Rosemount MS Operating Manual

Page 1
Quick Install Guide
00825-0100-00MS, Rev AA
November 2019
Rosemount™ MS Slurry Magnetic Flow Meter Sensor
Page 2
Quick Install Guide November 2019

1 Safety

Failure to follow these installation guidelines could result in serious injury
or death.
Installation and servicing instructions are for use by qualified personnel
only. Do not perform any servicing other than that contained in the operating instructions, unless qualified.
Potential electrostatic charging hazard: Rosemount Magnetic flow
meters ordered with non-standard paint options or non-metallic labels may be subject to electrostatic discharge. To avoid electrostatic charge build-up, do not rub the flow meter with a dry cloth or clean with solvents.
Verify that the operating environment of the sensor and transmitter is
consistent with the appropriate Agency Approval.
If installed in an explosive atmosphere, verify that the device certification
and installation techniques are suitable for that particular environment.
To prevent ignition of flammable or combustible atmosphere,
disconnect power before servicing circuits.
Explosion hazard: Do not disconnect equipment when a flammable or
combustible atmosphere is present.
Follow national, local, and plant standards to properly earth ground the
transmitter and sensor. The earth ground must be separate from the process reference ground.
Shock hazard: Shut off power before servicing. Do not operate without
power compartment cover.
2 Rosemount™ MS Slurry Magnetic Flow Meter Sensor
Page 3
November 2019 Quick Install Guide
CAUTION
The sensor liner is vulnerable to handling damage. Liner damage can
render the sensor useless. Failure to observe these instructions could result in severe damage to the sensor lining and possible sensor replacement.
To avoid possible damage to the sensor liner ends:Do not use metallic or spiral-wound gaskets. If spiral wound or
metallic gaskets are required for the application, lining protectors must be used.
If frequent removal is anticipated, attach short spool pieces to the
sensor ends.
Tighten bolts in the proper sequence to the specified torque limits.
Correct flange bolt tightening is crucial for proper sensor operation and life.
In cases where high voltage/high current are present near the meter
installation, ensure proper protection methods are followed to prevent stray voltage/current from passing through the meter. Failure to adequately protect the meter could result in damage to the transmitter and lead to meter failure.
Completely remove all electrical connections from both sensor and
transmitter prior to welding on the pipe. For maximum protection of the sensor, consider removing it from the pipeline.
Quick Install Guide 3
Page 4
Quick Install Guide November 2019

1.1 Handling and Lifting Safety

CAUTION
To reduce the risk of personal injury or damage to equipment, follow all lifting and handling instructions.
Handle all parts carefully to prevent damage. Whenever possible,
transport the system to the installation site in the original shipping container.
PTFE-lined sensors are shipped with end covers that protect it from both
mechanical damage and normal unrestrained distortion. Remove the end covers just before installation.
Keep the shipping plugs in the conduit ports until you are ready to
connect and seal them. Appropriate care should be taken to prevent water ingress.
The sensor should be supported by the pipeline. Pipe supports are
recommended on both the inlet and outlet sides of the sensor pipeline. There should be no additional support attached to the sensor.
Use proper PPE (Personal Protection Equipment) including safety glasses
and steel toed shoes.
Do not lift the meter by holding the electronics housing or junction box.
The sensor liner is vulnerable to handling damage. Never place anything
through the sensor for the purpose of lifting or gaining leverage. Liner damage can render the sensor useless.
Do not drop the device from any height.
4 Rosemount™ MS Slurry Magnetic Flow Meter Sensor
Page 5
November 2019 Quick Install Guide

1.1.1 Lifting lugs

CAUTION
If provided, use the lifting lugs on each flange to handle the flow meter when it is transported and lowered into place at the installation site. If lifting lugs are not provided, the flow meter must be supported with a lifting sling on each side of the housing.
Standard pressure 3-in. through 36-in. flanged magnetic flowmeters
come with lifting lugs.
High pressure (above 600#) 1-in. through 24-in. flanged magnetic flow
meters come with lifting lugs.
Figure 1-1: Example lifting without and with lifting lugs
A. Without lifting lugs B. With lifting lugs
Quick Install Guide 5
Page 6
Quick Install Guide November 2019

2 Introduction

This document provides basic installation guidelines for the Rosemount MS Slurry Magnetic Flow Meter sensor.
For transmitter installation instructions, refer to the 8782 transmitter
quick start guide, document number 00825-01xx-8782, where "xx" in the second segment of the document number indicates the language. See
Table 2-1.
For additional installation information, configuration, maintenance, and
troubleshooting, refer to the appropriate product reference manual.
Table 2-1: Document language codes
Code Language
00 English
02 Italian
03 French
05 German
06 Chinese (Simplified)
07 Russian
09 Spanish
22 Portuguese (Brazillian)
All user documentation can be found at www.emerson.com. For more contact information see Emerson Flow customer service.
2.1
6 Rosemount™ MS Slurry Magnetic Flow Meter Sensor

Return policy

Emerson procedures must be followed when returning equipment. These procedures ensure legal compliance with government transportation agencies and help provide a safe working environment for Emerson employees. Failure to follow Emerson procedures will result in your equipment being refused delivery.
Page 7
November 2019 Quick Install Guide

2.2 Emerson Flow customer service

Email:
Worldwide: flow.support@emerson.com
Asia-Pacific: APflow.support@emerson.com
Telephone:
North and South America Europe and Middle East Asia Pacific
United States 800 522 6277 U.K. 0870 240
Canada +1 303 527
5200
Mexico +41 (0) 41
7686 111
Argentina +54 11 4837
7000
Brazil +55 15 3413
8000
Venezuela +58 26 1731
3446
The Netherlands
France 0800 917 901 India 800 440 1468
Germany 0800 182
Italy 8008 77334 China +86 21 2892
Central & Eastern
Russia/CIS +7 495 995
Egypt 0800 000
Oman 800 70101 Thailand 001 800 441
Qatar 431 0044 Malaysia 800 814 008
Kuwait 663 299 01
South Africa 800 991 390
Saudi Arabia 800 844 9564
UAE 800 0444
1978
+31 (0) 704 136 666
5347
+41 (0) 41 7686 111
9559
0015
0684
Australia 800 158 727
New Zealand 099 128 804
Pakistan 888 550 2682
9000
Japan +81 3 5769
6803
South Korea +82 2 3438
4600
Singapore +65 6 777
8211
6426
Quick Install Guide 7
Page 8
Quick Install Guide November 2019

3 Location and Position

3.1 Environmental considerations

To ensure maximum transmitter life, avoid extreme temperatures and excessive vibration. Typical problem areas include the following:
Tropical/desert installations in direct sunlight
Outdoor installations in arctic climates

3.2 Upstream and downstream piping

To ensure specified accuracy over widely varying process conditions, it is recommended to install the sensor with a minimum of five straight pipe diameters upstream and two pipe diameters downstream from the electrode plane.
Figure 3-1: Upstream and downstream straight pipe diameters
3.3
A
C
A. Five pipe diameters (upstream) B. Two pipe diameters (downstream) C. Flow direction
Installations with reduced upstream and downstream straight runs are possible. In reduced straight run installations, the meter may not meet accuracy specifications. Reported flow rates will still be highly repeatable.
B

Flow direction

The sensor should be mounted so that the arrow points in the direction of flow.
8 Rosemount™ MS Slurry Magnetic Flow Meter Sensor
Page 9
November 2019 Quick Install Guide
Figure 3-2: Flow direction arrow
Quick Install Guide 9
Page 10
Quick Install Guide November 2019

3.4 Sensor piping location and orientation

The sensor should be installed in a location that ensures it remains full during operation. Depending on where it is installed, orientation must also be considered.
Vertical installation with upward process fluid flow keeps the cross-
sectional area full, regardless of flow rate.
Horizontal installation should be restricted to low piping sections that
are normally full.
Figure 3-3: Sensor orientation
A. Flow direction
10 Rosemount™ MS Slurry Magnetic Flow Meter Sensor
Page 11
November 2019 Quick Install Guide

3.5 Electrode orientation

The electrodes in the sensor are properly oriented when the two measurement electrodes are in the 3 and 9 o’clock positions or within 45 degrees from the horizontal, as shown on the left side of Figure 3-4. Avoid any mounting orientation that positions the top of the sensor at 90 degrees from the vertical position as shown on the right of Figure 3-4.
Figure 3-4: Electrode orientation
A
B
A. Correct orientation B. Incorrect orientation
The sensor may require a specific orientation to comply with Hazardous Area T-code rating. Refer to the appropriate reference manual for any potential restrictions.
Quick Install Guide 11
Page 12
Quick Install Guide November 2019

4 Sensor Installation

4.1 Flanged sensors

Gaskets
The sensor requires a gasket at each process connection. The gasket material must be compatible with the process fluid and operating conditions. Gaskets are required on each side of a grounding ring (see Figure
4-1). All other applications (including sensors with lining protectors or a
grounding electrode) require only one gasket on each process connection.
Note
Metallic or spiral-wound gaskets should not be used as they will damage the liner face of the sensor. If spiral wound or metallic gaskets are required for the application, lining protectors must be used.
Figure 4-1: Gasket placement for flanged sensors
B
A
A. Grounding ring and gasket (optional) B. Customer-supplied gasket
12 Rosemount™ MS Slurry Magnetic Flow Meter Sensor
Page 13
November 2019 Quick Install Guide
Bolts
Note
Do not bolt one side at a time. Tighten both sides simultaneously. Example:
1. Snug upstream
2. Snug downstream
3. Tighten upstream
4. Tighten downstream
Do not snug and tighten the upstream side and then snug and tighten the downstream side. Failure to alternate between the upstream and downstream flanges when tightening bolts may result in liner damage.
Suggested torque values by sensor line size and liner type are listed in Table
4-2 for ASME B16.5 flanges and Table 4-3 or Table 4-4 for EN flanges. Consult
the factory if the flange rating of the sensor is not listed. Tighten flange bolts on the upstream side of the sensor in the incremental sequence shown in
Figure 4-2 to 20% of the suggested torque values. Repeat the process on the
downstream side of the sensor. For sensors with greater or fewer flange bolts, tighten the bolts in a similar crosswise sequence. Repeat this entire tightening sequence at 40%, 60%, 80%, and 100% of the suggested torque values.
If leakage occurs at the suggested torque values, the bolts can be tightened in additional 10% increments until the joint stops leaking, or until the measured torque value reaches the maximum torque value of the bolts. Practical consideration for the integrity of the liner often leads to distinct torque values to stop leakage due to the unique combinations of flanges, bolts, gaskets, and sensor liner material.
Check for leaks at the flanges after tightening the bolts. Failure to use the correct tightening methods can result in severe damage. While under pressure, sensor materials may deform over time and require a second tightening 24 hours after the initial installation.
Figure 4-2: Flange bolt torquing sequence
8
1
4
6
2
Quick Install Guide 13
5
3
7
Page 14
Quick Install Guide November 2019
Prior to installation, identify the lining material of the flow sensor to ensure the suggested torque values are applied.
Table 4-1: Lining material
Fluoropolymer liners Other liners
T - PTFE P - Polyurethane
K - PFA+ N - Neoprene
L - Linatex (Natural Rubber)
D - Adiprene
Table 4-2: Suggested flange bolt torque values for Rosemount (ASME) sensors
Size
Line size Fluoropolymer liners Other liners
code
030 3 inch (80 mm) 34 35 23 23
040 4 inch (100 mm) 26 50 17 32
060 6 inch (150 mm) 45 50 30 37
080 8 inch (200 mm) 60 82 42 55
100 10 inch (250 mm) 55 80 40 70
120 12 inch (300 mm) 65 125 55 105
140 14 inch (350 mm) 85 110 70 95
160 16 inch (400 mm) 85 160 65 140
180 18 inch (450 mm) 120 170 95 150
200 20 inch (500 mm) 110 175 90 150
240 24 inch (600 mm) 165 280 140 250
300 30 inch (750 mm) 195 415 165 375
360 36 inch (900 mm) 280 575 245 525
Class 150 (lbft)
Class 300 (lbft)
Class 150 (lbft)
Class 300 (pound feet)
Table 4-3: Suggested flange bolt torque values for Rosemount sensors with fluoropolymer liners (EN 1092-1)
Size
Line size Fluoropolymer liners (in Newton-meters)
code
030 3 inch (80 mm) N/A N/A N/A 50
040 4 inch (100 mm) N/A 50 N/A 70
14 Rosemount™ MS Slurry Magnetic Flow Meter Sensor
PN 10 PN 16 PN 25 PN 40
Page 15
November 2019 Quick Install Guide
Table 4-3: Suggested flange bolt torque values for Rosemount sensors with fluoropolymer liners (EN 1092-1) (continued)
Size
Line size Fluoropolymer liners (in Newton-meters)
code
060 6 inch (150mm) N/A 90 N/A 130
080 8 inch (200 mm) 130 90 130 170
100 10 inch (250 mm) 100 130 190 250
120 12 inch (300 mm) 120 170 190 270
140 14 inch (350 mm) 160 220 320 410
160 16 inch (400 mm) 220 280 410 610
180 18 inch (450 mm) 190 340 330 420
200 20 inch (500 mm) 230 380 440 520
240 24 inch (600 mm) 290 570 590 850
PN 10 PN 16 PN 25 PN 40
Table 4-4: Suggested flange bolt torque values for Rosemount MS sensors with non-fluoropolymer liners (EN 1092-1)
Size
Line size Non-fluoropolymer liners (in Newton-meters)
code
030 3 inch (80 mm) N/A N/A N/A 30
040 4 inch (100 mm) N/A 40 N/A 50
060 6 inch (150mm) N/A 60 N/A 90
080 8 inch (200 mm) 90 60 90 110
100 10 inch (250 mm) 70 80 130 170
120 12 inch (300 mm) 80 110 130 180
140 14 inch (350 mm) 110 150 210 288
160 16 inch (400 mm) 150 190 280 410
180 18 inch (450 mm) 130 230 220 280
200 20 inch (500 mm) 150 260 300 350
240 24 inch (600 mm) 200 380 390 560
PN 10 PN 16 PN 25 PN 40
Quick Install Guide 15
Page 16
Quick Install Guide November 2019

5 Process reference connection

The figures shown in this section illustrate best practice installations for process reference connections only. For installations in conductive, unlined pipe it may be acceptable to use one ground ring or one lining protector to establish a process reference connection. Earth safety ground is also required as part of this installation, but is not shown in the figures. Follow national, local, and plant electrical codes for safety ground.
Use Table 5-1 to determine which process reference option to follow for proper installation.
Table 5-1: Process reference options
Type of pipe Grounding
Conductive unlined pipe
Conductive lined pipe
Non­conductive pipe
straps
See Figure 5-1 See Figure 5-2 See Figure 5-4 See Figure 5-2
Insufficient grounding
Insufficient grounding
Grounding rings
See Figure 5-2 See Figure 5-1 See Figure 5-2
See Figure 5-3 Not
Reference electrode
recommended
Lining protectors
See Figure 5-3
Note
For line sizes 10-inch and larger the ground strap may come attached to the sensor body near the flange. See Figure 5-5.
Figure 5-1: Grounding straps in conductive unlined pipe or reference electrode in lined pipe
16 Rosemount™ MS Slurry Magnetic Flow Meter Sensor
Page 17
November 2019 Quick Install Guide
Figure 5-2: Grounding with grounding rings or lining protectors in conductive pipe
A. Grounding rings or lining protectors
Figure 5-3: Grounding with grounding rings or lining protectors in non­conductive pipe
A. Grounding rings or lining protectors
Quick Install Guide 17
Page 18
Quick Install Guide November 2019
Figure 5-4: Grounding with reference electrode in conductive unlined pipe
Figure 5-5: Grounding for line sizes 10-in. and larger
18 Rosemount™ MS Slurry Magnetic Flow Meter Sensor
Page 19
November 2019 Quick Install Guide

6 Wiring sensor to transmitter

Figure 6-1: Wiring using component cable
Quick Install Guide 19
Page 20
Quick Install Guide November 2019

7 Product Certifications

For detailed approval certification information and installation drawings, please see the appropriate document listed below:
Document number 00825-MA00-0009: Rosemount 8782 and MS
Approval Document - Class Division
Document number 00825-MA00-0010: Rosemount 8782 and MS
Approval Document - IECEx and ATEX
Document number 00825-MA00-0011: Rosemount 8782 and MS
Approval Document - North America Zone
Document number 00825-MA00-0012: Rosemount 8785 Approval
Document
Document number 00825-MA00-0013: Rosemount 8782 and MS
Approval Document - EAC EX
20 Rosemount™ MS Slurry Magnetic Flow Meter Sensor
Page 21
November 2019 Quick Install Guide
Quick Install Guide 21
Page 22
Quick Install Guide November 2019
22 Rosemount™ MS Slurry Magnetic Flow Meter Sensor
Page 23
November 2019 Quick Install Guide
Quick Install Guide 23
Page 24
*00825-0100-00MS*
00825-0100-00MS, Rev. AA
Quick Install Guide
November 2019
Emerson Automation Solutions USA
7070 Winchester Circle Boulder, Colorado USA 80301 T +1 303-527-5200 T +1 800-522-6277 F +1 303-530-8459
www.emerson.com
Emerson Automation Solutions Europe
Neonstraat 1 6718 WX Ede The Netherlands T +31 (0) 70 413 6666 F +31 (0) 318 495 556
www.micromotion.nl
©
2019 Rosemount, Inc. All rights reserved.
The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount, 8600, 8700, 8800 marks are marks of one of the Emerson Automation Solutions family of companies. All other marks are property of their respective owners.
Emerson Automation Solutions Asia
1 Pandan Crescent Singapore 128461 Republic of Singapore T +65 6363-7766 F +65 6770-8003
Emerson Automation Solutions United Kingdom
Emerson Process Management Limited Horsfield Way Bredbury Industrial Estate Stockport SK6 2SU U.K. T +44 0870 240 1978 F +44 0800 966 181
Loading...