• Failure to follow these installation guidelines could result in serious injury
or death.
• Installation and servicing instructions are for use by qualified personnel
only. Do not perform any servicing other than that contained in the
operating instructions, unless qualified.
• Potential electrostatic charging hazard: Rosemount Magnetic flow
meters ordered with non-standard paint options or non-metallic labels
may be subject to electrostatic discharge. To avoid electrostatic charge
build-up, do not rub the flow meter with a dry cloth or clean with
solvents.
• Verify that the operating environment of the sensor and transmitter is
consistent with the appropriate Agency Approval.
• If installed in an explosive atmosphere, verify that the device certification
and installation techniques are suitable for that particular environment.
• To prevent ignition of flammable or combustible atmosphere,
disconnect power before servicing circuits.
• Explosion hazard: Do not disconnect equipment when a flammable or
combustible atmosphere is present.
• Follow national, local, and plant standards to properly earth ground the
transmitter and sensor. The earth ground must be separate from the
process reference ground.
• Shock hazard: Shut off power before servicing. Do not operate without
power compartment cover.
2Rosemount™ MS Slurry Magnetic Flow Meter Sensor
Page 3
November 2019Quick Install Guide
CAUTION
• The sensor liner is vulnerable to handling damage. Liner damage can
render the sensor useless. Failure to observe these instructions could
result in severe damage to the sensor lining and possible sensor
replacement.
• To avoid possible damage to the sensor liner ends:
— Do not use metallic or spiral-wound gaskets. If spiral wound or
metallic gaskets are required for the application, lining protectors
must be used.
— If frequent removal is anticipated, attach short spool pieces to the
sensor ends.
— Tighten bolts in the proper sequence to the specified torque limits.
Correct flange bolt tightening is crucial for proper sensor operation
and life.
• In cases where high voltage/high current are present near the meter
installation, ensure proper protection methods are followed to prevent
stray voltage/current from passing through the meter. Failure to
adequately protect the meter could result in damage to the transmitter
and lead to meter failure.
• Completely remove all electrical connections from both sensor and
transmitter prior to welding on the pipe. For maximum protection of the
sensor, consider removing it from the pipeline.
Quick Install Guide3
Page 4
Quick Install GuideNovember 2019
1.1Handling and Lifting Safety
CAUTION
To reduce the risk of personal injury or damage to equipment, follow all
lifting and handling instructions.
• Handle all parts carefully to prevent damage. Whenever possible,
transport the system to the installation site in the original shipping
container.
• PTFE-lined sensors are shipped with end covers that protect it from both
mechanical damage and normal unrestrained distortion. Remove the
end covers just before installation.
• Keep the shipping plugs in the conduit ports until you are ready to
connect and seal them. Appropriate care should be taken to prevent
water ingress.
• The sensor should be supported by the pipeline. Pipe supports are
recommended on both the inlet and outlet sides of the sensor pipeline.
There should be no additional support attached to the sensor.
• Use proper PPE (Personal Protection Equipment) including safety glasses
and steel toed shoes.
• Do not lift the meter by holding the electronics housing or junction box.
• The sensor liner is vulnerable to handling damage. Never place anything
through the sensor for the purpose of lifting or gaining leverage. Liner
damage can render the sensor useless.
• Do not drop the device from any height.
4Rosemount™ MS Slurry Magnetic Flow Meter Sensor
Page 5
November 2019Quick Install Guide
1.1.1Lifting lugs
CAUTION
If provided, use the lifting lugs on each flange to handle the flow meter when
it is transported and lowered into place at the installation site. If lifting lugs
are not provided, the flow meter must be supported with a lifting sling on
each side of the housing.
• Standard pressure 3-in. through 36-in. flanged magnetic flowmeters
come with lifting lugs.
• High pressure (above 600#) 1-in. through 24-in. flanged magnetic flow
meters come with lifting lugs.
Figure 1-1: Example lifting without and with lifting lugs
A. Without lifting lugs
B. With lifting lugs
Quick Install Guide5
Page 6
Quick Install GuideNovember 2019
2Introduction
This document provides basic installation guidelines for the Rosemount MS
Slurry Magnetic Flow Meter sensor.
• For transmitter installation instructions, refer to the 8782 transmitter
quick start guide, document number 00825-01xx-8782, where "xx" in the
second segment of the document number indicates the language. See
Table 2-1.
• For additional installation information, configuration, maintenance, and
troubleshooting, refer to the appropriate product reference manual.
Table 2-1: Document language codes
CodeLanguage
00English
02Italian
03French
05German
06Chinese (Simplified)
07Russian
09Spanish
22Portuguese (Brazillian)
All user documentation can be found at www.emerson.com. For more
contact information see Emerson Flow customer service.
2.1
6Rosemount™ MS Slurry Magnetic Flow Meter Sensor
Return policy
Emerson procedures must be followed when returning equipment. These
procedures ensure legal compliance with government transportation
agencies and help provide a safe working environment for Emerson
employees. Failure to follow Emerson procedures will result in your
equipment being refused delivery.
Page 7
November 2019Quick Install Guide
2.2Emerson Flow customer service
Email:
• Worldwide: flow.support@emerson.com
• Asia-Pacific: APflow.support@emerson.com
Telephone:
North and South AmericaEurope and Middle EastAsia Pacific
United States 800 522 6277 U.K.0870 240
Canada+1 303 527
5200
Mexico+41 (0) 41
7686 111
Argentina+54 11 4837
7000
Brazil+55 15 3413
8000
Venezuela+58 26 1731
3446
The
Netherlands
France0800 917 901 India800 440 1468
Germany0800 182
Italy8008 77334China+86 21 2892
Central &
Eastern
Russia/CIS+7 495 995
Egypt0800 000
Oman800 70101Thailand001 800 441
Qatar431 0044Malaysia800 814 008
Kuwait663 299 01
South Africa800 991 390
Saudi Arabia800 844 9564
UAE800 0444
1978
+31 (0) 704
136 666
5347
+41 (0) 41
7686 111
9559
0015
0684
Australia800 158 727
New Zealand099 128 804
Pakistan888 550 2682
9000
Japan+81 3 5769
6803
South Korea+82 2 3438
4600
Singapore+65 6 777
8211
6426
Quick Install Guide7
Page 8
Quick Install GuideNovember 2019
3Location and Position
3.1Environmental considerations
To ensure maximum transmitter life, avoid extreme temperatures and
excessive vibration. Typical problem areas include the following:
• Tropical/desert installations in direct sunlight
• Outdoor installations in arctic climates
3.2Upstream and downstream piping
To ensure specified accuracy over widely varying process conditions, it is
recommended to install the sensor with a minimum of five straight pipe
diameters upstream and two pipe diameters downstream from the
electrode plane.
Figure 3-1: Upstream and downstream straight pipe diameters
3.3
A
C
A. Five pipe diameters (upstream)
B. Two pipe diameters (downstream)
C. Flow direction
Installations with reduced upstream and downstream straight runs are
possible. In reduced straight run installations, the meter may not meet
accuracy specifications. Reported flow rates will still be highly repeatable.
B
Flow direction
The sensor should be mounted so that the arrow points in the direction of
flow.
8Rosemount™ MS Slurry Magnetic Flow Meter Sensor
Page 9
November 2019Quick Install Guide
Figure 3-2: Flow direction arrow
Quick Install Guide9
Page 10
Quick Install GuideNovember 2019
3.4Sensor piping location and orientation
The sensor should be installed in a location that ensures it remains full
during operation. Depending on where it is installed, orientation must also
be considered.
• Vertical installation with upward process fluid flow keeps the cross-
sectional area full, regardless of flow rate.
• Horizontal installation should be restricted to low piping sections that
are normally full.
Figure 3-3: Sensor orientation
A. Flow direction
10Rosemount™ MS Slurry Magnetic Flow Meter Sensor
Page 11
November 2019Quick Install Guide
3.5Electrode orientation
The electrodes in the sensor are properly oriented when the two
measurement electrodes are in the 3 and 9 o’clock positions or within 45
degrees from the horizontal, as shown on the left side of Figure 3-4. Avoid
any mounting orientation that positions the top of the sensor at 90 degrees
from the vertical position as shown on the right of Figure 3-4.
Figure 3-4: Electrode orientation
A
B
A. Correct orientation
B. Incorrect orientation
The sensor may require a specific orientation to comply with Hazardous Area
T-code rating. Refer to the appropriate reference manual for any potential
restrictions.
Quick Install Guide11
Page 12
Quick Install GuideNovember 2019
4Sensor Installation
4.1Flanged sensors
Gaskets
The sensor requires a gasket at each process connection. The gasket
material must be compatible with the process fluid and operating
conditions. Gaskets are required on each side of a grounding ring (see Figure
4-1). All other applications (including sensors with lining protectors or a
grounding electrode) require only one gasket on each process connection.
Note
Metallic or spiral-wound gaskets should not be used as they will damage the
liner face of the sensor. If spiral wound or metallic gaskets are required for
the application, lining protectors must be used.
Figure 4-1: Gasket placement for flanged sensors
B
A
A. Grounding ring and gasket (optional)
B. Customer-supplied gasket
12Rosemount™ MS Slurry Magnetic Flow Meter Sensor
Page 13
November 2019Quick Install Guide
Bolts
Note
Do not bolt one side at a time. Tighten both sides simultaneously. Example:
1. Snug upstream
2. Snug downstream
3. Tighten upstream
4. Tighten downstream
Do not snug and tighten the upstream side and then snug and tighten the
downstream side. Failure to alternate between the upstream and
downstream flanges when tightening bolts may result in liner damage.
Suggested torque values by sensor line size and liner type are listed in Table
4-2 for ASME B16.5 flanges and Table 4-3 or Table 4-4 for EN flanges. Consult
the factory if the flange rating of the sensor is not listed. Tighten flange bolts
on the upstream side of the sensor in the incremental sequence shown in
Figure 4-2 to 20% of the suggested torque values. Repeat the process on the
downstream side of the sensor. For sensors with greater or fewer flange
bolts, tighten the bolts in a similar crosswise sequence. Repeat this entire
tightening sequence at 40%, 60%, 80%, and 100% of the suggested torque
values.
If leakage occurs at the suggested torque values, the bolts can be tightened
in additional 10% increments until the joint stops leaking, or until the
measured torque value reaches the maximum torque value of the bolts.
Practical consideration for the integrity of the liner often leads to distinct
torque values to stop leakage due to the unique combinations of flanges,
bolts, gaskets, and sensor liner material.
Check for leaks at the flanges after tightening the bolts. Failure to use the
correct tightening methods can result in severe damage. While under
pressure, sensor materials may deform over time and require a second
tightening 24 hours after the initial installation.
Figure 4-2: Flange bolt torquing sequence
8
1
4
6
2
Quick Install Guide13
5
3
7
Page 14
Quick Install GuideNovember 2019
Prior to installation, identify the lining material of the flow sensor to ensure
the suggested torque values are applied.
Table 4-3: Suggested flange bolt torque values for Rosemount sensors with
fluoropolymer liners (EN 1092-1)
Size
Line sizeFluoropolymer liners (in Newton-meters)
code
0303 inch (80 mm)N/AN/AN/A50
0404 inch (100 mm)N/A50N/A70
14Rosemount™ MS Slurry Magnetic Flow Meter Sensor
PN 10PN 16PN 25PN 40
Page 15
November 2019Quick Install Guide
Table 4-3: Suggested flange bolt torque values for Rosemount sensors with
fluoropolymer liners (EN 1092-1) (continued)
Size
Line sizeFluoropolymer liners (in Newton-meters)
code
0606 inch (150mm)N/A90N/A130
0808 inch (200 mm)13090130170
10010 inch (250 mm)100130190250
12012 inch (300 mm)120170190270
14014 inch (350 mm)160220320410
16016 inch (400 mm)220280410610
18018 inch (450 mm)190340330420
20020 inch (500 mm)230380440520
24024 inch (600 mm)290570590850
PN 10PN 16PN 25PN 40
Table 4-4: Suggested flange bolt torque values for Rosemount MS sensors with
non-fluoropolymer liners (EN 1092-1)
Size
Line sizeNon-fluoropolymer liners (in Newton-meters)
code
0303 inch (80 mm)N/AN/AN/A30
0404 inch (100 mm)N/A40N/A50
0606 inch (150mm)N/A60N/A90
0808 inch (200 mm)906090110
10010 inch (250 mm)7080130170
12012 inch (300 mm)80110130180
14014 inch (350 mm)110150210288
16016 inch (400 mm)150190280410
18018 inch (450 mm)130230220280
20020 inch (500 mm)150260300350
24024 inch (600 mm)200380390560
PN 10PN 16PN 25PN 40
Quick Install Guide15
Page 16
Quick Install GuideNovember 2019
5Process reference connection
The figures shown in this section illustrate best practice installations for
process reference connections only. For installations in conductive, unlined
pipe it may be acceptable to use one ground ring or one lining protector to
establish a process reference connection. Earth safety ground is also
required as part of this installation, but is not shown in the figures. Follow
national, local, and plant electrical codes for safety ground.
Use Table 5-1 to determine which process reference option to follow for
proper installation.
Table 5-1: Process reference options
Type of pipeGrounding
Conductive
unlined pipe
Conductive
lined pipe
Nonconductive
pipe
straps
See Figure 5-1See Figure 5-2See Figure 5-4 See Figure 5-2
Insufficient
grounding
Insufficient
grounding
Grounding
rings
See Figure 5-2 See Figure 5-1See Figure 5-2
See Figure 5-3 Not
Reference
electrode
recommended
Lining
protectors
See Figure 5-3
Note
For line sizes 10-inch and larger the ground strap may come attached to the
sensor body near the flange. See Figure 5-5.
Figure 5-1: Grounding straps in conductive unlined pipe or reference
electrode in lined pipe
16Rosemount™ MS Slurry Magnetic Flow Meter Sensor
Page 17
November 2019Quick Install Guide
Figure 5-2: Grounding with grounding rings or lining protectors in
conductive pipe
A. Grounding rings or lining protectors
Figure 5-3: Grounding with grounding rings or lining protectors in nonconductive pipe
A. Grounding rings or lining protectors
Quick Install Guide17
Page 18
Quick Install GuideNovember 2019
Figure 5-4: Grounding with reference electrode in conductive unlined
pipe
Figure 5-5: Grounding for line sizes 10-in. and larger
18Rosemount™ MS Slurry Magnetic Flow Meter Sensor
Page 19
November 2019Quick Install Guide
6Wiring sensor to transmitter
Figure 6-1: Wiring using component cable
Quick Install Guide19
Page 20
Quick Install GuideNovember 2019
7Product Certifications
For detailed approval certification information and installation drawings,
please see the appropriate document listed below:
• Document number 00825-MA00-0009: Rosemount 8782 and MS
Approval Document - Class Division
• Document number 00825-MA00-0010: Rosemount 8782 and MS
Approval Document - IECEx and ATEX
• Document number 00825-MA00-0011: Rosemount 8782 and MS
Approval Document - North America Zone
• Document number 00825-MA00-0012: Rosemount 8785 Approval
Document
• Document number 00825-MA00-0013: Rosemount 8782 and MS
Approval Document - EAC EX
20Rosemount™ MS Slurry Magnetic Flow Meter Sensor
Page 21
November 2019Quick Install Guide
Quick Install Guide21
Page 22
Quick Install GuideNovember 2019
22Rosemount™ MS Slurry Magnetic Flow Meter Sensor
Page 23
November 2019Quick Install Guide
Quick Install Guide23
Page 24
*00825-0100-00MS*
00825-0100-00MS, Rev. AA
Quick Install Guide
November 2019
Emerson Automation Solutions USA
7070 Winchester Circle
Boulder, Colorado USA 80301
T +1 303-527-5200
T +1 800-522-6277
F +1 303-530-8459
www.emerson.com
Emerson Automation Solutions Europe
Neonstraat 1
6718 WX Ede
The Netherlands
T +31 (0) 70 413 6666
F +31 (0) 318 495 556
The Emerson logo is a trademark and service mark of Emerson Electric Co.
Rosemount, 8600, 8700, 8800 marks are marks of one of the Emerson
Automation Solutions family of companies. All other marks are property
of their respective owners.
Emerson Automation Solutions Asia
1 Pandan Crescent
Singapore 128461
Republic of Singapore
T +65 6363-7766
F +65 6770-8003
Emerson Automation Solutions United
Kingdom
Emerson Process Management Limited
Horsfield Way
Bredbury Industrial Estate
Stockport SK6 2SU U.K.
T +44 0870 240 1978
F +44 0800 966 181
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.