Rosemount Millennium MLP Controller with UV/IRS-UVS or IR3S Flame Detector Manuals & Guides

4-20 mA FIRE HEAD
with

Analog/RS-485 Modbus (AD)

CONTROLLER

User Manual

Part Number: MAN-0069 Rev 2
May 2006
Net Safety Monitoring Inc
This manual is for informational purposes only. Although every effort has been made to ensure the correctness of the information, technical inaccuracies may occur and periodic changes may be made without notice. Net Safety Monitoring Inc., assumes no responsibility for any errors contained within this manual.
If the products or procedures are used for purposes other than as described in the manual, without receiving prior confirmation of validity or suitability, Net Safety Monitoring Inc., does not guarantee the results and assumes no obligation or liability.
No part of this manual may be copied, disseminated or distributed without the express written consent of Net Safety Monitoring Inc.
Net Safety Monitoring Inc., products are carefully designed and manufactured from high quality components and can be expected to provide many years of trouble free service. Each product is thoroughly tested, inspected and calibrated prior to shipment. Failures can occur which are beyond the control of the manufacturer. Failures can be minimized by adhering to the operating and maintenance instructions herein. Where the absolute greatest of reliability is required, redundancy should be designed into the system.

Warranty

Net Safety Monitoring Inc., warrants its sensors against defective parts and workmanship for a period of 24 months from date of purchase; other electronic assemblies for 36 months from date of purchase.
No other warranties or liability, expressed or implied, will be honoured by Net Safety Monitoring Inc.
Contact Net Safety Monitoring Inc., or an authorized representative for details.
We welcome your input at Net Safety Monitoring. If you have any comments please contact us at the phone/address below or visit our web site and complete our on-line customer survey: www.net-safety.com.

Contact Information

Net Safety Monitoring Inc. 2721 Hopewell Place NE Calgary, AB Canada T1Y 7J7 Telephone: (403) 219-0688 Fax: (403) 219-0694 www.net-safety.com E-mail: netsafe@net-safety.com
Copyright © 2004 Net Safety Monitoring Inc. Printed in Canada
Net Safety Monitoring Inc
TABLE OF CONTENTS
Important Information
Warranty Contact Information
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
The Product ...................................................................................................... 1
Fire Head ............................................................................................................... 1
The Controller ....................................................................................................... 1
The Manual ........................................................................................................... 1
Step 1 — Plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Figure 1: Dimensional Drawings ............................................................................. 1
Step 2 — Install . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Unpack ............................................................................................................. 2
Figure 2: Components .............................................................................................. 2
Locate Controller/Fire Head ............................................................................ 2
Fire Head ............................................................................................................... 2
Controller .............................................................................................................. 2
Step 3 — Wire . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Field Installation .............................................................................................. 3
Seal ................................................................................................................... 3
Connecting Wires ................................................................................................. 3
Figure 3: Internal PCB Boards ................................................................................. 3
Wiring—Controller .......................................................................................... 4
RS-485 Communication ........................................................................................ 4
Figure 4: Wiring—Fire Head, Junction Box and Controller .................................... 4
Non-Isolated/Isolated Wiring .......................................................................... 5
Terminal Connection ............................................................................................. 5
Figure 5: Non-isolated Terminal Connection .......................................................... 5
Figure 6: Isolated Terminal Connection .................................................................. 5
Current Output ....................................................................................................... 5
Figure 7: Jumper Positions-Current Output ............................................................. 5
MODBUS Termination .................................................................................... 6
Figure 8: Modbus Termination Jumpers .................................................................. 6
Step 4 — Operate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Figure 9: Controller Functionality ............................................................................7
The Main Menu ................................................................................................8
Accessing the Main Menu .....................................................................................8
Calibration Button ............................................................................................8
Magnetic Reed Switch .....................................................................................8
Main Menu Functionality ......................................................................................8
Power Up ...............................................................................................................8
Current Loop Measurement (Test Jacks) ...............................................................8
Status LED .............................................................................................................8
Select Display Language ..................................................................................9
Modbus Options ...............................................................................................9
Node Address ........................................................................................................9
Baud Rate ..............................................................................................................9
Reset .................................................................................................................9
Manual Reset .........................................................................................................9
Step 5 — Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Table 1: Current Output, LEDs and Display Messages .........................................10
RTU Registers ................................................................................................10
Table 2: RTU Output Register (400001) Read Only (binary) ................................10
Table 3: RTU Status Register (400002) Read Only (binary) .................................10
Step 6 — Maintain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
How to Return Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Face Rotation Option ......................................................................................12
Figure 10: Non-standard Orientation ......................................................................12
Rotate PCB Assembly .........................................................................................12
Figure 11: Rotate PCB Assembly ...........................................................................12
Appendix A: Electrostatic Sensitive Device (ESD) ........................13
Appendix B: Resistance Table (Ohms) ...........................................14
Appendix C: Specifications ..............................................................15
Net Safety Monitoring Inc

INTRODUCTION

Net Safety's line of premium industrial controllers are a microcontroller based system providing fast, accurate and continuous monitoring in extreme environments.

THE PRODUCT

Fire Head

Net Safety’s 4-20 mA output UV/IRS, UVS, IRS, and Phoenix IR3S fire detector heads can be used in conjunction with the Digital Controller.

The Controller

The Controller has an explosion-proof Housing, rated Class 1, Division 1, Groups B, C, and D for hazardous applications. It was designed for either a 1-man, intrusive calibration or 2-man non-intrusive calibration.

The Manual

The manual has been designed to make installation of the product easy. To ensure proper installation, follow the steps outlined in the following pages. If you encounter problems during operation, consult the troubleshooting section or contact your sales representative.
STEP 1 — PLAN

Figure 1: Dimensional Drawings

5.5996”
5.28”
4.06”
2.6000”
3/4” NPT
Controller
6.84920”
2.95”
Step 1 — PLAN
Step 2 — INSTALL
5.00”
Step 3 — WIRE
Step 4 — OPERATE
4.00”
Junction Box
Step 5 — MONITOR
Step 6 — MAINTAIN
Note: Refer to the specific Fire Head manual for Fire Head dimensions.
Modbus Controller & 4-20 Fire Head 1
Net Safety Monitoring Inc.
STEP 2 — INSTALL

UNPACK

Carefully remove all components from the packaging. Check components against the enclosed packing list and inspect all components for obvious damage such as broken or loose parts.
If you find any components missing or damaged, notify the representative or Net Safety Monitoring immediately.

Figure 2: Components

Controller Housing
Faceplate
Housing Cover

LOCATE CONTROLLER/FIRE HEAD

Fire Head

Locate Fire Heads as per the manual provided with the specific product.

Controller

The Controller should be mounted near eye-level and be easily accessible for maintenance purposes.
Ensure all devices are securely mounted, taking into consideration all requirements.
Use the Face Rotation Option to mount the Controller at a different orientation (refer to "Face Rotation Option" on page 12 for detailed instructions).
Note: Refer to the specific Fire Head manual for components.
Modbus Controller & 4-20 Fire Head 2
Net Safety Monitoring Inc
STEP 3 — WIRE

FIELD INSTALLATION

WARNING:
Wiring codes and regulations may vary. Compliance with regulations is the responsibility of the installer. Wiring must comply with applicable regulations relating to the installation of electrical equipment in a hazardous area. If in doubt, consult a qualified official before wiring the system.
• If the 4-20 mA output signal is not used, connect a jumper between the 4-20 terminal and the Common terminal.
• The use of shielded cable is highly recommended for signal, input, output and power wires to protect against interference caused by extraneous electrical or electromagnetic 'noise'.
• In applications where the wiring cable is installed in conduit, the conduit must not be used for wiring to other electrical equipment.
• The maximum distance between the Sensor and Controller is limited by the resistance of the connecting wiring, which is a function of the gauge of the wire being used.
• When developing a RS-485 chain of devices, the last device in the chain requires end of line termination.
• RS-485 connection 2-wire, multipoint serial line.

SEAL

• The jacket and shielding of the cable should be stripped back to permit the seal to form around the individual wires. This will prevent air, gas and water leakage through the inside of the shield and into the enclosure.
• It is recommended that explosion-proof drains and conduit breathers be used. In some applications, alternate changes in temperature and barometric pressure can cause 'breathing' which allows moist air to enter and circulate inside the conduit. Joints in the conduit system are seldom tight enough to prevent this 'breathing'.

Connecting Wires

1. Use a small screw driver to gently press down
and hold the spring connector open.
2. Insert appropriate wire into open connector
hole.

3. Release screw driver to secure wire.

Figure 3: Internal PCB Boards

Terminal Board
Option Board/RS-485 Modbus RTU Communication Board (refer to Figure 4 for details).
(refer to Figure 4 for details).
• Water-proof and explosion-proof conduit seals are recommended to prevent water accumulation within the enclosure.
• Seals should be located as close to the device as possible and not more than 18 inches (46 cm) away.
• Explosion-proof installations may require an additional seal where conduit enters a non-hazardous area. Ensure conformity with local wiring codes.
• When pouring a seal, use a fibre dam to assure proper formation of the seal. Seals should never be poured at temperatures below freezing.
Sensor Board (refer to Figure 4 for details).
Modbus Controller & 4-20 Fire Head 3
Net Safety Monitoring Inc
WIRINGCONTROLLER
WARNING:
Power to the unit must be OFF before wiring.
1. Once the Controller’s Housing Cover is removed, connect the Fire Head to
the Junction Box, the Junction Box to the Controller and the Output Terminals to the output signal wires.
2. Replace the Controller’s Housing Cover and turn Controller On.
3. Ensure display reads Start Delay, Status LED is Red Slow Flash and
current output displays 3.0 mA. This is the start-up delay sequence which will last approximately 90 seconds.
Figure 4: Wiring
Fire Head, Junction Box and Controller
A
B
COM
-
Modbus RTU Ter mina ls
to PLC
RST
+24V
COM
4-20
ISO
+24V
SIG
Shielded copper instrument wire (minimum 18 AWG) should be used for separations up to 500 feet. Shielded copper instrument wire (minimum 16 AWG) should be used for separations up to 2000 feet. Consult the factory if a greater separation distance is required. Ensure the appropriate wire is used for Class 1/Division 1 hazardous applications.
Note: If the 4-20 mA signal is not used, connect a jumper between the 4-20
terminal and the COM terminal on the Terminal Board.

RS-485 Communication

Connect devices in a chain via the Modbus terminals. The last device in the chain requires end of line termination (refer to "MODBUS Termination" on page 6).
RST = Remote Reset
+24V = Power +
Power Terminals
COM = Power -
4-20 = Current Output
ISO = +24V isolated 4-20 power
Com -
+24V = +24V
Shld
Manual Vi Test Button
Sig = 4-20
n/a
COM = COM
Shld
Sensor Terminals
Shield
Cut Shield
MVI
+24V
COM
4-20
Blu
W
Blk
Red
Fire Head Input to Junction Box
Internal Ground (Green Wire)
Modbus Controller & 4-20 Fire Head 4
Net Safety Monitoring Inc

NON-ISOLATED/ISOLATED WIRING

Terminal Connection

Figure 5: Non-isolated Terminal Connection

Terminal Board Power Terminal Strip
RST
+24V
COM
4-20
ISO

Figure 6: Isolated Terminal Connection

Terminal Board Power Terminal Strip
to Monitor
Power Supply

Current Output

To set an isolated current output, simply move the Jumper (shorting jack) to either the isolated or non-isolated current position (refer to Figure 7).
Note: Unless otherwise specified, all models ship with non-Isolated current
output.

Figure 7: Jumper Positions-Current Output

Termina l B oard
Position 1 & 2 = Isolated
Sensor Board
Jumper—Position Jumper
(shorting jack) over pins to set power source for current output.
Position 3 & 2 =
Non-isolated (default)
Termination Jumper—Is non-
functional in this application. Keep in position 3 & 2 or removed entirely.
RST
+24V
COM
4-20
ISO
to Monitor
Power Supply
Modbus Controller & 4-20 Fire Head 5
Net Safety Monitoring Inc.

MODBUS TERMINATION

Devices are networked in a daisy chain. The device located at the end of the chain requires end of line termination. Place both jumpers over the pins, as shown in Figure 8, for end of line termination.
Figure 8: Modbus Termination Jumpers
Modbus Controller & 4-20 Fire Head 6
Net Safety Monitoring Inc.
STEP 4 — OPERATE
The Controller faceplate contains most functional elements of the user interface. Below is a description of that functionality.

Figure 9: Controller Functionality

Scrolling 8-character display -
provides various status messages and
Magnetic Reed Switch - provides non-intrusive access for programming and resetting.
-Place magnet against Housing (where indicated) for less than one second to initiate a basic system reset (clear a latched alarm) and make selections.
-Place magnet against Housing (where indicated) and hold to program and view current settings.
Refer to "Magnetic Reed Switch" on page 8 for further information.
ON/OFF Switch - used to turn Controller on and off. Housing must be removed to access.
Pull Here knob - unscrew the two screws and pull to remove faceplate. Removal allows access to the PCB boards. The faceplate remains attached by the ribbon cable.
Current Test Jacks - to take current loop measurements use the following procedure:
-Insert your current meter leads into the Test Jacks.
-Set external devices to bypass, if necessary, to avoid unwanted alarm response
-Review current loop measurements.
Refer to "Current Loop Measurement (Test Jacks)" on page 8 and Table 4, "Current Output, LEDs and Display Messages", on page 10.
prompts. Refer to Table 4, "Current Output, LEDs and Display Messages", on page 10.
C
a
l
/
R
e
s
e
M
O
n
S
Power
t
a
g
n
e
t
i
d
e
Calibration/Setup
Pull Here
-Hold Cal/Reset or magnet until countdown is zero (~10 sec)
-Follow instruction on display
Current O/P Check
Connect current probes
to meter jacks and
read mA output
On
Off
Status
Slow Flash: Gas present Flast flash : Cal or Fault Solid: Overrange
Short Blips: Normal operation. No gas present
Red
Green
Here
Pull Here knob - unscrew the two screws and gently pull to remove faceplate. Removal allows access to the PCB boards. The faceplate remains attached by the ribbon cable.
Pull
Status Light (Red and Green) ­indicates status of unit. Refer to Table 4, "Current Output, LEDs and Display Messages", on page 10 for detailed explanation of states/status.
Calibration Button* - provides intrusive access for programming and resetting.
-Push for less than one second to initiate a basic system reset (clear a latched alarm) and make selections.
-Push and hold to program and view settings.
Refer to "Calibration Button" on page 8 for further information.
* Fire Heads do not require calibration. The button is used for reset and setup.
Modbus Controller & 4-20 Fire Head 7
Net Safety Monitoring Inc

THE MAIN MENU

The Main Menu allows for:
• Modbus Setup - Select Node Address and Baud Rate
• Select a display language - English, Spanish or French
Note: The current output will drop to 3.0 mA while in the Main Menu.

Accessing the Main Menu

There are two ways to activate the Main Menu:
• Calibration Button found on the faceplate (the Housing cover must be removed to access)
• Magnetic Reed Switch (a magnet must be used to activate)
Calibration Button
The Calibration Button provides access to the Main Menu, which allows options to be reviewed and set. Refer to Figure 9 for more information.
Press and hold the Calibration Button to access Main Menu.
Briefly press to make a selection (select YES?).
WARNING:
Opening the Controller’s Housing should be avoided when the presence of gas is possible (when in a hazardous environment). Do not power up the system, with the Housing removed, unless the area has been de-classified.

Main Menu Functionality

1. Ensure that the Controller has been turned on and no fault is present.

2. Hold the magnet against the Reed Switch or press and hold the Calibration Button until the message Switch On displays and the countdown (10 to
0) finishes.

3. An option will scroll across the display followed by the prompt YES?.

4. To select an option, momentarily place the magnet to the Reed Switch or press the Calibration Button at the YES? prompt.

5. If you do not wish to select that option wait until the next option appears and then select YES?.

6. A selection is acknowledged with a flashing YES.

7. If no option is selected, the Controller returns to normal operation.

Power Up

Turn power switch On. A 90 second warm-up routine will begin. The display shows Start Delay Millennium Net Safety, the Status LED is Red Slow Flash and current output displays 3.0 mA.
When power is applied, the system is automatically tested to ensure proper functionality.
After warm-up, the Controller will enter normal operation, the display reads NORM, Status LED will Green Blip/blink and analog output will change to
4.0 mA.
Magnetic Reed Switch
The Magnetic Reed Switch is provided to avoid opening the Housing in an environment where gas may be present. The Magnetic Reed Switch functions in the same manner as the Calibration Button but in a non-intrusive manner. Refer to Figure 9 for more information.
Attached to the side of the Controller is a magnet:
Place and hold the magnet to the Controller’s Housing (10 o’clock position) to access Main Menu.
Briefly place the magnet to the Controller’s Housing (10 o’clock position) to make a selection (select YES?).
Modbus Controller & 4-20 Fire Head 8

Current Loop Measurement (Test Jacks)

Use a standard meter to measure current loop during various states. The Controller’s Housing cover must be removed to access the Test Jacks.
Refer to Table 4, “Current Output, LEDs and Display Messages,” on page 10 for a detailed list and Figure 9 for more information.

Status LED

The Status LED will remain solid, flash, blip and/or blink, in either Red or Green, to indicate various states. Refer to Table 4, “Current Output, LEDs and Display Messages,” on page 10 for a detailed list.
Net Safety Monitoring Inc

SELECT DISPLAY LANGUAGE

Step 1: Wait for Select Display Language YES? to display. Press
the Calibration Button or use the Reed Switch to select. The flashing YES confirms the selection.
Step 2: When the required language displays (English, Espanol,
Francais) press the Calibration Button or use the Reed Switch to
select. The flashing YES confirms the selection.
Note: Factory default is English.

MODBUS OPTIONS

The digital RS-485 Modbus RTU protocol is used. There are two Modbus options: Node Address and Baud Rate.
Note: When a modbus option is changed, the message BUSY will display for a
few seconds while the unit is updated.

Node Address

Each device connected to the chain must be assigned a unique node address. The last number of the address is selected first.
Step 1: When Modbus Setup? YES? displays press the Calibration
Button or use the Reed Switch to select. The flashing YES confirms the selection.

Step 2: The current node address will display Node: 000.

Step 3: Wait for the prompt New Address? YES? and press the
Calibration Button or use the Reed Switch to select.
Step 4: Use the Calibration Button or Reed Switch to select each of three
numbers in the new address:
- select the last number in the address first: 0 thru 9.
- select the next number in the address: 0 thru 9.
- select the first number in the address last: 0 1 2.

Baud Rate

The transmission speed must be defined.
Step 1: When Modbus Setup? YES? displays press the Calibration
Button or use the Reed Switch to select. The flashing YES confirms the selection.
Step 2: After setting the Node Address, the current Baud Rate will display
XX.X BPS.
Step 3: Wait for the prompt New Baud Rate? YES? and press the
Calibration Button or use the Reed Switch to select.
Step 4: The available baud rates will display: 2400s, 4800s, 9600s,
14.4s, 19.2s, 28.8s, 38.4s, 57.6s.
Step 5: Use the Calibration Button or use the Reed Switch to select baud
rate when it displays.

Step 6: The flashing YES confirms the selection.

RESET

Manual Reset

A Manual Reset may be required to clear a latched relay alarm. Simply place and hold the magnet against the Reed Switch or press and hold the Calibration Button for 3-5 seconds. The unit will return to normal operation.
Modbus Controller & 4-20 Fire Head 9
Net Safety Monitoring Inc
STEP 5 — MONITOR
There are a variety of ways to indicate the status of the connected detectors: current output, LEDs and Display Messages.

Tab l e 4 : Current Output, LEDs and Display Messages

LED Status
Internal Power Fault or system power out of range
Automatic or manual VI Test Failure
Current
O/P
1.0 mA
2.0 mA
Start Delay (90 seconds) 3.0 mA Blip -
Normal Operation 4.0 mA - Blip
Background radiation source UV
Background radiation source IR
6.0 mA Flash -
8.0 mA Flash -
Early Warning ­Intermittent radiation
16.0 mA Flash -
detected
Fire confirmed 20.0 mA Flash -
Writing to memory - - Solid
Status LED
(red) (green)
Fast
Flash
Fast
Flash
-
-
Display Messages
Sensor Fault
VI Fault
Start Delay Millennium
NORM
UV Present
IR Present
Warning!!
FIRE (flashes)
BUSY

Tab le 5 : RTU Output Register (40001) Read Only (binary)

RTUfire_power_up 0x0001 power up delay
RTUfire_vi_fault 0x0002 failed self test
RTUfire_normal 0x0004 normal operation
RTUfire_fault 0x0008 fire head fault
RTUfire_ir_present 0x0010 background IR
RTUfire_uv_present 0x0020 background UV
RTUfire_warning 0x0040 Warning Fire
RTUfire_alarm 0x0080 Fire present

Tab le 6 : RTU Status Register (40002) Read Only (binary)

RTUstat_fault 0x0001 fault (sensor...)
RTUstat_mem_error 0x4000 memory error

RTU REGISTERS

Register 40001 = RTU Output (read only)
Register 40002 = RTU Status (read only)
Register 40101 = Reset latched relays (write)
Note: Many registers are used by the controller. Please do not write outside
the three registers.
Modbus Controller & 4-20 Fire Head 10
Net Safety Monitoring Inc
STEP 6 — MAINTAIN
The Controller on its own requires no maintenance. Refer to the Maintenance Section of the specific Fire Head manual for Fire Head maintenance and testing procedures.

HOW TO RETURN EQUIPMENT

A Material Return Authorization number is required in order to return equipment. Please contact Net Safety Monitoring at (403) 219-0688 returning equipment or consult our Service Department to possibly avoid returning equipment.
If you are required to return equipment, include the following information:

1. A Material Return Authorization number (provided over the phone to you by Net Safety).

2. A detailed description of the problem. The more specific you are regarding the problem, the quicker our Service department can determine and correct the problem.

3. A company name, contact name and telephone number.

4. A Purchase Order, from your company, authorizing repairs or request for quote.

5. Ship all equipment, prepaid to:
Net Safety Monitoring Inc
2721 Hopewell Place N. E. Calgary, Alberta, Canada
T1Y 7J7

6. Mark all packages: RETURN for REPAIR

before
Waybills, for shipments from outside Canada, must state:
Equipment being returned for repair All charges to be billed to the sender
Also, please ensure a duplicate copy of the packing slip is enclosed inside the box indicating item 1-4 along with the courier and account number for returning the goods.
All Equipment must be Shipped prepaid. Collect shipments will not be accepted.
Pack items to protect them from damage and use anti-static bags or aluminum­backed cardboard as protection from electrostatic discharge.
Modbus Controller & 4-20 Fire Head 11
Net Safety Monitoring Inc

FACE ROTATION OPTION

In some applications, it is necessary for the Controller to be mounted in a non­standard orientation. To accommodate such installations and ensure that the display will appear at the correct angle for viewing, the PCB Assembly can be rotated inside the Controller.
Figure 10: Non-standard Orientation
Note: Ensure orientation allows for connections and excess wire within Controller
Housing.
WARNING: See Appendix D, "Electrostatic Sensitive Device (ESD)", on page 13 for handling instructions of electronic components.

Rotate PCB Assembly

1. Remove the Controller’s Housing Cover.

2. Turn the power to the detector off.

3. Unscrew both the knobs marked "Pull Here".

4. Lift Controller faceplate from Housing and allow to hang from ribbon cable.

5. Unscrew the two metal standoffs.

6. Carefully remove the PCB Assembly from the Housing.

7. The Rotator plate is secured to the bottom of the Housing and is accessible after the PCB Assembly has been removed.

8. Rotate the PCB Assembly to desired position and line up the standoffs with the mounting holes.

9. Insert standoffs in the appropriate horizontal or vertical mounting holes.

10. Tighten standoffs to secure PCB Assembly.

11. Replace faceplate and tighten "Pull Here" knobs.

12. Return power to detector and replace Housing Cover.

Figure 11: Rotate PCB Assembly

Vertical Mounting Holes
(Insert Standoffs)
Horizontal Mounting Holes (Insert Standoffs)
Ribbon cable
Standoffs
PCB Assembly
Modbus Controller & 4-20 Fire Head 12
Faceplate
Net Safety Monitoring Inc

Appendix D: ELECTROSTATIC SENSITIVE DEVICE (ESD)

Electrostatic discharge (ESD) is the transfer, between bodies, of an electrostatic charge caused by direct contact or induced by an electrostatic field.
The most common cause of ESD is physical contact. Touching an object can cause a discharge of electrostatic energy occurs near electronic components, it can damage or destroy those components.
In some cases, damage is instantaneous and an immediate malfunction occurs. However, symptoms are not always immediate or seemingly normal for an indefinite period of time, followed by a sudden failure.
To eliminate potential ESD damage, review the following guidelines:
—ESD! If the charge is sufficient and
—performance may be marginal
• Handle boards by metal shields components
• Wear grounded wrist or foot straps, or ESD shoes or heel grounders to dissipate unwanted static energy
• Prior to handling boards, dispel any charge in your body or equipment
• Ensure components are transported and stored in static safe packaging
• When returning boards, carefully package in the original carton and static protective wrapping
• Ensure ALL personnel are educated and trained in ESD Control Procedures
In general, exercise accepted and proven precautions normally observed when handling electrostatic sensitive devices.
A warning label is placed on the packaging, identifying product using electrostatic sensitive semiconductor devices.
taking care not to touch electronic
Modbus Controller & 4-20 Fire Head 13
Net Safety Monitoring Inc

Appendix E: RESISTANCE TABLE (OHMS)

Distance (Feet) AWG #20 AWG #18 AWG #16 AWG #14 AWG #12 AWG #10 AWG #8
100 1.020.640.400.250.160.100.06
200 2.031.280.800.510.320.200.13
300 3.051.921.200.760.480.300.19
400 4.062.551.611.010.640.400.25
500 5.083.202.011.260.790.500.31
600 6.093.832.411.520.950.600.38
700 7.11 4.47 2.81 1.77 1.11 0.70 0.44
800 8.12 5.11 3.21 2.02 1.27 0.80 0.50
900 9.145.753.612.271.430.900.57
1000 10.20 6.39 4.02 2.53 1.59 1.09 0.63
1250 12.70 7.99 5.03 3.16 1.99 1.25 0.79
1500 15.20 9.58 6.02 3.79 2.38 1.50 0.94
1750 17.80 11.20 7.03 4.42 2.78 1.75 1.10
2000 20.30 12.80 8.03 5.05 3.18 2.00 1.26
2250 22.80 14.40 9.03 5.68 3.57 2.25 1.41
2500 25.40 16.00 10.00 6.31 3.97 2.50 1.57
3000 30.50 19.20 12.00 7.58 4.76 3.00 1.88
3500 35.50 22.40 14.10 8.84 5.56 3.50 2.21
4000 40.60 25.50 16.10 10.00 6.35 4.00 2.51
4500 45.70 28.70 18.10 11.40 7.15 4.50 2.82
5000 50.10 32.00 20.10 12.60 7.94 5.00 3.14
5500 55.80 35.10 22.10 13.91 8.73 5.50 3.46
6000 61.00 38.30 24.10 15.20 9.53 6.00 3.77
6500 66.00 41.50 26.10 16.40 10.30 6.50 4.08
7000 71.10 44.70 28.10 17.70 11.10 7.00 4.40
7500 76.10 47.90 30.10 19.00 12.00 7.49 4.71
8000 81.20 51.10 23.10 20.20 12.70 7.99 5.03
9000 91.40 57.50 36.10 22.70 14.30 8.99 5.65
10 000 102.00 63.90 40.20 25.30 15.90 9.99 6.28
Note: Resistance shown is one way. This figure should be doubled when determining closed loop resistance.
Modbus Controller & 4-20 Fire Head 14
Net Safety Monitoring Inc.

Appendix F: SPECIFICATIONS

CONTROLLER SPECIFICATION

Controller 4-20 mA ANALOG OUTPUT RS-485 MODBUS OUTPUT
Operating Temperature Range -40°C to +85°C (-40F to +185F)
Fire Head Power Consumption @ 24 V dc
Humidity Range 0 to 100% relative humidity, non-condensing
Operating Voltage Range 10.5 to 32.0 V dc at units power terminals
Enclosure Material Powder coated Copper Free Cast Aluminum
CSA and NRTL/C certified for hazardous locations. Class I, Division 1, Groups B, C and D. Temperature T5.
Certifications
Weight 3.2 Kg (7.0 lb)
Current Output
Digital Output -- Digital RS-485 Modbus RTU Protocol
Note: Units are factory sealed.
IEC Rating Ex d IIB+H2 T5 (Class1, Zone 1, Group 11B+H2 T5). Maximum operating ambient of 85°C. Enclosure Type 4X. Note: Electronics only-CSA and NRTL/C certified for hazardous locations Class I, Division 2 Groups A, B, C and D.
4 to 20 mA - Into a maximum loop impedance of 800 Ohms at 32 V dc or 150 Ohms at 10.5 V dc. Isolated or non-isolated loop supply.
Nominal 170 mA / 4.08 W
Maximum 230 mA / 5.52 W
--
Modbus Controller & 4-20 Fire Head 15
N
2
C
T
E
w
Distributed by:
ww.netsafety.com
-mail: netsafe@net-safety.com elephone: (403) 219-0688 Fax: (403) 219-0694
algary, Alberta, Canada T1Y 7J7
721 Hopewell Place NE
et Safety Monitoring Inc.,
Loading...