PROCEDURE). It is also recommended that certain parts of these startup procedures
be repeated once the unit is mounted on the stack or
duct.
Turn on power to the transceiver and
a.
retroreflector modules immediately after their
installation to the stack or duct. Refer to Section
IV for the complete installation procedure. Turn
on the purge air blowers to ensure that both the
transceiver window and retroreflector corner
cube will be kept dirt free.
Turn on the power source to the intelligent
b.
electronics and connect the HART Communicator per paragraph 6-2. Turn on the HART
Communicator and select CHECK OPTICS from
the DIAG/SERVICE menu. Next, select the
V
menu option to place the OPM 2000R in
STACK
the check optics mode.
Align the transceiver and retroreflector. (Refer to
c.
Section V for the complete procedure.) If the
alignment is performed off of the stack prior to
the installation to meet the “prior to installation”
requirements of 40 CFR, Part 60, Appendix B,
Specification 1, be sure the transceiver and
retroreflector modules are spaced within 1/4 in.
(6.35 mm) of the actual installed flange-to-flange
distance. Exit the CHECK OPTICS procedure
when alignment is complete.
Set up the operating parameters in the BASIC
d.
SETUP and DETAILED SETUP menus of the
HART Communicator. Refer to paragraphs 6-8
and 6-9 for the complete setup procedures.
Use the
Enter the PROCESS VARIABLES menu and
e.
select FLD DEVICE VOLTS per paragraph
6-6.a. Four voltages are listed: V
V
LAMP
(lamp), V
(ambient), and V
AMB
STACK
DARK
Selecting STACK TEMPERATURE displays
VAD590 (ambient voltage) and TEMP (transceiver electronics temperature). These voltages
and temperature readings indicate the up-to-date
levels of these measured variables. If the stack or
duct is clear of opacity, the stack and lamp
voltages will be within 0.5 volts of each other.
The typical values for both stack and lamp volts
as set by the factory are 4.0 V.
NOTE
The actual ambient conditions at the
installation site may not be the same as the
factory conditions at the time of testing.
Therefore, some variations in these two
voltages will be observed but will not affect
the operation of the opacity transmitter.
View the opacity reading on the HART
f.
Communicator display online menu. Ensure the
primary variable (PV) or the secondary variable
(SV) is set to display opacity. Refer to paragraph
6-6.b. Under clear stack conditions, or with zero
jig installed, the opacity should now read 0.0%. If
the opacity reading is other than 0.0 ±0.5%,
recalibrate the opacity transmitter.
Perform an offline calibration per paragraph
g.
6-7.b. Reference voltages from the last offline
calibration are stored in the REF. VOLTAGES
sub-menu in the DIAG/SERVICE menu. This
stored data should be recorded and saved for later
reference before proceeding with another offline
calibration.
(stack),
(dark).
IB-106-200R
1-7
Page 33
57
63
58
59
64
65
66
1
NOTE: NOT ALL PARTS SHOWN
ARE AVAILABLE FOR
PURCHASE SEPARATELY.
FOR A LIST OF AVAILABLE
PARTS, SEE SECTION IX.
54
34
53
55
55
56
35
49
52
36
38
48
60
47
51
37
61
62
46
50
40
41
2
39
45
42
3
43
5
4
44
4
12
11
10
6
7
8
9
32
33
31
26
23
25
24
30
27
8
28
29
Figure 2-1. Transceiver Module - Exploded View
IB-106-200R
2-0
20
21
22
19
18
17
13
14
24670029
15
16
Page 34
SECTION II. TRANSCEIVER AND RETROREFLECTOR MODULES
2-1.TRANSCEIVER MODULE.
nents of the transceiver module (Figure 2-1) are
optical assembly (1, Figure 2-1 and Figure 2-2), air
lens (58, Figure 2-1), and blower motor (5). The three
components are mounted to mounting plate (34) and
enclosed in weather housing (9). The optical
assembly contains all transceiver optical and
electronic components. Lifting and handling
instructions for the transceiver and the retroreflector
can be found in paragraph 4-5.
a. Optical System.
system is a special, long-life incandescent lamp.
The lamp contains a built-in lens that directs light
forward through a 1/8 in. (3 mm) diameter
crosshaired aperture.
The light source for the optical
The main compo-
Two Liquid Crystal Windows (LCWs) function
as shutters that either block or transmit light. The
LCWs are made of a normally translucent film
that scatters the light striking it. However, when
an electric current is applied to the film, the
LCW becomes transparent and allows light to
pass. The sequence in which the LCWs turn on
or off and the duration of each are softwarecontrolled.
LEGEND FOR FIGURE 2-1
ITEM DESCRIPTION
1Optical Assembly
2Power Cable
3Communications Cable
4Hose Clamp
5Blower Motor
6Hex Nut, 1/4-20
7Lockwash er, 1/ 4 in.
8Washer, 1/4 in.
9Weather Housing
10Mounting Plate
11Washer, 1/4 in.
12Pan Head Screw, 1/4- 20 x 7/ 8 in .
13Mounting Block
14Toggle Clamp
15Pan Head Screw, #8- 32 x 3/ 4 in.
16Pan Head Screw, #8- 32 x 3/ 8 in.
17Pan Head Screw, #8- 32 x 7/ 8 in.
18Filter Retainer
19Wing Nut, 1/4- 20
20Filter (Coarse)
21Filter (Fine)
22Nut, 1/4-20
23Filter Retainer
ITEM DESCRIPTION
24Pan Head Screw, #8- 32 x 3/ 8 in.
25Top Cover Plate
26Cable Grip
27Seal
28Bolt, 1/4-20 x 1- 1/ 4 in.
29Rivet
30Latch
31Conduit Lock Nut, 1/2 in.
32Gasket
33Flange
34Mounting Plate
35Bolt, 1/4-20 x 5/8 i n .
36Bottom Cover Plate
37Standoff, #6- 32 x 1/ 2 in.
38External Star Washer, #6
39Screw, #6-32 x 1/4 i n .
40Ground Cable
41Termination Board
42External Star Washer, #6
43Screw, #6-32 x 1/4 i n .
44Adapter
45Filter Base
46Filter Element Assembly
ITEM DESCRIPTION
47Filter Cover
48Flat Washer, 3/8 in.
49Wing Nut, 3/8- 16
50Hose
51Screw, #10-32 x 3/8 i n .
52External Star Washer, #10
53Purge Air Failure
1Cover Plate
2Thumbscrew, #6-32 x 3/8 in.
3Splitter Base
4Socket Head Screw,
#6-32 x 1 in.
5Beam Splitter
6Socket Head Screw,
#4-40 x 1/2 in.
7O-Ring
8Aperture
9LCW 1
10Aperture
11Mounting Block
12Retainer
13Socket Head Screw,
#6-32 x 3/8 in.
14Electronics Housing
15Stop Nut
16Lamp
17Lamp Holder
18Socket Head Screw,
#6-32 x 1/2 in.
19Socket Head Screw,
#6-32 x 1/2 in.
20Set Screw, 1/4-20 x 1/4 in.
21Heater
ITEM DESCRIPTION
22Op tical Mounting Channel
23CAL/CHECK Backlit
Pushbutton
24Pan Head Screw, #8-32 x 1/4 in.
25Latch Clip
26Conduit Lock Nut, 1/2 in.
27Mounting Plate
28Cable Grip
29Communication Cable
30Power Cable
31Flat Washer, 1/4 in.
32Lockwasher, 1/4 in.
33Hex Head Bolt, 1/4-20 x 1 in.
34Window Flange
35Gasket
36Threaded Retaining Ring
37Front Window
38O-Ring
39Socket Head Screw,
#6-32 x 5/8 in.
40Gasket
41Access Plate
42Latch Clip
43Rivet
44Latch
45Pan Head Screw, #8-32 x 1/4 in.
ITEM DESCRIPTION
46Pan Head Screw, #6-32 x 3/8 in.
47External Star Washer, #6
48Standoff, #6-32 x 1/2 in.
49Ground Cable
50Stack LON Board
51Socket Head Screw,
#6-32 x 3/8 in.
52Internal Star Washer, #6
53Detector Mount
54Green Filter
55Detector
56Detector/Amplifier Board
57Internal Star Washer, #6
58Socket Head Screw,
#6-32 x 3/8 in.
59Standoff, #6-32 x 1/2 in.
60Socket Head Screw,
#4-40 x 1/2 in.
61O-Ring
62Reflector
63LCW 2
64Aperture
65Mounting Block
66Iris
67Objective Lens
68Lens Retainer
Each measurement cycle consists of four different
light path modes; each mode produces a different
voltage. The four measurement modes are stack,
ambient, dark, and lamp and are explained as
follows:
1. Stack Mode. Refer to Figure 2-3. During the
stack mode, the light beam passes through the
aperture (with crosshairs), LCW 1, and beam
splitter. Then, the beam travels through the
objective lens, LCW 2 (center segment), and
APERTURE
(WITH CROSSHAIRS)
LAMP
LCW 1
BEAM
SPLITTER
DETECTOR
OBJECTIVE
LENS
IRIS
COMBINATION
LCW 2
an air window; across the stack; and into a
retroreflector. The retroreflector, by means of a
corner cube, r eflects the light back thr ough the
stack, air window, LCW 2, iris, and objective
lens. The beam strikes the beam splitter and is
reflected into the detector. The detector (a
photodiode) converts the light to a voltage that
can be processed. The desired spectral
response is achieved by a narrow green band
filter on the detector.
24670010
Figure 2-3. Stack Light Path
IB-106-200R
2-3
Page 37
LAMP
LCW 1
COMBINATION
LCW 2
OBJECTIVE
LENS
DETECTOR
Figure 2-4. Ambient Light Path
2. Ambient Mode. Refer to Figure 2-4. In the
ambient mode, LCW 1 blocks the lamp’s
light, preventing it from ever reaching the
detector. While the lamp light is blocked,
LCW 2 allows ambient light to reach the
objective lens, beam splitter, and detector.
LCW 1
LAMP
DETECTOR
24670011
3. Dark Mode. Refer to Figure 2-5. In the dark
mode, both LCWs are off. The voltage
measured during the dark mode is used to
compensate for any internal light leakage
within the transceiver.
COMBINATION
LCW 2
OBJECTIVE
LENS
24670012
Figure 2-5. Dark Mode
IB-106-200R
2-4
Page 38
4. Lamp Mode. Refer to Figure 2-6. The lamp
mode allows the OPM 2000R to compensate
for the effects of an aging bulb. In this
mode, the inner segment of LCW 2 is off,
stopping the beam from reaching the air
window and preventing the entrance of
ambient light. The lamp beam is directed
through the objec tive lens and the o uter r ing
segments of LCW 2 to an internal
retroreflector located behind the outer ring
segments. The beam is then directed back
through the objective lens to the beam
splitter and into the detector. The iris
installed over the objective lens can be
adjusted to keep the lamp voltage within
1/2 V of the stack voltage.
LAMP
LCW 1
COMBINATION
IRIS
DETECTOR
LCW 2
RETROREFLECTOR
Figure 2-6. Lamp Light Path
INTERNAL
24670013
IB-106-200R
2-5
Page 39
ISOLATION
WINDOW
WINDOW
CLEANING
AREA
ZERO JIG
ZERO JIG
LOCATING PIN
WINDOW
FLANGE
Figure 2-7. Zero Jig Mounting Location
b. Filters and Zero Jig.
An external neutral
density filter check is used to meet EPA
requirements concerning monitor accuracy and
calibration. To check the monitor, remove the
window access plate (Figure 2-7) and position
the zero jig onto the window flange. Then, insert
EPA-certified neutral density filters in the zero
jig, one at a time, and compare the filter values
with the actual monitor readings. This
comparison shows the monitor’s accuracy. Refer
to paragraph 6-7.g for complete instructions.
c.Detector/Amplifier PC Board.
The detector is
a photodiode that converts light energy to a
voltage. A green filter in front of the detector is
used to achieve the desired spectral response.
The filter’s maximum response is at 550 nm
(Figure 2-8). At below 400 nm and above
700 nm, the filter transmits less than 2% of the
light.
LATCH
100
90
80
70
60
50
40
RELATIVE RESPONSE, %
30
20
10
0
300400500600700800
WINDOW
ACCESS
PLATE
PHOTOPIC REGION
WAVELENGTH, NM
24670014
24670015
IB-106-200R
2-6
Figure 2-8. Effective Spectral Response Curve
Page 40
Detector CR1 (Figure 2-9) is mounted to the
detector/amplifier PC board, which amplifies the
signal. The board contains a 2-po sition j umper to
adjust the range of gain. If the jumper is in the
low position (JM1), the gain adjustment is from 1
to 10. In the high position (JM2), the gain is from
10 to 100. Potentiometer R1 allows adjustment
within the range determined by the jumpers
(Figure 2-10).
DETECTOR/
AMPLIFIER
BOARD
R1
d. Stack LON Board.
Refer to Figures 2-9 and
2-11. The stack LON board is mounted to the
optical mounting channel. The electronics on the
stack LON board include the communications
electronics, temperature sensor, heater controller,
purge air failure flow switch input modules, and
DC power supplies. Power supply 1 (PS1)
supplies power to the lamp and electronics.
Power supply 2 (PS2) supplies power to LCW 1,
LCW 2, and a status LED.
NOTE: -0.5 VDC AND +4.75 VDC ARE DETECTOR AMPLIFIER SATURATION VALUES. TYPICALLY, LAMP
AND STACK MODE VOLTAGE READINGS ARE +3.0 VDC TO +4.0 VDC. POTENTIOMETER R1 CAN
BE ADJUSTED TO PREVENT AMPLIFIER SATURATION. POTENTIOMETER R1 DOES NOT AFFECT
CALIBRATION.
Figure 2-10. Detector Circuit
IB-106-200R
2-7
Page 41
e.Termination Board.
Termination board (41,
Figure 2-1) is installed on mounting plate (34)
and provides a connection point for cables to and
from the transceiver. The board provides
connections for the transceiver and retroreflector
purge air failure flow switches, stack LON board
power supplies, and AC power input. Refer to
Figure 4-9 or 4-10 for an illustration and wiring
schematic of the termination board.
f.Heater.
Allowing the temperature in the optical
unit to reach or fall below freezing could result in
improper OPM 2000R operation. For this reason,
a heater is installed on the optical mounting
channel. The temperature circuitry on the stack
LON board turns the heater on when the
temperature in the transceiver assembly is below
85.1°F (29.5°C) and off when the temperature in
the transceiver assembly is above 86°F (30°C).
LCW
DRIVER
CHIP
TO LIQUID
CRYSTAL
WINDOWS
TOLCWs
SERVICE
SWITCH
STATUS
LED
TO LON
TO STACK LON
TERMINATION
BOARD
TO CAL/CHECK
PUSHBUTTON
TEMPERATURE SENSOR
(ON BACK OF BOARD)
TEST
POINTS
SRPOL
+
CAL
PRSW1 PRSW2
LIGHT
HEATER CAL SW
U10 MOUNTED
ON SOLDERSIDE
TOCAL SW
& CALLIGHT
++
ISOLATION
TRANSFORMER
AND LIGHT
TEST
POINTS
+
+15V
AGND
-15V
+60V
+5V
GND
+5VP
-5VP
TO DETECTOR/
AMPLIFIER BOARD
EPROM
+
+
xxx VAC
PARTNUMBER
PS2
3D39698G REV
60V
PS2 60 VDC
POWER
SUPPLY
TODET. BRD
3D39700Gxx
TO LAMP
xxx VAC
PARTNUMBER
PS1 5V,+15V, -15V
PS1 +5 VDC
15 VDC
+
POWER
SUPPLY
PURGE AIR
FAILURE FLOW
SWITCH #1
INTERFACE
MODULE
FUSE 1
TOLAMP
TO PS2
XXXA
250VAC
(SLOW BLOW)
TO PS1
XXXAXXXA
250VAC
(SLOW BLOW)
FUSE 2
FUSE 3
INTERFACE
LINE
FILTER
FUSE CHART
100/115 VAC 220/240 VAC
1A97913H12
1
1A97913H17
PURGE AIR
FAILURE FLOW
SWITCH #2
INTERFACE
MODULE
TO HTR
250VAC
(SLOW BLOW)
HEATER
MODULE
GROUND
PR SW1
PR SW2
HTR
TO
HEATER
TO
HEATER
MAINS &
PR SWS.
TRANSCEIVER
POWER
TO
Figure 2-11. Stack LON Board
IB-106-200R
2-8
1A97913H10
2
1A97913H03
3
1A97913H09
1A97913H16
24670018
Page 42
2-2.RETROREFLECTOR MODULE.
The retroreflector module is similar to the transceiver module.
However, instead of an optical assembly (1, Figure
2-1), the retroreflector module has a corner cube
reflector mounted to the air lens assem bly (Figu re 2-12).
3
7
6
2
1
5
4
NOTE 1
NOTE 2
8
The retroreflector consists of retroreflector body
(2, Figure 2-12) and end cap and corner cube
assembly (3). The latter consists of corner cube
holder (4), corner cube (5), gasket (6), and end cap
(zero reflector) (7). Light from the transceiver passes
through the stack and into the retroreflector. The
corner cube reflects the beam back along the same
path. Refer to Section V for more information on
checking and aligning the transceiver and
retroreflector modules.
During calibration, it is possible to simulate 100%
opacity by removing the end cap and corner cube
assembly. Upon removal, reverse the end cap and
reinstall with the flat (zero reflector) side facing the
retroreflector body.
NOTE:
NOT ALL PARTS SHOWN
ARE AVAILABLE FOR PURCHASE
SEPARATELY. FOR A LIST
OF AVAILABLE PARTS,
SEE SECTION IX.
9
NOTE 1:
NOTE 2:
DIFFERENT CORNER CUBES AND HOLDERS
ARE USED AS FOLLOWS:
PATHLENGTH
3 to 10 ft (0.915 to 3.05 m)
10 to 20 ft (3.05 to 6.1 m)
20 to 26 ft (6.1 to 7.9 m)
THE FLAT SURFACE SIDE OF THE END CAP IS A
“ZERO-REFLECTOR” AND CAN BE USED TO SIMULATE
100% OPACITY.
CORNER CUBE
0.5 in. (12.7 mm) Diameter
Corner Cube
1 in. (25.4 mm) Diameter
Corner Cube
1.5 in. (38.1 mm) Diameter
Corner Cube
ITEM DESCRIPTION
1Air Window
2Retroreflector Body
3End Cap and Cor ner Cube Assembly
4Corner Cube Holder
5Corner Cube (Retroreflector)
6Gasket
7End Cap (Zero Reflector)
8Retaining Strap
9Screws (3)
29170013
2-3.PURGE AIR FAILURE FLOW SWITCH.
OPM 2000R contains two purge air failure flow
switches (Figure 2-13). One switch is mounted on the
transceiver module mounting plate; the other is
mounted on the retroreflector module mounting plate.
Each switch continuously monitors the differential
pressure across its respective air lens assembly. If the
differential pressure falls below a preset value, the
AIR LENS
ASSEMBLY
STRAIGHT
TO LOW
PRESSURE
SIDE
AIR FROM
BLOWER
PURGE AIR
FAILURE FLOW
SWITCH
FITTINGS
SEAL
PLATE
TO HIGH
PRESSURE
SIDE
24670020
The
Figure 2-12. Retroreflector and Air Lens Assembly
Figure 2-13. Air Lens Assembly
and Purge Air Failure Flow Switch
IB-106-200R
2-9
Page 43
affected switch opens. The purge air failure flow
switch interface module sends an alarm signal
through the stack LON board to the intelligent
electronics. The intelligent electronics distinguishes
which unit has failed (transceiver or retroreflector)
and displays the flow switch status using a HART
Communicator.
2-4.AIR LENS ASSEMBLY.
An air lens assembly
(Figure 2-14) is mounted to the mounting plate inside
the weather housing of both the transceiver and
retroreflector modules. Each air lens, by receiving
purge air from its own blower, is capable of
maintaining a clean space of air between the module’s
NOTE: NOT ALL PARTS SHOWN ARE
AVAILABLE FOR PURCHASE
SEPARATELY. FOR A LIST OF
AVAILABLE PARTS, SEE SECTION IX.
optics and the stack gases and particulates. A manually
positioned sliding seal plate is used to protect the
instrument from flue gases and particulates when the
blower is off. Ball-joint construction of the assembly
provides for horizontal and vertical alignment
adjustments. Refer to paragraph 5-1.
Coarse and fine filters (20 and 21, Figure 2-1) are
located at the bottom of the weather housings. The
filters remove airborne particulates as air is drawn
through the filters by the suction of the blower.
Secondary filter element (46) mounts directly to the
blower intake. The filters can be easily removed for
cleaning and reuse. Refer to paragraph 8-2.d.
3
2
1
13
4
5
9
8
10
Figure 2-14. Air Lens Assembly - Exploded View
IB-106-200R
2-10
6
7
24670021
Page 44
SECTION III. INTELLIGENT ELECTRONICS
3-1.GENERAL.
The intelligent electronics is the control
unit of the OPM 2000R. It continuously receives
digital signals from the transceiver via the
communications link and converts them into read ings
of opacity, transmittance, optical density, extinction,
and dust density. In addition, the intelligent
electronics sends commands to the transceiver to
initiate diagnostic tests and provides an operator
interface via HART communications.
Two types of intelligent electronics are available: the
standard general purpose version for indoor use and
the optional Type 4X weatherproof version for
outdoor use.
ITEM DESCRIPTIONITEM DESCRIPTION
14-Pin Plug96-Pin Plug
23-Pin Plug109-Pin Plug
3Screw, M3 x 611Grommet
4Endplate12Standoff, #4-40 x 15/16 in.
5Enclosure13External Star Lockwasher, #4-40
6IG-1 Software Board14Screw, #4-40 x 1/4 in.
7Lock Nut, #4-4015HART Daughter Board
8Endplate
3-2.INTELLIGENT ELECTRONICS (GENERAL
PURPOSE).
The general purpose intelligent
electronics unit (Figure 3-1) consists of two boards:
the IG-1 software bo ard (6) and the HART daughter
board (15).
a. IG-1 Software Board.
The IG-1 software board
(6, Figure 3-1 and Figure 3-2) contains the
software program, three LED indicators, and
connections to the transceiver, power source, and
HART daughter bo ard (15, Figure 3-1).
1
2
10
14
13
12
11
9
3
8
15
3
4
5
7
6
29170015
Figure 3-1. General Purpose Intelligent Electronics - Exploded View
IB-106-200R
3-1
Page 45
1. IG-1 Software. The software program that
controls the intelligent electronics resides in
PROM U4 (Figure 3-2). To check the
version level of your software, access the
REVIEW menu using the HART
Communicator. Refer to Section VI for more
information. It is only necessary to replace
the PROM for a software upgrade. The
factory will determine if the software change
is mandatory for units already shipped. If
you require a replacement board, the new
board will contain the latest software
revision.
2. LEDs. Three LEDs are mounted to the side
of the software board: FAULT, COMM, and
POWER.
(a)The yellow FAULT LED turns on
when a fault occurs on the IG-1
software board.
(b) The COMM LED indicates when data
is transferring between the transceiver
and the intelligent electronics. A green
light indicates the intelligent electronics is receiving information. A red
light indicates the intelligent electronics is sending information.
(c)The green POWER LED lights when
the power source to the intelligent
electronics is turned on.
3. LON Connection. The wiring that attaches
to the LON connector provides the
communication link between the intelligent
electronics and the transceiver.
4. +24 V Connection. The +24 V connector is
wired directly to the HART daughter board.
5. RS-232 Connector. The 9-pin connector
establishes a communication link between
the HART daughter board and the software
board.
6. F1 Fuse. This Pico II, 1/2 amp, Slo Blo fuse
provides board circuit protection from the
incoming power source.
b. HART Daughter Board.
The HART daughte r
board (15, Figure 3-1 and Figure 3-3) contains
the real-time clock, relay jumper blocks, and
connections to the transceiver, power source,
HART Communicator, analog outputs, relay
contacts, and digital input.
1. Clock. The HART daughter b oard co ntains
a real-time clock that receives power from
an on-board rechargeable lithium battery
during power outages and when the board is
removed from the intelligent electronics.
2. 4-20 mA LOOP TO STACK Connection
(J2). The wiring that attaches to the
4-20 mA LOOP TO STACK connector
establishes a 4-20 mA signal loop between
the intelligent electronics and the transceiver. The HART Communicator only
operates on the 4-20 mA signal loop. By
running the signal loop between the
intelligent electronics and the transceiver,
you can use the HART Communicator to
interface with the OPM 2000R at either the
intelligent electronics or transceiver installation site.
TO LON
FAULT LED
COMM LED
POWER LED
TO 24 VDC
POWER
SOURCE
IN A NEMA 4X INTELLIGENT ELECTRONICS, THE 24 VDC
NOTE:
CONNECTOR CONNECTS TO A UNIVERSAL POWER SUPPLY
THAT CONVERTS THE INCOMING LINE VOLTAGE TO 24 VDC.
1
LON
2
F1
1/2A
SLO BLO
1 (+)
24 VDC
2 (-)
}
3 (EARTH GND)
U4
SOFTWARE
PROGRAM
Figure 3-2. IG-1 Software Board
IB-106-200R
3-2
NOT USED
TO RS-232
ON HART
DAUGHTER
BOARD
29170007
Page 46
4-20 mA
LOOP TO
STACK
4-20mA
LOOP
TO STACK
+
-
RELAY JUMPER BLOCKS
J2
+
+
J4
RELAY 3
RELAY 6
RELAY 5
RELAY
CONTACTS
J1
TO RELAY
CONTACTS
J5
DIGITAL
TO DIGITAL
INPUT
TO 24 VDC
POWER
SOURCE
+
-
24VDC
+
+
-
INPUT
J3
U7
3D39650G REV
RELAY 1
+
+
+
+
+
+
+
REAL-TIME
CLOCK AND BATTERY
NOTE: IN A NEMA 4X INTELLIGENT ELECTRONICS UNIT, THE 24 VDC
CONNECTOR CONNECTS TO A UNIVERSAL POWER SUPPLY THAT
CONVERTS THE INCOMING LINE VOLTAGE TO 24 VDC.
Figure 3-3. HART Daughter Board
3. 24 VDC Connection (J3). The 24 VDC
connector is wired directly to the 24 VDC
power source. Rosemount offers an optional
115 VAC or 220 VAC/24 VDC power
supply that will transform the voltage to the
24 VDC needed.
4. Digital Input (J5). The digital input
connector gives you the opportunity to
initiate a zero/span check via a remote input
such as a computer control system. This is in
addition to the scheduled zero/span check
configured with the HART Communicator.
The contact input is interrogated by the
intelligent electronics with 5 VDC.
5. Relay Contact Connection (J1). The relay
contact connector can be wired to external
devices that utilize OPM 2000R status
indications. The six relays are configured
using the HART Communicator. Refer to
paragraph 6-9.a for more information.
6. Analog Output Connection (J6). The analog
output connector can be wired to a recorder,
controller, or computer that utilizes isolated
RELAY 2
J9
P1
RELAY 4
J11
P1
+
+
RS-232
2
+
J8
ANALOG
OUTPUTS
J6
-
+
J7
3
1
HART
-
+
+
-
+
+
+
TO ANALOG
OUTPUT
DEVICES
TO HART
COMMUNICATOR
SWITCHES
(MUST BE IN UP
POSITION FOR
TO RS-232
ON IG-1
INTERNALLY POWERED
SIGNAL LOOPS)
SOFTWARE
BOARD
analog readings from the OPM 2000R. The
three analog outputs are determined by the PV,
SV, and TV values configured using the HART
Communicator. Analog output 1 (AO1), which
always has the PV value, also carries the digital
HART communications signal. Refer to
paragraph 6-6.d for more i nf orm ation.
7. HART Connection (J7). The intelligent
electronics provides two banana jack
receptacle cable assemblies to plug the
HART Communicator into the 4-20 mA
signal loop. The cable assemblies are
located on the endplate of the intelligent
electronics, and their terminals plug into
HART connecto r J7 on the HART da ughter
board. Refer to paragraph 6-2 for more
information on attaching the HART
Communicator to the signal loop.
8. Switches 1, 2, and 3. These switches can be
configured in the up position to power the
analog outputf circuit by the OPM 2000R or
in the down position to power the analog
output circuit by the field device receiving
the analog output signal from the OPM
2000R.
29170002
IB-106-200R
3-3
Page 47
9. Relay Jumper Blocks (J9 and J11). The
relays on the HART daughter boa rd are now
configurable via two jumper blocks: J9 and
J11 (Figure 3-4). This new feature was
added to provide additional flexibility when
configuring the instrument’s alarm outputs.
J9 can be configured so the instrument’s
relay contacts are either normally energized
or normally de-energized during normal
operating conditions. J11 can b e configured
so the contacts are either normally open or
closed during normal operating conditions.
These terms are explained below:
jumper position for relay 6 is the opposite of
the jumper positions fo r relays 1 through 5.
Two example relay configurations are
default and failsafe.
(a)Default Configuration. The default
configuration of the relays minimizes
the amount of nuisance alarms during
power interruptions to the instrument’s
electronics. This configuration also
minimizes power usage and maximizes
relay life during normal operations.
Normally Open Relay —
A relay with open
contacts when it is in an unpowered state.
Normally Closed Relay —
A relay with
closed contacts when it is in an unpowered
state.
Normally Energized Relay —
A relay with
its coil energized during normal operating
conditions.
Normally De-Energized Relay —
A relay
with its coil de-energized during normal
operating conditions.
Normal Operating Conditions —
The
operating condition when no alarms or
special states are active.
The normally energized/normally deenergized states of relay 6 are reversed in
the on-board logic. Consequently, the
In the default configuration, relays 1
through 5 are normally de-energized
and normally open and relay 6 is normally energized and normally closed.
Therefore, all six contacts are open
during normal operating conditions and
close when an alarm condition occurs.
If a power failure occurs, relays 1
through 5 open a nd relay 6 closes.
(b) Failsafe Configuration. The failsafe
configuration of the relays places normally open relay contacts in a closed
state during normal operating conditions and in an open state during an
alarm or no power condition.
In the failsafe configuration, all of the
relays are normally energized and
normally open. Therefore, all of the
relay contacts are closed during normal
operating condi tions and op en when an
alarm or no power condition occurs.
In addition to the IG-1 software board
and the HART daughter board of the intelligent
electronics unit, the Type 4X version (Figure 3-5)
also includes a weatherproof enclosure, power supply,
optional heater, and termination board.
b. HART Daughter Board.
The HART daughte r
board (Figure 3-3 and 9, Figure 3-5) contains the
real-time clock, relay jumper blocks, and
connections to the transceiver, power source,
HART Communicator, analog outputs, relay
contacts, and digital input.
a. IG-1 Software Board.
(Figure 3-2 and 19, Figure 3-5) contains the
software program, three LED indicators, and
connections to the transceiver, power source, and
HART daughter board (9).
The Type 4X and the general p urpose intelligent
electronics units use the same software board.
The only difference that exists is in the 24 VDC
connection. The software board in the general
purpose unit is wired directly to a 24 VDC power
source; the software board in the Type 4X unit is
wired to a universal power supply that transforms
the incoming line voltage into the required
24 VDC.
ITEM DESCRIPTION
1Enclosure
2Cable Grip
3Conduit Lock Nut, 1/2 in.
4Standoff, #6-32 x 1 in.
5Termination Bo ard
6Screw, #6-32 x 1/4 in.
76-Pin Plug
89-Pin Plug
9HART Daughter Board
10Standoff, #4-40 x 1 in.
11Standoff, #4-40 x 15/16 in.
12Screw, #4-40 x 1/4 in.
13Cable
14Screw, #10-32 x 3/8 in.
15Top Cover Plate
16
15
14
J1
J2
18
17
J3
The IG-1 software board
23
22
21
20
19
9
12
13
J7
6
The general purpose and Type 4X units use the
same HART daughter boa rd, but two di fferences
exist. The HART daughter board in the general
purpose unit is wired directly to a 24 VDC power
source; the HART daughter bo ar d in the T ype 4 X
unit is wired to a universal power supply that
transforms the incoming line voltage into the
required 24 VDC.
The other difference is the HART Communicator
connection location. On top cover plate (15) of the
Type 4X unit are two banan a jacks , J2 and J3, used
to attach the HART Communicator to the
4-20 mA signal loop. These banana jacks connect
to HART connector J7 on the HART daughter
board via connector J1 on the top cover plate.
1
24
3
2
10
11
7
8
ITEM DESCRIPTION
16Standoff, #10-32 x 4 in.
174-Pin Plug
183-Pin Plug
19IG-1 S oftware Board
20Screw, #6-32 x 1/4 in.
21Power Supply
4
5
22Standoff, #6-32 x 1/2 in.
23Heater (Optional)
24Mounting Plat e
29170016
Figure 3-5. Type 4X Intelligent Electronics - Exploded View
IB-106-200R
3-6
Page 50
c.Type 4X Enclosure.
Enclosure (1, Figure 3-5) is
weatherproof so the intelligent electronics can be
installed outdoors. Top cover plate (15) provides
convenient access to the 4-20 mA signal loop
needed to attach the HART Communicator
operator interface.
d. Termination Board.
Termination board (5,
Figure 3-5 and Figure 3-6) connects to the
incoming line voltage and supplies the operating
voltage to the power supply and heater. The 5 A,
250 V Slo Blo fuse on the termination board
protects the system components from the incoming
voltage.
GND
M1M2
SK 1
N1
L3
TO TERMINATION
BOARD
TO HART DAUGHTER
BOARD AND IG-1
SOFTWARE BOARD
24 VDC CONNECTORS
SK 2
1
2
3
4
5
6
+24V
+24V
+24V
COMMON
COMMON
COMMON
24670028
4850B34G REV
TO POWER
SUPPLY
LNLN
J2J3
J1
LN
TO INCOMING
LINE VOLTAGE
TO HEATER
!
FUSE
Figure 3-6. Termination Board
F1
5A,250VAC
SLO BLO
29170017
Figure 3-7. Power Supply
e.Power Supply.
Universal power supply (21,
Figure 3-5 and Figure 3-7) transforms the
incoming line voltage into the 24 VDC used by
the IG-1 software bo ard and the HART daughter
board. The power supply receives power through
its connection to the termination board
(Figure 3-6).
f.Heater (Optional).
Optional 300 watt heater (23,
Figure 3-5), available in 115 VAC or 220 VAC
depending on the customer requirement, keeps the
Type 4X unit components at an ambient operating
temperature. If the ambient temperature falls below
60°F (16°C), the heater turns on. If the temperature
rises above 75°F (24°C), the heater turns off. The
heater receives power through its connection to the
termination board (Figure 3-6).
IB-106-200R
3-7
Page 51
32 (813) CLEARANCE
NEEDED TO REMO VE
WEATHER HOUSING
(TYP. BOTH SIDES)
CONDUIT TO
INSTR UMENT
ENCLOSURE
NOTES:
1.
SYSTEM TO BE INSTALLED PER LOCAL AND
NATIONAL ELECTRIC CODES.
2.
FOR U.S. APPLICATIONS, REFER TO E.P.A.
INSTAL L ATION REQUIREMENTS , 4 0 CFR 60,
APPENDIX B, PERFORMANCE TEST 1.
3.
POWER REQUIREMENTS:
400 WATTS - TRANSCEIVER WITH HEATER
400 WATTS - EACH BLOWER
4.
DIMENSIONS ARE IN INCHES WITH
MILLIMETERS IN P ARENTHESES.
5.
CONNECT WIRING/CONDUIT PER NATIONAL
AND LOCAL ELECTRICAL CODE ST ANDARDS.
PURGE AIR FAILURE
FLOW SWITCH CABLE
(10, FIGURE 1-1)
(SEE NOTE 5)
CUSTOMER-SUPPLIED SIGNAL CABLE
[1 MILE (1.5 KM ) MAXIMUM L ENGTH]
TO INT E L L IGENT
ELECTRONICS
29170011
Figure 4-1. Transmitter Location Considerations
IB-106-200R
4-0
Page 52
SECTION IV. INSTALLATION
Before starting to install this equipment,
read the "Safety instructions for the
wiring and installatio n of this apparat us"
at the front of this Instruction Bulletin.
Failure to follow the safety instructions
could result in serious injury or death.
4-1.GENERAL.
OPM 2000R Opacity/Dust Density Transmitter
depends on proper installation. All procedures in this
section must be followed carefully.
4-2.CHOOSING A LOCATION.
OPM 2000R is important for obtaining maximum
accuracy in the reading of the stack particulates. Keep
in mind both clearance and process/regulatory
considerations.
a. Clearance Considerations.
Proper functioning of the Rosemount
The location of the
1. Locate the transmitter across a section of a
duct or stack that will provide a particulate
matter flow through the path of the transmitter beam representative of the duct or
stack flow.
2. Ensure the transmitter location is downstream
from all particulate control equipment.
3. Locate the transmitter as far from bends and
obstructions as practical.
4. If a transmitter is to be located less than 4
duct diameters downstream from a bend,
install the transmitter in the plane defined by
the bend. See Figure 4-2.
1. Ensure the location is accessible and
provides adequate clearance to service and
maintain the transmitter.
2. Allow 32 in. (813 mm) for clearance on each
side of the stack to remove and install the
weather housings (Figure 4-1).
3. Locate the transmitter no further than one mile
(1.5 km) from the intelligent electronics.
b. Regulatory/Process Considerations.
The EPA
has established the following guidelines for
choosing an opacity/dust density transmitter
installation site:
LESS THAN
4 DUCT
DIAMETERS
24670062
Figure 4-2. Transmi tter L ocation
IB-106-200R
4-1
Page 53
5. Ideally, locate the transmitter eight to ten stack
diameters upstream from the stack exit and
three to five diameters downstream from any
bends, junctions, or other constrictions in the
stack or duct.
For best results, mount the transceiver and
retroreflector modules so the light beam is
exactly perpendicular to the stack or duct
and the beam goes through the center. Do
not install the transmitter downstream of a
wet scrubber. The water droplets introduced to the gas stream by such equipment
will interfere with the opacity readings. For
an accurate measurement under these
conditions, choose a location upstream
from a wet scrubber or a location downstream from the scrubber where the water
droplets are vaporized by the reheating of
the gas.
4-3.CALIBRATION.
The OPM 2000R is factory
calibrated for the flange-to-flange distance (lf)
(Figur e 1-3) of the installation site. If the unit needs to
be recalibrated, refer to paragraph 6-7.b.
If a Dust Concentration (DC) output is required after
installation, it is necessary to perform isokinetic
sampling on the flue gas while simultaneously
measuring the extinction (E) value. Refer to paragraph
1-3 for a description of th i s procedu re.
4-4.MOUNTING FLANGES TO STACK.
Form two mounting holes in the stack at
a.
locations specified in paragraph 4-2. Holes must
be on the same horizontal and vertical axes. A
liquid level can be used to ensure that modules
are installed on same horizontal plane.
Install 6 in. pipe and 6 in., 150 lb flanges
b.
following the notes in Figure 4-3. Pipe must be
horizontal and should protrude at least 4 to 6 in.
(102 to 153 mm).
Weld a flange to each pipe. Align flanges so that
c.
they are relative to a common centerline. Total
module deviation should not exceed ±5 degrees.
Deviation within this limit can be compensated
for by the air lens ball joint adjustment.
IB-106-200R
4-2
Page 54
7/8 (22) DIA. - 8 HOLES
EQUALLY SPACED ON
9-1/2 (241) DIA. B.C.
STRADDLING THE VERTICAL
AND HORIZONTAL CENTERLINES.
11.00
(279) O.D.
FIELD WELD
PIPE TO
FLANGE
OUTSIDE WALL
SURFACE
STUD ANCHORS
3
6
FIELD WELD
PIPE TO
FLANGE AND
METAL STACK
OR DUCT
WALL
6-5/8 (168)
O.D. REF.
3
6 IN. 150 LB R.F. (RAISED FLANGE)
ANSI FLANGE (B16.5)
SUPPLIED BY CUSTOMER
DIMENSIONS ARE IN INCHES WITH
NOTES:
1.
MILLIMETERS IN PARENTHESES.
ALL MATERIAL AND FIELD WORK ARE PROVIDED
2.
BY THE CUSTOMER TO INSTALL THE TRANSCEIVER
AND RETROREFLECTOR MODULES OF THE OPACITY
MONITOR.
3.
WHEN FLUE GAS TEMPERATURE IS LESS THAN
600 F (316 C), INSULATE AND LAG THIS AREA TO
°°
PREVENT CONDENSATION AND CORROSION.
4.
A BLANK 11.0 IN. (279 MM) O.D. BLIND 150 LB FLANGE
DRILLED TO A 6.72 IN. (171 MM) I.D. AND DRILLED
AND TAPPED TO 0.75 - 16 UNF (M20) - 8 HOLES
EQUALLY SPACED ON 9.50 IN. (241 MM) DIA. B.C. MAY
BE SUBSTITUTED FOR THE 6 IN. 150 LB RF FLANGE.
6.72
(171) I.D.
4
4 (102)
MINIMUM
CLEARANCE
TYPICAL
MASONRY STACK
WALL INSTALLATION
5.
EXTEND INSULATION ON METAL STACK OR
DUCT SURFACES TO 24 IN. (610 MM). THIS WILL
PREVENT RADIANT HEAT FROM DAMAGING
THE OPACITY MONITOR.
6.
WHEN FLUE GAS TEMPERATURE EXCEEDS 600 F
(316 C), INSERT AN INSULATING GASKET SUCH
°
AS MANUFACTURED BY BNZ MATERIALS, INC.
RECOMMENDED GASKET MATERIAL IS MARINITE
P, AT LEAST 1 IN. (25 MM) THICK. REFER TO
PARAGRAPH 4-7.b.1 REGARDING THERMO
ISOLATORS.
Figure 4-3. Stack Flange Installation
6
6 IN. SCHED. 40
PIPE SUPPLIED
BY CUSTOMER
METAL WALL STACK
OR DUCT INSTALLATION
5
29170008
°
IB-106-200R
4-3
Page 55
5
2
4
6
HANDLING PROCEDURE
TO MOUNT ON STACK, REMOVE WEATHER HOUSING
(1) AND OPTICAL ASSEMBLY (2). LIFT MOUNTING
PLATE ASSEMBLY (3) BY A SLING (4) THROUGH THE
AIR WINDOW.
THE AIR LENS SEAL PLATE (6) MUST REMAIN
CLOSED UNTIL THE BLOWER MOTORS ARE
POWERED.
1
4-5.LIFTING AND HANDLING.
Use the following
procedure to hoist the modules to the installation site
and mount them to the stack:
Remove the weather housings by releasing the
a.
four toggle clamps (5, Figure 4-4) that hold each
housing to the mounting plate.
Remove transceiver optical assembly or
b.
retroreflector from air lens assembly (Figures 2-1
and 2-12).
Run a lifting sling through the air lens op ening in
c.
the mounting plate (Figure 4-4). Make sure all
hooking devices are secure. Lift the mounting
plate assembly to the installation site.
4-6.MOUNTING INSTRUCTIONS.
a. Transceiver and Retroreflector Modules.
3
Figure 4-4. Lifting and Handling
2. Make sure heat-resistant gasket (32, Figure
3. Install stabilizers to provide firm support for
Shutter must remain closed until the blower
is powered up.
4. Close air lens assembly shutter (seal plate) (6,
24670032
2-1) is installed between each module and its
stack flange. Attach each module to the four
bolts installed in each stack flange and secure
with four customer-supplied washers and
nuts.
each module and secure with customersupplied bolts, nuts, and washers from the
inside of the mounting plate (Figure 4-5).
Figure 4-4) until the blowers are powered up.
1. Install customer-supplied 0.75-16 bolts in
the stack mounted spool piece and flange
for the mounting plate per Figures 4-3 and
4-5.
IB-106-200R
5. Install the transceiver optical assembly
and retroreflector to the mounting plates
and install the weather housings to the
modules (Figure 4-5).
4-4
Page 56
CUSTOMER-SUPPLIED
STABILIZERS
(2 REQUIRED)
TRANSCEIVER
STACK
TYPICAL PLAN VIEW
SQUARE OPENING
(4 PLCS) SPACED
0.88 (22) CLEARANCE
FOR STABILIZERS
4.62 (117)
(SEE NOTE 2)
0.81 (21) DIA.
ON9.50 (241)
DIA. B.C. (SEE
NOTE 4 AND
NOTE 5)
16.13
(410)
FOR CUSTOMER
HOLES (2 PLCS)
NOTES:
1.
2.
3.
4.
5.
6.
7.
(4 PLCS)HOLES
WIRING
0.81 (21)
CLEARANCE
DIMENSIONS ARE IN INCHES WITH
MILLIMETERS IN PARENTHESES.
MOUNTING PLATE OPENING TO STACK.
FOUR TOGGLE CLAMPS ARE PROVIDED
TO ATTACH MOUNTING PLATE TO
WEATHER HOUSING.
0.75-16 UNF X 3.0 (M20 X 75 MM) HEX HEAD
BOLTS WITH WASHERS AND NUTS
(CUSTOMER-SUPPLIED) REQUIRED TO ATTACH
INSTRUMENT TO 6 IN. 150 LB ANSI FLANGE.
BOLT HOLE PATTERN TO CUSTOMER FLANGE
STRADDLES THE CENTERLINE. MOUNTING
FLANGE AND BOLTS ARE CUSTOMER-SUPPLIED.
SYSTEM TO BE INSTALLED PER LOCAL AND
NATIONAL ELECTRIC CODES.
FOR U.S. APPLICATIONS, REFER TO E.P.A
INSTALLATION REQUIREMENTS, 40CFR60,
APPENDIX B, PERFORMANCE TEST 1.
12.50
(318)
3.50
(89)
7.00
(178)
SECTION A-A
RETROREFLECTOR
6.25
(159)
°
22.5
28.77
(731)
22.27
(566)
33.94
(862)
TOGGLE
CLAMP
(SEE NOTE 3)
0.75-16 UNF ANCHOR STUD
STABILIZER
MOUNTING
PLATE
VIEW B
STABILIZER
LENGTH
TO BE 1/8 (0.125)
LESS THAN
DIMENSION X
CUSTOMER-
SUPPLIED MOUNTING
B
(2 REQUIRED)
STACK
SPOOL PIECE
AND FLANGE
X
CUSTOMER-
SUPPLIED
STABILIZERS
A
A
12.50
(318)
4 (102)
MIN. OR
LARGER
AS SPECIFIED
OR INSTALLED
BY CUSTOMER
WIRING
CONDUIT
FLUE
GAS
FLOW
29170009
Figure 4-5. Stack Installation Dimensions
IB-106-200R
4-5
Page 57
b. Intelligent Electronics.
The outline drawings in
Figure 4-6 show the mounting centers and
clearances for the two versions of the intelligent
electronics.
1. General Purpose Intelligent Electronics.
2. Type 4X Intelligent Electronics.
(a)Mount the Type 4X intelligent
electronics to a wall or bulkhead no
further than 1 mile (1.5 km) from the
stack-mounted transceiver unit.
0.177
(4)
(a)Install the general purpose intelligent
electronics no further than 1 mile
(1.5 km) from the stack-mounted
transceiver unit.
(b) Due to the type of enclosure, the
general purpose unit must be installed
indoors where the ambient temperature
is between 40° to 120°F (4° to 50°C).
(c)If mounting the unit on a wall or
bulkhead, use cable clamps and straps
on the wiring as needed to avoid
straining the connections.
0.57 (14)
4.71
(120)
5.13
(130)
(b)Locate units without the optional heater
where the ambient temperature is
between 40° to 120°F (4° to 50°C). For
units with the optional heater, install
where the ambient temperature is
between -40° to 120°F (-40° to 50°C).
Keep in mind that the Type 4X version
can also be installed ou t doors.
c.Model 751 Indicator (Optional).
If using the
Model 751 indicator, mount in an accessible
location per the instructions in document PDS
4378A00.
TYPE 4X INTELLIGENT ELECTRONICSGENERAL PURPOSE INTELLIGENT ELECTRONICS
11.00
(279)
8.00
(203)
12.94
(329)
12.50
(318)
NOTE:
5.19 (132)
6.00 (152)
7.00 (178)
DIMENSIONS ARE IN INCHES
WITH MILLIMETERS IN PARENTHESES.
Measuring opacity in high
temperature applications such as incinerators can
be detrimental to the physical well-being of
opacity transmitters. Flue gases from incinerators
approach 2000°F (1093°C). Opacity transmitters
have reportedly “melted” at these high
temperatures.
Other less severe temperatures just over 400°F
(204°C) can also cause opacity transmitter
operation problems. In these applications, the
opacity transmitter is mounted to a steel duct or
steel stack. Radiant heat from the duct or stack
can cause the temperature within the transceiver
and retroreflector modules to exceed ambient
temperature limits.
b. Solution.
The heat at the opacity transmitter
must be reduced to permit accurate opacity
monitoring in these applications. Rosemount
Analytical offers several solutions to help with
these applications.
1. Thermo Isolators. Thermo isolators should
be used whenever the stack temperature is
above 600°F (316°C): for example,
incinerator and hot steel stack applications.
They provide a heat-resistant barrier
between the stack and opacity transmitter
flanges. Thermo isolators are a must with
the higher temperature incinerators.
Rosemount Analytical offers thermo
isolators for the OPM 2000R’s 6 in.
mounting flanges. This 1 in. (25.4 mm)
thick high-temperature gasket provides
sufficient thermo isolation to withstand hot
face temperatures of 1700° to 1800°F
(927° to 982°C). Two thermo isolators are
required for each OPM 2000R. Remember
to add 2 in. (51 mm) to the flange-to-flange
dimension
(lf)
when thermo isolators are
used.
In addition, insulation and a cooling fin
(Figure 4-7) can be installed between the
duct and the opacity transmitter to ward off
radiant heat. This barrier is recommended
for high radiant heat applic ations as found
in incinerators and hot steel stacks.
2. Purge Air. A duct or stack maximum
pressure is limited to plus 10 in. WC in
order to supply a minimum flow of
40 SCFM purge air. These constraints must
also be adhered to for this applicatio n to be
successful. A flow of cool purge air must be
maintained or the opacity transmitter may
suffer heat damage.
12 IN.
(305 MM)
STACK
OPM
2000R
INSULATION
12 IN.
(305 MM)
MINIMUM
STACK
INSULATION
4TO6IN.
(102 TO 152 MM)
SIDE VIEWFRONT VIEW
FLANGE
COOLING FIN
AND HEAT SHIELD
MINIMUM
Figure 4-7. Insulation and Cooling Fin Installation
IB-106-200R
4-7
INSULATION
24670033
Page 59
NOTES: 1. REMOVE COPPER CHECK VALVE FROM AIR
WINDOW THEN INSTALL HEATER IN SAME
LOCATION.
2. 40 AMP BREAKER REQUIRED.
3. AIR WINDOW ALIGNMENT NUTS MAY NEED
TO BE LOOSENED SO AIR HEATER
ASSEMBLY CAN SWING CLEAR OF
OBSTACLES AS IT IS SCREWED INTO AIR
WINDOW.
4. REALIGN TRANSCEIVER AFTER
INSTALLATION OF AIR HEATER.
BLK
GRN
WHT
HEATER
WIRE
115 VAC
HEATER
HEATER
WIRE
AIR WINDOW
BLK
GRN
WHT
220 VAC
HEATER
120 VOLT BLOWER
MOTOR JUNCTION
BOX
BLU
YEL
WHT
THERMOSTAT
55 F (13 C) CLOSE
°°
70 F (21 C) OPEN
°°
WHT
BLK
GRN
Figure 4-8. Optional Purge Air Heater
4-8.MONITORING OPACITY AT LOW AM BIENT
TEMPERATURES.
a. Introduction.
Measuring opacity in locations
where ambient temperatures can be expected to
go below -20°F (-28.9°C) can cause false
readings as a result of the extremely cold ambient
air being used by the purge air blowers. When
extremely cold purge air mixes with the hot
process gases, “fogging” can occur. This
phenomenon takes place at the outlet of the purge
air window assembly and directly in the path of
the opacity measurement. As a result, the opacity
reading is falsely represented as a higher than
expected value due to the presence of the fog.
240 VOLT BLOWER
MOTOR JUNCTION
BOX
BLK
GRN
b. Solution.
WHT
The OPM 2000R can be ordered
and/or field retrofitted with purge air heaters.
This heater mounts between the blower and the
purge air window assembly in place of the check
valve and elevates the temperature of the purge
air to prevent fogging. Refer to Figure 4-8.
4-9.SYSTEM WIRING INSTALLATION.
a. Wiring Practices.
The wire selected for
supplying power to the intelligent electronics and
modules must be sized to meet the current carrying requirements (capacity) for the application.
Refer to the specifications in paragraph 1-4. The
National Electrical Code contains tables that may
be used as a guide. Voltage classification must be
equal to or exceed the rated circuitry voltage.
BLU
YEL
29170010
IB-106-200R
4-8
Page 60
All customer-supplied wiring must conform to
standard wiring practices in accordance with
local code. The wire must be able to withstand
the physical stresses to which it may be subjected
during installation.
NOTE
If wiring an OPM 2000R with a general
purpose intelligent electronics, refer to
Figure 4-9. If wiring an OPM 2000R with a
Type 4X intelligent electronics, refer to
Figure 4-10.
b. Transceiver Module.
Refer to Figure 4-9 or
Figure 4-10 as appropriate.
1. Make sure communications cable (3, Figure
2-1) from the transceiver is plugged into
connector J2 on the stack termination board.
2. Make sure power cable (2, Figure 2-1) from
the transceiver is plugged into c onnector J4
on the stack termination board.
3. Attach the customer-supplied signal cable to
HART and LON connectors J1 and J5 on
the stack termination board. Run the cable
through the cable grip in the mounting p late
and tighten the seal onto the cable.
4. Make sure cable (53, Figure 2-1) from the
transceiver purge air failure flow switch is
connected to PR SW 1 connector J7 on the
stack termination board.
module as shown in Figure 4-1. Tighten both
seals at each end of the cable. Connect the wires
to the retroreflector purge air failure flow switch.
d. Blower Motor.
Refer to Figure 4-9 or Figure
4-10 as appropriate.
NOTE
The retroreflector blower motor has its own
independent power source but is wired the
same as the transceiver blower motor at the
motor junction box.
1. Run a line voltage power cable, depending
on the system application, through a cable
grip on the retroreflector mounting plate to
the retroreflector blower motor.
2. Connect the wires at the blower motor
junction box.
3. Tighten the cable seal.
e.General Purpose Intelligent Electronics.
to Figure 4-10.
NOTE
Relay jumper blocks J9 and J11 on the
HART daughter board can be co nfigured for
either the default or failsafe configuration.
For more information, refer to Section III,
INTELLIGENT ELECTRONICS.
1. Run the customer-supplied signal cable
through a suitable conduit.
Refer
Check transceiver data plate for the actual
voltage rating. Failure to connect the power
cable to the appropriate power source will
damage equipment.
5. Attach a line voltage power cable to AC IN
connector J3 on the stack termination board.
Run the cable through the cable grip in the
mounting plate. Tighten the seal onto the
cable. Connect the power cable to a suitable
line voltage power source.
6. Refer to paragraph 6-2 for the procedure to
connect the HART communicator to the
4-20 mA signal loop at the transceiver
location.
c.Retroreflector Module.
Refer to Figure 4-9 or
Figure 4-10 as appropriate. Run a customersupplied cable from PR SW 2 connector J8 on
the transceiver stack termination bo ard thro ugh a
cable grip in the transceiver mounting plate to the
purge air failure flow switch in the retroreflector
2. Connect the signal cable to the 4-20 mA TO
STACK and LON connectors on the
intelligent electronics.
Check the intelligent electronics data plate
for the required intelligent electronics
voltage. Connecting the unit to the wrong
supply voltage will damage the equipment.
3. Attach a customer-supplied 24 VDC power
cable to the two +24 V connectors on the
unit. If a 24 VDC power source is not
available, attach the optional universal
power supply to the two +24 VDC
connectors and plug the power supply into
the customer-supplied voltage source.
4. Connect a customer-supplied digital input
cable for remote initialization of zero/span
checks to the DIGITAL INPUT connector
on the intelligent electronics.
IB-106-200R
4-9
Page 61
RD
BLK
WH
BLK
SHIELD
J9 CONNECTS TO
GROUND ON
MOUNTING PANEL
POWER TO J7
ON STACK
LON BOARD
STACK
TERMINATION
BOARD
GRN/YLW
WH
BLK
GRN/YLW
WH
CUSTOMER-
SUPPLIED
SIGNAL CABLE
COMMUNICATION
LINK TO TRANSCEIVER
COMMUNICATIONS
CABLE
CABLE GRIP
MOUNTING PANEL
AC POWER
CUSTOMER
WIRING
NOTE 1: BOTH PURGE AIR FAILURE FLOW
NOTE 2: THE OPTIONAL 751 INDICATOR
SWITCHES ARE WIRED THE SAME.
HOWEVER, THE RETROREFLECTOR
PURGE AIR FAILURE FLOW SWITCH
MUST BE WIRED IN THE FIELD,
WHEREAS THE TRANSCEIVER
PURGE AIR FAILURE FLOW SWITCH
IS PRE-WIRED AT THE FACTORY.
CAN BE LOCATED ANYWHERE IN
THE 4-20 mA SIGNAL LINE.
RD
CONNECTIONS
FOR HART
COMMUNICATOR
++
%
++
BLK
WH
BLK
BLK
WH
AC POWER
CUSTOMER WIRING
OPTIONAL 751 INDICATOR
(SEE NOTE 2)
SHIELD
BLK
GRN/YLW
TRANSCEIVER
PURGE AIR FAILURE
FLOW SWITCH
(SEE NOTE 1)
TO RETROREFLECTOR PURGE
AIR FAILURE FLOW SWITCH
A
B
TO INTELLIGENT ELECTRONICS
29170003
Figure 4-9. Customer Connections for OPM 2000R with General Purpose Intelligent Electronics (Sheet 1 of 2)
IB-106-200R
4-10
C
Page 62
(SEE NOTES 3 AND 4)
GRN/YLW
NOTE 3:
NOTE 4:
BLK
BLU
ORN
WHT
WHT
BLK
BRN
YLW
WHT
GRN/YLW
BLK
BLU
ORN
WHT
GRN/YLW
BLK
BLK
WHT
YLW
BRN
SHIELD
BLK
WH
BLK
RD
4-20mA
TO STACK
LON
DIGITAL INPUT
LED
LED
FAULT
COMM
+24V
LED
POWER
WHT
BLK
+24V
24 VDC
CUSTOMERWIRING
OR OPTIONAL 24 VDC
POWER SUPPLY
GENERAL PURPOSE
INTELLIGENT ELECTRONICS
24670040
Figure 4-9. Customer Connections for OPM 2000R with General Purpose Intelligent Electronics (Sheet 2 of 2)
IB-106-200R
4-11
Page 63
RD
BLK
WH
BLK
SHIELD
J9 CONNECTS TO
GROUND ON
MOUNTING PANEL
POWER TO J7
ON STACK
LON BOARD
STACK
TERMINATION
BOARD
GRN/YLW
WH
BLK
GRN/YLW
WH
CUSTOMER-
SUPPLIED
SIGNAL CABLE
COMMUNICATION
LINK TO TRANSCEIVER
COMMUNICATIONS
CABLE
NOTE 1: BOTH PURGE AIR FAILURE FLOW
SWITCHES ARE WIRED THE SAME.
HOWEVER, THE RETROREFLECTOR
PURGE AIR FAILURE FLOW SWITCH
MUST BE WIRED IN THE FIELD,
WHEREAS THE TRANSCEIVER PURGE
AIR FAILURE FLOW SWITCH IS
PRE-WIRED AT THE FACTORY.
RETROREFLECTOR PURGE
AIR FAILURE FLOW SWITCH
(SEE NOTE 1)
WHT
CONNECTIONS
COMMUNICATOR
MOUNTING
PANEL
AC POWER
CUSTOMER
FOR HART
CABLE
GRIP
WIRING
BLK
++
%
++
WH
GRN/YLW
OPTIONAL
751 INDICATOR
(SEE NOTE 2)
BLK
TRANSCEIVER
PURGE AIR FAILURE
FLOW SWITCH
(SEE NOTE 1)
AC POWER
CUSTOMER WIRING
A
GRN/YLW
BLK
RD
BLK
WH
BLK
NOTE 2: THE OPTIONAL 751 INDICATOR
SHIELD
TO INTELLIGENT ELECTRONICS
CAN BE LOCATED ANYWHERE
IN THE 4-20 mA SIGNAL LINE.
29170004
Figure 4-10. Customer Connections for OPM 2000R with Optional Type 4X Intelligent Electronics (Sheet 1 of 2)
IB-106-200R
4-12
B
Page 64
(SEE NOTES 3 AND 4)
GREEN/
GRN/YLWGRN/YLW
YELLOW
BLK
BLU
ORN
FACTORY WIRED
TO POWER SUPPLY
NNLL
J2J3
L
N
J1
AC POWER CUSTOMERWIRING
(115 OR 220 VAC, 50/60 HZ)
A
B
WHT
WHT
!
WHT
BLK
SHIELD
TO POWER
RD
BLK
TRANSCEIVER
BLOWER MOTOR
JUNCTION BOX
G02 - 220/240 VAC
Check the intelligent electronics data plate
for the required intelligent electronics
voltage. Connecting the unit to the wrong
supply voltage will damage the equipment.
5. Run a customer-supplied 115 VAC or
220 VAC power cable, depending on the
power source, through the cable grip
specified in Figure 4-6. Connect the power
cable to connector J1 on the Type 4X
intelligent electronics termination board as
shown in Figure 4-10. Once the cable is
connected, tighten the cable seal.
6. Make sure connector J2 on the Type 4X
intelligent electronics termination board
connects to power supply connector SK1.
Figure 4-11. General Purpose Intelligent Electronics
Relay and Analog Output Connections
5. Connect a customer-supplied relay output
cable to the RELAYS connector on the
intelligent electronics. Refer to Figure 4-11
to match the terminals to the relay functions.
6. Connect a customer-supplied analog output
cable to the ANALOG OUTPUTS connector as shown in Figure 4-11. If any analog output is unused, connect a 250 ohm
resistor between the (+) and (-) terminals.
f.Type 4X Intelligent Electronics (Optional).
NOTE
Relay jumper blocks J9 and J11 on the
HART daughter board (Figure 4- 10) ca n be
configured for either the default or failsafe
configuration. For more information, refer
to Section III, INTELLIGENT ELECTRONICS.
1. Run the customer-supplied signal cable
through a suitable cond uit.
2. Run the signal cable through the cable gr ip
specified in Figure 4-6.
3. Connect the signal cable to the LON connector
on the IG-1 software board and the 4-20 mA
LOOP TO STACK connector on the HART
daughter board as shown in Figure 4-10.
4. Once the cable is connected, tighten the
cable seal.
7. Make sure power supply connector SK2
connects to the 24 V connectors on the IG-1
software board and HART daughter boa rd.
8. If the optional heater is installed, make sure
connector J3 on the Type 4X intelligent
electronics termination board connects to
the heater.
9. Run a customer-supplied digital input cable
for remote initialization of zero/span checks
through the cable grip sp ecified in Figure 4 -
6. Connect the cable to the DIGITAL
INPUT connector on the HART daughter
board as shown in Figure 4-10. Once the
cable is connected, tighten the cable seal.
10. Run a customer-supplied relay output cable
through the cable grip sp ecified in Figure 4 -
6. Connect the cable to the RELAY
CONTACTS connector on the HART
daughter board. Refer to Figure 4-10 to
match the terminals to the relay functions.
Once the cable is connected, tighten the
cable seal.
11. Run a customer-supplied analog output
cable through the cable grip specified in
Figure 4-6. Connect the cable to the
ANALOG OUTPUTS connector on the
HART daughter board. Once the cable is
connected, tighten the cable seal.
g. Model 751 Indicator (Optional).
Attach the
Model 751 indicator in series with the 4-20 mA
signal loop. See Figure 4-10.
IB-106-200R
4-14
Page 66
SECTION V. ALIGNMENT
5-1.OPTICAL ALIGNMENT.
Thermal deformation of the stack or duct
can affect the accuracy of the alignment. To
reduce the effects of thermal deformation,
ensure the wall of the stack or duct is
stabilized at the normal operating
temperature prior to performing the final
alignment procedure.
Stack gases can cause serious damage to the
opacity monitor. To prevent damage to the
unit, ensure purge air is on prior to opening
the air lens seal plates. Ensure the seal plates
are closed whenever the purge air blower is
not running.
Turn on power to the transceiver and retro-
a.
reflector.
Run the process long enough to stabilize the
b.
stack walls at normal operating temperature. The
stack walls must be at the same temperature
during final alignment as during the operation
since thermal distortion of the walls can affect
alignment.
Enter the check optics mode as follows:
c.
1. Attach the HART Communicator and turn on
the device. Refer to paragraph 6-2 for HART
Communicator installation information.
2. From the online menu, select DEVICE
SETUP.
3. Next, select DIAG/SERVICE from the
DEVICE SETUP menu.
4. From the DIAG/SERVICE sub-menu, select
CHECK OPTICS.
Failure to remove the OPM 2000R from
automatic control loops prior to performing
the CHECK OPTICS procedure may result
in undesired equipment performance.
5. A “Loop should be removed from automatic
control” warning appears. Remove the OPM
2000R from any automatic control loops and
press OK to continue. Then, an “About to
begin check optics” status message briefly
displays.
6. In the next screen, the system prompts you
to select the LCW state. Select the V
option. The present V
value will
STACK
display. Proceed to the stack. A steady beam
of light should be leaving the transceiver.
At the stack, use a screwdriver to pry open the
d.
latches on the weatherproof housings a nd remove
the weather housings from the transceiver and
retroreflector.
Verify that each purge air blower is running
e.
properly.
STACK
IB-106-200R
5-1
Page 67
ALIGNMENT
NUT
(4)
SEAL PLATE
END CAP
AND CORNER
CUBE ASSEMBLY
RETROREFLECTOR
BODY
6 IN.
OPTICAL
EXTENSION
TUBE
Figure 5-1. Optical Alignment
VIEW
END CAP
INSTALLED
OPTICAL
ALIGNMENT
SIGHT
A
24670042
Push down the seal plates on both the transceiver
f.
and retroreflector to open the purge air path to
the flue, but do not remove the air lens seal plates
(Figure 5-1).
Align the transceiver as follows:
g.
1. Remove the end cap and corner cube
assembly from the retroreflector body.
2. Attach the optical alignment sight (without
the extension tube) to the retroreflector
body.
NOTE
Three concentric areas are visible through
the alignment sight. Longer pathlengths use
the larger diameter circles.
3. Observe the crosshair image projected by
the transceiver onto the alignment sight.
Note that three concentric areas provide
tolerance definition for three different
pathlength ranges (Figure 5-2).
4. Refer to Figure 5-2. If the crosshair
intersection is within the concentric area for
the given pathlengths, the unit is aligned
within ±2% opacity.
If the crosshair intersection is not in the center o f
h.
the circles, adjust the ball joint in the transceiver
module using the four alignment nuts (Figure 5-1).
3-10 FT
(0.915-3.05 M)
2.00 IN.
(50.8 MM)
AA
DIA REF.
B
10-20 FT
(3.05-6.1 M)
THE FIGURE ILLUSTRATESTOLERANCE AREAS FORTHREE
PATHLENGTH RANGES. THE THREE EXAMPLE READINGS
(FROMTHREE DIFFERENT ALIGNMENTS) ARE AS
FOLLOWS:
A - WITHIN ±2% OPACITY FOR ALL PATHLENGTHS.
B - WITHIN ±2% OPACITY FOR PATHLENGTHS 10 FT
( 3.05 M), BUT OUT OF ALIGNMENT FOR
≥
PATHLENGTHS <10 FT (<3.05 M).
C - WITHIN ±2% OPACITY FOR 20TO 40 FT (6.1 TO 12.2 M)
PATHLENGTHS, BUT OUT OF ALIGNMENT FOR
SHORTER LENGTHS.
C
20-40 FT
(6.1-12.2 M)
≥
24670043
Figure 5-2. View of Crosshairs and Tolerance Areas
in Optical Alignment Sight
IB-106-200R
5-2
Page 68
When alignment is complete, all four alignment
i.
nuts should be tight.
Align the retroreflector as follows:
j.
1. Remove the alignment sight at the
retroreflector.
2. Attach the 6 in. extension tube and
alignment sight to the retroreflector (Figure
5-1). The extension tube is required to
square the retroreflector to the projected
light beam.
3. Look directly through the alignment sight
and check for a centered beam of light from
the transceiver.
4. Use the alignment nuts on the retroreflector’s air window to center the beam of
light onto the frosted field of the alignment
sight. Carefully tighten the nuts while maintaining alignment.
5. Recheck the crosshairs by removing the
extension tube. The crosshairs should remain
centered. If not, readjust the transceiver ball
joint.
Remove the alignment sight and extension tube
k.
from the retroreflector.
Install the end cap and corner cube assembly on
l.
the retroreflector.
Install the weatherproof housings over the trans-
m.
ceiver and retroreflector modules .
5-2.OBJECTIVE LENS ADJUSTMENT.
OPM 2000R is configured at the factory for the user’s
stack diameter. If readjustment is ever necessary, the
transceiver assembly and retroreflector body must be
set in a clean environment and at the same distance
apart (flange-to-flange) as when installed on the
stack. The following steps are performed to focus the
objective lens.
Removing covers from the optical assembly
or making optical repairs or adjustments in
an unsuitable environment can affect the
accuracy of the unit. Removal of the
electronics housing and optical cover, as well
as all repairs and adjustments to the optical
assembly, must be performed in a clean,
dust-free environment.
Enter the check optics mode as follows:
a.
1. Attach the HART Communicator to the
4-20 mA signal line and turn on the device.
Refer to paragraph 6-2 for HART Communicator installation information.
2. From the online menu, select DEVICE
SETUP.
3. Next, select DIAG/SERVICE from the
DEVICE SETUP menu.
4. From the DIAG/SERVICE sub-menu, select
CHECK OPTICS.
The
Using the HART Communicator, select the EXIT
n.
option to leave the check optics m ode.
At the “Return control loop to automatic control”
o.
message, return the OPM 2000R to the automatic
control loops previousl y removed and press En t er.
After waiting 30 minutes for the unit to stabilize,
p.
check the calibration. Recalibrate if necessary.
Calibration can be checked by inserting the zero
jig. If opacity differs from 0.0% by more than
±0.5%, recalibrate per paragraph 6-7.b.
Failure to remove the OPM 2000R from
automatic control loops prior to performing
the CHECK OPTICS procedure may result
in undesired equipment performance.
5. A “Loop should be removed from automatic
control” warning appears. Remove the OPM
2000R from any control loops and press OK
to continue. Then, an “About to begin check
optics” status message briefly displays.
IB-106-200R
5-3
Page 69
6. In the next screen, the system prompts you
to select the LCW state. Scroll to V
and press Enter. The present V
STACK
will display. Proceed to the stack. A steady
beam of light should be leaving the
transceiver.
Remove the end cap from the retroreflector body.
b.
Install the alignment sight in the retroreflector
c.
body (Figure 5-1).
Refer to Figure 2-2:
d.
1. Remove electro nics housing (14).
2. Remove thumbscrew (2) and optical
enclosure cover plate (1).
necessary, and exit the check optics mode as
follows:
1. When prompted for the next step, select the
REFRESH option. Note the current V
value.
2. When prompted again for the next step,
select V
to display the current V
LAMP
value.
3. If V
STACK
and V
are not both 4.0 ±0.1 V,
LAMP
adjust the gain per paragraph 8-3.d.
4. Once the two voltages are 4.0 ±0.1 V, select
the EXIT option.
STACK
LAMP
During the adjustment, look through the
g.
alignment sight at the aperture crosshairs. Stop
the adjustment when the crosshairs are in sharp
focus and tighten the set screws.
Remove the alignment sight from the
h.
retroreflector body (Figure 5-1).
APERTURE
Figure 5-3. Objective Lens Adjustment
SET
SCREWS
OBJECTIVE
5. At the “Return control loop to automatic
control” message, return the OPM 2000R to
the automatic control loops previously
removed and press Enter.
LCW 2
LENS
24670044
IB-106-200R
5-4
Page 70
SECTION VI. OPERATION
6-1.OVERVIEW.
held communications interface device. It provides the
operator interface to the OPM 2000R. Its 8 line x 21
character liquid crystal display (LCD) and 25 keys are
used to view data and to configure and calibrate the
unit. A pocket-sized manual is also included with the
HART Communicator that details the specific
functions of all the keys.
The HART Communicator accomplishes its task
using a frequency shift keying (FSK) technique. With
the use of FSK, high-frequency digital communication signals are superimposed on the 4-20 mA
transmitter current loop. The communicator does not
disturb the 4-20 mA signals since no net energy is
added to the loop.
To interface with the OPM 2000R, the HART
Communicator requires a termination point along the
4-20 mA current loop and a minimum load resistance
of 250 ohms between the communicator and the
power supply. To simplify the connection procedure,
The HART Communicator is a hand-
the OPM 2000R provides two banana jacks at each of
the transceiver and intelligent electronics sites so the
HART Communicator can be used at either location
as shown in Figure 6-1.
There is an option to interface the HART Communicator with a personal computer by loading the
designated AMS software into the PC and linking the
HART Communicator to the PC using the PC
interface adapter. The adapter connects to the serial
port on the rear panel of the communicator. Refer to
the proper HART Communicator documentation for
more information.
6-2.HART COMMUNICATOR SIGNAL LINE
CONNECTIONS.
connecting the HART Communicator to the signal
line. For applications in which the signal line has a
load resistance of 250 ohms or more, refer to method
1. For applications in which the signal line load
resistance is less than 250 ohms, refer to method 2.
There are two methods of
IB-106-200R
6-1
Page 71
TRANSCEIVER
STACKTERMINATION BOARD
NOTE: BOARD DETAILSWERE
OMITTED FOR CLARITY.
GENERAL PURPOSE
INTELLIGENT ELECTRONICS
FRONTVIEW
HART
J7
3
3
112
ANALOG OUTPUTS
3
3
112
2
4-20 mA
SIGNAL LINE
LOAD RESISTANCE (R )
2
6
6
445
5
RELAYS
NOT USED
LEAD SET
L
4-20 mA
SIGNAL LINE
4-20mA
TO STACK
J6
LON
BACKVIEW
DIGITALINPUT
+24V
LED
LED
LED
FAULT
POWER
COMMON
J1
LEAD SET
+24V
J6 J10
4-20 mA
SIGNAL LINE
OPTIONALTYPE 4X
INTELLIGENT ELECTRONICS
HARTTERMINATION BOARD
4-20mA
LOOP
TOSTACKTO
STACK
J2
+
-
DIGITAL
INPUT
+
-
24VDC
+
-
+
-
3D39650G REV
TOP COVER PLATE
J1
J2J3
RELAY
CONTACTS
ANALOG
OUTPUTS
-
+
J7
-
+
HART
-
+
4-20 mA
SIGNAL LINE
LOAD RESISTANCE (R )
J6
L
ANALOG OUTPUT
DEVICE
(ONLY USED IF R
250 OHM LOAD RESISTOR
< 250 OHMS)
L
COMMUNICATOR
Figure 6-1. HART Terminal Connections
HART
LEAD SET
IB-106-200R
6-2
LEAD SET
LOOP
CONNECTORS
SERIALPORT & BATTERY
CHARGER MUST
NOTBE USED IN
HAZARDOUS AREAS
LOOPCONNECTORS
HART COMMUNICATOR
TOP PANEL
USE INTERFACE
00275 0013ONLY
SERIAL PORT
ANALOG OUTPUT
DEVICE
29170018
Page 72
HART
ANALOG OUTPUTS
112
3
2
>
R250LΩ
RELAYS
3
3
112
445
NOT USED
2
6
6
5
4-20 mA SIGNAL LINE
3
GENERAL PURPOSE
INTELLIGENT ELECTRONICS
LOOP
CONNECTORS
SERIALPORT & BATTERY
CHARGERMUST
NOTBE USED IN
HAZARDOUSAREAS
LOOPCONNECTORS
USEINTERFACE
002750013 ONLY
SERIAL PORT
HART COMMUNICATOR
TOP PANEL
Figure 6-2. Signal Line Connections,
a. Method 1, for Load Resistance
≥≥≥≥
250 Ohms.
Explosions can result in death or serious
injury. Do not make connections to the
HART Communicator’s serial port, 420 mA signal line, or NiCad recharger
jack in an explosive atmosphere.
HART
COMMUNICATOR
ANALOG OUTPUT DEVICE
≥≥≥≥
250 Ohms Lead Resistance
(b) Connect the opposite end of the lead
set to the banana jacks on either the
intelligent electronics or the stack
termination board.
2. If attaching the HART Communicator to an
OPM 2000R using a wiring termination
point in the analog output (AO1) 4-20 mA
signal line, refer to Figure 6-2 and the
following procedure:
LEAD SET
24670049
1. If attaching the HART Communicator to an
OPM 2000R using the banana jacks provided at the stack termination board or the
intelligent electronics, refer to Figure 6-1
and the following procedure.
(a)Connect the supplied lead set to the
loop connectors on the HART Communicator top panel.
IB-106-200R
(a)Connect the supplied lead set to the
loop connectors on the HART Communicator top panel.
(b) Using the banana clips supplied with
the lead set, connect the HART
Communicator in parallel to the load
resistance.
6-3
Page 73
HART
ANALOG OUTPUTS
112
3
2
RELAYS
3
3
112
445
NOT USED
2
6
6
5
3
GENERAL PURPOSE
INTELLIGENT ELECTRONICS
4-20 mA SIGNAL LINE
250 OHM LOAD
RESISTOR (SEE NOTE)
>
250ΩR
L
ANALOG OUTPUT DEVICE
LOOP
CONNECTORS
SERIAL PORT& BATTERY
CHARGER MUST
NOT BE USED IN
HAZARDOUS AREAS
LOOP CONNECTORS
USE INTERFACE
00275 0013 ONLY
SERIAL PORT
COMMUNICATOR
HART COMMUNICATOR
TOP PANEL
Figure 6-3. Signal Line Connections, <250 Ohms Lead Resistance
b. Method 2, for Load Resistance < 250 Ohms.
Explosions can result in death or serious
injury. Do not make connections to the
HART Communicator’s serial port, 420 mA signal line, or NiCad recharger
jack in an explosive atmosphere.
THE 250 OHM LOAD
RESISTOR IS ONLY USED
IF R < 250 OHMS.
L
(b)Connect the supplied lead set to the
250 ohm load resistor and to the banana
jacks on either the intelligent electronics
or the stack termination board.
2. If attaching the HART Communicator to an
OPM 2000R using a wiring termination
point in the analog output (AO1) 4-20 mA
signal line, refer to Figure 6-3 and the
following procedure:
24670065
1. If attaching the HART Communicator to an
OPM 2000R using the banana jacks provided at the stack termination board or the
intelligent electronics, refer to Figure 6-1
and the following procedure:
(a)Connect a 250 ohm load resistor to the
loop connectors on the HART Communicator top panel.
IB-106-200R
(a)Connect a 250 ohm load resistor to the
loop connectors on the HART Communicator top panel.
(b) Connect the supplied lead set to the
250 ohm load resistor.
(c)At a convenient point, break the analog
output (AO1) 4-20 mA signal line and,
using the banana clips supplied with
the lead set, connect the HART Communicator to the 4-20 mA signal line.
6-4
Page 74
6-3.OFFLINE AND ONLINE OPERATIONS.
HART Communicator can be operated both offline
and online.
In the online mode, the communicator is connected
a.
to the 4-20 mA analog output signal line. The
communicator is connected in parallel to the OPM
2000R or in parallel to the 250 oh m load resistor.
Offline operations are those in which the
b.
communicator is not connected to the OPM
2000R. The only offline operation used with the
OPM 2000R is interfacing the HART
Communicator with a PC. (Refer to the
applicable HART documentation regarding
HART/PC applications.)
LCD
DISPLAY
The
6-4.HART OPERATOR INTERFACE DESCRIP-
The HART Communicator (Figure 6-4) has
TION.
an 8-line, 21-character liquid crystal display (LCD)
and 25 keys that provide communication between you
and the OPM 2000R.
a. LCD Display.
When connected to a HART
Communicator, the top line of each online menu
displays the model name of the connected device
and its tag. In addition, the bottom line of each
menu is reserved for the dynamic labels for each
software-defined function key (F1 through F4)
directly below the display.
OPM 2000R @@@@@@
Online
1 Device setup
2 PV 50.00 %
3 SV 12.00 mA
4 TV 0.00 degC
5 Mode Run
FUNCTION KEYS
ACTION KEYS
ALPHANUMERIC KEYS
SHIFT KEYS
F1F2
I
O
ABC DEF
7
JKL
4
STU
12
#%&
0
F3
GHI
89
PQR
MNO
5
6
YZ/
VWX
3
<>
:+
*
_
.
F4
Figure 6-4. HART Communicator Operator Interface
IB-106-200R
6-5
24670056
Page 75
b. Function Keys (F1 through F4).
The function
of each key varies depending on the name that
displays above it in the last line of the LCD
display. Table 6-1 provides the location and
purpose of each key.
c.Action Keys.
The action keys are located just
below the function keys on the HART
Communicator. Table 6-2 describes the function
of each key.
If you press only the alphanumeric key within an
edit menu, only the bold numeric character in the
center of the key is selected.
To select the other characters on the key, first
press and release the appropriate shift key and
then press the alphanumeric key. For example, to
select the letter K, first press the second shift key
and then press the K key.
d. Alphanumeric and Shift Keys.
numeric keys (Figure 6-4) can be used to select
menu options or enter data.
F1F2F3F4
HELP
Accesses online help
Activates or deactivates a bit-
enumerated binary variable
RETRY
Tries to re-establish
Deletes current character
communication
EXIT
Leaves the current menu
Sends configuration data to
YES
Answer to yes/no question
Moves up one help screen
ALL
Includes current Hot Key item
Goes to a previous message in
on Hot Key Menu for all
devices
NEXT
Goes to the next variable in
Saves information to memory
offline edit
FILTR
Opens customization menu to
sort configurations
Toggles marked configuration
variables for sending to a
Opens detailed configuration
The alpha-
Table 6-1. Function Keys.
ON/OFF
DEL
SEND
the device
PGUP
PREV
a list of messages
SAVE
module or data pack
MARK
field device
XPAND
information
ABORT
Terminates current task
without saving configuration
Acknowledges information
OK
on the screen
data
ESC
Leaves a value uncha nged
QUIT
Terminates a session because
Accepts user-entered data
Leaves the current menu
ENTER
EXIT
of a communication error
PGDN
Moves down one help screenNOAnswer to yes/no question
NEXT
Goes to the next message in a
list of messages
Includes Hot Key item
ONE
for one device
HOME
Goes to the top menu in the
device description
BACK
Goes back to the menu from
which HOME was pressed
EDIT
Edits a variable value
CMPRS
Closes detailed configuration
information
IB-106-200R
ADD
Adds current item to
Hot Key Menu
6-6
Page 76
Table 6-2. Action Keys.
KEYFUNCTION
I/O
××××
〉〉〉
〉〉〉
〉〉〉〉〉〉
ÕÕÕÕ
ØØØØ
ÖÖÖÖ
6-5.USING THE HART INTERFACE.
Turns the HART Communicator ON and OFF.
The up arrow key moves the cursor up through
a menu or list of options. An up arrow symbol
next to a menu option on the display indicates
that you can scroll upward for more options.
The hot key provides fast access to your most
frequently used tasks. Refer to the HART
Communicator manual for more information.
The left arrow key moves the cursor to the left
in an editable field or returns to a previous
menu. A left arrow symbol in the top righthand corner of the display indicates that you
can return to a previous menu.
The down arrow key moves the cursor down
through a menu or list of optio ns. A down
arrow symbol next to a menu option on the
display indicates that you can scroll downward
for more options.
The right arrow key moves the curso r to the
right in an editable field or selects a menu
option. A right arrow symbol next to a
highlighted menu option indicates the option
contains more selections.
Once the HART
Commun i cator i s con n ected t o th e OPM 2000R system,
turn on the HART Communicator using the I/O key.
The first screen that displays is the online menu (Figure
6-5) which has the following menu optio ns: DEVICE
SETUP, PV, SV, TV, and MODE.
NOTE
As you set up your OPM 2000R system,
record all of your settings for reference on
the worksheet provided in Appendix C.
a. DEVICE SETUP.
the menu tree shown in Figure 6-10 at the end of
this section. It contains all of the displays and
procedures used to monitor and control the
OPM 2000R system. Refer to paragraphs 6-6
through 6-10 for more information.
To select a menu option within the DEVICE
SETUP menu structure, either press the right
arrow action key or use the alphanumeric keypad
and press the number that corresponds with the
menu option.
This menu item expands into
b. PV, SV, and TV.
HART terms for primary value, secondary value,
and tertiary value. These menu items are displayonly variables that display critical, up-to-date
device information such as opacity, stack
temperature, transmittance, etc. The information
monitored by these three variables are also
connected to the three analog outputs.
c.MODE.
status. The system can be in one of ten modes as
described in Table 6-3. These mode indications
aid in troubleshooting the system. Refer to
Section VII for more information.
The mode continuously disp lays system
PV, SV, and TV are standard
OPM 2000R @@@@@@
Online
1 Device setup
2 PV 50.00 %
3 SV 12.00 mA
4 TV 0.00 degC
5 Mode Run
Figure 6-5. Online Menu
Table 6-3. System Status Modes.
MODEDESCRIPTION
RUN
CAL
OPTICS CHK
FLTR CHK
ZSP CHK
CALF
COMF
SYSFLT
CALF&SYSFLT
FIXED MA
Normal operating mode.
An offline calibration is in progress.
An optics check is in progress.
A filter check is in progress.
A zero/span check is in progress.
The last calibration failed.
A communication failure exists
between the transceiver and the
intelligent electronics.
A system fault condition exists, such
as a lamp failure, high lamp voltage
reading, or blower failure.
The last calibration failed and a
system fault exists.
A trim DAC procedure or loop test is
in progress.
24670057
IB-106-200R
6-7
Page 77
Table 6-4. FLD DEVICE VOLTS Sub-menu.
V
STACK
MENU
ITEM
TYPICAL
VALUEDESCRIPTION
3.239 VVoltage produced when a generated light beam is sent across the stack
(read-only)
V
LAMP
3.848 VVoltage produced when a generated light beam is reflected within the
(read-only)
V
AMB
0.205 VVoltage produced from the ambient light coming from the stack.
(read-only)
V
DARK
0.343 VVoltage produced when the voltage detector is blocked from the light
(read-only)
Stack Temperature
Vad590
N/AMenu item that further sub-divides into Vad590 and Temp.
3.000 VVoltage produced from the temperature of the optical assembly in the
(read-only)
Temp
27 °CStack temperature (in °C). The stack temperature is calculated using
(read-only)
6-6.PROCESS VARIABLES Menu.
displays the variables critical to the OPM 2000R
process, such as the voltages produced by the
different light paths in the transceiver and
retroreflector. Also, it gives you the opportunity to
specify three variables (PV, SV, and TV) to monitor
on the online menu.
To access the PROCESS VARIABLES menu, select
the DEVICE SETUP menu item from the online
menu and select PROCESS VARIABLES. Four menu
options are available: FLD DEVICE VOLTS,
OUTPUT VARIABLES, VARIABLE MAPPING,
and VARIABLE RE-MAP.
and reflected back to the transceiver by the retroreflector.
transceiver; used to compensate for the effects of an aging bulb, other
aging components, and power fluctuations.
beam and ambient light; used to compensate for any internal light
leakage within the transceiver.
transceiver; used to calculate the stack temperature.
the following equation:
(Vad590 × 100) - 273 = Stack Temperature
This menu
The light paths are controlled by the Liquid
Crystal Windows (LCWs) shown in Figure 6-6.
The LCWs are transparent when ON and
translucent when OFF. In the translucent state,
light is scattered and effectively blocked. Table
6-5 shows the LCW state for each measured
voltage. LCW 2 has five sectors that can be
individually controlled during the zero and span
checks. See paragraph 6-9.b. During normal
operation, all of the sectors are turned ON and
OFF at the proper time.
Table 6-5. LCW States.
a. FLD DEVICE VOLTS.
This sub-menu displays
the current values of four voltages produced by
the different light paths taken in each
measurement cycle. It also displays the stack
temperature and the voltage needed to calculate
the stack temperature. To access the FLD
DEVICE VOLTS sub-menu, select FLD
DEVICE VOLTS from the PROCESS
VARIABLES menu. The available menu items
are explained in Table 6-4.
V
V
V
V
IB-106-200R
6-8
VOLTAGELCW 1
STACK
LAMP
AMB
DARK
ONONOFF
ONOFFON
OFFONOFF
OFFOFFOFF
LCW 2
(Sector 5)
LCW 2
(Sectors 1 - 4)
Page 78
LCW 1
BEAM
SPLITTER
LCW 2
LAMP
DETECTOR
Figure 6-6. LCW Locations
b. OUTPUT VARIABLES.
This sub-menu is used
to identify the three variables (PV, SV, and T V)
that define the analog outputs (AO1, AO2, and
AO3). To access this display, select OUTPUT
VARIABLES from the PROCESS VARIABLES
menu. Selecting a variable on this sub-menu
accesses a display listing the four parameters that
define each variable as explained in Table 6-6.
Table 6-6. OUTPUT VARIABLES Sub-menu.
MENU ITEMDESCRIPTION
PV Output Vars
PV is (read-only)
Displays the four parameters that define PV (analog output 1).N/A
Identifies the type of output variable. PV can represent opacity, transmittance,
optical density, extinction, or dust concentration.
PV Value (read-only)
% Range (read-only)
Displays the PV value in the appropriate units for the variable selected.N/A
Displays the upper range value that corresponds to the full-scale analog output
as a percentage of range. This variable is used to scale the analog output. For
example, if % RANGE is set to 25%, any variable value greater than or equal
to 25% of full range will force the analog output to be 20 mA. Refer to
paragraph 6-8.b for more information.
PV AO (read-only)
SV Output Vars
(read-only)
TV Output Vars
(read-only)
Displays the analog output value in milliamps.N/A
Displays the four parameters that define SV (analog output 2). SV can
or one of the 12 averages detailed in paragraph 6-9.c.
Displays the four parameters that define TV (analog output 3). TV can
represent opacity, transmittance, optical density, extinction, dust concentration,
temperature,
lx/lt,
or one of the 12 averages detailed in paragraph 6-9.c.
OBJECTIVE
LENS
c.VARIABLE MAPPING.
24670060
This display-only
menu item identifies the three variables selected
to represent PV, SV, and TV. To access this
display, select VARIABLE MAPPING from the
PROCESS VARIABLES menu. To exit the
display, press Exit.
DEFAULT
SETTING
Opacity
N/A
Transmittance
Temperature
IB-106-200R
6-9
Page 79
d. VARIABLE RE-MAP.
This procedure allows
you to select the three variables that represent
PV, SV, and TV.
Use the following procedure to change the PV,
SV, and TV output variables.
1. Select VARIABLE RE-MAP from the
PROCESS VARIABLES menu.
Failure to remove the OPM 2000R from
automatic control loops prior to performing
the VARIABLE RE-MAP procedure may
result in undesired equipment performance.
2. Next, a “Pressing OK will change device
output. Put loop in manual” message
appears. Remove the OPM 2000R from any
automatic control loops to avoid undesirable
equipment performance and press OK.
NOTE
The MORE option in the scrollable list
indicates that additional selections are
available on the next screen. However, if
you select the MORE option, you cannot
return to the selections on the previous
screen.
3. The next screen prompts you to select a PV
variable. Select one of the variables from the
scrollable list and press Enter.
6-7. DIAG/SERVICE Menu.
This menu is used to
perform diagnostics to troubleshoot and service the
OPM 2000R. To access the DIAG/SERVICE menu,
select the DEVICE SETUP menu item from the
online menu and select DIAG/SERVICE. Seven submenus are available: STATUS, OFFLINE CAL, REF.
VOLTAGES, TRIM DAC, LOOP TEST, CHECK
OPTICS, and FLTR CHK.
a. STATUS.
The menu items in the STATUS submenu indicate current instrument status, alarm
status, and possible equipment or communication
failures. Whenever the status mode on the online
menu indicates a CALF, COMF, SYSFLT, or
CALF&SYSFLT mode, access the STATUS submenu to display the current instrument status and
alarm statuses that may indicate a possible
equipment or communication failure. All of the
menu items displayed will be either ON or OFF.
To access the STATUS sub-menu, select
STATUS from the DIAG/SERVICE menu.
Refer to Section VII for more information on
how the STATUS menu items are used to
troubleshoot the OPM 2000R.
b. OFFLINE CAL.
The OFFLINE CAL menu item
provides a procedure to perform an offline
calibration. The OPM 2000R is calibrated at the
factory per customer data specifications. Only
recalibrate the unit in a clean laboratory area, or
on a clear stack while using the zero jig option.
The resulting voltages are stored in the nonvolatile memory of the software chip on the stack
LON board in the transceiver.
4. The following screen prompts you to select
an SV variable. Select one of the variables
from the scrollable list and press Enter.
5. The next screen prompts you to select a TV
variable. Select one of the variables from the
scrollable list and press Enter.
6. Next, a “Return control loop to automatic
control” note appears. Return the OPM
2000R to the automatic control loops
previously removed and press Enter.
7. Access the VARIABLE MAPPING display
to verify if the variables reflect the latest
changes.
IB-106-200R
To calibrate the unit, use the following
procedure.
1. If calibrating while the unit is installed on
the stack using a zero jig, go to step 2. If
calibrating the unit in a clean laboratory, use
the following procedure:
(a)Remove optical assembly (1, Figure
2-1) from the transceiver module per
paragraph 8-3.a.1.
(b) Remove the retroreflector weather
housing, turn off power to the
retroreflector blower, and remove the
retroreflector body (Figure 5-1). Install
the weather housing on the retroreflector module.
6-10
Page 80
(c)Turn off power to the intelligent
electronics (Figure 3-1 or Figure 3-5 as
appropriate). Tag and remove all
cables and wires from the intelligent
electronics and remove the unit from
its mounting location.
(d) Move optical assembly, retroreflector
body, and intelligent electronics to a
clean laboratory.
(e)Set up the transceiver and retro-
reflector in a zero opacity location.
Ensure the test setup has the same
flange-to-flange distance
(lf)
as on the
stack and make sure the transceiver and
retroreflector are properly aligned.
Refer to Section V for alignment
information if necessary.
2. If not attached, connect the HART Communicator at the stack termination board or the
intelligent electronics per paragraph 6-2 and
turn on the comm u n icator.
3. If using a zero jig for this offline calibration,
insert the jig per paragraphs 6-7.g.2(c)
through (e).
4. Select OFFLINE CAL from the DIAG/
SERVICE menu.
5. The first screen prompts you to press the
pushbutton light to begin the calibration.
Press the CAL/CHECK backlit button
(Figure 6-7) on the front mounting plate of
the transceiver, and the system automatically
begins to measure 0% opacity and record
0% opacity reference volts.
(f)Connect the LON test cable to
communications cable (3, Figure 2-1)
and the LON connector on the
intelligent electronics.
(g) Connect the transceiver power test
cable to power cable (2) and a suitable
voltage source.
(h) Connect the HART Communicator to
the intelligent electronics and turn on
the communicator.
(i)To access the FLD DEVICE VOLTS
sub-menu, select DEVICE SETUP
from the online menu and select
PROCESS VARIABLES. Next, select
FLD DEVICE VOLTS. Examine the
V
STACK
and V
variables. Both
LAMP
variables should be between 3.0 and
4.0 V.
(j)If necessary, remove electronics
housing (14, Figure 2-2) to adjust the
gain potentiometer on the detector
amplifier board so both the V
V
values are between 3.0 and
LAMP
STACK
and
4.0 V. For best performance, try to
adjust V
STACK
and V
to 4.0 ±0.1 V.
LAMP
Refer to paragraph 8-3.d for the
procedure to adjust the gain.
(k) Insta ll electronics housing (1 4).
(l)Make sure the laboratory is dimly lit
before performing the offline calibration procedure.
6. The next screen informs you to wait while the
system performs a 0% calibration. Once 0%
calibration is complete, the system instructs
you to turn the corner cube around and press
the pushbutton light to begin 100%
calibration. The back of the corner cube is a
black reflector that simulates 100% opacity. If
the zero jig is in use, insert the black paddle
that shipped with the zero jig instead of using
the back of the corner cube. Press the
CAL/CHECK backlit pushbutton on the front
mounting panel of the transceiver.
7. The next screen informs you to wait while
the system performs a 100% calibration.
When 100% calibration is complete, the
system instructs you to turn the corner cube
back around and press the pushbutton light
to continue. If the zero jig is in use, remove
the black paddle from the zero jig instead of
turning the corner cube around. Press the
CAL/CHECK backlit pushbutton on the
front mounting panel of the transceiver.
8. Next, the screen displays the current PV value
and Optical Correction Factor (OCRF) and
gives you three options: REFRES H, CHANGE
OCRF, and END CALIBRA TION.
The OCRF provides a correction factor for
an offline calibration. Normally, this value
should be left at 0.00. If certified neutral
density filters (NDFs) are available, they can
be inserted into the light path to verify the
calibration. The OCRF can then be adjusted
to force the unit to better match the filter
values. The OCRF is a percent of reading
IB-106-200R
6-11
Page 81
correction and is limited to ±10%. This
factor normally is not required because the
OPM 2000R is capable of measuring well
within 2% opacity.
The following example demonstrates the use
of the OCRF.
10. Select the REFRESH menu item to update
the PV and OCRF values.
11. Select END CALIBRATION to return to the
DIAG/SERVICE menu.
12. Remove the zero jig if it is in use.
NOTE
In these examples,
lx/lt
equals 1. If
lx/t
does
not equal 1, correct the opacity reading for
lx/lt
. Refer to paragraph 6-7.g.4. Then,
adjust the OCRF if necessary.
The certified values for three different NDFs
are the following:
NDF #1 = 8.1%
NDF #2 = 20.5%
NDF #3 = 37.9%
During an offline calibration of the OPM
2000R, the three NDFs have the following
opacity readings while the OCRF equals 0:
NDF #1 = 8.5%
NDF #2 = 22.5%
NDF #3 = 41.0%
Since the opacity readings of the three NDFs
are not the same as their certified values, the
OCRF should be changed to make the
opacity reading more accurate. When the
OCRF is changed to 2, the three NDFs have
the following opacity readings:
NDF #1 = 8.65%
NDF #2 = 22.9%
NDF #3 = 41.6%
When the OCRF is changed to -10, the three
NDFs have the following opacity readings:
NDF #1 = 7.7%
NDF #2 = 20.5%
NDF #3 = 37.8%
In this example, changing the OCRF value
to -10 is the best setting because it changes
the opacity readings of all three of the NDFs
closest to their certified values—NDFs 2
and 3 in particular.
9. To change the OCRF, select the CHANGE
OCRF menu item, change the OCRF to a
value between -10.0 and +10.0, and press
Enter.
c.REF. VOLTAGES.
menu displays voltages that were measured
during the last offline calibration at 0% opacity
and at 100% opacity. It also displays the date and
time of the last offline calibration. The current
voltages can be compared to the reference values
to determine how much they have changed since
the last calibration. The opacity monitor formulas
compensate for changes in ambient light and the
lamp intensity. Table 6-7 identifies the reference
voltages and provides typical values for each. For
definitions of the voltage values refer to Table
6-4.
Table 6-7. REF. VOLTAGES Sub-menu.
MENU
TYPICA
ITEM
VALUES
CalDate
10/21/97Date of the last calibration
(read-only)
CalTime
02:00Time of day of the last
(read-only)
V
STACK
0
3.972Voltage value at 0% opacity.
(read-only)
V
LAMP
0
3.691
(read-only)
V
0
AMB
0.399
(read-only)
V
DARK
0
0.186
(read-only)
V
STACK
1
1.207Voltage value at 100% opacity.
(read-only)
V
LAMP
1
3.694
(read-only)
V
1
AMB
0.187
(read-only)
V
DARK
1
0.184
(read-only)
OCRF
0.000Correction factor for an offline
(read-only)
REF. VOLTAGES sub-
L
DESCRIPTION
(DD/MM/YY). This parameter
automatically updates upon
calibration.
calibration (HH:MM). This
parameter automatically updates
upon calibration.
calibration.
IB-106-200R
6-12
Page 82
d. TRIM DAC.
The TRIM DAC procedure is used
to calibrate the PV (AO1) 4-20 mA signal loop
by referencing a high and low count. The PV
needs to be trimmed because it uses an integrated
circuit to control AO1 that is different than the
circuits in SV and TV. The digital information
needed to set the analog output correctly varies
between integrated circuits. Therefore, to make
the integrated circuit accurate, the software needs
the digital information collected by trimming the
analog output. This diagnostic procedure helps to
maintain optimum accuracy and efficiency when
communicating with other devices.
6. When the “Returning fld device to original
output” message displays, remove the
reference meter from the analog output
connections and press Enter.
7. Next, a “Loop may be returned to automatic
control” note appears. Return the OPM
2000R to the automatic control loops
previously removed and press Enter. If you
were to repeat the TRIM DAC procedure, the
values that display on the reference meter will
match the output of the digital-to-analog
converter.
In the TRIM DAC procedure, the OPM 2000R is
placed in the fixed mA mode in which the digitalto-analog converter outputs a specified milliamp
signal, such as 4 mA. By attaching a reference
meter to the analog output connections, you can
view what the instrument is actually outputting,
which may not be 4 mA. The TRIM DAC
procedure uses the reference meter value to
calibrate the digital-to-analog converter to ensure it
outputs 4 mA. Use the following procedure to
calibrate the analog outputs:
1. To access the TRIM DAC procedure, select
TRIM DAC from the DIAG/SER VICE m enu .
Failure to remove the OPM 2000R from
automatic control loops prior to performing
the TRIM DAC procedure may result in
undesired equipment performance.
2. Next, a “Loop should be removed from
automatic control” warning appears. Remove
the OPM 2000R from any automatic control
loops to avoid undesirable equipment performance and press En ter.
3. The next screen directs you to connect a
reference meter. Connect an ammeter to the
analog output connections (Figure 4-10 or
Figure 4-11 as appropriate) o n the intelligent
electronics and press Enter.
4. Next, the screen prompts you to enter the
meter value. Observe the value displayed on
the reference meter, enter that value, and
press Enter.
5. Next, the screen prompts you to enter the
meter value. Observe the value displayed on
the reference meter, enter that value, and
press Enter.
e.LOOP TEST.
The loop test is a diagnostic
procedure that allows you to apply a specific
current to the 4-20 signal loop to verify that the
analog output is connected correctly. To access
this sub-menu, select LOOP TEST from the
DIAG/SERVICE menu.
1. To verify the current in analog output 1,
select LOOP TEST PV from the LOOP
TEST sub-menu.
Failure to remove the OPM 2000R from
automatic control loops prior to performing
a loop test may result in undesired equipment
performance.
2. Next, a “Loop should be removed from
automatic control” warning appears.
Remove the OPM 2000R from any
automatic control loops to avoid
undesirable equipment performance. At
this time, also install a reference meter to
analog output 1 that will register the signal
current. To continue the procedure, press
Enter.
3. The next screen prompts you either to select
a current or to end the test. Choose 4 mA,
20 mA, or OTHER, which gives you the
opportunity to enter a different value.
4. Once you make your selection, check the
reference meter. If the reference meter
value does not match the selected value,
you must check your connections. If the
values match, analog output 1 is connected
correctly.
IB-106-200R
6-13
Page 83
5. Select END to leave the LOOP TEST
procedure.
6. Next, a “Loop may be returned to automatic
control” note appears. Return the OPM
2000R to the automatic control loops
previously removed, disconnect the reference meter, and press Enter.
7. To verify the analog output 2 or 3, repeat
steps 1 through 6 for LOOP TEST SV or
LOOP TEST TV, respectively.
f.CHECK OPTICS.
Refer to Section V for the
complete CHECK OPTICS procedure.
g. FLTR CHK.
The menu items in the FLTR CHK
sub-menu are used to verify the calibration
validity of the OPM 2000R using a zero jig and
neutral density filters (NDFs). A set of three
different NDFs are used multiple times to comply
with the EPA Filter Check Method 203 Audit.
Typically, this procedure takes less than one
hour. NDFs placed in the zero jig will display
NDF values corrected for the pathlength
correction ratio (OPLR)—referred to as the
ratio in the OPM 2000R. The values will be in
the units configured for PV. These measurements
are stored by the OPM 2000R and recorded using
a data recorder connected to analog output 1. To
access this sub-menu, select FLTR CHK from the
DIAG/SERVICE menu. Refer to Table 6-8 for
descriptions of the available menu items.
Table 6-8. FLTR CHK Sub-menu.
MENU
ITEMDESCRIPTION
Filter Check
(method)
Provides the procedure to check the
NDFs to comply with the EPA Filter
Check Method 203 Audit.
Fltr Chk
Values
(method)
Provides the procedure to display each
neutral density filter value, in terms of
PV, by selecting the filter number. It also
displays time (HH:MM) the value was
taken.
Erase Fltr
Values
(method)
Provides the procedure to erase test filter
data currently stored by the OPM
2000R. The old filter data is usually
erased before starting a new filter check.
lx/lt
1. Use the following procedure to erase test
filter data currently stored by the
OPM 2000R:
NOTE
If the stored filter values are erased before
starting the FILTER CHECK procedure,
the procedure will begin at filter 1. If the
stored filter values are not erased before
starting the FILTER CHECK procedure,
the procedure will begin where it previously
ended.
(a)Select ERASE FLTR VALUES from
the FLTR CHK sub-menu.
(b) Next, an “About to erase filter values”
message appears. Press Enter to clear
all values of previous filter checks or
press Abort to exit from the screen
without erasing the values.
2. Perform the filter check procedure as
follows:
(a)Select FILTER CHECK from the
FLTR CHK sub-menu.
Failure to remove the OPM 2000R from
automatic control loops prior to performing
the FILTER CHK procedure may result in
undesired equipment performance.
(b) Next, a “Loop should be removed from
automatic control” warning appears.
Remove the OPM 2000R from any
automatic control loops to avoid
undesirable equipment performance
and press Enter.
(c)The next sc reen displays an “About to
begin filter check” message. At this
time, remove the window access plate
from the transceiver optical assembly
(Figure 6-7).
IB-106-200R
6-14
Page 84
NOTE: FLANGE NOZZLE
PARTIALLY CUT AWAY
TO SHOW PHANTOM
VIEW OF LOCATOR PIN.
WINDOW
ACCESS
PLATE
WINDOW
CLEANING
AREA
MAGNETS
NEUTRAL
DENSITY
FILTER
WINDOW
FLANGE
LOCATOR PIN
(SEE NOTE)
CAL/CHECK
BACKLIT
PUSHBUTTON
ZERO JIG
LOCATOR
PIN SLOT
24670061
Figure 6-7. Zero Jig and EPA Filter Placement
NOTE
A zero jig is specific to the transceiver to
which it has been calibrated. Check that the
serial number of the zero jig is the same as
the serial number of the transceiver.
The zero jig requires periodic calibration
(typically once per year). Refer to paragraph 8-4 for the zero jig calibration
procedure.
(d) Remove the keepers from the zero jig
magnets and place the zero jig through
the window cleaning area. Slide the jig
on the window flange and onto the
locating pin.
(e)Slightly rotate the jig back and forth
until the 2 in. (50.8 mm) diameter
raised section falls into place. The
locator pin and the two permanent
magnets hold the jig in position.
(f)Insert neutral de nsity filter 1.
(g)Press Enter on the HART Com m unicator.
(h) The next screen prompts you to press
the pushbutton light to begin reading
filter 1. Press the CAL/CHECK backlit
button on the front mounting plate of
the transceiver.
(i)The following screen informs you to
please wait (approximately five
seconds) while the system is reading
the filter.
(j)At the prompt to begin reading filter 2,
remove filter 1, and insert filter 2.
(k) Repeat steps (g) through (j) for the
remaining filters.
(l)If you do not wish to check all 30
filters, press Abort to exit the FILTER
CHK procedure.
(m) At this time, remove the neutral density
filter and zero jig from the transceiver
(Figure 6-7).
IB-106-200R
6-15
Page 85
The zero jig is a sensitive, calibrated
instrument. Store the jig in its protective
case when not in use. Failure to properly
store the jig can lead to damage or an outof-calibration condition.
To determine the correct expected opacity
value at your site, use the following
procedure:
(a)Convert the NDF-certified opacity
value to the equivalent optical density
(OD) value using the table in
Appendix A.
(n) Install the keepers on the zero jig
magnets and return the jig to its
protective case.
(o) Install the window access plate.
(p) When the “Loop may be returned to
automatic control” note appears, return
the OPM 2000R to the automatic
control loops previously removed and
press Enter.
3. Use the following procedure to view the
filter check values:
(a)Select FLTR CHK VALUES from the
FLTR CHECK sub-menu.
(b) T he next screen prompts you to select
a filter. Enter the number of the filter
(1 through 30) you wish to view and
press Enter.
(c)The following screen displays the filter
number; the filter value, in terms of
PV; and the time the filter was
checked. To view another filter, select
the NEW FILTER option. To exit the
procedure, select EXIT.
4. The OPM 2000R adjusts all readings for the
lx/lt
ratio, including those taken with an NDF.
The NDF-certified opacity values are based
on an
lx/lt
ratio of 1.0. If the
lx/lt
ratio at your
site is not equal to 1.0, an adjustment must be
applied to the given NDF-certified opacity
value that will yield the correct expected
value for your specific site.
(b) Multiply the OD value by the
to get an expected OD value.
(c)Convert the expected OD value back to
an (expected) opacity value using the
table in Appendix A.
The equation for the relationship is as
follows:
expected NDF OD value = certified OD value *
Example 1:
lx/lt
ratio = 0.8
certified NDF opacity value = 36.9%
certified OD value = 0.2000 (from
Appendix A)
expected NDF OD value = 0.2
* 0.8 = 0.16
expected NDF opacity value = 30.8%
(from Appendix A)
Example 2:
lx/lt
ratio = 0.8
certified NDF opacity value = 87.4%
certified OD value = 0.9000 (from
Appendix A)
expected NDF OD value = 0.9
* 0.8 = 0.72
expected NDF opacity value = 80.9%
(from Appendix A)
Example 3:
lx/lt
ratio = 3.0
certified NDF opacity value = 36.9%
certified OD value = 0.2000 (from
Appendix A)
expected NDF OD value = 0.2
* 3.0 = 0.6
expected NDF opacity value = 74.9%
(from Appendix A)
lx/lt
lx/lt
ratio
ratio
IB-106-200R
6-16
Page 86
6-8.BASIC SETUP MENU.
This menu is used to view
and configure basic system requirements. To access
the BASIC SETUP menu, select the DEVICE SETUP
menu item from the online menu and select BASIC
SETUP. Four sub-menus are available: SETUP
CLOCK, RANGE VALUES, LX/LT, and DEVICE
INFO.
4. The system then returns to the SETUP
CLOCK sub-menu. Verify that the read-only
displays in the sub-menu reflect the latest
changes.
Table 6-9. SETUP CLOCK Sub-menu.
a. SETUP CLOCK.
This sub-menu displays the
real-date and real-time and provides a procedure
to reset both. To access the SETUP CLOCK submenu, select SETUP CLOCK from the BASIC
SETUP menu. The menu items available are
explained in Table 6-9.
Use the following procedure to change the date
and time:
1. From the BASIC SETUP sub-menu, Select
CLOCK SETUP.
2. The next three screens will prompt you to
enter the current date in month, day, and
year, respectively. After typing each entry in
the highlighted area, press Enter.
3. The next three screens will prompt you to
enter the current time in hours, minutes, and
seconds, respectively. After typing each
entry in the highlighted area, press Enter.
MENU
ITEM
Date
(readonly)
Time
(readonly)
Clock
Setup
(method)
TYPICAL
VALUEDESCRIPTION
09/30/97Displays the current date (in
MM/DD/YY). The date is
maintained by the real-time
clock chip on the HART
daughter PC board. A batter y
on the board backs up the realtime clock in the event of a
power failure.
09:30:27Displays the current time (in
HH:MM:SS). The time is
maintained by the real-time
clock chip on the HART
daughter PC board. A batter y
on the board backs up the realtime clock in the event of a
power failure.
N/AProvides the procedure to reset
the date and time of the internal
clock.
IB-106-200R
6-17
Page 87
Table 6-10. PV, SV, and TV
RANGE VALUES Sub-menu.
MENU ITEMDESCRIPTION
Select PV Range
Contains the following three
parameters that define the PV
range.
URV
(read-only)
Displays the upper range value for
the selected variable as a percentage
of the analog output. A typical
value for this variable is 100.00%.
The URV can be modified using the
PV RANGE SETUP method.
LRV
(read-only)
Displays the lower range value for
the selected variable as a percentage
of the analog output. A typical
value for this variable is 0.00%.
This parameter cannot be modified.
PV Range Setup
(method)
Select SV Range
Provides the procedure to change
the URV of the selected variable.
Refer to the Select PV Range menu
item.
Select TV Range
Refer to the Select PV Range menu
item.
Failure to remove the OPM 2000R from
automatic control loops prior to performing
the URV procedure may result in undesired
equipment performance.
2. Next, a “Loop should be removed from
automatic control” warning appears.
Remove the OPM 2000R from any
automatic control loops to avoid undesirable
equipment performance and press Enter.
3. The next screen prompts you to enter a new
upper range value for analog output 1 (PV).
Type the value in the highlighted area and
press Enter. A typical value for this variable
is 100.00% of the analog output.
4. A “Saving range values” message displays
while the system updates.
5. Next, a “Loop may be returned to automatic
control” note appears. Return the OPM
2000R to the automatic control loops
previously removed and press Enter. Verify
that the read-only URV menu item reflects
the change.
b. RANGE VALUES.
The RANGE VALUES
sub-menu allows you to set up the ranges for the
user-selected PV, SV, and TV variables (analog
outputs 1, 2, and 3). To access this sub-menu,
select RANGE VALUES from the BASIC
SETUP menu. The menu items are SELECT PV
RANGE, SELECT SV RANGE, and SELECT
TV RANGE. The menu items for this sub-menu
are explained in Table 6-10.
Use the following procedure to change the URV
for the PV range:
1. From the SELECT PV RANGE sub-menu,
select PV RANGE SETUP.
6. Repeat steps 1 thr ough 5 for the SV and TV
URV values.
NOTE
If any of the three HART variables (PS, SV,
or TV) have the same process variable (i.e.,
opacity, transmittance, average 1, etc.),
setting the URV of one analog output will
affect the URV of each analog output whose
corresponding HART variable has been
assigned the same process variable. For
example, if SV and TV are both assigned
the process variable of opacity, then setting
the URV of analog output 2 (SV) to 50%
will automatically set the URV of analog
output 3 (TV) to 50%.
IB-106-200R
6-18
Page 88
lx/lt
c.LX/LT.
is the ratio of the inside diameter at
the top of the stack to the inside diameter of the
stack where the instrument is located. See Figure
6-8. If the ratio is greater than 1.0, the exit
opacity will be greater than the opacity at the
instrument location. The OPM 2000R uses this
correction factor to calculate the stack exit
opacity. It is not practical to have an
lx/lt
much greater than 2.0 because the error of the
instrument increases as
lx/lt
becomes greater.
The LX/LT sub-menu allows you to view and
configure the
a read-only display of the current
lx/lt
ratio. The LX/LT menu item is
lx/lt
default setting is 1.00. This value can be changed
using the LX/LT SETUP menu item.
factor
value. Its
Table 6-11. DEVICE INFO Sub-menu.
MENU ITEMDESCRIPTION
Dev id
(read-only)
Identifies the device used with the
HART Communicator. The device
ID also appears at the top of each
screen in the HART Communicator.
Descriptor
(read, write)
Tag
(read, write)
Provides a 16-character entry to
convey user information.
Provides an 8-character entry to
convey user information. Appears
on the top line of every HART
display next to the device ID.
Message
(read, write)
Provides a 32-character entry to
convey user information.
Use the following procedure to change the
variable:
1. From the LX/LT sub-menu, select LX/LT
2. The next screen prompts you for the
TRANSCEIVER
MODULE
lx/lt
SETUP.
lx/lt
variable. Calculate the ratio to three decimal
places by dividing the inside diameter of the
top of the stack (lx) by the inside diameter
of the stack at the instrument (lt). Type the
new value in the highlighted area and press
Enter.
lx
STACK
RETROREFLECTOR
MODULE
lt
3. A “Saving Lx/Lt” message displays while
the system updates. Once the value is saved,
the system returns to the LX/LT sub-menu.
Verify that the read-only Lx/Lt display
reflects the change.
d. DEVICE INFO.
This sub-menu allows you to
program descriptive or pertinent user information. To access this sub-menu, select DEVICE
INFO from the BASIC SETUP menu. The menu
items for this sub-menu are explained in Table
6-11.
Use the following procedure to enter a descriptor,
tag, or message:
1. To add descriptive information, select
DESCRIPTOR, TAG, or MESSAGE from
the DEVICE INFO sub-menu. Refer to
Table 6-11 for an explanation of each
parameter type.
2. The next screen prompts you to enter the
descriptive information. Type the entry in
the highlighted area and press Enter.
lf
Figure 6-8. lx and lt Stack Dimensions
24670006
IB-106-200R
3. The system exits to the DEVICE INFO submenu. Verify that the parameter you modified
reflects the latest changes.
6-19
Page 89
6-9.DETAILED SETUP MENU.
The DETAILED
SETUP menu is used to configure the OPM 2000R for
specific applications. To access the DETAILED
SETUP menu, select the DEVICE SETUP menu ite m
from the online menu and then select DETAILED
SETUP. Five sub-menus are available: RELAY
CONFIG, ZERO/SPAN CHECK, AVERAGES,
ALARMS, and DUST SETUP.
a. RELAY CONFIG.
The RELAY CONFIG submenu allows you to configure the relays to
energize upon certain alarm or status conditions. It
also allows you to view the currently selected
trigger signals. To access this sub-menu, select
RELAY CONFIG from the DETAILED SETUP
menu. The menu items in the sub-menu are
explained in Table 6-12.
NOTE
Relays 1 through 5 are normally open. Relay
6 is normally closed.
To change a default relay output setting, use the
following procedure:
1. From the RELAY CONFIG menu, select the
RELAY CONFIG menu item .
2. The next screen prompts you to select a relay
or exit. Scroll through the list, select a relay,
and press Enter.
3. At the next prompt, select one of the signal
variables from the scrollable list and press
Enter. Note that no two relays can have the
same trigger signal.
4. The display will then prompt you to configure
another relay or exit the procedure. To
configure another relay, repeat steps 2
through 4. When finished, p re ss Exit to re turn
to the RELAY CONFIG sub-menu. Verify
that the settings reflect the latest changes by
accessing the read-only displays in the submenu.
MENU
ITEM
Relay Config
(method)
Relay 1
(read-only)
Relay 2
(read-only)
Relay 3
(read-only)
Relay 4
(read-only)
Relay-5
(read-only)
Relay-6
(read-only)
Table 6-12. RELAY CONFIG Sub-menu.
POSSIBLE
VARIABLESDESCRIPTION
N/AProvides the relay configuration procedure by
DEFAULT
SETTING
N/A
selecting the variable that triggers each relay.
Off
Displays the currently s elected v ariable f or relay 1.Alarm 1
Sysflt (System Fault)
Span (Span Check)
Zero (Zero Check)
Flt Chk (Filter Check)
Alarm 1
Alarm 2
On
Same as Relay 1Displays the currently selected variable for relay 2.Alarm 2
Same as Relay 1Displays the currently selected variable for relay 3.Fltr Chk
Same as Relay 1Displays the currently selected variable for relay 4.Zero Chk
Same as Relay 1Displays the currently selected variable for relay 5.Span Chk
Same as Relay 1Displays the currently selected variable for relay 6.Sysflt
IB-106-200R
6-20
Page 90
b. ZERO/SPAN CHECK.
The ZERO/SPAN
CHECK sub-menu allows you to periodically
verify the operation of the unit. Zero and span
checks are required by EPA performance
specification 1, section 5.1.5, as repeated below:
“5.1.5 Simulated Zero and Upscale Calibration
System. Each analyzer must include a zero (or no
greater than 10%) opacity and an upscale opacity
value for the purpose of performing periodic
checks of the transmissometer calibration while
on an operating stack or duct. This calibration
system will provide, as a minimum, a system
check of the analyzer internal optics and all
electronic circuitry including the lamp and
photodetector assembly.”
The OPM 2000R uses a sectored Liquid Crystal
Window (LCW) to simulate an intermediate zero
and upscale calibration check value. The
individual sectors are identified in Figure 6-9.
The ZERO/SPAN CHECK sub-menu allows you
to view and configure the zero and span check
parameters. To access this sub-menu, select
ZERO/SPAN CHECK from the DETAILED
SETUP menu. Table 6-13 explains the
ZERO/SPAN menu items.
S3S4
S2
S5
S1
24670058
Figure 6-9. Sectored LCW2
The typical values displayed in Table 6-13
exemplify a zero/span check that is performed
once a day at 2:00 a.m. SPAN VAL will assume
the span check value of 23.45% opacity for six
minutes. The zero check value will then be
output for the next six minutes. If using the
default relay setup described in Table 6-12, relay
5 is energized during the span check, and relay 4
is energized during the zero check. This function
is enabled when the blower motors are running.
Any fault condition will disable this function.
MENU
ITEM
Zero Val
(read-only)
Zero Fltr
(read, write)
Span Val
(read-only)
Span Fltr
(read, write)
Period
(read-only)
Start
(read-only)
Zero Dur
(read-only)
Span Dur
(read-only)
Zero/Span
Config (method)
Table 6-13. ZERO/SPAN CHECK Sub-menu.
POSSIBLE
VARIABLES
TYPICAL
VALUEDESCRIPTION
N/A6.22%Displays the analog output value as a percentage
of opacity during the last zero check.
S0 through S15
(Refer to Table 6-14 for
filter descriptions.)
S14Displays and selects the LCW sectors that
determine the nominal opacity value for zero
check. To change the variable, select ZERO
FLTR and follow the instructions on the screen.
N/A23.45%Displays the analog output value as a percentage
of opacity during the last span check.
S0 through S15
(Refer to Table 6-14 for
filter descriptions.)
S12Displays and selects the LCW sectors that
determine the nominal opacity value for span
check. To change the variable, select SPAN
FLTR and follow the instructions on the screen.
value within the 00:00
to 24:00 hour range
value within the 00:00
to 24:00 hour range
value within the 00:00
to 10:00 minute ran g e
value within the 00:00
to 10:00 minute ran g e
24:00Indicates the length of time between check
cycles (in HH:MM).
02:00Indicates the time of day the check cycle will
begin (in HH:MM).
6.00Indicates the length of the zero check cycle (in
MM:SS).
6:00Indicates the length of the span check cycle (in
MM:SS).
N/AN/AProvides the procedure to set the parameters for
the zero/span check.
DEFAULT
SETTING
N/A
S0
N/A
S0
00:00
00:00
00:00
00:00
N/A
IB-106-200R
6-21
Page 91
The user-required span and zero check values
determine which sectors to select. Table 6-14
shows the on/off status of the sectors with each
filter check value. All values listed in Table 6-14
are nominal. What is important is that the span
check and the zero check values remain
consistent from day to day.
5. The next two screens will prompt you to
enter the span duration in minutes and
seconds, respectively. After typing each
entry in the highlighted area, press Enter.
6. At the next screen prompt, select the zero
filter from the scrollable list and press Enter.
To configure the zero/span check, use the
following procedure:
1. From the ZERO/SPAN CHECK sub-menu,
select ZERO/SPAN CONFIG.
7. In the following screen, select the span filter
from the scrollable list and press Enter.
8. Next, a “Writing zero/span configuration”
message appears as the system updates.
After configuring the zero/span check, the
2. The following two screens will direct you to
enter the zero/span period in hours and
minutes, respectively. After typing each
entry in the highlighted area, press Enter.
3. The next two screens will direct you to enter
the zero/span start time in hours and
minutes, respectively. After typing each
entry in the highlighted area, press Enter.
c.AVERAGES.
system returns to the ZERO/SPAN CHECK
sub-menu. Verify that the settings reflect the
latest changes by viewing the read-only
displays in the sub-menu.
This sub-menu allows you to
configure up to two averages of opacity,
transmittance, optical density, extinction, dust
concentration, or none (no variable specified). For
each variable, a time period is specified and the
4. The following two screens will prompt you
to enter the zero duration in minutes and
seconds, respectively, After typing each
entry in the highlighted area, press Enter.
average is calculated from the number of
measurements taken during that time period. To
access this sub-menu, select AVERAGES from the
DETAILED SETUP menu. Table 6-15 explains
the menu items in the AVERAGES sub-menu.
To configure an average, use the following
procedure:
1. From the AVERAGES sub-menu, select the
average you wan t to configure.
2. The next screen prompts you to configure
either the variable type or the time period of
the selected average. Select VAR.
4. Next, select PER to configure the time period
of the selected average.
5. At the prompt, select one of the time periods
from the scrollable list and press Enter. To
exit the screen without making a selection,
press Esc.
MENU
ITEM
Average 1
Average 2
(read-only)
Avg X
Variable
(read-only)
Avg X
Period
(read-only)
3. At the prompt, select one of the variables
from the scrollable list and press Enter. To
exit the screen without making a selection,
press Esc.
Table 6-15. AVERAGES Sub-menu.
POSSIBLE
VARIABLES
TYPICAL
VALUEDESCRIPTION
N/AN/ADisplays the curren t av erag e v alue. Selectin g
None
Opacity
Opacity
(for Avg 1)
Transmittance
Optical Density
Extinction
Dust Concentration
15 sec
6 min.Displays the time period during which the
1 min.
2 min.
3 min.
4 min.
5 min.
6 min.
10 min.
12 min.
15 min.
20 min.
30 min.
60 min.
6. To configure another average, repeat steps 1
through 5. Once all desired averages are
configured, press Send to send the average
configurations to the intelligent electronics.
each average displays the v ariable type and the
time period of that average.
Displays the type of variable specified for the
average calculation.
variable measuremen ts are collected.
DEFAULT
SETTING
N/A
None
15 sec
IB-106-200R
6-23
Page 93
d. ALARMS.
This sub-menu allows the
configuration of two alarms. Through the relay
outputs, each alarm can indicate when a variable is
not within range. In the default system setup,
alarms 1 and 2 control relay outputs 1 and 2,
respectively. To access this sub-menu, select
ALARMS from the DETAILED SETUP menu.
The nine available menu items are explained in
Table 6-16.
Alarm configuration is flexible. However, the
alarms are normally configured for high values of
opacity or opacity averages. Use the following
procedure to configure the alarm s:
1. From the ALARMS sub-menu, select
ALARM CONFIG.
3. The next screen prompts you to select the
alarm 1 type. Select one of the variables from
the scrollable list and press Enter.
4. At the alarm 1 setpoint prompt, type the new
value in the highlig ht ed f ield an d pres s En ter.
5. At the alarm 1 deadband prompt, type the
new value in the highlighted field and press
Enter.
6. Repeat steps 2 thr ough 5 to configure alarm
2.
2. The next screen prompts you to select the
MENU
ITEM
Alarm
Configuration
(method)
Alarm 1
Alarm 2
(read-only)
Alarm 1 Type
Alarm 2 Type
(read-only)
AL1 Setpoint
AL2 Setpoint
(read-only)
AL1 Deadband
AL2 Deadband
(read-only)
7. After configuring both alarms, the system
Alarm 1 setting. Select one of the variables
from the scrollable list and press Enter.
returns to the ALARMS sub-menu. Verify
that the settings reflect the latest changes.
Table 6-16. ALARMS Sub-menu.
POSSIBLE
VARIABLES
TYPICAL
VALUEDESCRIPTION
N/AN/AProvides the procedure to change the alarm
configurations.
None
OpacityIdentifies the variable to monitor.None
Opacity
Transmittance
Optical Density
Extinction
Dust Concentration
Lx/Lt
Avg 1 through 12
High
Low
None
HighIdentifies which end of the variable range to monitor. For
example, if a high alarm type is selected, the alarm will
activate if the variable exceeds the alarm setpoint. If a
low alarm type is selected, the alarm will activate if the
variable falls below the alarm setpoint. Selecting none
will not configure an alarm.
XXX.XX%100.00%Identifies the high or low limit of the v ariable, dependin g
on the alarm type setting.
X.XX%1.0%Represents the valu e that must be subtracted from the
setpoint before the alarm w ill deactiv ate. For a h ig h
alarm, the variable will activate the alarm if its value
exceeds the alarm setpoint. The alarm will not deactivate
until the variable value drops below the alarm setpoint
minus th e deadban d. The deadban d is des i g n ed t o
prevent a chattering alarm.
DEFAULT
SETTING
N/A
None
0
0
IB-106-200R
6-24
Page 94
Table 6-17. DUST SETUP Sub-menu.
MENU ITEM
Dust C (read-only)
Dust K (read-only)
Date (read-only)
Time (read-only)
Dust Configuration
(method)
e.DUST SETUP.
menu enable the unit for dust concentration
measurements. To access this sub-menu, select
DUST SETUP from the DETAILED SETUP
menu. The five available menu items are
explained in Table 6-17.
After iso-kinetic sampling has occurred and data
has been plotted for the c and k values, c and k
can be entered as constants.
Use the following procedure to enter the values
needed to relate extinction readings to the dust
concentration (DC).
1. From the DUST SETUP sub-menu, select
DUST CONFIGURATION.
TYPICAL
DEFAULT
VALUEDESCRIPTION
0.400Offset constant determined by gravim etric s ampling.0
66.800Gain constant determined by gravimetric sam pling.0
09/30/97Records w h en th e du s t con s tan t s were last changed
N/A
(MM/DD/YY). The system automatically updates this
parameter.
14:32Records when the dust constants were last changed (HH:MM).
N/A
The system automatically updates this parameter.
N/AProvides the procedure to change the dust constants.N/A
The menu items in this sub-
Table 6-18. REVIEW Menu.
SUB-MENUDESCRIPTION
IG-1 S/W Version
(read-only)
Identifies the revision level and
release date of the IG-1 software.
The revision date includes the
year, month, day, hour, and
minute.
Stack S/W Version
(read-only)
Identifies the revision level and
release date of the stack software.
The release date includes the
year, month, day, hour, and
minute.
Serial Numbers
(read-only)
Displays the serial number of the
OPM 2000R system.
SETTING
2. The next screen prompts you to enter the
dust C constant. Type the new value in the
highlighted field and press E nter.
3. The next screen prompts you to enter the
dust K constant. Type the new value in the
highlighted field and press E nte r.
4. A “Writing dust constants” message appe ars
as the system updates. Then, the system
returns to the DUST SETUP sub-menu.
Verify that the constants and date and time
reflect the latest changes.
6-10. REVIEW MENU.
The RE VI EW me nu su mmar iz es
the revision information for both the IG-1 software
and the stack software and displays the OPM 2000R
system serial number. To access this menu, select the
DEVICE SETUP from the online menu and select
REVIEW. The three available sub-menus are
explained in Table 6-18.
6-11. HART COMMUNICATOR MENU TREE FOR
IB-106-200R
6-25
OPM 2000R.
The HART menu tree shown in
Figure 6-10 identifies all of the displays and procedures used to monitor and control the OPM 2000R
system.
The first column in Figure 6-10 represents the online
menu. From that menu, only the DEVICE SETUP
selection subdivides into more specific menu options,
which consist of methods and/or informational
displays. A method is a procedure that you can use to
perform a specific task. If a method is not associated
with a menu option, the option will be a read-only or
read, write (editable) display.
To select a menu or menu option, either press the
right arrow action key or use the alphanumeric
keypad and press the number shown on the display
that corresponds to the menu option. For further
information about a specific menu option, refer to
paragraphs 6-6 through 6-10.
Page 95
FLD DEVICE
VOLTS
Vstack
Vlamp
Vamb
Vdark
STACK
TEMPERATURE
PV OUTPUT
VARS
Vad590
Temp
PV is
PV value
% rnge
PV AO
DEVICE SETUP
PV
SV
TV
MODE
PROCESS
VARIABLES
OUTPUT
VARIABLES
VARIABLE
MAPPING
VARIABLE
RE-MAP
STATUS
SV OUTPUT
VARS
TV OUTPUT
VARS
PV is
TV is
SV is
Variable re-map
method
STATUS
GROUP 0
STATUS
GROUP 1
STATUS
GROUP 2
STATUS
GROUP 3
SV is
SV value
% rnge
SV AO
TV is
TV value
% rnge
TV AO
LON COM Status
AO1 DAC Trim
Blower Failure
Chk Optics Mode
TCVR Cal Status
Dtcr V too High
Lamp Status
Heater Status
PR SW #1 Status
LP Button Status
PR SW #2 Status
Vlamp too High
DIG IN Status
Figure 6-10. HART Menu Tree for the OPM 2000R (Sheet 1 of 3)
AO1
AO2
AO3
AO1
AO2
AO3
Loop Test PV
method
Loop Test SV
method
Loop Test PV
method
29170019
IB-106-200R
6-26
Page 96
(CONTINUED
SHEET )
FROM
1
(CONTINUED
SHEET )
FROM
1
DEVICE SETUP
PV
SV
TV
MODE
BASIC SETUP
CHECK OPTICS
FLTR CHK
SETUP CLOCK
RANGES
VALUES
LX/LT
DEVICE INFO
Check Optics
method
FILTER CHECK
FLTR CHK
VALUES
ERASE FLTR
VALUES
Date
Time
CLOCK SETUP
SELECT PV
RANGE
SELECT SV
RANGE
SELECT TV
RANGE
Lx/Lt
LX/LT SETUP
Dev id
Descriptor
Ta g
Message
Filter Check
method
Fltr Chk Values
method
Erase Fltr Values
method
Clock Setup
method
URV
LRV
URV
LRV
URV
LRV
Lx/Lt Setup
method
URV
method
URV
method
URV
method
RELAY CONFIG
Relay 1
Relay 2
Relay 3
Relay 4
Relay 5
Relay 6
zero val
zero fltr
span val
span fltr
period
start
zero dur
span dur
ZERO/SPAN
CONFIG
DETAILED
SETUP
(CONTINUED ON
SHEET )3
RELAY
CONFIG
ZERO/SPAN
CHECK
(CONTINUED ON
SHEET )3
Figure 6-10. HART Menu Tree for the OPM 2000R (Sheet 2 of 3)
Zero/Span Config
method
24670002
IB-106-200R
6-27
Page 97
(CONTINUED
SHEET )
FROM
2
(CONTINUED
SHEET )
AVERAGES
FROM
2
AVERAGE 1
AVERAGE 2
Avg1Var
Avg 1 Per
Avg2Var
Avg 2 Per
DEVICE SETUP
PV
SV
TV
MODE
DETAILED
SETUP
REVIEW
ALARMS
DUST SETUP
IG-1 S/W
VERSION
STACK S/W
VERSION
SERIAL
NUMBERS
ALARM CONFIG
Alarm 1
Alarm 1 Type
Al1 Setpoint
Al1 Deadband
Alarm 2
Alarm 2 Type
Al2 Setpoint
Al2 Deadband
dust C
dust K
Date
Time
DUST
CONFIGURATION
Rev Num
Rev Year
Rev Month
Rev Day
Rev Hour
Rev Minute
Rev Num
Rev Year
Rev Month
Rev Day
Rev Hour
Rev Minute
System SN
Alarm Config
method
Dust Configuration
method
24670003
Figure 6-10. HART Menu Tree for the OPM 2000R (Sheet 3 of 3)
IB-106-200R
6-28
Page 98
SECTION VII. TROUBLESHOOTING
Install all protective equipment covers
and safety ground leads after
troubleshooting. Failure to replace covers
and ground leads could result in serious
injury or death.
7-1.GENERAL.
This section covers the system mode
fault indicators generated from system selfdiagnostics and provides a general troubleshooting
chart and simple test procedures to correct possible
fault conditions.
7-2.SYSTEM MODE INDICATORS.
2000R Opacity/ Dust Density Transmitter has built-in
system diagnostics features that indicate fault
conditions. These indications appear in the MODE line
of the HART communicator online menu. Normal
opacity measurement functions cannot proceed when a
system status alarm is indicated. The following modes
indicate a fault condition.
a. CALF.
This fault occurs if the last calibration
failed for any of the following voltage conditions:
The OPM
b. COMF.
This fault indicates a communication
failure caused by bad connections, faulty stack
LON board microprocessor, or corrupt stack
LON board EEPROM.
c.SYSFLT.
failure (V
This fault occurs if there is a lamp
LAMP
- V
< 1.0 VDC), blower
DARK
failure, the detector voltage is too high (V
V
> 4.75 V), or the lamp voltage is too high.
STACK
d. CALF&SYSFLT.
This fault indicates that both
a CALF and SYSFLT have occurred
independently of each other.
7-3.DIAGNOSTICS.
The OPM 2000R has a selfdiagnostic feature to aid in troubleshooting. Before
troubleshooting, access the STATUS sub-menu of the
DIAG/SERVICE menu to find up-to-date, ON/OFF
indications of system status and fault conditions that
will help direct your troubleshooting efforts. Refer to
Table 7-1 for explanations of these indicators.