This manual is for informational purposes only. Although every effort has been
made to ensure the correctness of the information, technical inaccuracies m ay
occur and periodic changes may be made without notice. Net Safety Monitoring
Inc., assumes no responsibility for any err ors contained within this manual.
If the products or procedures are used for purposes other than as described in the
manual, without receiving prior confirmation of validity or suitability , Net
Safety Monitoring Inc., does not guarantee the results and assumes
obligation
or liability.
No part of this manual may be copied, disseminated or distributed without the
express written consent of Net Safety Monitoring Inc.
Net Safety
Monitoring
Inc., products are
carefully
designed and
high quality components and can be expected to provide many years of trouble free
service. Each product is thoroughly tested, inspected and calibrated prior to
shipment. Failures can occur which are beyond the control of the manufacturer.
Failures can be minimized by adhering to the operating and maintenance
instructions herein. Where the absolute greatest of reliability is
redundancy
should be designed into the system.
required,
no
manufactured
from
Warranty
Net Safety Monitoring Inc., warrants its electronic assemblies for 36 months
from date of purchase.
No other warranties or liability, expressed or implied, will be honoured by Net
Safety Monitoring Inc.
Contact Net Safety Monitoring Inc., or an authorized representative for details.
We welcome your input at Net Safety Moni toring. If you have any comments
please contact us at the phone/address below or visit our web site and complete
our on-line customer survey: www.net-safety.com.
Contact Information
Net Safety Monitoring Inc.
2721 Hopewell Place NE
Calgary, AB
Canada
T1Y 7J7
T elephone: (403) 219-0688
Fax: (403) 2 19-069 4
www.net-safety.com
E-mail: netsafe@net-safety.com
The RM2-ARD is a 2-channel, 4-20 mA input
of Net Safety’s monitoring devices. Channel #1
independently and can be used for any c ombination of
detectors, toxic gas
available outputs from this device are: 4-20 mA analog signal, relay and
digital for Modbus applications. For Modbus setup see pages 17-20.
Note: All three (3) outputs can be utilized at the same time.
Y S T E M
monitor for use with a variety
and Channel #2 function
Net Safety’s fire
se
nsors or combustible sensor with transmitters. The
Fire Head
Net Safety’s UV/IRS, UVS, IRS, UVU-120-H2 and Phoenix IR3S fire detector
heads can be used in conjunction with the RM2.
ST Series Sensors
A variety of Net Safety’s ST Series 4-20 mA Toxic gas sensors can be
connected to the RM2.
Combustible
Net Safety’s Uni-Tr an and Millennium Combustible Gas Controllers or
Transmitters can be used in conjunction with the RM2. Com bustible sensors
should always be connected to transmitter or controller . The 4-20 output from
this combination then connected to the RM2.
Manual
The manual has been designed to m ake installation of the RM2 System easy . To
ensure proper installation and usage follow the simple steps outlined in the
following pages. Consult the manual provided with the detector device(s) being
connected to the RM2 for specific information.
If you encounter any problems, consult th e troubleshooting section or contact
your sales representative.
Sensors and Tr a nsmitters / C o n trollers
Step 1 — INSTALL
Step 2 — WIRE
Step 3 —
O
PERATE
Step 4 — MONITOR
Step 5 —
RM2-ARD 1
M
AINTAIN
Net Safety Monitoring Inc.
STEP 1 — I
NSTALL
U
N P A C K
Carefully remove all components from the packaging. Check components
against the enclosed packing list and inspect all components for obvious
damage such as broken or loose parts. If you find any components missing or
damaged, notify your representative or Net Safety Monitoring immediately .
Locate
Locate Fire Heads, Sensors, Controllers or Transmitters as per the manual
provided with the specific product.
Figure 1: Dimensional Drawings
Mount
The RM2 can be fitted into a cage and located in a Class 1, Division 2 location.
0.690"
8.566"
0.576"
0.059"
0.540"
0.970"
STEP 2 — W
F
I E L
D IN S T A L L A T I O N
IRE
WARNING: Wiring codes and regulations may vary . W iring must comply
with applicable regulations relating to the installation of electrical equi pment
and is the responsibility of the installer. If in doubt, consult a qualified official
before wiring the system.
The following figures illustrate the basic connections f or a Fire Head, Sensor,
Controller or Transmitter as well as information for external equipment.
Consult the manual for the specific Fire Head, Controller or Transmitter
regarding further wiring information.
Configuration
T wo Analog Input chan nels wi th Current Loop an d Relay a nd Dig ita l Output.
Refer to Figure 2, "Analog/Relay/Digital RM2 System Board—W iring",
on page 3 for illustration.
S
E T T I N G S
Once field wiring is complete, the Relay Contacts and the Isolated/Non-isolated
analog outputs should be configured.
Usi ng J um p er s
Place Jumper(s) over appropriate pins in order to set
Relays Contacts as Open or Closed, and set Isolated or
Non-isolated analog output. See Figure 2 on page 3.
Relay Outputs
The relay outputs have SPDT, form C, normally open/normally closed contacts
rated for 5 Amps @ 30 V dc or 250 V ac. Each channel has two dedicated alarm
relays and a fifth relay is a Common Fault relay.
Current Outputs
A 4-20 mA dc analog current output (isolated/non-isolated) transmits
information to other devices.
Digital Outputs
For digital output, connections to PLC (RTU) are made via terminals
19 and 20 (A and B)for Modbus communications. See page 3 and pages 17-20.
RS 485 Bus Terminator Jumpers (JP9 and JP11) should be placed over jumper pins
for Modbus communication. The user should wire the system according to RS 485
convention and local Electrical codes.
RM2-ARD 2
Net Safety Monitoring Inc.
Figure 2: Analog/Relay/ Digital RM2 System Board—
Wiring
Note: The Common System Fault Relay is fixed as Energized/Non-latching.
Refer to T able 2 on page 13, T a ble 4 on page 15 and Table 5 on page 16 for status indicators.
COMMON FAILURE FAULT
CHANNEL#1 FAULT LOW
R1
CHANNEL#1 FIRE HIGH
CHANNEL#2 FAULT LOW
CHANNE #2 FIRE HIGH
+24 V Supply
4-20 mA Signal
Manual Visual Integrity (Fire O
Manual Visual Integrity (Fire ONL
FIREHEADS/SENSORS
Digital output to PLC (RTU)
Digital output to PLC (RTU)
TRANSMITTERS/CONTROLLERS
Supply Common
4-20 mA Signal
Supply Common
Isolated Power +24V
NLY)
+24 V Supply
Y)
R2
R3
R4
A
B
4-20 mA Output CH#1
4-20 mA Output CH#2
RM2 Remote Reset
Main Power (+24V)
Supply Common
Relay contacts are jumper selectable as
Normally OPEN or Normally CLOSED
Position 1 & 2 = CLOSED
Position 2 & 3 = OPEN
(default Closed - 1 & 2)
RS 485 Bus
Termination jumpers
(JP 9 & JP 11)
Analog Output - Channel #1
Analog Output - Channel #2
Analog Outputs are jumper selectable as
Position 1 & 2 = Non -i solat ed (default)
Position 2 & 3 = Isol ated dc
(default Closed - 1 & 2)
Earth Ground
Note: Connect Shield to Supply Common (COM). Refer to "Remote Reset—W iring" on page 4 for instructions on wiring a Remote Reset button.
Note: For FIRE HEAD and
C
ONTROLLER/TRANSMITTER
wiring, consult the manual provided with the fire or gas product for specific wiring instructions.
RM2-ARD 3
Net Safety Monitoring Inc.
Figure 3: ST Series Toxic
S
ENSOR
—
Wiring
RM2
ST Series
ST1200/01
ST1300/01
ST1500
ST1600
ST1800
ST1250
Note: Refer to MAN-0081 for terminal designations if the Net Saftey
multi-purpose junction box is being used.
Note: For ST Series Toxic sensors, use shielded copper instrument wire
(minimum 18 AWG) for separations up to 500 feet; use 16 A WG for
separations of 500 to 2000 feet. Consult t he factory if greater distance
Note: To compensate for distance when remotely calibrating(sensor wired for
required.
separation), decrease the tubing diameter or increase the calibration gas
flow rate. Always confirm calibration at the sensor.
Sensors
Figure 4: F
IRE HEAD and CONTROLLER/TRANSMITTER
+24V / +24Vdc
4-20 / 4-20 O/P
COM / COMMON
RM2
White
Black wire
Red
Blue
wire
wire
wire
RM2
Note: Refer to the F
more detailed wiring instructions.
Figure 5: Remote Reset
Note: Clears latched alarms for both RM2 channels.
IRE HEAD or CONTROLLER/TRANSMITTER
—Wiring
—
Wiring
manual for
RM2-ARD 4
Net Safety Monitoring Inc
STEP 3 —
O
PERATE
Figure 6: RM2 Front Panel Functionali ty
S
T A R
T UP
Once all terminal wiring and Jumper settings are complete, the RM2 may be
powered up.
The time it takes the RM2 to power up is dependent on whether it is connected
to a Fire head , a transmitter/controller with sensor or directly to ST series sensor.
For
C
ONTROLLERS
after the system has been powered up;
current output is 3.0 mA.
with sensor and
FIRE Heads , a 90 seconds routine will begin
the System Status LED blips green and
The unit will power up immediately when a
ST series
sensor is directly connected to it.
Note:
Channel types are defined at purchase and factory set.
Normal Operation
Once the warm-up routine has ended, normal operation begins as indicated in
T able 1.
Table 1: Normal Operation Indicators
Type
Fire Head
ST Series Sensors
Controllers/
Transmitters
System
Status LED
Green Blip
Channel 1 or 2
Display Message
N O R M
0 0
Current
Output
4.0 mA
Operational Test
Once normal operation has been established, consult the manual provided with
the Fire Head, Sensor, Controller or Transmitter for instructions on operational
testing.
Ensure that all safety precautions and regulatory requirements for the
application are met.
F
RO N
T PA N E L
The RM2 Front Panel contains convenient LEDs and displays to provide
information regarding the RM2 status; the push button facilitates various
settings/activities; and the RS-232 port supports communication with a PC.
Channel Type Identifier
(YELLOW) Functions as
(1 per channel)
Fault LED for Fire;
Low Alarm for Gas
%LEL
CHANNEL
1
R1 R2
Cal/Reset
FIR
E
CHANNEL
Scrolling Display
(1 per channel)
(RED) Functions as
Alarm LED for Fire;
High Alarm f or Gas
2
Calibration/Reset
Button
(1 per
channel)
System Fault LED
R3 R4
Cal/Reset
Fault Status
RS-232
PC COMM
Model#: RM2
System Status LED
(also active during
calibration)
Serial Port
PC Communication
Interface RJ-11
LEDs
There are two LEDs dedicated to each channel and two additional System
LEDs. The LEDs will turn solid or flash depending upon the status of the RM2.
Refer to the section titled "Monitor" on page 12 and review the tables listing the
various devices, LEDs and states.
RM2-ARD 5
Net Safety Monitoring Inc.
Channel LEDs
T wo LEDs are dedicated to each channel and, dependi ng on the type of detector
connected (fire or gas), the LED indicates which relay has been tripped.
LED MARKED GAS CONNECTED FIRE CONNECTED LED
R1 or R3 LOW alarm FAULT alarm yellow
R2 or R4 HIGH alarm FIRE alarm red
C
OLOUR
Common System LEDs
A Fault and Status LED are provided and are common to both channels. The
Status LED is also active during calibration.
Display
Each channel has a separate, 4-character scrolling display visible in most
lighting conditions.
Cal/Reset Button
Each channel has a push button for calibration (ST SENSORS only), setting relay
options, clearing latched alarms, turning channels on or off and bypassing
channels.
RS-232 PC COMM port
The COMM port is an RJ-11 compatible, RS-232 suitable PC communications
port for interfacing with the RM2 at the Front Panel (refer to
"Communication" on page 6 for details).
Using the Front Panel
1. Ensure that the RM2 has been turned on and no fault is present.
2. Press and hold the Cal/Reset button until the message
S w i t c h O n
displays and the countdown 10 to 1 finishes.
3. An option will scroll across the display followed by the prompt
Y E S ?
4. To select an option, momentarily press the Cal/Reset button at the Y E S
prompt.
5. If you do not wish to select that option wait until the next option appears
and then select
Y E S ?
6. A selection is acknowledged with a flashing Y E S .
7. If no option is selected, the RM2 returns to normal operation.
C
O M M U N I C A T I O N
RS-232 Communications Port
The RS-232 is compatible with standard terminal software which m ust be used
to communicate with the RM2. The terminal software can be used to modify
various options, set parametres and view the Event L og.
A RJ-11 compatible cable and DB9 connector are required to connect the RM2
serial port (refer to "Part Numbering" on page 18) to an interface device such as
PDA or computer loaded with standard Terminal software.
WARNING: The Alarm System connected to the RM2 must be in
Bypass.
Terminal Software
RS-232 compatible terminal software must be installed on the device
communicating with the RM2 (i.e., computer , PDA, etc.). When creating a new
connection definition, the appropriate COM port must be defined for proper
communication to be established. The Properties for that port must be set as
shown in Figure 7, "Terminal Software—Setup Properties", on page 6.
Figure 7: Terminal Software
?
—Setup Properties
RM2-ARD 6
T
Net Safety Monitoring Inc
Using Terminal Software
1. Open terminal software and establish a connection.
2. Once connected, press Enter for Main Menu.
3. The Main Menu will display an entry for each channel plus Event Logging
and Display Language as well as a serial and version number.
4. Enter a number 1, 2, 3, etc., and press Enter to m ake a selection from any
menu.
5. Press Enter twice to return to the Main Menu.
Figure 8: Terminal Software—Main Menu
S
E T T I N
G OP T I O N S
Options can be set from the Front Panel, the RS-232 T erminal interface or, in some
cases, both.
WARNING: DO NOT interrupt setup from Front Panel by using Terminal
software.
Front Panel / Terminal Functionality
Calibrate
S
ENSOR
*
Set and Review Relay settings
Set Sensor Range
Set Display Language
Reset Channel
Power Down mode per channel
Momentary BYP ASS** m ode per channel
Channel Permanent OFF
Define Channel T ype
Event Logging - setup and review
Current Firmware version
Front Panel
*
* *
*
*
*
erminal
*
*
*
*
*
*
* ST Series Sensors only; otherwise calibrate from Uni-Tran/Millennium
controller/transmitter.
** BYPASS mode is only available when both channel types are FIRE.
Power Down Mode
Each channel can be individually turned of f from the Front Panel for
maintenance.
WARNING: When in power down mode, the RM2 channel will neither
alarm nor transmit current output.
1. Press and hold the Cal/Reset button on the Front Panel. Wait for the
S w i t c h O n message and countdown (10-0) to complete.
2. When
P o w e r D o w n C h a n n e l Y E S ? displays press the Cal/Reset
Button.
3. The message
A r e y o u s u r e ? Y E S ? displays. At the Y E S ? prompt,
press the Cal/Reset button to select. The RM2 channel is now powered
down.
4. The message
O f f will continue to scroll on the display while the channel is
in power down mode.
5. To return to normal channel operation, press the Cal/Reset button. Channels
defined as
FIRE have a 90 second start delay prior to returning to normal
operation.
RM2-ARD 7
Net Safety Monitoring Inc
BYPASS Mode—FIRE only
When both Channels are defined as FIRE, each channel can be individually
placed into Bypass mode from the Front Panel for testing and detector
replacement. When in Bypass mode, the channel relays will not trip nor will an
output signal be transmitted.
Bypass mode is momentary; pressing the Cal/Reset Button will return the
Channel to normal operation.
1. Press and hold the Cal/Reset button on the Front Panel. Wait for the
S w i t c h O n message and countdown (10-0) to complete.
2. When
C h a n n e l B y p a s s Y E S ? displays press the Cal/Reset Button.
3. The message A r e y o u s u r e ? displays. At the Y E S ? prompt, press the
Cal/Reset button to select.
4. The message
B y p a s s C h a n n e l will continue to scroll and the Yellow
System Fault LED will turn Solid. Press the Cal/Reset Button at any time to
return channel to
N O R M .
Permanent OFF
If a channel is not required, it can be permanently turned OFF using the
T erminal Software.
1. Open terminal software and establish a connection.
2. Once connected, press Enter for Main Menu.
3. Select the Channel number to be turned off.
4. Enter 1 (sensor type) until =
Off is displayed.
Note: The Terminal Software must also be used to turn the Channel ON.
R
E L A
Y OP T I O N S
Review Relay Settings
The current relay settings can be viewed using either the Terminal Software or
the Front Panel. Use Cal/Reset button for either channel and select
R e l a y S e t t i n g s when using Front Panel; enter a channel number and
R e v i e w
review displayed settings using T erm inal Software.
Figure 9: Terminal Software
—Relay Settings
Current
1) Sensor type=Fire
2) Coil Status=De-Energized
3) Latch Status=Non Latching
Press 1->3, then press the Enter key
Current
1) Sensor type=ST Series
2) Coil Status=De-Energized
3) Latch Status=Non Latching
4) High Alarm Level=40
5) Coil Status=De-Energized
6) Latch Status=Non Latching
7) Low Alarm Level=20
8) Sensor Range=100
Press 1->8, then press the Enter key
Note: When switching Sensor Type, establish a new connection and reset all
WARNING: Do not attempt to setup the RM2 using the Terminal
Software if setup has already begun at Front Panel.
Set the Low and High Alarm relays for Gas as well as Sensor range. Set the
High Alarm for Fire. The Fault Relay is fixed as Energized/Non-latching and
cannot be changed.
WARNING: The scale (PPM) of the sensor connected, with or without a
controller, must match the scale entered in the field Sensor Range.
1. Open terminal software and establish a connection.
2. Once connected, press Enter twice for Main Menu.
3. Enter a number 1 or 2 for the required Channel.
4. Enter the number for a setting. In most cases, entering a number will toggle
between setting options; for alarm levels and range, a prompt will appear at
the bottom of the screen
. Enter level/range and press Enter again to confirm
entry.
5. Press Enter twice to return to the Main Menu.
Setting Relays—Front Panel
F
IRE
The High Alarm (Fire relay) can be set to Energized or De-Energized and
Latching or Non-latching. The Fault Relay is fixed as Energized/Non-latching.
Step 1: Press and hold the Cal/Reset button on the Front Panel. Wait for the
S w i t c h O n message and countdown (10-0) to complete.
Step 2: When S e t R e l a y O p t i o n s Y E S ? displays press the Cal/
Reset Button.
Step 3: The message
display then shows
E n e r g i z e d Y E S ?
setting when it displays. The flashing
H i g h A l a r m – – – C o i l S t a t u s displays. The
E n e r g i z e d Y E S ? and then D e -
. Press the Cal/Reset Button to select the
Y E S confirms the selection.
If no selection is made, the next option displayed.
Step 4: The message
L a t c h i n g Y E S ? and then N o n L a t c h i n g Y E S ? . Press the
L a t c h S t a t u s displays. The display then shows
Cal/Reset Button to select the setting when it displays. The flashing
Y E S confirms the selection.
Step 5: Once set, the RM2 will return to
N O R M .
ERIES SENSORS/CONTROLLERS
ST S
There are two settings for the Alarm Relays: Low and High. The Coil Status,
Latch Status and Alarm Level for the Low alarm are set first, followed by the
High. The Fault Relay is fixed as Energized/Non-latching and cannot be
changed.
Step 1: Press the Cal/Reset button, wait for countdown to finish and when
S e t R e l a y O p t i o n s Y E S ? displays press the Cal/Reset
Button again to select. The flashing
Step 2: The message
display then shows
E n e r g i z e d Y E S ?
setting when it displays. The flashing
Step 3: The message
L a t c h i n g Y E S ? and then N o n L a t c h i n g Y E S ? . Press the
Cal/Reset Button to select. The flashing
L o w A l a r m – – – C o i l S t a t u s displays. The
E n e r g i z e d Y E S ? and then D e -
. Press the Cal/Reset Button to select the
L a t c h S t a t u s displays. The display then shows
Y E S confirms the selection.
Y E S confirms the selection.
Y E S confirms the
selection.
Step 4: The message
S e t L o w displays. Low alarm set-points are then
displayed in varying increments (increment dependant upon
defined sensor range). When the required level displays, press the
Cal/Reset Button to select. The level chosen will flash to confirm
the selection.
Step 5: The message
display then shows
E n e r g i z e d Y E S ? . Press the Cal/Reset Button to select. The
flashing
Step 6: The message
L a t c h i n g Y E S ? and then N o n L a t c h i n g Y E S ? . Press the
Cal/Reset Button to select. The flashing
H i g h A l a r m – – – C o i l S t a t u s displays. The
E n e r g i z e d Y E S ? and then D e -
Y E S confirms the selection.
L a t c h S t a t u s displays. The display then shows
Y E S confirms the
selection.
Step 7: The message
S e t H i g h displays. High alarm set-points are then
displayed in varying increments (increment dependant upon
defined sensor range). The high alarm set-point is always higher
than the low alarm level. When the required level displays, press
the Cal/Reset Button to select. The level chosen will flash to
confirm the selection.
Step 8: Once set, the RM2 will return to
0 0 .
RM2-ARD 9
Net Safety Monitoring Inc
S
E L E C
T DI S P L A
Y LA N G U A G E
The display language can onl y be set using the Terminal interface.
1. Open terminal software and establish a connection.
2. Once connected, press Enter twice for Main Menu.
3. The Main Menu will display.
4. Enter the number 4 to select
4) Display Language.
5. The language will change to Espanol then Francais and back to English
each time 4 is entered.
6. Press Enter twice for Main Menu.
Note: The factory default is English.
C
A L I B R A T I O N
WARNING: When using a combustible sensor with the RM2 , the
sensor has to be connected to a transmitter or controller. The 4-20 output
from this configuration is then connected to the RM2 as signal. Calibration
must be performed transmitter or controller NOT the RM2. Refer to the
Uni-Tran or
Use the
messages will appear at RM2.
Calibration Procedure—ST Series
WARNING: The calibration procedure requires approximately
5 minutes to complete. If gas is not applied at the appropriate time, a calibration
failure may occur (refer to "Calibration Failure/Interruption" on page 11 for
specific information).
For accurate performance, calibrate sensors using 50% span of the specific gas
of concern. The concentration of gas, c orresponding to 100% of full scale, is
converted to a linear 4 to 2 0 mA output signal which can be powered from the
primary dc supply of the instrument. Power up the unit for at least 4 hours
BEFORE first calibration.
The following calibration procedure should be followed to ensure an accurate
correlation between the 4 to 20 mA output signal and the gas concentration.
Millennium transmitter manuals for calibration instructions.
ONTROLLERS /TRANSMITTERS to monitor display messages. Not all
C
S
ENSORS
Note: The ST Series S
1. Confirm successful power up of RM2
ENSORS must be calibrated from the RM2 Front Panel.
—Status LED Green Blip; no fault
indicated.
2. Press and Hold Cal/Reset Button until
S w i t c h O N and countdown
completes.
3. When
4. When
5. Wait for
C a l i b r a t e S e n s o r Y E S ? displays, press the Cal/Reset Button
to select
Y E S ? Selection will be confirmed by a flashing Y E S .
A p p l y C l e a n A i r displays apply clean air.
A p p l y 5 0 % S p a n G a s to display and apply specific gas at a
rate of 0.5 litres per minute.
6. The display will show the actual gas value at last calibration.
7. Re move span gas when the message
8. The message
9. Apply zero gas (clean air) again to purge system.
C a l C o m p l e t e will display when calibration is complete.
R e m o v e G a s displays.
Note: Always apply test gas after calibration to verify operation.
The Calibration procedure may be aborted. When the display shows
Display
Shows
C a l i b r a t e
S e n s o r
Y E S
A p p l y C l e a n
A i
A p p l y 5 0
S p a n G a s
C a l i b r a t i n
G a s V a l u e @
l a s t c a l i b r a t i o
R e m o v e G a s
Action
Select Y E S
?
Apply clean (zero air)
r
%
g
Apply specific gas
n
Remove gas
Wait
?
Status LED and
Current Output
Status LED Solid
Green / 3.0 mA
Status LED Fast
Flash Red / 3.3 mA
Status LED Fast
Flash Red / 3.3 mA
Status LED Solid
Green / 3.6 mA
5 0 % S p a n G a s , press and hold the Cal/Reset button until the abort
calibration countdown 10-0 com pletes and the displa y retur ns to
Calibration Failure/In terru ptio n
If the calibration procedure fails, the Status LED alternates between Green and
Red and the analog output changes back and forth from 3. 0 to 3.3 mA. The
message
message
F a i l Z e r o is displayed if span gas is not applied or recognized; the
F a i l S p a n will display if the calibration process is interrupted.
The unit remains in a failed state until manually reset. After the Manual Reset,
the unit will return to normal operation based on previous calibration values.
See "Manual Reset" on page 1 1 for instructions.
R
E S E T
Manual Reset
A Manual Reset is required to clear a latched relay alarm for individual
channels. Simply press the specific Channel’s Cal/Reset Button, on the Front
Panel of the RM2, to clear a latched alarm.
C a l
C o m p l e t e
0 0
Apply clean air
purge
system
Normal
Operation
to
Status LED Solid
Green / 3.6 mA
Status LED Blip /
Green 4.0 mA
Remote Reset
The RM2 can be wired to an external device (refer to illustration"Remote
Reset—Wiring" on page 4) so latched alarms for both channels may be
remotely cleared.
A p p l
0 0 .
y
RM2-ARD 11
Net Safety Monitoring Inc
STEP 4 —
M
ONITOR
E
V E N
T LO G G I N G
The Event Logging feature securely stores in protected RAM up to 1000 events.
The time and date of each occurrence is recorded along with the channel,
detector type and the associated alarm, fault or calibration event. A maximum of
1000 events are stored although as few as 10 events may be viewed at a time.
When the 1000th event is reached, the first event stored will be removed.
In order to accurately track events, the time and date must first be set.
Setting Time and Date
Step 1: Open terminal software and establish a connection.
Step 2: Press Enter for Main Menu.
Step 3: T ype 3 and press Enter to select 3) Event
Step 4: T ype 1 and press Enter to select
Step 5: Enter the hour (24 hours) and then minutes.
Step 6: T ype 2 and press enter to select 2) Date.
Step 7: Enter the day/month/year using 2-di gits for each and separate with
Step 8: Press Enter to confirm entry.
Use 2-digits for hour/minutes and separate with a space.
a space.
Log
Menu.
1) Time.
Figure 1 1: Event Logging Menu
Event Logging Menu
1) Time (HH:MM)=14/04
2) Date (DD/MM/YY)=03/12/03
3) Display last 10 Events
4) Display All Events
Enter 1->4, then press the Enter key
Once the time and date have been set the RM2 will automatically and accurately
track the alarm and fault conditions as well as other events such as sensor
calibration.
Figure 12: Event Logging Display Menu
Time(HH:MM):14.12 - Date (DD/MM/YY):03/12/03 - Ch:02 Event: vi fault
Time(HH:MM):14.12 - Date (DD/MM/YY):03/12/03 - Ch:02 Event: Warning!!
Time(HH:MM):14.12 - Date (DD/MM/YY):03/12/03 - Ch:01 Event: high alarm
Time(HH:MM):03.11 - Date (DD/MM/YY):03/17/03 - Ch:02 Event: fire
Time(HH:MM):19.12 - Date (DD/MM/YY):05/02/03 - Ch:02 Event: fault
Time(HH:MM):22.09 - Date (DD/MM/YY):06/22/03 - Ch:01 Event: high alarm
Time(HH:MM):06.01 - Date (DD/MM/YY):08/11/03 - Ch:01 Event: calibrate
Press Enter Key to exit
Note: Press Enter at any time to stop the scroll through all events.
RM2-ARD 12
Net Safety Monitoring Inc.
F
I RE
Table 2: FIRE—Current Output, LEDs and Display Messages
Status
Power Down Mode 0 mA
Current O/P
Channel 1 and
LEDs
R1 &
R3
Fault
(yellow)
off
R2 &
Fire
(red)
off
2
R4
(yellow
System LEDs
Fault
off
Status
(red)
(green)
-
Blip
Scrolled
Display
Messages
O f f
RM2 System failure 0 mA
Fire Head Electronic failure 0-0.5 mA Solid
Internal Power Fault or system power out of
range
1.0 mA Solid
Automatic VI Test Failure 2.0 mA Solid
Start Delay (90 seconds) 3.0 mA
Normal Operation 4.0 mA
Bypass mode 4.0 mA
Background radiation source UV 6.0 mA
Background radiation source IR 8.0 mA
Early W arni ng - Intermittent radiation
detected
16.0 mA
Fire confirmed 20.0 mA
off
off
off
off
off
off
off
Solid
* The last message displayed prior to the failure will remain on the display .
-
Solid -
off
off
off
off
off
off
Solid - Blip
off
off
off
off
off
off
off
off
off
off
off
off
-
Blip
-
Blip
-
Blip
-
Blip
-
Blip
-
Blip
-
Blip
-
Blip
-
Blip
-
l a s t m e s s a g e *
S e n s o r F a u l t
S e n s o r F a u l t
V I F a u l t
S t a r t D e l a y M i l l e n n i u m
N O R M
C h a n n e l B y p a s s
U V P r e s e n t
I R P r e s e n t
W a r n i n g ! !
F I R E ( f l a s h e s )
RM2-ARD 13
Net Safety Monitoring Inc
FIRE ONLY—Manual Visual Integrity (VI) Testing
The RM2 can be wired (using Terminal 13 for Channel 1 and T erminal 17 for
Channel 2) so F
IRE HEAD Visual Integrity test results can be displayed and
monitored by the RM2.
WARNING: Both Channels must be set to F
IRE for VI Testing and the
connected alarm system placed in bypass. The Phoenix IR3S cannot be wired
for VI testing.
Step 1: Press and hold Channel #1 or #2 Cal/Reset button on the Front
Panel. W ait for the
complete.
S w i t c h O n message and countdown (10-0) to
Step 2: When M a n u a l V I T e s t Y E S ? displays press the Cal/Reset
Button.
Step 3: After 5 seconds, the test lamp turns on for 30 seconds and analog
output drops to 3 mA.
Step 4: Refer to T able 3 below for the list of possible status messages for
the Visual Integrity Test.
Step 5: The VI T est message is displayed for 30 seconds or press and hold
the Cal/Reset Button until the VI display message flashes
(approximately 10 seconds) to return to
30 seconds.
N O R M before the
Table 3: Manual Visual Integrity Testing—FIRE only
Status Display Message
F
IRE ONLY—Force Al a rm O u tp ut Test
The Force Alarm Output tests Relay contacts by switching relays for 2 seconds
and stepping Analog output through the primary alarm levels. Test s are initiated
from the RM2.
WARNING: The connected alarm system must be placed in bypass
during the Force Alarm Output test.
Step 1: Press and hold Channel #1 or #2 Cal/Reset button on the Front
Panel. W ait for the
S w i t c h O n message and countdown (10-0) to
complete.
Step 2: When
F o r c e A l a r m O u t p u t Y E S ? displays press the Cal/
Reset Button.
Step 3: When I s i t S a f e t o A c t i v a t e A l a r m s ? Y E S ? displays,
press the Cal/Reset Button.
Note: If you do not press
Y E S ? as this prompt, the RM2 will return to
normal operation.
Step 4: When
R e l a y s Y E S ? displays, press the Cal/Reset Button. The
flashing
times during the Relay test and then return to
If
Y E S confirms the selection. The message O n will flash 4
N O R M .
Y E S ? is not selected, the next option is displayed.
Step 5: When A n a l o g O P ? Y E S ? displays, press the Cal/Reset
Button. The RM2 will then test primary analog output responses
and then return to
When calibrating a sensor, status is reflected by the System LEDs.
Table 4: ST SERIES SENSORS—Current Output, LEDs and Display Messages
Status
Current O/P
Start Delay (few seconds) 3.0 mA
Normal operation 4.0 mA
Power Down Mode 0 mA
RM2 System failure 0 mA
Sensor Fault <2.5 mA
Excess drift (>10%) 2.5 mA
Calibrate Sensor 3.0 mA
Apply clean air 3.0 mA
Apply calibration gas - 50% span
3.3 mA
Span is set, remove gas 3.6 mA
Return to normal operation 3.6 mA
Calibration procedure failed/interrupted 3.0 / 3.3 mA
Gas present
>4.0-20.0 mA
* The last message displayed prior to the failure will remain on the display .
Channel 1 and
LEDs
1&R3
Low
(yellow)
(when
off
off
off
off
off
off
off
off
off
off
off
ON
set
point
reached)
2
R2 &
R4
High
(red)
off
off
off
-
Solid off
off
off
off
off
off
off
off
ON
(when
(yellow)
Solid - Blip
Solid - Blip
set
point
reached)
System LEDs
Fault
off
off
off
off
off
off
off
off
off
Alternate
off
Status
(red)
(green)
-
Blip
-
Blip
-
Blip
-
Solid
Fast
Flash
-
Solid
-
Solid
-
S t a r t D e l a y M i l l e n n i u m
-
l a s t m e s s a g e *
C a l i b r a t e S e n s o r
Solid
-
Blip
A p p l y C l e a n A i r
A p p l y 5 0 % S p a n G a s
1 t o 1 0 0 % f u l l S c a l e
Scrolled
Display
S e n s o r F a u l t
( g a s v a l u e
R e m o v e g a s
C a l . c o m p l e t e
( g a s v a l u e
Messages
0 0
O f f
N e g D r i f t
F a i l Z e r o
F a i l S p a
)
n
)
RM2-ARD 15
R
Net Safety Monitoring Inc.
C
O N T RO L L E R S
/TR A N S M I T T E R S
The RM2 receives and interprets the 4-20 current output sent by the Un i-Tran or the Millennium. Not all visuals
Table 5: CONTROLLERS/TRAN SMITTERS—Current Output, LEDs and Display Messages
Status
Start Delay (90 seconds)
Message will also appear
when calibrating
the
C
ONTROLLER
RANSMITTER
T
from
/
Normal operation
Message will also appear
when calibrating
the
C
ONTROLLER
RANSMITTER
T
from
/
Current O/P
3.0 mA
4.0 mA
Power Down Mode 0 mA
Channel 1 and 2 LEDs System LEDs
1&R3
Low
(yellow)
off
off
off
R2 &
High
(red)
off
off
off
R4
Fault
(yellow)
off
off
off
Status
(red)
off
off
off
(green)
Blip
Blip
Blip
aler
ts will appear at the RM2.
Scrolled
S t a r t D e l a y M i l l e n n i u m
Display
Messages
0 0
O f f
RM2 System failure 0 mA
Sensor Fault 2.5 mA
Gas present
>4.0-20.0 mA
off
off
ON
(when set
reached)
point
off
off
ON
(when set
reached)
Solid
Solid
off
off
point
off
off
off
l a s t m e s s a g e *
Blip
Blip
S e n s o r F a u l t
1 t o 1 0 0 % f u l l S c a l e
* The last message displayed prior to the failure will remain on the display .
RM2-ARD 16
Digital output from Modbus Set-up:
The RM2-ARD also allows digital output to be monitored by the user. Ensure that the proper connections are made when connecting the RM2ARD output terminals 19 and 20 (marked ‘A’ and ‘B’) to PLC (RTU). For output bit assignments for Combustible and Toxic sensor see table 7
and table 8. For output bit assignment for Fire head see table 9.
Hardware Setup
Figure 13: User interface for Modbus setup
For Hyper Terminal connection: An RJ11 cable with DB9 (female) connector is
used for RS-232 serial connection. Use the RJ 11 and DB9 (female) connector
with a RS-232(male) to USB converter, if the computer doesn’t ha ve a RS-232
serial connection.
RM2‐ARD
RJ11 connection
Output terminal A
Output terminal B
Front of unit Rear of unit
Modbus RTU Slave Modbus RTU Master
Note: For Modbus communication, the user should w ire the system according RS 485 conventions and adhere to local electrical codes.
User input interface for hyper terminal
Computer
USB or RS232 serial input
PLC
A
B
RM2‐ARD
17
Software Setup
Connect the Modbus output using baud rates of 4800, 9600, 14.4 K, 19.2K, 28.8 K, 38.4K or 57.6 K bps. Parity is none and stop bit is 1.
Addresses are assigned by the user.
Modbus Register definitions
Four Modbus registers are utilized when setting up for digital output. They are as follows:
Binary values of Registers 40003 and 40004 are used indicate the type of sensor /detector being used. With 16 bits( 2 byte) assigned to each
register , only bits # ‘s 0, 1, 2 and 3 are utilized at this time. Table 1 below shows the bits assigned for combustible sensor setup, toxic sensor and
Flame detector.
Table 6: Status bit assignment for sensor type (Combustible, Toxic and Fire)
Note: Channel bypass is only available if both channels are set for fire.
Sensor power OFF
(loss of power fromFire head)
RM2‐ARD
20
Net Safety Monitoring Inc
STEP 5 —
SENSORS—Periodic Response Test
M
AINTAIN
We recommend the sensors be verified or calibrated every 3 months. A typical
response check involves the application of calibration gas to the sensor, then t he
observation of the response LEDs, analog output, display and external
monitoring equipment. Be sure to prevent unwanted response of external
monitoring devices and equipment during this procedure. If the response to
calibration gas is within its specified accuracy then it is not necessary
perform
a calibration. For example, when 50% of full scale is applied, the
to
response is expected to be between 11.5 mA (47% of full scale) and 12.5 mA
(53% of full scale). An additional consideration is the accuracy tolerance of the
calibration gas which may be + or - a few percent. If t he calibration gas is + or 10% of full scale then the reading may be from 10.7 mA (42% of full scale) to
13.3 mA (58% of full scale).
T
RO U B L E SH O OT
- Response to the input should be checked and, if necessary, calibration should
be performed whenever any of the following occur. Refer to "Calibration" on
page 10 for calibration instructions.
•Excess negative drift is indicated by 2.5 mA current output
•Sensor or controller/transmitter is connected or disconnected
•Long term or high concentration exposure to gas
- The RM2 is not designed to be repaired in the field. If a problem should
develop, first calibrate the device and carefully check for faulty wiring. If it is
determined that the problem is caused by an electronic failure, the device must
be returned to the factory for repair. Refer "How to Return Equipment" on
page 18 for detailed instructions.
- Apparent sensor failure (see "Calibration Failure/Interruption" on page 11)
may occur if calibration process has begun but span gas is not applied when
prompted or if span gas is removed during calibration process. Perform a
manual reset (refer to "Manual Reset" on page 11) and re-calibrate sensor.
- If Front Panel buttons appear non-responsive
—recycle power. (Can occur
when set up at Front Panel is interrupted by an attempt to also set up using
T erminal) . DOES NOT af fect detection functionalit y.
- Consult the manual supplied with the Fire Head, Millennium or Uni-Tran for
further troubleshooting information.
RM2-ARD 21
Net Safety Monitoring Inc.
HOW TO RETURN
E
QUIPMENT
A Material Return Authorization number is required in order to return
equipment. Please contact Net Safety Monitoring at (403) 219-0688 before
returning equipment or consult our Service Department to possibly avoid
returning equipment.
If you are required to return equipment, include the following i nformation:
1. A Material Return Authorization number (provided over the phone to you
by Net Safety).
2. A detailed description of the problem. The more specific you are regarding
the problem, the quicker our Service department can determine and correct
the problem.
3. A company name, contact name and telephone number.
4. A Purchase Order, from your company , authorizing repairs or request for
quote.
5. Ship all equipment, prepaid to:
Net Safety Monitoring Inc
2721 Hopewell Place NE
Calgary, Alberta, Canada
T1Y 7J7
6. Mark all packages: RETURN for REP AIR
W a ybills, for shipments from outside Canada, m ust state:
Equipment being returned for repair
All charges to be billed to the sender
Also, please ensure a duplicate copy of the packing slip is enclosed inside the
box indicating item 1-4 along with the courier and account number for returning
the goods.
All Equipment must be Shipp ed prepaid. Collect shipments will not be
accepted.
Pack items to protect them from damage and use anti-static bags or aluminumbacked cardboard as protection from electrostatic discharge.
S
P A
RE PA R T S
/AC C E S S O R I E S
Table 10: Part Numbering
Description Net Safety Part Number
Communications Kit RM2-COM-KIT
W all m ount Controller Box WM2-HSG-ASSY
Solar Shield, 2-channel Analog/Relay
Output for Toxic and Combustible sensors or
SS2-AR
Fire Detectors
Solar Shield, 2-channel Controller/Terminal
Box
SS2-HSG-ASSY -12V or
24V
Solar Shield 2-Battery Enclosure SS-2BAT-ASSY
Solar Shield Pole Installation Assembly SS-POLE-ASSY
Solar Shield 50 Ft Power Cable Extension CAB-0035
Solar Shield Battery Box Interconnect cable CAB-0041
RM2-ARD 22
Net Safety Monitoring Inc
Appendix A:
E
LECTROSTATIC SENSITIVE DEVICE (ESD)
Electrostatic discharge (ESD) is the transfer, between bodies, of an electrostatic
charge caused by direct contact or induced by an electrostatic field.
The most common cause of ESD is physical contact. Touching an object can
cause a discharge of electrostatic energy
occurs near electronic components, it can damage or destroy those components.
In some cases, damage is instantaneous and an immediate malfunction occurs.
However, symptoms are not always
or seemingly normal for an indefinite period of time, followed by a sudden
failure.
T o eliminate potential ESD damage, review the following guidelines:
• Handle boards by metal shields—taking care not to touch electronic
components
• Wear grounded wrist or foot straps, or ESD shoes or heel grounders to
dissipate unwanted static energy
• Prior to handling boards, dispel an y charge in your body or equi pment
• Ensure components are transported and stored in static safe packaging
• When returning boards, carefully package in the original carton and static
protective wrapping
• Ensure ALL personnel are educated and trained in ESD Control Procedures
In general, exercise accepted and proven precautions normally observed when
handling electrostatic sensitive devices.
A warning label is placed on the packaging, identifying product using
electrostatic sensitive semiconductor devices.
Note: Resistance shown is one way . This figure should be doubled when determining closed loop resistance.
WG #20
WG #18
WG #16
WG #14
WG #12
WG #10
WG #8
RM2-ARD 24
Net Safety Monitoring Inc
Appendix C: RM2 S
PECIFICATIONS
MILLENNIUM RM2-ARD (ANALOG / RELAY / DIGITAL)
Operating V oltage
Power Consumption 12 V dc
Power Consumption 24 V dc
Operating T emperature
Humidity Range
Chassis Material
Weight
Certifications
Current Outputs-2 channel
Relay Output-5 relays
Digital Output
10.5 V dc to 32 V dc
nominal 150 mA/250 mA (1.8 W/3.0 W) de-energized/energized m aximum 290 mA/3.48 W
nominal 80 mA/130 mA (1.92 W/3.12 W) de-energized/energized maximum 160 mA/3.84 W
-40
°C to +80°C (-40F to +176F)
0-100% relative humidity , non-condensing
16 gauge steel / powder coated or chromatic
2 lbs (0.9 kilograms)
CSA and NRTL/C for hazardous locations. Class 1, Division 2, Groups A, B, C and D
4 to 20 mA - Into a maximum loop im pedance of 800 Ohms at 32 V dc or 150 Ohms at 10.5 V dc. Isolated or non-
isolated loop supply.
Form C contacts rated 5 Am ps at 30 V dc / 250 V ac. Sel ectable ener gized/de-energized, latching/non-latching Fire
Relay . Fault relay is factory set as energized, non-latching and cannot be modified.
Digital output available via terminals 19 and 20 (A and B) for Modbus communication.
RM2-ARD25
Y
NET SAFET
MONITORING
Net Safety Monitoring
2721
Hopewell Place NE
C
algary,
Alberta, Canada Tl Y 7J7
Telephone: (403) 219-0688 Fax: (403)
netsafe@net-safety.com
E-mail:
N\'/W.netsafety.com
Inc.,
INC.
219-0694
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.