Rosemount Millennium SIR100 IR Combustible Gas Detector Manuals & Guides

MILLENNIUM
Infrared Combustible
Gas Detector
User Manual
Models:
MLP-A-SIR100,
MLP-AD-SIR100 & (all available options)
MLP-AR-SIR100
July 2008
Net Safety Monitoring Inc
IMPORTANT INFORMATION
This manual is for informational purposes only. Although every effort has been made to ensure the correctness of the information, technical inaccuracies may occur and periodic changes may be made without notice. Net Safety Monitoring Inc., assumes no responsibility for any errors contained within this manual.
If the products or procedures are used for purposes other than as described in the manual, without receiving prior confirmation of validity or suitability, Net Safety Monitoring Inc., does not guarantee the results and assumes no obligation or liability.
No part of this manual may be copied, disseminated or distributed without the express written consent of Net Safety Monitoring Inc.
Net Safety Monitoring Inc., products are carefully designed and manufactured from high quality components and can be expected to provide many years of trouble free service. Each product is thoroughly tested, inspected and calibrated prior to shipment. Failures can occur which are beyond the control of the manufacturer. Failures can be minimized by adhering to the operating and maintenance instructions herein. Where the absolute greatest of reliability is required, redundancy should be designed into the system.
Warranty
Net Safety Monitoring Inc., warrants its sensors against defective parts and workmanship for a period of 24 months from date of purchase; other electronic assemblies for 36 months from date of purchase.
No other warranties or liability, expressed or implied, will be honoured by Net Safety Monitoring Inc.
Contact Net Safety Monitoring Inc., or an authorized representative for details.
We welcome your input at Net Safety Monitoring. If you have any comments please contact us at the phone/address below or visit our web site and complete our on-line customer survey: www.net-safety.com.
Contact Information
Net Safety Monitoring Inc. 2721 Hopewell Place NE Calgary, AB Canada T1Y 7J7 Telephone: (403) 219-0688 Fax: (403) 219-0694 www.net-safety.com E-mail: netsafe@net-safety.com
Copyright © 2005
Net Safety Monitoring Inc. Printed in Canada
Net Safety Monitoring Inc
TABLE OF CONTENTS
Important Information
Warranty Contact Information
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
The Product ...................................................................................................... 1
The Sensor ............................................................................................................. 1
The Controller ....................................................................................................... 1
The Manual ........................................................................................................... 1
Step 1 — Plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Locate Controller/Sensor ................................................................................. 2
Figure 1: Locate Sensor/Controller ......................................................................... 2
Figure 2: Dimensional Drawings ............................................................................ 3
Step 2 — Install . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Unpack ............................................................................................................. 3
Figure 3: Components ............................................................................................. 3
External Equipment ............................................................................................... 3
Mount .................................................................................................................... 4
Step 3 — Wire . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Field Installation .............................................................................................. 4
Seal ................................................................................................................... 4
Connecting Wires .................................................................................................. 4
Board Assembly .................................................................................................... 5
Figure 4: Millennium Modular Boards ................................................................... 5
Figure 5: Wiring—Controller and Sensor ............................................................... 6
Sensor and Controller ...................................................................................... 6
Table 1: Controller/Sensor Terminal Connections ................................................. 6
RS-485 Communication ........................................................................................ 6
Sensor Separation ............................................................................................ 7
Figure 6: Wiring—Sensor Separation ..................................................................... 7
Non-Isolated/Isolated Wiring .......................................................................... 8
Terminal Connection ............................................................................................. 8
Figure 7: Non-isolated Terminal Connection ......................................................... 8
Figure 8: Isolated Terminal Connection ................................................................. 8
Current Output ....................................................................................................... 8
Figure 9: Jumper Positions ...................................................................................... 8
Remote Reset .................................................................................................... 9
Figure 10: Remote Reset ........................................................................................9
MODBUS Termination ....................................................................................9
Figure 11: Modbus Termination Jumpers ...............................................................9
Step 4 — Operate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Figure 12: Controller Functionality .......................................................................10
Table 2: Status LEDs, Display Messages and Current Loop ................................11
RTU Registers .....................................................................................................11
Table 3: RTU Status Register (400002) Read Only (binary) ................................ 11
Calibration Button ...............................................................................................11
Magnetic Reed Switch .........................................................................................12
Power Up .............................................................................................................12
Current Loop Measurement (Test Jacks) .............................................................12
Status LED ...........................................................................................................12
The Main Menu ..............................................................................................12
Accessing the Main Menu ...................................................................................12
Main Menu Functionality ....................................................................................12
Step 5 — Calibrate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Calibration Procedure .....................................................................................13
Calibration Procedure ..........................................................................................13
Figure 13: Calibration Procedure ..........................................................................13
Calibration Failure .........................................................................................14
Step 6 — Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Review Relay Settings ....................................................................................14
Set Relay Options ...........................................................................................14
Table 4: Default Relay Settings .............................................................................14
Setting Relay Options ..........................................................................................15
Select Gas Curve ............................................................................................15
Select Display Language ................................................................................15
Modbus Options .............................................................................................16
Node Address ......................................................................................................16
Baud Rate ............................................................................................................16
Alarms ............................................................................................................16
Sensor Fault .........................................................................................................16
Gas Present ..........................................................................................................16
Sensor Life ...........................................................................................................16
Reset ...............................................................................................................17
Manual Reset .......................................................................................................17
Remote Reset .................................................................................................17
Net Safety Monitoring Inc
Outputs ........................................................................................................... 17
Relay .................................................................................................................... 17
Modbus ................................................................................................................ 17
Current ................................................................................................................. 17
Step 7 — Maintain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Periodic Response Check ............................................................................... 18
Troubleshoot . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
How to Return Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Spare Parts/Accessories ................................................................................. 19
Table 5: Part Numbering ....................................................................................... 19
Face Rotation Option ..................................................................................... 19
Figure 14: Non-standard Orientations ................................................................... 19
Rotate PCB Assembly .........................................................................................19
Appendix A: Electrostatic Sensitive Device (ESD) . . . . . . . . . . . .20
Appendix B: Resistance Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Table 6: Wire Resistance In Ohms ........................................................................ 21
Appendix C: Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Net Safety Monitoring Inc.
INTRODUCTION
The Millennium series is Net Safety's latest innovation in a line of continuously evolving industrial gas detectors and sensors. The microcontroller based system provides fast, accurate and continuous monitoring of gases in extreme environments.
THE PRODUCT
The Sensor
Step 1 — PLAN
Step 2 — INSTALL
Step 3 — WIRE
The SIR100 digital infrared sensor employs a simple and effective optical design. There are no mirrors to be fogged, fouled, misaligned or cleaned. The entire optical path is protected from airborne contaminates such as mist, dust and oil and de-fogging heaters are not required.
The Controller
The Millennium Controller has an explosion-proof Housing, rated Class 1, Division 1, Groups B, C, and D for hazardous applications. It was designed for either a 1-man, intrusive calibration or 2-man non-intrusive calibration.
The Controller has convenient user interface functionality to make installation, operation and maintenance easy.
The Manual
The manual has been designed to make installation of the Millennium product easy. To ensure proper installation, follow the steps outlined in the following pages. If you encounter problems during operation, consult the troubleshooting section or contact your sales representative.
Step 4 — OPERATE
Step 5 — CALIBRATE
Step 6 — MONITOR
Step 7 — MAINTAIN
MLP-A-AR-D-SIR100 1
Net Safety Monitoring Inc
STEP 1 — PLAN
LOCATE CONTROLLER/SENSOR
Prior to the installation process, a location plan for placing the Controller and Sensor should be developed. Although there are no absolute rules for determining the quantity and location of a sensor or controller, the following points should be considered when planning the installation.
• Locate the Controller where it will be accessible and visible.
• Carefully locate Sensor in an area where gases may potentially accumulate.
• Use redundant systems to enhance protection and reliability.
• Light gases tend to rise; heavy gases tend to accumulate in low areas.
• Consider air movement patterns within the facility.
• Consider the construction of the facility (such as trenches where heavy gases may accumulate or peaks where light gases may accumulate).
• Seek advice from experts knowledgeable about the primary gas to be detected.
• Use common sense and refer to various regulatory publications that discuss general guidelines for your industry.
The two most common installation options are as follows.
WARNING:
To compensate for distance when remotely calibrating (sensor wired for separation), decrease the tubing diameter or increase the calibration gas flow rate between gas canister and sensor. Always confirm calibration by applying gas at the sensor (not separated).
Figure 1: Locate Sensor/Controller
Conduit to Controller
Controller
Option 1
Sensor is located lower to the ground to detect heavy gases
The Sensor is attached directly to the Controller. A Calibration Cover is slipped onto the bottom of the Sensor and the calibration gas is attached to the side calibration fitting.
Side Calibration Fitting
Tubing for Calibration Gas
SIR100
Sensor
See "Wiring—Controller and Sensor" on page 6 for detailed instructions.
Option 2
Calibration Cover
Locate Sensor separate from Controller using a Junction Box. The Controller is located near eye-level. Conduit is run from the Controller to the Sensor. A Junction Box is used to connect the conduit from the Controller to the Sensor. A Calibration Cover is slipped onto the Sensor to concentrate the gas. Tubing can be run from the side calibration fitting on the Sensor to a
TIP:
The Calibration Cover (CC-SIR100-SEP) prevents air circulation affecting the Calibration process and concentrates the gas during calibration.
convenient location accessible for calibration gas to be applied.
See "Sensor Separation" on page 7 for detailed instructions.
MLP-A-AR-D-SIR100 2
Net Safety Monitoring Inc.
Figure 2: Dimensional Drawings
5.31"
(134.9 mm)
Controller and SIR Sensor
4.06”
(103.1 mm)
2.60”
(66.0 mm)
5.60”
(142.2 mm)
4.82”
(122.4 mm)
5.68”
(144.3 mm)
2.89”
(73.4 mm)
13.11”
(333.0 mm)
STEP 2 — INSTALL
UNPACK
Carefully remove all components from the packaging. Check components against the enclosed packing list and inspect all components for obvious damage such as broken or loose parts.
If you find any components missing or damaged, notify the representative or Net Safety Monitoring immediately.
Figure 3: Components
Controller Housing
Millennium Faceplate
Housing Cover
Ribbon connecting faceplate/controller
SIR100 Sensor
Multi-purpose Junction box and SIR Sensor
7.46”
(189.4 mm)
12.62”
(320.5 mm)
External Equipment
It is necessary that reliable monitoring and indicating devices or systems be connected to the detector. These devices must be designed to produce clear visual and audible danger signals when high signal levels occur.
Note: A Certified Junction Box is used when Sensor and Controller are separated. Refer to MAN-0081 for terminal designation.
MLP-A-AR-D-SIR100 3
Net Safety Monitoring Inc
Mount
The Controller should be mounted near eye-level and be easily accessible for calibration and maintenance purposes. The Sensor should be placed where gas is likely to accumulate.
Ensure all devices are securely mounted, taking into consideration all requirements.
Use the Face Rotation Option to mount the Millennium Controller at a different orientation (refer to "Face Rotation Option" on page 20 for detailed instructions).
STEP 3 — WIRE
FIELD INSTALLATION
WARNING: Wiring codes and regulations may vary. Wiring must comply
with applicable regulations relating to the installation of electrical equipment in a hazardous area and is the responsibility of the installer. If in doubt, consult a qualified official before wiring the system.
• If the 4-20 mA signal is not used, connect a jumper between the 4-20 terminal and the Common terminal.
• The use of shielded cable is highly recommended for signal, input, output and power wires to protect against interference caused by extraneous electrical or electromagnetic 'noise'.
• In applications where the wiring cable is installed in conduit, the conduit must not be used for wiring to other electrical equipment.
• The maximum distance between the Sensor and Controller is limited by the resistance of the connecting wiring, which is a function of the gauge of the wire being used.
• When developing a RS-485 chain of devices, the last device in the chain requires end of line termination.
• RS-485 connection 2-wire, multipoint serial line.
SEAL
• Water-proof and explosion-proof conduit seals are recommended to prevent water accumulation within the enclosure.
• Seals should be located as close to the device as possible and not more than 18 inches (46 cm) away.
• Explosion-proof installations may require an additional seal where conduit enters a non-hazardous area. Ensure conformity with local wiring codes.
• When pouring a seal, use a fibre dam to assure proper formation of the seal. Seals should never be poured at temperatures below freezing.
• The jacket and shielding of the cable should be stripped back to permit the seal to form around the individual wires. This will prevent air, gas and water leakage through the inside of the shield and into the enclosure.
• It is recommended that explosion-proof drains and conduit breathers be used. In some applications, alternate changes in temperature and barometric pressure can cause 'breathing' which allows moist air to enter and circulate inside the conduit. Joints in the conduit system are seldom tight enough to prevent this 'breathing'.
Note: Seals are not required for all Class 1 Division 2 locations in Canada.
However, to fully avoid any exposure, the use of seals are still recommended, especially for installations that use high-pressure or steam cleaning devices in proximity to the controller and/or sensor.
Connecting Wires
1. Use a small screw driver to gently press down and hold the spring connector
open.
2. Insert appropriate wire into open connector hole.
3. Release screw driver to secure wire.
MLP-A-AR-D-SIR100 4
Net Safety Monitoring Inc.
Board Assembly
There are three different fixed boards, two optional relay boards and an optional Modbus board which make up the PCB Assembly. Depending upon requirements, either a Electromechanical or Solid State Relay Board module can be used. Boards are field replaceable. Simply loosen the three locking standoffs, remove one board, insert the other board and tighten screws.
Note: Boards are susceptible to ESD. Refer to Appendix A, "Electrostatic Sensitive Device (ESD)", on page 21.
Figure 4: Millennium Modular Boards
Solid State Relay Board/Terminals
Fault
Low
High
+
­+
­+
Option Board
-
Terminal Board
Electromechancial Relay Board/Terminals
FNO FCOM common FNC normally closed LNO LCOM common LNC normally closed HNO HCOM common HNC normally closed
MLP-A-AR-D-SIR100 5
normally open
FAULT
normally open
LOW
normally open
HIGH
Modbus Ter min als
A B COM
-
Sensor Board
Net Safety Monitoring Inc
Figure 5: Wiring—Controller and Sensor
Terminal Board
RST
+24V
COM
4-20
A
B
COM
-
Modbus RTU Terminals
to PLC
ISO
+Vdc
Sig A
Sig B
COM
Shld
RST +24V COM 4-20 ISO
Wht Blu Red Blk Shld
Power Terminals
Sensor Terminals
SENSOR AND CONTROLLER
WARNING:
Power to the unit must be OFF before wiring.
Note: The Sensor may be factory installed to the Controller. If so, you need
only connect the Power Terminals.
4. Remove the Controller’s Housing Cover.
5. Connect the Sensor to the Sensor Terminals (if necessary) and the Output
Terminals to the output signal wires.
Tab l e 1 : Controller/Sensor Terminal Connections
Sensor Terminals Power Terminals
Sensor Wire
White = +Vdc RST = Remote Reset Blue = Sig A +24V = Power (+) Red = Sig B COM = Power (-) Black = COM (-)
Shield Shld
Controller (Sensor Board)
Controller (Terminal Board)
4-20
ISO
Power Connections
= Current Loop
Output
= +24 V isolated
4-20 power
Note: For Sensor Separation instructions, see Figure 6, "Wiring—Sensor
Sensor Board
Sensor Wires
Green Wire Earth Ground
6. Replace the Controller’s Housing Cover.
7. Turn Controller On.
8. Ensure display reads
Separation", on page 7.
Start Delay, Status LED is Red Slow Flash and
current output displays 3.0 mA. This is the start-up delay sequence which
SIR100 Sensor
will last approximately 90 seconds.
RS-485 Communication
Connect devices in a chain via the Modbus terminals. The last device in the chain requires end of line termination (refer to "MODBUS Termination" on
Note: If the 4-20 mA signal is not used, connect a jumper between the 4-20
terminal and the COM terminal on the Terminal Board.
MLP-A-AR-D-SIR100 6
page 9).
Net Safety Monitoring Inc
SENSOR SEPARATION
Figure 6: WiringSensor Separation
Power
Terminal B oard
Terminals*
Modbus RTU Terminals
to PLC*
Sensor Terminals*
RST
+24V
COM
4-20
ISO
+Vdc
Sig A
Sig B
COM
Shld
Sensor Board
As the Sensor must be located where gas is likely to accumulate and the Controller where it can be easily reached, it is often necessary to “separate” the Controller and Sensor.
The Sensor separation kit (SEP) is composed of a junction box and terminal strip. Refer to the Net Safety Multi-purpose Junction Box(MAN-0081) for terminal designation when wiring for sensor separation.
Shielded copper instrument wire (minimum 18 AWG) should be used for separations up to 500 feet. Shielded copper instrument wire (minimum 16 AWG) should be used for separations up to 2000 feet. Consult the factory if a greater separation distance is required.
To designated terminal board and SIR Sensor. See MAN-0081 Multi-purpose Junction Box.
Shield
Ensure that the appropriate wire is used for Class 1/Division 1 hazardous applications.
Note: If the 4-20 mA signal is not used, connect a jumper between the 4-20
terminal and the COM terminal on the Terminal Board.
WARNING:
To compensate for distance when remotely calibrating (sensor wired for separation), decrease the tubing diameter or increase the calibration gas flow rate between gas canister and sensor. Always confirm calibration by applying gas at the sensor (not separated).
MLP-A-AR-D-SIR100 7
Net Safety Monitoring Inc
NON-ISOLATED/ISOLATED WIRING
Terminal Connection
Figure 7: Non-isolated Terminal Connection
Termina l B oard Power Terminal
RST
+24V
COM
4-20
ISO
to Monitor
Figure 8: Isolated Terminal Connection
Terminal Board Power Terminal
RST
+24V
COM
4-20
ISO
to Monitor
Power Supply
Power Supply
Current Output
To set an isolated current output, simply move the Jumper (shorting jack) to either the isolated or non-isolated current position (refer to Figure 9, "Jumper Positions", on page 8).
Note: Unless otherwise specified, all models ship with non-Isolated current
output.
Figure 9: Jumper Positions
Termina l B oard
Position 1 & 2 = Isolated
Sensor Board
Jumper—Position Jumper
(shorting jack) over pins to set power source for current output.
Position 3 & 2 =
Non-isolated (default)
SIR100 Sensor RS-485 Terminator—Jumper must remain installed over pins 1 & 2.
MLP-A-AR-D-SIR100 8
Net Safety Monitoring Inc
REMOTE RESET
The Millennium can be set for remote reset. A normally open Push Button Switch must be connected between the RST and the COM terminals on the Terminal Board and the Relay Option Latch Status must be set to
Latching.
Figure 10: Remote Reset
RST
Termina l B oard
Power Terminal Strip
+24V
COM
4-20
ISO
MODBUS TERMINATION
Devices are networked in a daisy chain. The device located at the end of the chain requires end of line termination. Place both jumpers over the pins, as shown in Figure 11, "Modbus Termination Jumpers", on page 9, for end of line termination.
Figure 11: Modbus Termination Jumpers
MLP-A-AR-D-SIR100 9
Net Safety Monitoring Inc.
STEP 4 — OPERATE
The Controller faceplate contains most functional elements of the user interface. Below is a description of that functionality.
Figure 12: Controller Functionality
Scrolling 8-character display -
Magnetic Reed Switch - provides non-intrusive access for
programming, calibrating and resetting.
-Place magnet against Housing (where indicated) for less than one second to initiate a basic system reset (clear a latched alarm) and make selections.
-Place magnet against Housing (where indicated) and hold to program, view current settings and calibrate.
Refer to "Magnetic Reed Switch" on page 12 for further information.
ON/OFF Switch - used to turn Controller on and off. Housing must be removed to access.
Pull Here knob - unscrew the two screws and pull to remove faceplate. Removal allows access to PCBs. The faceplate remains attached by the ribbon cable.
Current Test Jacks - to take current loop measurements use the following procedure:
-Insert your current meter leads into the Test Jacks.
-Set external devices to bypass, if necessary, to avoid unwanted alarm response
-Review current loop measurements.
Refer to "Current Loop Measurement (Test Jacks)" on page 12 and Table 2, "Status LEDs, Display Messages and Current Loop", on page 11.
provides various status messages and prompts. Refer to "Status LEDs, Display Messages and Current Loop" on page 11.
C
a
l
/
R
e
s
e
M
O
n
S
Power
t
a
g
n
e
t
i
d
e
Calibration/Setup
Pull Here
-Hold Cal/Reset or magnet until countdown is zero (~10 sec)
-Follow instruction on display
Current O/P Check
Connect current probes
to meter jacks and
read mA output
On
Off
Status
Red
Slow Flash: Gas present Flast flash : Cal or Fault Solid: Overrange
Green
Short Blips: Normal operation. No gas present
Here
Pull Here knob - unscrew the two screws and gently pull to remove faceplate. Removal allows access to terminal boards. The faceplate remains attached by the ribbon cable.
Pull
Status Light (Red and Green) - indicates status of unit. Refer to "Status LEDs, Display Messages and Current Loop" on page 11 for detailed explanation of states/ status.
Calibration Button - provides intrusive access for programming, calibrating and resetting.
-Push for less than one second to initiate a basic system reset (clear a latched gas alarm) and make selections.
-Push and hold to program, view current settings and calibrate.
Refer to "Calibration Button" on page 12 for further information.
MLP-A-AR-D-SIR100 10
Net Safety Monitoring Inc
Tab l e 2 : Status LEDs, Display Messages and Current Loop
Status LED
State Current O/P
RED or
GREEN
Calibrate Sensor Set Relay Options
3.0 mA n/a n/a
Review Settings
Normal operation 4.0 mA
Start-up delay (90 sec) 3.0 mA
Slow flash
Blip/ blink
Access Main Menu 3.0 mA Solid
Memory Error (contact factory)
White, Blue, Red or Black Sensor lead open
2.5 mA
2.5 mA
Slow flash
Slow flash
Auto zero set 3.0 mA Solid
Apply calibration gas 3.3 mA
Fast flash
Span is set, remove gas 3.6 mA Solid
Return to normal operation
3.6 mA Solid
Display
00 %LEL
Start Delay
Switch On 10-0
Memory Error
Sensor Fault
Setting zero
Apply 50% Span
Remove gas
Cal. Complete
Gas present >4.0-20.0 mA
Calibration procedure failed/Sensor failed
3.0 / 3.3 mA Flash Flash
Blip/ blink
1 to 100% full Scale
Fail Cal
RTU Registers
Register 40001 = LEL output (read only)
Register 40002 = RTU Status (read only)
Register 40101 = Reset latched relays (write)
MLP-A-AR-D-SIR100 11
Net Safety Monitoring Inc
Tab l e 3 : RTU Status Register (40002) Read Only (binary)
RTUstat_fault 0x0001 fault (sensor...)
RTUstat_low_alarm 0x0002 low alarm tripped
RTUstat_high_alarm 0x0004 high alarm tripped
RTUstat_low_alarm_latched 0x0008 low alarm latched
RTUstat_high_alarm_latched 0x0010 high alarm latched
RTUstat_powerUp 0x0080 power up delay
RTUstat_cal_cycle 0x0100 calibration cycle in progress
Magnetic Reed Switch
The Magnetic Reed Switch is provided to avoid opening the Housing in an environment where gas may be present. The Magnetic Reed Switch functions in the same manner as the Calibration Button but in a non-intrusive manner. Refer to Figure 12, "Controller Functionality", on page 10 for more information.
Attached to the side of the Controller is a magnet:
Place and hold the magnet to the Controller’s Housing (10 o’clock position) to Calibrate and access Main Menu.
Briefly place the magnet to the Controller’s Housing (10 o’clock position) to make a selection (select
YES?).
RTUstat_zeroing 0x0200
RTUstat_apply_span_gas 0x0400
RTUstat_calibrating 0x0800
RTUstat_remove_gas 0x1000
RTUstat_cal_complete 0x2000
RTUstat_mem_error 0x4000 memory error
Calibration Button
The Calibration Button provides access to the Millennium’s Main Menu, which in turn allows calibration and options to be reviewed and set. Refer to Figure 12, "Controller Functionality", on page 10 for more information.
Press and hold the Calibration Button to Calibrate and access Main Menu.
Briefly press to make a selection (select
WARNING:
Opening the Controller’s Housing should be avoided when the presence of gas is possible (when in a hazardous environment). Do not power up the system, with the Housing removed, unless the area has been de-classified.
YES?).
Power Up
Turn power switch On. A 90 second warm-up routine will begin. The display
Start Delay Millennium Net Safety, Status LED is Red Slow Flash
reads and current output displays 3.0 mA.
When power is applied, the system is automatically tested to ensure proper functionality.
After warm-up, the Controller will enter normal operation, the display reads
, Status LED will Green Blip/blink and analog output will change to 4.0
%LEL
00
mA.
Current Loop Measurement (Test Jacks)
Use a standard meter to measure current loop during various states. The Controller’s Housing cover must be removed to access the Test Jacks.
Refer to Table 2, “Status LEDs, Display Messages and Current Loop,” on page 11 for a detailed list and Figure 12, "Controller Functionality", on page 10 for more information.
Status LED
The Status LED will remain solid, flash, blip and/or blink, in either Red or Green, to indicate various states. Refer to Table 2, “Status LEDs, Display Messages and Current Loop,” on page 11 for a detailed list.
MLP-A-AR-D-SIR100 12
Net Safety Monitoring Inc.
THE MAIN MENU
The Main Menu provides access to various functional settings and viewing of current settings.
• Calibrate Sensor.
• Review Relay Settings (optional) - Review the current Fault, Low and High alarm settings. This is a read only section.
• Set Relay Options (optional) - Set the Low and High alarm settings.
• Select Gas Curve (methane or propane).
• Select a display language - English, Spanish or French.
• Select Modbus Options.
Note: The current output will drop to 3.0 mA while in the Main Menu.
Accessing the Main Menu
There are two ways to access the Main Menu:
• Calibration Button found on the faceplate (the Housing cover must be removed to access)
• Magnetic Reed Switch (a magnet must be used to activate)
Main Menu Functionality
1. Ensure that the Controller has been turned on and no fault is present.
2. Hold the magnet against the Reed Switch or press and hold the Calibration Button until the message
3. An option will scroll across the display followed by the prompt
YES?.
4. To select an option, momentarily place the magnet to the Reed Switch or press the Calibration Button at the
5. If you do not wish to select that option wait until the next option appears and then select
6. A selection is acknowledged with a flashing
7. If no option is selected, the Controller returns to
YES.
00 %LEL (normal operation).
YES?.
Switch On displays and the countdown (10 to 0) finishes.
YES? prompt.
MLP-A-AR-D-SIR100 13
Net Safety Monitoring Inc
STEP 5 — CALIBRATE
CALIBRATION PROCEDURE
WARNING: The calibration procedure requires about 5 minutes to
complete. If gas is not applied at the appropriate time, a calibration failure may occur (refer to "Calibration Failure" on page 14 for specific information).
For accurate performance, the Millennium should be calibrated using 50% span of the specific gas of concern. The concentration of gas, corresponding to 100% of full scale, is converted to a linear 4 to 20 mA output signal which can be powered from the primary dc supply of the instrument. Power up the unit for at least 4 hours BEFORE first calibration.
Note: Air movement, drafts and wind can cause dilution of calibration gas
flow which can cause an erroneous calibration and inaccurate performance. To avoid this, use a Calibration Cover to cover the slots on the Sensor. The cover MUST be removed for normal operation. When slots are covered, inject calibration gas at a rate of 1.0 litre per minute or greater; when not covered, ensure area is free of drafts/wind and inject calibration gas at a rate of
3.0 litres per minute or greater. The following calibration procedure should be followed to ensure an accurate correlation between the 4 to 20 mA output signal and the gas concentration.
Figure 13: Calibration Procedure
Display Shows
Calibrate Sensor YES?
Setting Zero
Apply 50% Span
Calibration Procedure
The unit can be set up to detect Methane or Propane. To determine the gas to be detected go to “Select Gas Curve” option in the menu and make the selection, then calibrate with the target gas. See “Select Gas Curve” option on page 16.
1. Confirm successful power up of ControllerLED Green Blip/blink every 2
seconds; no fault indicated.
2. Flow certified ZERO AIR at a rate of 1.0 litre per minute to the calibration nipple/fitting, when using the Calibration Cover. If separated or not using the Calibration Cover, a rate of at least 3.0 litres per minute is
3. Press and hold the Calibration Button or use the Reed Switch to access the Main Menu and wait for countdown (10-0) to complete.
4. When
Calibrate Sensor YES? displays, use the Calibration Button or
Reed Switch to select
YES?
Selection will be confirmed by a flashing YES.
5. When
6. Wait for
Setting Zero displays apply clean air.
Apply 50% LEL to display and apply specific gas. If in windy
conditions and using a Calibration Cover, apply at a rate of 1.0 litre per minute otherwise 3.0 litres per minute is recommended.
7. The display will show
8. Remove span gas when the message (Status LED
9. The message
Green solid and 3.6 mA output).
Cal Complete will display when calibration is complete.
Calibrating as gas detected.
“Remove Gas”
10. Apply zero gas (clean air) again to purge system.
Note: Always apply test gas after calibration to verify operation.
Calibrating
Remove Gas
Cal Complete
recommended.
displays
Action
Select YES?
Apply clean (zero air)
Calibration Failure
If the calibration procedure fails, the display shows
Fail Cal, the Status LED
alternates Red/Green flashes and the analog output changes back and forth from
3.0 to 3.3 mA.
The unit remains in a failed state until manually reset. After the Manual Reset, the unit will return to normal operation based on previous calibration values. See "Manual Reset" on page 18 for instructions.
MLP-A-AR-D-SIR100 14
Apply specific gas
STEP 6 — MONITOR
REVIEW RELAY SETTINGS
This is a read-only mode; changes cannot be made.
Step 1: Press and hold the Calibration Button or the magnet to the Reed
Switch to enter the Main Menu; wait for the countdown, from 10 to
Remove gas
Apply clean air to purge system
Net Safety Monitoring Inc.
0, to end.
Step 2: When
Review Relay Settings displays press the Calibration
Button or use the Reed Switch to select. The flashing
Step 3: The Fault Alarms are fixed (
YES confirms the selection.
Energized / Non-Latching) and
display first. Then the Low Alarm level, coil and latch status display, followed by the High Alarm level, coil and latch status.
Step 4: At this point, the option to
Set Relay Options YES? is displayed.
SET RELAY OPTIONS
Use to set the alarm level, coil status and latch status for the Low and High relays (Fault Alarm is fixed).
Tab l e 4 : Default Relay Settings
Alarm Levels Coil Status
Millennium
Model Number
MLP-A/AR/AD 20% 40%
Low High Fault
Energ./Non­latching
Latching
Non Latching
**
Energized
De-energized
MLP-A-AR-D-SIR100 15
Net Safety Monitoring Inc
Setting Relay Options
There are two settings for Relay Options: Low and High. The Fault Relay is fixed as Energized/Non-latching and cannot be changed. The low alarm level, coil energization and latch status for low alarm are set first; high alarm level, coil energization and latch status for high alarm are then set. All ranges are in %LEL.
Step 1: When
Step 2: The message
Step 3: When the required level displays, press the Calibration Button or
Step 4: The message
Step 5: Press the Calibration Button or use the Reed Switch to select.
Step 6: The message
Set Relay Options YES? displays press the Calibration
Button or use the Reed Switch to select. The flashing
YES confirms the selection.
Set Low displays. Low Alarm set-points are then
displayed in increments of 5 (5 to 95).
use the Reed Switch to select. The level selected will flash to confirm the selection.
Coil Status displays. The display then shows
Energized YES? and then De-Energized YES?.
The flashing
YES confirms the selection. If no selection is made,
Coil Status option is repeated.
Latch Status displays. The display then shows
Latching YES? and then Non-Latching YES?.
SELECT GAS CURVE
Steps to set up target gas (Methane or Propane).
Step 1:
Press and hold the Cal/Reset button or use the magnet to access the Main menu and wait for countdown(10-0) to complete. Skip / ignore “Calibrate sensor” option and wait for “Select Gas Curve” option.
Step 2: When the message
Select Gas Curve YES? displays press the
Calibration Button or use the Reed Switch to select. The flashing
Step 3: The message
Button or use the Reed Switch to select or wait for
Yes?
to display and select.
Step 4: The flashing
YES confirms the selection.
Methane %LEL Yes? displays. Use the Calibration
Propane %LEL
YES confirms the selection and will continue to flash
for a few seconds. The Millennium display will shortly return to normal operation
00 %LEL.
Note: If the gas curve is modified, the Millennium must be recalibrated (refer
to "Calibration Procedure" on page 14).
SELECT DISPLAY LANGUAGE
Step 7: Press the Calibration Button or use the Reed Switch to select.
The flashing
YES confirms the selection. If no selection is made,
Latch Status option is repeated.
Step 8: The message
Set High displays.
The High Alarm level cannot be set to a value lower than the Low Alarm level (as set in Step 3), nor higher than the maximum of 100% LEL. The High Alarm level is displayed in increments of 5
greater than the Low Alarm level (as set in Step 3).
Step 1: When Select Display Language YES? displays press the
Calibration Button or use the Reed Switch to select. The flashing
Step 2: When the required language displays (
Francais) press the Calibration Button or use the Reed Switch to
YES confirms the selection.
English, Espanol,
select. The flashing
YES confirms the selection.
Note: Factory default is English.
Step 9: Repeat Steps 3 through 7 to complete the High Alarm level, coil
and latch status settings.
Note: If no selection is made, a 5 minute timer expires, in which case the unit
returns to normal operation.
MLP-A-AR-D-SIR100 16
Net Safety Monitoring Inc.
MODBUS OPTIONS
The digital RS-485 Modbus RTU protocol is used. There are two Modbus options: Node Address and Baud Rate.
Node Address
Each device connected to the chain must be assigned a unique node address. The last number in the address is selected first.
Step 1: When
Step 2: The current node address will display
Step 3: Wait for the prompt
Step 4: Use the Calibration Button or Reed Switch to select each of three
Baud Rate
Modbus Setup? YES? displays press the Calibration Button
or use the Reed Switch to select. The flashing
YES confirms the selection.
Node: 000.
New Address? YES? and press the Calibration
Button or use the Reed Switch to select.
numbers in the new address:
- select the last number in the address first:
- select the next number in the address:
- select the first number in the address last:
0 thru 9.
0 thru 9.
0 1 2.
ALARMS
Sensor Fault
WARNING:
The fault detection circuitry does not monitor the operation of external response equipment or the external wiring to these devices. It is important that these devices be checked periodically to ensure they are operational.
Self-testing circuitry continuously checks for problems that could prevent proper response. When power is applied, the microcontroller automatically tests the system to ensure that it is functioning properly. During normal operation, it continuously monitors the signal from the internal sensor source. In addition, a "watchdog" timer is maintained to ensure the program is running correctly. When a system fault is detected, the Status LED will Red Slow flash, the displays shows
Gas Present
When gas is present, 1 to 100% Full Scale will display, the analog output switches to between 4 and 20 mA and the Status LED Blip/blinks Red.
Sensor Life
Sensor Fault and analog output changes to 2.5 mA.
The transmission speed must be defined.
Depending on various factors, sensor response may slowly deteriorate over a period of years. If calibration becomes impossible for any reason, the display
Step 1: When
Modbus Setup? YES? displays press the Calibration Button
or use the Reed Switch to select. The flashing
YES confirms the selection.
will show
Fail Cal, the analog output will switch repeatedly between 3.0 mA
and 3.3 mA and the Status LED alternates Red and Green flashes.
Step 2: After setting the Node Address, the current Baud Rate will display
XX.X BPS.
Step 3: Wait for the prompt
New Baud Rate? YES? and press the
Calibration Button or use the Reed Switch to select.
Step 4: The available baud rates will display:
19.2s, 28.8s, 38.4s, 57.6s.
2400s, 4800s, 9600s,14.4s,
Step 5: Use the Calibration Button or use the Reed Switch to select baud
rate when it displays.
Step 6: The flashing
MLP-A-AR-D-SIR100 17
YES confirms the selection.
Net Safety Monitoring Inc
RESET
Manual Reset
A Manual Reset is required after a calibration failure or to clear a latched relay alarm. Simply place and hold the magnet against the Reed Switch or press and hold the Calibration Button for 3-5 seconds. The unit will return to normal operation using previous calibration values.
Remote Reset
If Relay Option is set to and an open Push Button Switch is connected between the RST terminal and the COM terminal on the Terminal Board, Remote Reset is possible. Also refer to "Remote Reset" on page 9 for details.
Latching (refer to "Setting Relay Options" on page 16)
OUTPUTS
Relay
Note: The fault relay output is not used to activate an automatic shutdown
procedure. The fault output indicates a potential problem with the
Controller not an alarm condition. Standard electro-mechanical relay outputs have Form C SPDT contacts rated 5 Amps at 30 V dc/ 250 V ac. Three relay outputs are available; one for Fault; one for Low alarm; and one for High alarm. All relays have normally open and normally closed contacts available at the output terminals.
Modbus
Digital RS-485 Modbus RTU protocol is used.
Register 40001 = LEL output (read only)
Register 40002 = Status (read only)
Register 40101 = Reset latched alarms (write)
Note: Many registers are used by the controller. Please do not write outside
the three registers.
Current
A 4-20 mA dc current output is used to transmit the alarm status and fault codes to other devices. This output can be wired for isolated or non-isolated operation. A 4.0 mA output indicates normal operation; a 4.0 - 20.0 mA output indicates the presence of gas. Current output of 2.5 mA indicates the presence of a system fault.
The fault relay is set for normally energized operation and is non-latching. If a system fault is detected, the fault relay becomes de-energized. The fault relay is factory set and cannot be altered. The Low alarm and High alarm relays can be selected for either normally energized or normally de-energized operation and latching/non-latching.
MLP-A-AR-D-SIR100 18
Net Safety Monitoring Inc
STEP 7 — MAINTAIN
PERIODIC RESPONSE CHECK
Net Safety Monitoring recommends that a bump test be performed every 90 days to ensure continued functionality and accuracy of the detector. Full calibration is recommended when the sensor fails to meet acceptable accuracy standards. This involves the application of calibration gas to the sensor, then the observation of the response LEDs, analog output, and external monitoring equipment. Be sure to prevent unwanted response of external monitoring devices and equipment during this procedure. If the Millennium response to calibration gas is within the specified accuracy then it is not necessary to perform a calibration. For example, when 50% of full scale is applied, the response is expected to be between 11.5 mA (47% of full scale) and 12.5 mA (53% of full scale). An additional consideration is the accuracy tolerance of the calibration gas which may be + or - a few percent. If the calibration gas is + or ­10% of full scale then the reading may be from 10.7 mA (42% of full scale) to
13.3 mA (58% of full scale).
TROUBLESHOOT
Response to the input should be checked and, if necessary, calibration should be performed whenever any of the following occur. Refer to "Calibration Procedure" on page 14 for calibration instructions.
• Sensor or transmitter is connected or disconnected
• Gas Curve is modified
The Millennium is not designed to be repaired in the field. If a problem should develop, first calibrate the device and carefully check for faulty wiring. If it is determined that the problem is caused by an electronic failure, the device must be returned to the factory for repair. Refer "How to Return Equipment" on page 19 for detailed instructions.
HOW TO RETURN EQUIPMENT
A Material Return Authorization number is required in order to return equipment. Please contact Net Safety Monitoring at (403) 219-0688 returning equipment or consult our Service Department to possibly avoid returning equipment.
If you are required to return equipment, include the following information:
1. A Material Return Authorization number (provided over the phone to you by Net Safety).
2. A detailed description of the problem. The more specific you are regarding the problem, the quicker our Service department can determine and correct the problem.
3. A company name, contact name and telephone number.
4. A Purchase Order, from your company, authorizing repairs or request for quote.
5. Ship all equipment, prepaid to:
Net Safety Monitoring Inc
2721 Hopewell Place NE Calgary, Alberta, Canada
T1Y 7J7
6. Mark all packages: RETURN for REPAIR
Waybills, for shipments from outside Canada, must state:
Equipment being returned for repair All charges to be billed to the sender
Also, please ensure a duplicate copy of the packing slip is enclosed inside the box indicating item 1-4 along with the courier and account number for returning the goods.
All Equipment must be Shipped prepaid. Collect shipments will not be accepted.
before
Pack items to protect them from damage and use anti-static bags or aluminium­backed cardboard as protection from electrostatic discharge.
MLP-A-AR-D-SIR100 19
Net Safety Monitoring Inc
SPARE PARTS/ACCESSORIES
Tab le 5: Part Numbering
Calibration Cover for windy conditions CC-SIR100-SEP
Magnet assembly
Aluminium or Stainless Steel Junction box
Terminal Connector Board
IR Adapter Ring/Flame Arrestor Housing
IR Adapter Ring/Flame Arrestor Housing
Replacement IR Sensor Assembly w/Methane & Propane curve, Aluminium housing
Replacement IR Sensor Assembly w/Methane & Pentane curve, Aluminium housing
Replacement IR Sensor Assembly w/Methane & Propane curve, Stainless Steel housing
Replacement IR Sensor Assembly w/Methane & Pentane curve, Stainless Steel housing
Magnet-1
JB-MPD-A/S
PCBA-0252D
SIR100-RING
SIR100-RING-SS
SIR100-100
SIR100P
SIR100-100-SS
SIR100-100P-SS
FACE ROTATION OPTION
In some applications, it is necessary for the Millennium Controller to be mounted in a non-standard orientation. To accommodate such installations and ensure that the display will appear at the correct angle for viewing, the PCB Assembly can be rotated inside the Controller.
Rotate PCB Assembly
1. Remove the Controller’s Housing Cover.
rebmuNtraPytefaSteNnoitpircseD
2. Turn the power to the detector off.
3. Unscrew both the knobs marked "Pull Here".
4. Lift Controller faceplate from Housing and allow to hang from ribbon cable.
5. Unscrew the two metal standoffs.
6. Carefully remove the PCB Assembly from the Housing.
7. The Rotator plate is secured to the bottom of the Housing and is accessible after the PCB Assembly has been removed.
8. Rotate the PCB Assembly to desired position and line up the standoffs with the mounting holes.
9. Insert standoffs in the appropriate horizontal or vertical mounting holes.
10. Tighten standoffs to secure PCB Assembly.
11. Replace faceplate and tighten "Pull Here" knobs.
12. Return power to detector and replace Housing Cover.
Vertical Mounting Holes (Insert Standoffs)
Horizontal Mounting Holes (Insert Standoffs)
Figure 14: Non-standard Orientations
Ribbon cable
Standoffs
PCB Assembly
Note: Ensure orientation allows for connections and excess wire within Controller
Housing.
MLP-A-AR-D-SIR100 20
WARNING:
page 21 for handling instructions of electronic components.
See Appendix A, "Electrostatic Sensitive Device (ESD)", on
Faceplate
Net Safety Monitoring Inc.
Appendix A: E
LECTROSTATIC SENSITIVE DEVICE (ESD)
Electrostatic discharge (ESD) is the transfer, between bodies, of an electrostatic charge caused by direct contact or induced by an electrostatic field.
The most common cause of ESD is physical contact. Touching an object can cause a discharge of electrostatic energy near electronic components, it can damage or destroy those components.
In some cases, damage is instantaneous and an immediate malfunction occurs. However, symptoms are not always immediate seemingly normal for an indefinite period of time, followed by a sudden failure.
To eliminate potential ESD damage, review the following guidelines:
• Handle boards by metal shields
• Wear grounded wrist or foot straps, or ESD shoes or heel grounders to dissipate unwanted static energy
• Prior to handling boards, dispel any charge in your body or equipment
• Ensure components are transported and stored in static safe packaging
• When returning boards, carefully package in the original carton and static protective wrapping
• Ensure ALL personnel are educated and trained in ESD Control Procedures
In general, exercise accepted and proven precautions normally observed when handling electrostatic sensitive devices.
A warning label is placed on the packaging, identifying product using electrostatic sensitive semiconductor devices.
taking care not to touch electronic components
—ESD! If the charge is sufficient and occurs
performance may be marginal or
MLP-A-AR-D-SIR100 21
Net Safety Monitoring Inc.
Appendix B: RESISTANCE TABLE
Tab l e 6 : Wire Resistance In Ohms
Distance (Feet) AWG #20 AWG #18 AWG #16 AWG #14 AWG #12 AWG #10 AWG #8
100 1.020.640.400.250.160.100.06
200 2.031.280.800.510.320.200.13
300 3.051.921.200.760.480.300.19
400 4.062.551.611.010.640.400.25
500 5.083.202.011.260.790.500.31
600 6.093.832.411.520.950.600.38
700 7.11 4.47 2.81 1.77 1.11 0.70 0.44
800 8.12 5.11 3.21 2.02 1.27 0.80 0.50
900 9.145.753.612.271.430.900.57
1000 10.20 6.39 4.02 2.53 1.59 1.09 0.63
1250 12.70 7.99 5.03 3.16 1.99 1.25 0.79
1500 15.20 9.58 6.02 3.79 2.38 1.50 0.94
1750 17.80 11.20 7.03 4.42 2.78 1.75 1.10
2000 20.30 12.80 8.03 5.05 3.18 2.00 1.26
2250 22.80 14.40 9.03 5.68 3.57 2.25 1.41
2500 25.40 16.00 10.00 6.31 3.97 2.50 1.57
3000 30.50 19.20 12.00 7.58 4.76 3.00 1.88
3500 35.50 22.40 14.10 8.84 5.56 3.50 2.21
4000 40.60 25.50 16.10 10.00 6.35 4.00 2.51
4500 45.70 28.70 18.10 11.40 7.15 4.50 2.82
5000 50.10 32.00 20.10 12.60 7.94 5.00 3.14
5500 55.80 35.10 22.10 13.91 8.73 5.50 3.46
6000 61.00 38.30 24.10 15.20 9.53 6.00 3.77
6500 66.00 41.50 26.10 16.40 10.30 6.50 4.08
7000 71.10 44.70 28.10 17.70 11.10 7.00 4.40
7500 76.10 47.90 30.10 19.00 12.00 7.49 4.71
8000 81.20 51.10 23.10 20.20 12.70 7.99 5.03
9000 91.40 57.50 36.10 22.70 14.30 8.99 5.65
10 000 102.00 63.90 40.20 25.30 15.90 9.99 6.28
Note: Resistance shown is one way. This figure should be doubled when determining closed loop resistance.
MLP-A-AR-D-SIR100 22
Net Safety Monitoring Inc.
Appendix C: SPECIFICATIONS
• Response Time: <5 seconds to T20
<7 seconds to T40
SENSOR SPECIFICATIONS
• Operating Temperature Range: -40°C to +75°C (-40F to +167F)
• Linearity/Repeatability:
• Certification: CSA and NRTL/C certified for
• Weight: 0.9 Kg (2.0 lb)
• Enclosure Material: Powder Coated or Anodized Aluminum (optional stainless steel)
• Range of Detection: 0 to100% LEL methane/propane
• Accuracy:
±3% LEL up to 50% LEL
±5% LEL above 50% LEL
CONTROLLER SPECIFICATIONS
MILLENNIUM 4-20 mA ANALOG OUTPUT
Operating Temperature Range -40°C to +85°C (-40F to +185F)
Power Consumption
24 V dc @ 50 Span
Nominal 3.02 W
Maximum 3.38 W
Humidity Range 0 to 100% Relative humidity, non-condensing
Operating Voltage Range 10.5 to 32.0 V dc
Enclosure Material Powder coated Copper Free Cast Aluminum
1
4-20 mA with RELAY OUTPUT MODULE
Nominal 3.36 W
Maximum 4.5 W
±3% LEL / ±2% LEL
hazardous locations. Class I, Division 1, Groups B, C and D. IEC Rating Ex d IIB+H2 T5. Performance certified to CSA C22.2 No. 152.
12
DIGITAL
3
Nominal 3.02 W
Maximum 3.38 W
Certifications CSA and NRTL/C certified for hazardous locations. Class I, Division 1, Groups B, C and D. Temperature Code T5. Rating Ex
d IIB+H2 T5 (Class1, Zone 2, Group IIB+H2T5). Maximum operating ambient of 85
°C. Enclosure Type 4X.
Note: Electronics only-CSA and NRTL/C certified for hazardous locations Class I, Division 2 Groups A, B, C and D.
Weight 3.5 Kg (7.7 lb)
1
4 to 20 mA - Into a maximum loop impedance of 800 Ohms at 32 V dc or 150 Ohms at 10.5 V dc. Isolated or non-isolated loop supply.
2 Form C contacts rated 5 Amps at 30 V dc / 250 V ac. Selectable energized / de-energized, latching/non-latching configurable low and high alarms. Fault relay is factory set as energized, non-latching and cannot be modified.
3
Digital RS-485 Modbus protocol.
MLP-A-AR-D-SIR100 23
istributed by: et Safety Monitoring Inc.,
721 Hopewell Place NE Calgary, Alberta, Canada T1Y 7J7 Telephone: (403) 219-0688 Fax: (403) 219-0694
-mail: netsafe@net-safety.com
ww.net-safety.com
Loading...