Rosemount Manual: The Rosemount Annubar® Flowmeter Series (Part 7) Manuals & Guides

Reference Manual
00809-0100-4809, Rev CB March 2012
Annubar Flowmeter Series
Appendix A Reference Data
3051SFA Ordering Information . . . . . . . . . . . . . . . . . . . . . page A-1
3051SFA Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . .page A-10
3051CFA Performance Specifications . . . . . . . . . . . . . . .page A-27
2051CFA Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . .page A-38
3095MFA Ordering Information . . . . . . . . . . . . . . . . . . . . .page A-43
3095MFA Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . page A-48
485 Annubar Primary Element Ordering Information . . .page A-57
485 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page A-62
585 Annubar Primary Element Ordering Information . . .page A-67
3051CF Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . page A-82
2051CF Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . page A-88
3095MFA Dimensional Drawings . . . . . . . . . . . . . . . . . . . . page A-91
485 Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . . . . page A-97
585 Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . . . . page A-103
3051SFA ORDERING INFORMATION
Table A-1. Rosemount 3051SFA Annubar Flowmeter Ordering Information
The Standard offering represents the most common options. The starred options () should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.
Measurement
Type
Model Product Description
3051SFA Annubar Flowmeter
Measurement Type Standard Standard
1 MultiVariable (Fully Compensated Mass & Energy Flow) – Differential & Static Pressures w/
Temperature 2 MultiVariable (Compensated Flow) – Differential & Static Pressures 3 MultiVariable (Compensated Flow) – Differential Pressure & Temperature 4 MultiVariable (Compensated Flow) – Differential Pressure 5 MultiVariable (Direct Measurement) – Differential & Static Pressures with Temperature 6 MultiVariable (Direct Measurement) – Differential & Static Pressures 7 MultiVariable (Direct Measurement) – Differential Pressure & Temperature D Differential Pressure
D 1-7
• = Available — = Unavailable
www.rosemount.com
Reference Manual
00809-0100-4809, Rev CB
Annubar Flowmeter Series
Table A-1. Rosemount 3051SFA Annubar Flowmeter Ordering Information
The Standard offering represents the most common options. The starred options () should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.
Fluid Type Standard Standard
L Liquid G Gas S Steam
Line Size D 1-7 Standard Standard
020 2-in. (50 mm) 025 21/2-in. (63.5 mm) 030 3-in. (80 mm) 035 31/2-in. (89 mm) 040 4-in. (100 mm) 050 5-in. (125 mm) 060 6-in. (150 mm) 070 7-in. (175 mm) 080 8-in. (200 mm) 100 10-in. (250 mm) 120 12-in. (300 mm)
Expanded
140 14-in. (350 mm) • 160 16-in. (400 mm) • 180 18-in. (450 mm) • 200 20-in. (500 mm) • 240 24-in. (600 mm) • 300 30-in. (750 mm) • 360 36-in. (900 mm) • 420 42-in. (1066 mm) • 480 48-in. (1210 mm) • 600 60-in. (1520 mm) • 720 72-in. (1820 mm) • 780 78-in (1950 mm) • 840 84-in. (2100 mm) • 900 90-in. (2250 mm) • 960 96-in (2400 mm)
Pipe I.D. Range Standard Standard
C Range C from the Pipe I.D. table D Range D from the Pipe I.D. table
Expanded
A Range A from the Pipe I.D. table • B Range B from the Pipe I.D. table • E Range E from the Pipe I.D. table • Z Non-standard Pipe I.D. Range or Line Sizes greater than 12-in. (300 mm)
Pipe Material / Mounting Assembly Material Standard Standard
C Carbon steel (A105) S 316 Stainless Steel
(1)
0
No Mounting (Customer Supplied)
March 2012
A-2
Reference Manual
00809-0100-4809, Rev CB March 2012
Table A-1. Rosemount 3051SFA Annubar Flowmeter Ordering Information
The Standard offering represents the most common options. The starred options () should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.
Expanded
G Chrome-Moly Grade F-11 • N Chrome-Moly Grade F-22 • J Chrome-Moly Grade F-91
Piping Orientation Standard Standard
H Horizontal Piping D Vertical Piping with Downwards Flow U Vertical Piping with Upwards Flow
Annubar Type D 1-7 Standard Standard
P Pak-Lok F Flanged with opposite side support
Expanded
L Flange-Lok • G Gear-Drive Flo-Tap • M Manual Flo-Tap
Sensor Material Standard Standard
S 316 Stainless Steel
Expanded
H Alloy C-276
Sensor Size Standard Standard
1 Sensor size 1 — Line sizes 2-in. (50 mm) to 8-in. (200 mm) 2 Sensor size 2 — Line sizes 6-in. (150 mm) to 96-in. (2400 mm) 3 Sensor size 3 — Line sizes greater than 12-in. (300 mm)
Mounting Type Standard Standard
T1 Compression or Threaded Connection A1 150# RF ANSI A3 300# RF ANSI A6 600# RF ANSI D1 DN PN16 Flange D3 DN PN40 Flange D6 DN PN100 Flange
Expanded
(2)
A9
(2)
AF
(2)
AT R1 150# RTJ Flange • R3 300# RTJ Flange • R6 600# RTJ Flange
(2)
R9
(2)
RF
(2)
RT
Opposite Side Support or Packing Gland Standard Standard
0 No opposite side support or packing gland (Required for Pak-Lok and Flange-Lok models)
C NPT Threaded Opposite Support Assembly – Extended Tip D Welded Opposite Support Assembly – Extended Tip
900# RF ANSI
1500# RF ANSI
2500 # RF ANSI
900# RTJ Flange
1500# RTJ Flange
2500# RTJ Flange
Opposite Side Support – Required for Flanged Models
Annubar Flowmeter Series
A-3
Reference Manual
00809-0100-4809, Rev CB
Annubar Flowmeter Series
Table A-1. Rosemount 3051SFA Annubar Flowmeter Ordering Information
The Standard offering represents the most common options. The starred options () should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.
Expanded
Packing Gland – Required for Flo-Tap Models
Packing Gland Material Rod Material Packing Material
J Stainless Steel Packing Gland / Cage Nipple Carbon Steel PTFE • K Stainless Steel Packing Gland / Cage Nipple Stainless Steel PTFE • L Stainless Steel Packing Gland / Cage Nipple Carbon Steel Graphite • N Stainless Steel Packing Gland / Cage Nipple Stainless Steel Graphite • R Alloy C-276 Packing Gland / Cage Nipple Stainless Steel Graphite
Isolation Valve for Flo-Tap Models D 1-7 Standard Standard
(1)
0
Expanded
1 Gate Valve, Carbon Steel • 2 Gate Valve, Stainless Steel • 5 Ball Valve, Carbon Steel • 6 Ball Valve, Stainless Steel
Temperature Measurement Standard Standard
(3)
T
(4)
0
Expanded
(3)
R
Transmitter Connection Platform Standard Standard
3 Direct-mount, Integral 3-valve Manifold– not available with Flanged model greater than class
5 Direct -mount, 5-valve Manifold – not available with Flanged model greater than class 600 7 Remote-mount NPT Connections (1/2-in. FNPT)
Expanded
6 Direct-mount, High Temperature 5-valve Manifold – not available with Flanged model greater
8 Remote-mount SW Connections (1/2-in.)
Differential Pressure Range Standard Standard
1 0 to 25 in H2O (0 to 62,3 mbar) 2 0 to 250 in H2O (0 to 623 mbar) 3 0 to 1000 in H2O (0 to 2,5 bar)
Static Pressure Range Standard Standard
(5)
A D Absolute 0.5 to 800 psia (0,033 to 55,2 bar)
(6)
E J Gage -14.2 to 800 psig (-0,979 to 55,2 bar)
(6)
K
Transmitter Output Standard Standard
A 4–20 mA with digital signal based on HART protocol F FOUNDATION fieldbus protocol (requires PlantWeb housing)
(7)
X
Not Applicable or Customer Supplied
Integral RTD – not available with Flanged model greater than class 600#
No Temperature Sensor
Remote Thermowell and RTD
600
than class 600
None
Absolute 0.5 to 3626 psia (0,033 to 250 bar)
Gage -14.2 to 3626 psig (-0,979 to 250 bar)
Wireless (Requires wireless options and Wireless Plantweb housing)
March 2012
A-4
Reference Manual
00809-0100-4809, Rev CB March 2012
Table A-1. Rosemount 3051SFA Annubar Flowmeter Ordering Information
The Standard offering represents the most common options. The starred options () should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.
Transmitter Housing Style Material Standard Standard
00 None (Customer-supplied electrical connection) 1A PlantWeb Housing Aluminum 1B PlantWeb Housing Aluminum M20 x 1.5 1J PlantWeb Housing SST 1K PlantWeb Housing SST M20 x 1.5 2A Junction Box Housing Aluminum 2B Junction Box Housing Aluminum M20 x 1.5 2E Junction Box housing with output for remote display and
2F Junction Box housing with output for remote display and
2J Junction Box Housing SST 2M Junction Box housing with output for remote display and
5A Wireless PlantWeb housing Aluminum 5J Wireless PlantWeb housing SST
(7)(8)
7J
Expanded
1C PlantWeb Housing Aluminum G1/2 • 1L PlantWeb Housing SST G1/2 • 2C Junction Box Housing Aluminum G1/2 — 2G Junction Box housing with output for remote display and
Transmitter Performance Class D 1-7 Standard Standard
3051S MultiVariable SuperModule, Measurement Types 1, 2, 5, and 6
3 Ultra for Flow: 0.8% flow rate accuracy, 14:1 flow turndown, 10-year stability. limited 12-year
5 Classic MV: 0.85% flow rate accuracy, 8:1 flow turndown, 5-yr. stability
3051S Single Variable SuperModule, Measurement Types 3, 4, 7, and D
1 Ultra: up to 0.9% flow rate accuracy, 8:1 flow turndown, 10-year stability, limited 12-year
2 Classic: up to 1.1% flow rate accuracy, 8:1 flow turndown, 5-year stability
(9)
3
interface
interface
interface
Quick Connect (A size Mini, 4-pin male termination)
interface
warranty
warranty
Ultra for Flow: 0.8% flow rate accuracy, 14:1 flow turndown, 10-year stability,. limited 12-year
warranty
Annubar Flowmeter Series
Conduit Entry Size
1
/2-14 NPT
1
/2-14 NPT
1
/2-14 NPT
Aluminum
Aluminum M20 x 1.5
SST
Aluminum G1/2
1
/2-14 NPT
1
/2-14 NPT
1
/2-14 NPT
1
/2-14 NPT
1
/2-14 NPT
Wireless Options (Requires option code X and wireless PlantWeb housing)
Update Rate, Operating Frequency and Protocol Standard Standard
WA User Configurable Update Rate
Operating Frequency and Protocol Standard
3 2.4 GHz DSSS, WirelessHART
Omnidirectional Wireless Antenna Standard
(10)
WK
SmartPower Standard
(11)
1
Long Range, Integral Antenna
Power Module Adapter, Intrinsically Safe (Power Module separate)
A-5
Reference Manual
00809-0100-4809, Rev CB
Annubar Flowmeter Series
March 2012
Table A-1. Rosemount 3051SFA Annubar Flowmeter Ordering Information
The Standard offering represents the most common options. The starred options () should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.
Other Options (Include with selected model number)
Pressure Testing Expanded
(12)
P1
(12)
PX
Special Cleaning Expanded
P2 Cleaning for Special Services • PA Cleaning per ASTM G93 level D (section 11.4)
Material Testing Expanded
V1 Dye Penetrant Exam
Material Examination Expanded
V2 Radiographic Examination
Flow Calibration Expanded
W1 Flow Calibration (Average K)
Special Inspection Standard Standard
QC1 Visual and Dimensional Inspection with Certificate QC7 Inspection and Performance Certificate
Surface Finish Standard Standard
RL Surface finish for Low Pipe Reynolds Number in Gas and Steam RH Surface finish for High Pipe Reynolds Number in Liquid
Material Traceability Certification Standard Standard
(13)
Q8
Code Conformance Expanded
(14)
J2
(14)
J3
Material Conformance Expanded
(15)
J5
Country Certification Standard Standard
J6 European Pressure Directive (PED)
Expanded
J1 Canadian Registration
Installed in Flanged Pipe Spool Section Expanded
H3 150# Flanged Connection with Rosemount Standard Length and Schedule • H4 300# Flanged Connection with Rosemount Standard Length and Schedule • H5 600# Flanged Connection with Rosemount Standard Length and Schedule
Instrument Connections for Remote Mount Option Standard Standard
G2 Needle Valves, Stainless Steel G6 OS&Y Gate Valve, Stainless Steel
Hydrostatic Testing with Certificate
Extended Hydrostatic Testing
D 1-7
Material Traceability Certificate per EN 10204:2004 3.1
ANSI B31.1
ANSI B31.3
NACE MR-0175 / ISO 15156
A-6
Reference Manual
00809-0100-4809, Rev CB March 2012
Table A-1. Rosemount 3051SFA Annubar Flowmeter Ordering Information
The Standard offering represents the most common options. The starred options () should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.
Expanded
G1 Needle Valves, Carbon Steel • G3 Needle Valves, Alloy C-276 • G5 OS&Y Gate Valve, Carbon Steel • G7 OS&Y Gate Valve, Alloy C-276
Special Shipment Standard Standard
Y1 Mounting Hardware Shipped Separately
Special Dimensions Expanded
VM Variable Mounting • VT Variable Tip • VS Variable length Spool Section
Transmitter Calibration Certification Standard Standard
Q4 Calibration Certificate for Transmitter
Quality Certification For Safety Standard Standard
QS Certificate of FMEDA data
(16)(17)(19)
QT
Product Certifications Standard Standard
E1 ATEX Flameproof I1 ATEX Intrinsic Safety IA ATEX FISCO Intrinsic Safety; for FOUNDATION fieldbus protocol only N1 ATEX Type n ND ATEX Dust K1 ATEX Flameproof, Intrinsic Safety, Type n, Dust (combination of E1, I1, N1, and ND) E4 TIIS Flameproof E5 FM Explosion-proof, Dust Ignition-proof I5 FM Intrinsically Safe, Division 2 K5 FM Explosion-proof, Dust Ignition-proof, Intrinsically Safe, Division 2 (combination of E5 and I5)
(16)
E6 I6 CSA Intrinsically Safe
(16)
K6
E7 IECEx Flameproof, Dust Ignition-proof I7 IECEx Intrinsic Safety K7 IECEx Flameproof, Dust Ignition-proof, Intrinsic Safety, Type n (combination of E7, I7, and N7) E3 China Flameproof I3 China Intrinsic Safety
(16)
KA
(16)
KB
KC FM and ATEX Explosion-proof, Intrinsically Safe, Division 2 (combination of E5, E1, I5, and I1)
(16)
KD
Alternate Transmitter Material of Construction Standard Standard
L1 Inert Sensor Fill Fluid
L2 Graphite-Filled (PTFE) O-ring LA Inert Sensor Fill Fluid and Graphite-Filled (PTFE) O-ring
Safety certified to IEC 61508 with certificate of FMEDA data
CSA Explosion-proof, Dust Ignition-proof, Division 2
CSA Explosion-proof, Dust Ignition-proof, Intrinsically Safe, Division 2 (combination of E6 and
I6)
ATEX and CSA Explosion-proof, Intrinsically Safe, Division 2 (combi nation of E1, I1, E6, and I6)
FM and CSA Explosion-proof, Dust Ignition-proof, Intrinsically Safe, Division 2
(combination of E5, E6, I5, and I6)
FM, CSA, and ATEX Explosion-proof, Intrinsically Safe (combination of E5, I5, E6, I6, E1, and
I1)
Note: Silicone fill fluid is standard.
Annubar Flowmeter Series
D 1-7
A-7
Reference Manual
00809-0100-4809, Rev CB
Annubar Flowmeter Series
Table A-1. Rosemount 3051SFA Annubar Flowmeter Ordering Information
The Standard offering represents the most common options. The starred options () should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.
Digital Display Standard Standard
M5 PlantWeb LCD display (Requires PlantWeb housing)
(18)(19)
M7
(18)(19)(20)
M8
(18)(19)(20)
M9
Transient Protection Standard Standard
(21)
T1
Manifold for Remote Mount Option Standard Standard
F2 3-Valve Manifold, Stainless Steel F6 5-Valve Manifold, Stainless Steel
Expanded
F1 3-Valve Manifold, Carbon Steel • F3 3-Valve Manifold, Alloy C-276 • F5 5-Valve Manifold, Carbon Steel • F7 5-Valve Manifold, Alloy C-276
PlantWeb Control Functionality Standard Standard
A01 FOUNDATION fieldbus Advanced Control Function Block Suite
PlantWeb Diagnostic Functionality Standard Standard
D01 FOUNDATION fieldbus Diagnostics Suite
(22)
DA2
PlantWeb Enhanced Measurement Functionality Standard Standard
(23)
H01
Cold Temperature Standard Standard
BRR -60 °F (-51 °C) Cold Temperature Start-up
Alarm Limit Standard Standard
C4 NAMUR Alarm and Saturation Levels, High Alarm C5 NAMUR Alarm and Saturation Levels, Low Alarm C6 Custom Alarm and Saturation Levels, High Alarm C7 Custom Alarm and Saturation Levels, Low Alarm C8 Low Alarm (Standard Rosemount Alarm and Saturation Levels)
Hardware Adjustments and Ground Screw Standard Standard
D1 Hardware Adjustments (zero, span, alarm, security) D4 External Ground Screw Assembly DA Hardware Adjustments (zero, span, alarm, security) and External Ground Screw Assembly
Conduit Electrical Connector Standard Standard
(25)
GE
(25)
GM
Typical Model Number: 3051SFA D L 060 D C H P S 2 T1 0 0 0 3 2A A 1A 3
(1) Provide the “A” dimension for Flanged (page A-78), Flange-Lok (page A-77), and Threaded Flo-Tap (page A-81) models. Provide the “B” dimension for
Flange Flo-Tap models (page A-80). (2) Available in remote mount applications only. (3) Temperature Measurement Option code T or R is required for Measurement Type codes 1, 3, 5, and 7. (4) Required for Measurement Type codes 2, 4, 6, and D. (5) Required for Measurement Type codes 3, 4, 7, and D.
(17)
Remote mount LCD display and interface, no cable; PlantWeb housing, SST bracket Remote mount LCD display and interface, 50 ft. (15 m) cable; PlantWeb housing, SST bracket Remote mount LCD display and interface, 100 ft. (31 m) cable; PlantWeb housing, SST bracket
Transient terminal block
D 1-7
Advanced HART Diagnostic Suite
FOUNDATION fieldbus Fully Compensated Mass Flow Block
(18)(24)
M12, 4-pin, Male Connector (eurofast®) A size Mini, 4-pin, Male Connector (minifast®)
March 2012
A-8
Reference Manual
00809-0100-4809, Rev CB March 2012
(6) For Measurement Type 1, 2, 5, and 6 with DP range 1, absolute limits are 0.5 to 2000 psi (0,03 to 137,9 bar) and gage limits are
-14.2 to 2000 psig (-0,98 to 137,9 bar).
(7) Available approvals are FM Int rinsically Safe, Division 2 (opt ion code I5), CSA Intrinsicall y Safe (option code I6), ATEX Intrinsic Safety (o ption code I1), and
IECEx Intrinsic Safety (option code I7). (8) Available with output code A only. (9) This option is only available with differential pressure ranges 2 and 3, and silicone fill fluid. (10) Long-Life Power Module must be shipped separately, order Part #00753-9220-0001.
(11) Long-life Power Module must be shipped separately, order Part No. 00753-9220-0001. (12) Applies to assembled flowmeter only, mounting not tested. (13) Instrument Connections for Remote Mount Options and Isolation Valves for Flo-tap Models are not included in the Material Traceability Certification. (14) Not available with Transmitter Connection Platform 6. (15) Materials of Construction comply with metallurgical requirements within NACE MR0175/ISO 15156 for sour oil field production environment s. Environmental
limits apply to certain materials. Consult latest standard for details. Selected materials also conform to NACE MR0103 for sour refining environments. (16) Not available with M20 or G ½ conduit entry size. (17) Not available with housing code 7J. (18) Not available with output code X. (19) Not available with output code F, option code DA2, or option code QT. (20) Cable supplied is Belden 3084A, rated for ambient temperatures up to 167 °F (75 °C). (21) Not available with Housing code 00, 5A, or 7J. External ground screw assembly (option code D4) is included with t he T1 option. The T1 option is not needed
with FISCO Product Certifications, transient protection is included with the FISCO Product Certification code IA. (22) Includes Hardware Adjustments (option code D1) as standard. (23) Requires Rosemount Engineering Assistant version 5.5.1 to configure. (24) Not available with Output Protocol code F. (25) Not available with Housing code 00, 5A, or 7J. Available with Intrinsically Safe approvals only. For FM Intrinsically Safe, Division 2 (option code I5) or FM
FISCO Intrinsically Safe (option code IE), install in accordance with Rosemount drawing 03151-1009 to maintain outdoor rating (NEMA 4X and IP66).
Annubar Flowmeter Series
A-9
Reference Manual
00809-0100-4809, Rev CB
Annubar Flowmeter Series
March 2012
3051SFA SPECIFICATIONS 3051SFA
PERFORMANCE SPECIFICATIONS
Performance assumptions include: measured pipe I.D, transmitter is trimmed for optimum flow accuracy, and performance is dependent on application parameters.
Table A-2. MultiVariable Flow Performance - Flow Refe rence Accuracy (Measurement Type 1)
3051SFA Annubar Flowmeter
Classic MV (8:1 flow turndown) Ultra for Flow (14:1 flow turndown)
Ranges 2-3 1.15% of Flow Rate ±0.80% of Flow Rate
(1) Measurement Types 2 - 4 assume that the unmeasured variables are constant. Additional uncertainty will depend on the variation in the unmeasured
variables.
Table A-3. Flow Performance - Flow Reference Accuracy (Measurement Type D)
3051SFA Annubar Flowmeter
Classic (8:1 flow turndown) Ultra (8:1 flow turndown) Ultra for Flow (14:1 flow turndown)
Ranges 2-3 ±1.4% of Flow Rate ±0.95% of Flow Rate ±0.80% of Flow Rate
(1) For Measurement Types 5 - 7, refer to the Reference Accuracy specification for the 3051SMV with Measur ement Type P. (2) These flow measurement accuracies assume a constant density, viscosity, and expansibility factor.
(1)(2)
(1)
3051SFA DYNAMIC PERFORMANCE
Total Time Response at 75 °F (24 °C), includes dead time
3051SF_D 3051SF_1, 2, 5, or 6 3051SF_3, 4, or 7
DP Ranges 2-5: 100 ms Range 1: 255 ms Range 0: 700 ms
(1) For F
OUNDATION fieldbus (output code F), add 52 ms to stated values (not including
segment macro-cycle). For option code DA2, add 45 ms (nominal) to stated values.
DP Range 1: 310 ms DP Range 2: 170 ms DP Range 3: 155 ms AP & GP: 240 ms
DP Ranges 2-5: 145 ms DP Range 1: 300 ms DP Range 0: 745 ms
(1)
A-10
Dead Time
3051SF_D 3051SF_1-7
45 ms (nominal) DP: 100 ms
(1) For option code DA2, dead time is 90 milliseconds (nominal).
Update Rate
3051SF_D 3051SF_1-7
22 updates per sec. DP: 22 updates per sec.
(1) Does not apply to Wireless (output code X). See “Wireless Self-Organizing Networks” on page A-17
(1)
(1)
for wireless update rate.
AP & GP: 140 ms RTD Interface: 1 s
AP & GP: 11 updates per sec. RTD Interface: 1 update per sec.
Calculated Variables: Mass / Volumetric Flow Rate: 22 updates per sec. Energy Flow Rate: 22 updates per sec. Totalized Flow: 1 update per sec.
Reference Manual
00809-0100-4809, Rev CB March 2012
Annubar Flowmeter Series
Mounting Position Effects
Models Ultra, Ultra for Flow, Classic and Classic MV
3051SF_3, 4, 7, or D Zero shif ts up to ±1.25 inH2O (3,11 mbar), which can be
3051SF_1, 2, 5, or 6 DP Sensor: Zero shifts up to ±1.25 inH2O (3,11 mbar), which can be
GP/AP
Sensor:
zeroed Span: no effect
zeroed Span: no effect Zero shifts to ±2.5 inH2O (6,22 mbar), which can be zeroed Span: no effect
Vibration Effect Less than ±0.1% of URL when tested per the requirements of IEC60770-1
field or pipeline with high vibration level (10-60 Hz 0.21mm displacement peak amplitude / 60-2000 Hz 3g).
For Housing Style codes 1J, 1K, 1L, 2J, and 2M: Less than ±0.1% of URL when tested per the requirements of IEC60770-1 field with general application or pipeline with low vibration level (10-60 Hz
0.15 mm displacement peak amplitude / 60-500 Hz 2g).
Power Supply Effect Less than ±0.005% of calibrated span per volt change in voltage at the
transmitter terminals
Electromagnetic Compatibility (EMC)
T ransient Protection (Option T1)
Meets all relevant requirements of EN 61326 and NAMUR NE-21.
(1) NAMUR NE-21 does not apply to wireless output code X. (2) 3051SMV and 3051SF_1, 2, 3, 4, 5, 6, 7 requires shielded cable for
both temperature and loop wiring.
Meets IEEE C62.41.2-2002, Location Category B
6 kV crest (0.5 s - 100 kHz) 3 kA crest (8 × 20 microseconds) 6 kV crest (1.2 × 50 microseconds)
Meets IEEE C37.90.1-2002 Surge Withstand Capability
SWC 2.5 kV crest, 1.0 MHz wave form
(1) (2)
A-11
Annubar Flowmeter Series
3051SFA FUNCTIONAL SPECIFICATIONS
Range and Sensor Limits Flowmeter with Coplanar Sensor Module
DP Sensor (3051SF_3, 4, or 7)
Range
1 0 inH2O (0 mbar) 25 inH2O (62,3 mbar) 2 0 inH2O (0 bar) 250 inH2O (0,62 bar) 3 0 inH2O (0 bar) 1000 inH2O (2,49 bar)
Flowmeter with MultiVariable Sensor Module
Range
1 0 inH2O (0 mbar) 25.0 inH2O (62,3 mbar) 2 0 inH2O (0 bar) 250.0 inH2O (0,62 bar) 3 0 inH2O (0 bar) 1000.0 inH2O (2,49 bar)
Range
3 GP
4 GP
(1) For SP Range 4 with DP Range 1, the URL is 2000 psi (137,9 bar). (2) Inert Fill: Minimum pressure = 1.5 psia (0,10 bar) or -13.2 psig (-0,91 bar).
Lower (LRL) Upper (URL)
DP Sensor (3051SF1, 2, 5, or 6)
Lower (LRL) Upper (URL)
Static Pressure Sensor (GP/AP)
Lower (LRL) Upper (URL)
(2)
: -14.2 psig (0,98 bar)
AP: 0.5 psia (34,5 mbar)
(2)
: -14.2 psig (0,98 bar)
AP: 0.5 psia (34,5 mbar)
Reference Manual
00809-0100-4809, Rev CB
March 2012
(1)
GP: 800 psig (55,16 bar) AP: 800 psia (55,16 bar)
GP: 3626 psig (250 bar) AP: 3626 psia (250 bar)
Process Temperature RTD Interface (3051SF_1, 3, 5 or 7)
Lower (LRL) Upper (URL)
-328 °F (-200 °C) 1562 °F (850 °C)
(1) Transmitter is compatible with any Pt 100 RTD sensor. Examples of compatible RTDs include
Rosemount Series 68 and 78 RTD Temperature Sensors.
(1)
Minimum Span Limits Transmitter with Coplanar Sensor Module (Single Variable)
DP Sensor (3051SF_D, 3, 4 or 7)
Range
1 0.5 inH2O (1,24 mbar) 0.5 inH2O (1,24 mbar) 2 1.3 inH2O (3,11 mbar) 2.5 inH2O (6,23 mbar) 3 5.0 inH2O (12,4 mbar) 10.0 inH2O (24,9 mbar)
Transmitter with MultiVariable Sensor Module
Range
1 0.5 inH2O (1,24 mbar) 0.5 inH2O (1,24 mbar) 2 1.3 inH2O (3,11 mbar) 2.5 inH2O (6,23 mbar) 3 5.0 inH2O (12,4 mbar) 10.0 inH2O (24,9 mbar)
Range
3 4.0 psi (276 mbar) 8.0 psi (522 mbar) 4 18.13 psi (1,25 bar) 36.26 psi (2,50 bar)
Ultra & Ultra for Flow Classic
DP Sensor (3051SF_1, 2, 5, or 6)
Ultra for Flow Classic MV
Static Pressure Sensor (GP/AP)
Ultra for Flow Classic MV
A-12
Reference Manual
00809-0100-4809, Rev CB March 2012
Annubar Flowmeter Series
Process Temperature RTD Interface (3051SF_1, 3, 5, or 7)
Minimum Span = 50 °F (28 °C)
Service
3051SF_5, 6, 7, or D (Direct Process Variable Output):
Liquid, gas, and steam applications
3051SF_1, 2, 3, or 4 (Mass and Energy Flow Output):
Some fluid types are only supported by certain measurement types
Fluid Compatibility with Pressure and Temperature
Ordering
Code
Measurement Type
1 DP / P/ T (Full
Compensation) 2 DP / P • 3 DP / T — 4 DP only
Compensation
Liquids
Fluid Types
Saturated
Steam
• Available — Not available
Superheated
Steam
Gas and
Natural Gas
4–20 mA/HART
Zero and Span Adjustment
Zero and span values can be set anywhere within the range. Span must be greater than or equal to the minimum span.
Output
Two-wire 4–20 mA is user-selectable for linear or square root output. Digital process variable superimposed on 4– 20 mA signal, available to any host that conforms to the HART protocol.
Power Supply
External power supply required.
• 3051SF_D: 10.5 to 42.4 Vdc with no load
• 3051SF_D with Advanced HART Diagnostics Suite: 12 to 42.4 Vdc with no load
• 3051SF_1-7: 12 to 42.4 Vdc with no load
Load Limitations
Maximum loop resistance is determined by the voltage level of the external power supply, as described by:
A-13
Annubar Flowmeter Series
Voltage (Vdc)
Load (Ohms)
Operating
Region
1387
1000
500
0
10.5 20 30
42.4
Voltage (Vdc)
Load (Ohms)
Operating
Region
1322
1000
500
0
12.0 20 30
42.4
Maximum Loop Resistance = 43.5 * (Power Supply Voltage – 10.5)
The Field Communicator requires a minimum
loop resistance of 250
3051SF_1-7 and 3051SF_D with HART Diagnostics
Maximum Loop Resistance = 43.5 * (Power Supply Voltage – 12.0)
3051SF_D
for communication.
(option code DA2)
Reference Manual
00809-0100-4809, Rev CB
March 2012
The Field Communicator requires a minimum
loop resistance of 250
for communication.
Advanced HART Diagnostics Suite (Option Code DA2)
The 3051SF provides Abnormal Situation Prevention indication for a breakthrough in diagnostic capability. The 3051SF ASP Diagnostics Suite for HART includes Statistical Process Monitoring (SPM), variable logging with time stamp and advanced process alerts. The enhanced EDDL graphic display provides an intuitive and user -fr ie nd ly inte rf ac e to be tter visualize these diagnostics.
The integral SPM technology calculates the mean and standard deviation of the process variable 22 times per second and makes them available to the user. The 3051SF uses these values and highly flexible configuration options for customization to detect many user-defined or application specific abnormal situations (e.g. detecting plugged impulse lines and fluid composition change). Variable logging with time stamp and advanced process alerts capture valuable process and sensor data to enable quick troubleshooting of application and installation issues.
A-14
Reference Manual
00809-0100-4809, Rev CB March 2012
Annubar Flowmeter Series
FOUNDATION fieldbus
Power Supply
External power supply required; transmitters operate on 9.0 to 32.0 Vdc transmitter terminal voltage.
Current Draw
17.5 mA for all configurations (including LCD display option)
OUNDATION fieldbus Parameters
F
Schedule Entries 14 (max.) Links 30 (max.) Virtual Communications Relationships (VCR) 20 (max.)
Standard Function Blocks Resource Block
• Contains hardware, electronics, and diagnostic information.
Transducer Block
• Contains actual sensor measurement data including the sensor diagnostics and the ability to trim the pressure sensor or recall factory defaults.
LCD Block
• Configures the local display.
2 Analog Input Blocks
• Processes the measurements for input into other function blocks. The output value is in engineering or custom units and contains a status indicating measurement quality.
PID Block with Auto-tune
• Contains all logic to perform PID control in the field including cascade and feedforward. Auto-tune capability allows for superior tuning for optimized control performance.
Backup Link Active Scheduler (LAS)
The transmitter can function as a Link Active Scheduler if the current link master device fails or is removed from the segment.
Software Upgrade in the Field
Software for the 3051SF with F the field using the F
OUNDATION fieldbus Common Device Software
Download procedure.
PlantWeb Alerts
Enable the full power of the PlantWeb digital architecture by diagnosing instrumentation issues, communicating ad visory, mainte nance, and failure details, and recommending a solution.
Advanced Control Function Block Suite (Option Code A01)
Input Selector Block
• Selects between inputs and generates an output using specific selection strategies such as minimum, maximum, midpoint, average, or first “good.”
Arithmetic Block
• Provides pre-defined application-based equations including flow with partial density compensation, electronic remote seals, hydrostatic tank gauging, ratio control, and others.
OUNDATION fieldbus is easy to upgrade in
A-15
Annubar Flowmeter Series
Signal Characterizer Block
• Characterizes or approximates any function that defines an input/output relationship by configuring up to twenty X, Y coordinates. The block interpolates an output value for a given input value using the curve defined by the configured coordinates.
Integrator Block
• Compares the integrated or accumulated value from one or two variables to pre-trip and trip limits and generates discrete output signals when the limits are reached. This block is useful for calculating total flow, total mass, or volume over time.
Output Splitter Block
•Splits the output of one PID or other control block so that the PID will
control two valves or other actuators. Control Selector Block
• Selects one of up to three inputs (highest, middle, or lowest) that are normally connected to the outputs of PID or other control function blocks.
Block Execution Time
Resource ­Transducer ­LCD Block ­Analog Input 1, 2 20 milliseconds PID with Auto-tune 35 milliseconds Input Selector 20 milliseconds Arithmetic 20 milliseconds Signal Characterizer 20 milliseconds Integrator 20 milliseconds Output Splitter 20 milliseconds Control Selector 20 milliseconds
Reference Manual
00809-0100-4809, Rev CB
March 2012
Fully Compensated Mass Flow Block (Option Code H01)
Calculates fully compensated mass flow based on differential pressure with external process pressure and temperature measurements over the fieldbus segment. Configuration for the mass flow calculation is easily accomplished using the Rosemount Engineering Assistant.
ASP Diagnostics Suite for F
OUNDATION fieldbus
(Option Code D01)
The 3051SF ASP Diagnostics Suite for F
OUNDATION fieldbus provides
Abnormal Situation Prevention indication and enhanced EDDL graphic displays for easy visual analysis.
The integral Statistical Process Monitoring (SPM) technology calculates the mean and standard deviation of the process variable 22 times per second and makes them available to the user . The 3051SF uses these values and highly flexible configuration options for customization to detect many user-defined or application specific abnormal situations (e.g. detecting plugged impulse lines and fluid composition change).
A-16
Reference Manual
00809-0100-4809, Rev CB March 2012
Annubar Flowmeter Series
Wireless Self-Organizing Networks
Output
WirelessHART, 2.4 GHz DSSS.
Local Display
The optional five-digit LCD can display user-selectable information such as primary variable in engineering units, percent of range, sensor modu le temperature, and electronics temperature. Display updates at up to once per minute.
Update Rate
WirelessHART, user selectable 8 sec. to 60 min.
Power Module
Field replaceable, keyed connection eliminates the risk of incorrect installation, Intrinsically Safe Lithium-thionyl chloride Power Module with polybutadine terephthalate (PBT) enclosure. Ten-year life at one minute update rate.
(1) Reference conditions are 70 °F (21 °C), and routing data for three additional network devices.
NOTE: Continuous exposure to ambient temperature limits of
-40 °F or 185 °F (-40 °C or 85 °C) may reduce specified life by less than 20 percent.
(1)
Overpressure Limits Transmitters withstand the following limits without damage:
Coplanar Sensor Module (Single Variable)
(1)
DP
Range
1 2000 psi (137,9 bar) 2 3626 psi (250,0 bar) 3 3626 psi (250,0 bar)
(1) The overpressure limit of a DP Sensor with the P9 option is 4500
psig (310,3 bar). The overpressure limit of a DP Sensor with the P0 option is 6092 psig (420 bar).
3051SF_3, 4, 7, or D
Coplanar MultiVariable Sensor Module (3051SF_1, 2, 5, or 6)
Static
Pressure
Range 3
GP/AP
Range 4
GP/AP
Range 1 Range 2 Range 3
1600 psi
(110,3 bar)
2000 psi
(137,9 bar)
Differential Pressure
1600 psi
(110,3 bar)
3626 psi
(250 bar)
1600 psi
(110,3 bar)
3626 psi
(250 bar)
Static Pressure Limits Coplanar Sensor Module
Operates within specifications between static line pressures of:
DP Sensor
Range
1 0.5 psia to 2000 psig (0,03 to 137,9 bar) 2 0.5 psia to 3626 psig (0,03 to 150 bar) 3 0.5 psia to 3626 psig (0,03 to 150 bar)
(1) The static pressure limit of a DP Sensor wit h the P9 option i s 4500
psig (310,3 bar). The static pressure limit of a DP Sensor with the P0 option is 6092 psig (420 bar).
3051SF_3, 4, 7, or D
(1)
A-17
Annubar Flowmeter Series
Coplanar MultiVariable Sensor Module (3051SF_1, 2, 5, or 6)
Operates within specifications between static line pressures of 0.5 psia (0,03 bar) and the values in the table below:
Static Pressure
Range 3
GP/AP
Range 4
GP/AP
Range 1 Range 2 Range 3
800 psi
(57,91 bar)
2000 psi
(137,9 bar)
Burst Pressure Limits Coplanar Sensor Module
10000 psig (689,5 bar)
Temperature Limits Ambient
-40 to 185 °F (-40 to 85 °C) With LCD display With option code P0: -20 to 185 °F (-29 to 85 °C)
(1) LCD display may not be readable and LCD upda tes will be slower
at temperatures below -4 °F (-20 °C).
(1)
: -40 to 175 °F (-40 to 80 °C)
Differential Pressure
800 psi
(57,91 bar)
3626 psi
(250 bar)
Reference Manual
00809-0100-4809, Rev CB
March 2012
800 psi
(57,91 bar)
3626 psi
(250 bar)
Storage
-50 to 185 °F (-46 to 85 °C) With LCD display: -40 to 185 °F (-40 to 85 °C) With Wireless Output: -40 to 185 °F (-40 to 85 °C)
Process Temperature Limits
For 3051SFA Temperature Limits, see page A-63. At atmospheric pressures and above:
Humidity Limits 0–100% relative humidity
(1)
(1)
3
(0,08 cm3)
Turn-On Time
When power is applied to the transmitter during startup, performance will be within specifications per the time period described below:
Transmitter Turn-On Time (Typical)
3051S, 3051SF_D 2 seconds Diagnostics 5 seconds 3051SMV, 3051SF_1-7 5 seconds
(1) Does not apply to wireless option code X.
Volumetric Displacement Less than 0.005 in
Damping
Analog output response time to a step change is user-selectable from 0 to 60 seconds for one time constant. For 3051SF_1-7, each variable can be individually adjusted. Software damping is in addition to sensor module response time.
(1) Does not apply to wireless option code X.
A-18
Reference Manual
00809-0100-4809, Rev CB March 2012
Annubar Flowmeter Series
Failure Mode Alarm HART 4-20 mA (output option code A)
If self-diagnostics detect a gross transmitter failure, the analog signal will be driven offscale to alert the user. Rosemount standard (default), NAMUR, and custom alarm levels are available (see Alarm Configuration below).
High or low alarm signal is software-selectable or hardware-select able via the optional switch (option D1).
Alarm Configuration
High Alarm Low Alarm
Default 21.75 mA 3.75 mA NAMUR compliant Custom levels
(1) Analog output levels are compliant with NAMUR
recommendation NE 43, see option codes C4 or C5.
(2) Low alarm must be 0.1 mA less than low sa turati on and high
alarm must be 0.1 mA greater than high saturation.
(1)
(2)
22.5 mA 3.6 mA
20.2 - 23.0 mA 3.4 - 3.8 mA
Safety-Certified Transmitter Failure Values
Safety accuracy: 2.0% Safety response time: 1.5 seconds
(1) Does not apply to wireless option code X. (2) A 2% variation of the transmitter mA output is allowed before a
(1)
(2)
safety trip. T rip values in the DCS or safety logic solver should be derated by 2%.
3051SFA PHYSICAL SPECIFICATIONS
Electrical Connections
1
/2–14 NPT, G1/2, and M20 × 1.5 conduit. HART interface connections fixed to
terminal block for Output code A and X.
Process Connections
Coplanar Sensor Module
Standard1/4-18 NPT on 2 1/8-in. centers
Process-Wetted Parts For 3051SFA wetted parts, see “Annubar Sensor Material” on page A-63.
Process Isolating Diaphragms
Coplanar Sensor Module
316L SST (UNS S31603), Alloy C-276 (UNS N10276), Alloy 400 (UNS N04400), T antalum (UNS R05440), Gold-Plated Alloy 400, Gold-plated 316L SST
A-19
Annubar Flowmeter Series
Drain/Vent Valves
316 SST, Alloy C-276, or Alloy 400/K-500 material (Drain vent seat: Alloy 400, Drain vent stem: Alloy K-500)
Process Flanges and Adapters
Plated carbon steel SST: CF-8M (Cast 316 SST) per ASTM A743 Cast C-276: CW-12MW per ASTM A494 Cast Alloy 400: M-30C per ASTM A494
Non-Wetted Parts Electronics Housing
Low-copper aluminum alloy or CF-8M (Cast 316 SST) NEMA 4X, IP 66, IP 68 (66 ft (20 m) for 168 hours) Note: IP 68 not available with Wireless Output.
Paint for Aluminum Housing
Polyurethane
Coplanar Sensor Module Housing
SST: CF-3M (Cast 316L SST)
Reference Manual
00809-0100-4809, Rev CB
March 2012
Bolts
Plated carbon steel per ASTM A449, Type 1 Austenitic 316 SST per ASTM F593 ASTM A453, Class D, Grade 660 SST ASTM A193, Grade B7M alloy steel ASTM A193, Class 2, Grade B8M SST Alloy K-500
Sensor Module Fill Fluid
Silicone or inert halocarbon
Cover O-rings
Buna-N
Wireless Antenna
PBT/ polycarbonate (PC) integrated omnidirectional antenna
Power Module
Field replaceable, keyed connection eliminates the risk of incorrect installation, Intrinsically Safe Lithium-thionyl chloride Power Module with PBT enclosure.
A-20
Reference Manual
00809-0100-4809, Rev CB March 2012
Annubar Flowmeter Series
3051CFA ORDERING INFORMATION
Table A-4. Rosemount 3051CFA Annubar Flowmeter Ordering Information
The Standard offering represents the most common options. The starred options () should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.
Model Product Description
3051CFA Annubar Flowmeter
Measurement Type
Standard Standard
D Differential Pressure
Fluid Type
Standard Standard
L Liquid G Gas S Steam
Line Size
Standard Standard
020 2-in. (50 mm) 025 21/2-in. (63.5 mm) 030 3-in. (80 mm) 035 31/2-in. (89 mm) 040 4-in. (100 mm) 050 5-in. (125 mm) 060 6-in. (150 mm) 070 7-in. (175 mm) 080 8-in. (200 mm) 100 10-in. (250 mm) 120 12-in. (300 mm)
Expanded
140 14-in. (350 mm) 160 16-in. (400 mm) 180 18-in. (450 mm) 200 20-in. (500 mm) 240 24-in. (600 mm) 300 30-in. (750 mm) 360 36-in. (900 mm) 420 42-in. (1066 mm) 480 48-in. (1210 mm) 600 60-in. (1520 mm) 720 72-in. (1820 mm) 780 78-in (1950 mm) 840 84-in. (2100 mm) 900 90-in. (2250 mm) 960 96-in (2400 mm)
Pipe I.D. Range
Standard Standard
C Range C from the Pipe I.D. table D Range D from the Pipe I.D. table
Expanded
A Range A from the Pipe I.D. table B Range B from the Pipe I.D. table E Range E from the Pipe I.D. table Z Non-standard Pipe I.D. Range or Line Sizes greater than 12 inches
A-21
Reference Manual
00809-0100-4809, Rev CB
Annubar Flowmeter Series
Table A-4. Rosemount 3051CFA Annubar Flowmeter Ordering Information
The Standard offering represents the most common options. The starred options () should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.
Pipe Material / Mounting Assembly Material
Standard Standard
C Carbon steel (A105) S 316 Stainless Steel 0 No Mounting (Customer Supplied)
Expanded
G Chrome-Moly Grade F-11 N Chrome-Moly Grade F-22 J Chrome-Moly Grade F-91
Piping Orientation
Standard Standard
H Horizontal Piping D Vertical Piping with Downwar ds Flow U Vertical Piping with Upwards Flow
Annubar Type
Standard Standard
P Pak-Lok F Flanged with opposite side support
Expanded
L Flange-Lok G Gear-Drive Flo-Tap M Manual Flo-Tap
Sensor Material
Standard Standard
S 316 Stainless Steel
Expanded
H Alloy C-276
Sensor Size
Standard Standard
1 Sensor size 1 — Line sizes 2-in. (50 mm) to 8-in. (200 mm) 2 Sensor size 2 — Line sizes 6-in. (150 mm) to 96-in. (2400 mm) 3 Sensor size 3 — Line sizes greater than 12-in. (300 mm)
Mounting Type
Standard Standard
T1 Compression or Threaded Connection A1 150# RF ANSI A3 300# RF ANSI A6 600# RF ANSI D1 DN PN16 Flange D3 DN PN40 Flange D6 DN PN100 Flange
Expanded
(1)
A9
(1)
AF
(1)
AT R1 150# RTJ Flange R3 300# RTJ Flange R6 600# RTJ Flange
(1)
R9
(1)
RF
(1)
RT
900# RF ANSI 1500# RF ANSI 2500 # RF ANSI
900# RTJ Flange 1500# RTJ Flange 2500# RTJ Flange
March 2012
A-22
Reference Manual
00809-0100-4809, Rev CB March 2012
Table A-4. Rosemount 3051CFA Annubar Flowmeter Ordering Information
The Standard offering represents the most common options. The starred options () should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.
Opposite Side Support or Packing Gland
Standard Standard
0 No opposite side support or packing gland (Required for Pak-Lok and Flange-Lok models)
Opposite Side Support – Required for Flanged Models
C NPT Threaded Opposite Support Assembly – Extended Tip D Welded Opposite Support Assembly – Extended Tip
Expanded
Packing Gland – Required for Flo-Tap Models
Packing Gland Material Rod Material Packing Material
J Stainless Steel Packing Gland / Cage Nipple Carbon Steel PTFE K Stainless Steel Packing Gland / Cage Nipple Stainless Steel PTFE L Stainless Steel Packing Gland / Cage Nipple Carbon Steel Graphite N Stainless Steel Packing Gland / Cage Nipple Stainless Steel Graphite R Alloy C-276 Packing Gland / Cage Nipple Stainless Steel Graphite
Isolation Valve for Flo-Tap Models
Standard Standard
0 Not Applicable or Customer Supplied
Expanded
1 Gate Valve, Carbon Steel 2 Gate Valve, Stainless Steel 5 Ball Valve, Carbon Steel 6 Ball Valve, Stainless Steel 7 Ball Valve, Alloy C-276
Temperature Measurement
Standard Standard
T Integral RTD – not available with Flanged model greater than class 600# 0 No Temper ature Sensor
Expanded
R Remote Thermowell and RTD
Transmitter Connection Platform
Standard Standard
3 Direct-mount, Integral 3-valve Manifold– not available with Flanged model greater than class 600 5 Direct -mount, 5-valve Manifold – not available with Flanged model greater than class 600 7 Remote-mount NPT Connections (1/2-in. NPT)
Expanded
6 Direct-mount, high temperature 5-valve Manifold – not available with Flanged model greater than class 600 8 Remote-mount SW Connections (1/2-in.)
Differential Pressure Range
Standard Standard
1 0 to 25 in H2O (0 to 62,3 mbar) 2 0 to 250 in H2O (0 to 623 mbar) 3 0 to 1000 in H2O (0 to 2,5 bar)
Transmitter Output
Standard Standard
A 4–20 mA with digital signal based on HART Protocol F FOUNDATION fieldbus Protocol
(2)
W
Expanded
M Low-Power, 1-5 Vdc with Digital Signal Based on HART Protocol
Profibus PA Protocol
Annubar Flowmeter Series
A-23
Reference Manual
00809-0100-4809, Rev CB
Annubar Flowmeter Series
March 2012
Table A-4. Rosemount 3051CFA Annubar Flowmeter Ordering Information
The Standard offering represents the most common options. The starred options () should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.
Transmitter Housing Material Conduit Entry Size
Standard Standard
A Aluminum B Aluminum M20 x 1.5 J SST K SST M20 x 1.5
Expanded
D Aluminum G1/2 M SST G1/2
Transmitter Performance Class
Standard Standard
1 1.6% flow rate accuracy, 8:1 flow turndown, 5-yr. stability
1
/2-14 NPT
1
/2-14 NPT
Options (Include with selected model number)
Pressure Testing Expanded
(3)
P1
(3)
PX
Special Cleaning Expanded
P2 Cleaning for Special Services PA Cleaning per ASTM G93 Level D (Section 11.4)
Material Testing Expanded
V1 Dye Penetrant Exam
Material Examination Expanded
V2 Radiographic Examination
Flow Calibration Expanded
W1 Flow Calibration (Average K)
Special Inspection Standard Standard
QC1 Visual & Dimensional Inspection with Certificate QC7 Inspection & Performance Certificate
Surface Finish Standard Standard
RL Surface finish for Low Pipe Reynolds # in Gas & Steam RH Surface finish for High Pipe Reynolds # in Liquid
Material Traceability Certification Standard Standard
(4)
Q8
Code Conformance Expanded
J2 ANSI/ASME B31.1 J3 ANSI/ASME B31.3
Materials Conformance Expanded
(6)
J5
Country Certification Standard Standard
J6 European Pressure Directive (PED)
Expanded
J1 Canadian Registration
Hydrostatic Testing with Certificate Extended Hydrostatic Testing
Material Traceability Certification per EN 10474:2004 3.1
(5)
NACE MR-0175 / ISO 15156
A-24
Reference Manual
00809-0100-4809, Rev CB March 2012
Table A-4. Rosemount 3051CFA Annubar Flowmeter Ordering Information
The Standard offering represents the most common options. The starred options () should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.
Installed in Flanged Pipe Spool Section Expanded
H3 150# Flanged Connection with Rosemount Standard Length and Schedule H4 300# Flanged Connection with Rosemount Standard Length and Schedule H5 600# Flanged Connection with Rosemount Standard Length and Schedule
Instrument Connections for Remote Mount Options Standard Standard
G2 Needle Valves, Stainless Steel G6 OS&Y Gate Valve, Stainless Steel
Expanded
G1 Needle Valves, Carbon Steel G3 Needle Valves, Alloy C-276 G5 OS&Y Gate Valve, Carbon Steel G7 OS&Y Gate Valve, Alloy C-276
Special Shipment Standard Standard
Y1 Mounting Hardware Shipped Separately
Special Dimensions Expanded
VM Variable Mounting VT Variable Tip VS Variable length Spool Section
PlantWeb Control Functionality Standard Standard
(7)
A01
PlantWeb Diagnostic Functionality Standard Standard
(7)
D01
Product Certifications Standard Standard
C6 CSA Explosion-proof, Dust Ignition-proof, Intrinsically Safe, Division 2 E5 FM Explosion-proof, Dust Ignition-proof
(8)
E7 E8 ATEX Flameproof, Dust
(8)
I1 I5 FM Intrinsically Safe, Division 2 IA ATEX FISCO Intrinsic Safety; for FOUNDATION fieldbus protocol only K5 FM Explosion-proof, Dust Ignition-proof, Intrinsically Safe, Division 2 (combination of E5 and I5)
(8)
K6
(8)
K8 KB FM and CSA Explosion-proof, Dust Ignition-proof, Intrinsically Safe, Division 2 (combination of K5 and C6)
(8)
KD
(8)
N1
Alternate Transmitter Material of Construction Standard Standard
L1 Inert Sensor Fill Fluid Note: Silicone fill fluid is standard. L2 Graphite-Filled (PTFE) O-ring LA Inert Sensor Fill Fluid and Graphite-Filled (PTFE) O-ring
Display and Interface Options Standard Standard
(9)
M4 M5 LCD Display
FOUNDATION fieldbus Advanced Control Function Block Suite
FOUNDATION fieldbus Diagnostics Suite
IECEx Flameproof, Dust Ignition-proof
ATEX Intrinsic Safety
CSA Explosion-proof, Dust Ignition-proof, Intrinsically Safe, Division 2 (combination of E6 and I6) ATEX Flameproof, Intrinsic Safety, Type n, Dust (combination of E8, I1 and N1)
FM, CSA, and ATEX Explosion-proof, Intrinsically Safe (combination of K5, C6, I1, and E8) ATEX Type n
LCD Display with Local Operator Interface
Annubar Flowmeter Series
A-25
Reference Manual
00809-0100-4809, Rev CB
Annubar Flowmeter Series
Table A-4. Rosemount 3051CFA Annubar Flowmeter Ordering Information
The Standard offering represents the most common options. The starred options () should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.
Transmitter Calibration Certification Standard Standard
Q4 Calibration Certificate for Transmitter
Quality Certification for Safety Standard Standard
(11)
QS
Transient Protection Standard Standard
(10)
T1
Manifold for Remote Mount Option Standard Standard
F2 3-Valve Manifold, Stainless Steel F6 5-Valve Manifold, Stainless Steel
Expanded
F1 3-Valve Manifold, Carbon Steel F3 3-Valve Manifold, Alloy C-276 F5 5-Valve Manifold, Carbon Steel F7 5-Valve Manifold, Alloy C-276
Lower Power Output Standard Standard
(11)
C2
Alarm Limit Standard Standard
(11)(12)
C4
(11)(12)
CN
Ground Screw Standard Standard
(13)
V5
Typical Model Number: 3051CFA D L 060 D C H P S 2 T1 0 0 0 3 2 A A 1
(1) Available in remote mount applications only. (2) Option code M4 - LCD Display with Local Operator Interface req uired for local addressing and configuration. (3) Applies to assembled flowmeter only, mounting not tested. (4) Instrument Connections for Remote Mount Options and Isolation Valves for Flo-ta p Models are not included in the Material Traceability Certification. (5) Not available with Transmitter Connection Platform 6. (6) Materials of Construction comply with metallurgical requ irements within NACE MR0175/ISO fo r sour oil field production enviro nments. Environmenta l limits
(7) Only valid with F (8) Not available with Low Power code M. (9) Available only with output co de W - Profibus PA. (10) The T1 option is not needed with FISCO Product Certifications, transient protection is included with the FISCO Product Certification code IA. (11) Not available with F (12) NAMUR-Compliant operation is pre-set at the factory and cannot be changed to standard operation in the field. (13) The V5 option is not needed with the T1 option; external ground screw assembly is included with the T1 option.
Certificate of FMEDA data
Transient terminal block
0.8-3.2 Vdc Output with Digital Signal Based on Hart Protocol
NAMUR Alarm and Saturation Levels, High Alarm NAMUR Alarm and Saturation Levels, Low Alarm
External Ground Screw Assembly
apply to certain materials. Consult latest standard for details. Selected mat erials also conform to NACE MR0103 for sour refining environments.
OUNDATION fieldbus Output Code F.
OUNDATION fieldbus (Output Code F) or Profibus (Output Code W).
March 2012
A-26
Reference Manual
00809-0100-4809, Rev CB March 2012
Annubar Flowmeter Series
3051CFA PERFORMANCE SPECIFICATIONS
3051CFA FUNCTIONAL SPECIFICATIONS
Performance assumptions include: measured pipe I.D, transmitter is trimmed for optimum flow accuracy, and performance is dependent on application parameters.
Table 1. Flow Perfor mance - Flow Reference Accuracy
3051CFA Annubar Flowmeter
Ranges 2-3 ±1.60% of Flow Rate at 8:1 flow turndown
Range and Sensor Limits
Table 2. 3051CF Range and Sensor Limits
Range 3051CF Minimum Span Range and Sensor Limits
1
0.5 inH2O (1,2 mbar) 0 to 25 inH2O (62,3 mbar)
2
2.5 inH2O (6,2 mbar) 0 to 250 inH2O (0,63 bar)
3
10 inH2O (24,9 mbar) 0 to 1000 inH2O (2,49 bar)
Zero and Span Adjustment Requirements (HART and Low Power)
Zero and span values can be set anywhere within the range limits state d in Table 2 and Table 3.
Span must be greater than or equal to the minimum span stated in Table 2 and Table 3.
Service
Liquid, gas, and vapor applications
4–20 mA (Output Code A)
Output
Two-wire 4–20 mA, user-selectable for linear or square root output. Digital process variable superimposed on 4–20 mA signal, available to any host that conforms to the HART protocol.
Power Supply
External power supply required. Standard transmitter (4–20 mA) opera tes on
10.5 to 55 Vdc with no load.
A-27
Annubar Flowmeter Series
Voltage (Vdc)
Load (Ohms)
Communication requires a minimum
loop resistance of 250 ohms.
(1) For CSA approval, power supply must not exceed 42.4 V.
Max. Loop Resistance = 43.5 (Power Supply Voltage – 10.5)
Operating
Region
Load Limitations
Maximum loop resistance is determined by the voltage level of the external power supply, as described by:
Reference Manual
00809-0100-4809, Rev CB
March 2012
FOUNDATION fieldbus (output code F) and Profibus (output code W)
Power Supply
External power supply required; transmitters operate on 9.0 to 32.0 Vdc transmitter terminal voltage.
Current Draw
17.5 mA for all configurations (including LCD display option)
OUNDATION fieldbus Function Block Execution Times
F
Block Execution Time
Resource ­Transducer ­LCD Block ­Analog Input 1, 2 30 milliseconds PID 45 milliseconds Input Selector 30 milliseconds Arithmetic 35 milliseconds Signal Characterizer 40 milliseconds Integrator 35 milliseconds
F
OUNDATION fieldbus Parameters
Schedule Entries 7 (max.) Links 20 (max.) Virtual Communications Relationships (VCR) 12 (max.)
A-28
Reference Manual
00809-0100-4809, Rev CB March 2012
Annubar Flowmeter Series
Standard Function Blocks Resource Block
Contains hardware, electronics, and diagnostic information.
Transducer Block
Contains actual sensor measurement data including the sensor diagnostics and the ability to trim the pressure sensor or recall factory defaults.
LCD Block
Configures the local display.
2 Analog Input Blocks
Processes the measurements for input into other function blocks. The output value is in engineering units or custom and contains a status indicating measurement quality.
PID Block
Contains all logic to perform PID control in the field including cascade and feedforward.
Backup Link Active Scheduler (LAS)
The transmitter can function as a Link Active Scheduler if the current link master device fails or is removed from the segment.
Advanced Control Function Block Suite (Option Code A01) Input Selector Block
Selects between inputs and generates an output using specific selection strategies such as minimum, maximum, midpoint, average, or first “good.”
Arithmetic Block
Provides pre-defined application-based equations including flow with partial density compensation, electronic remote seals, hydrostatic tank gauging, ratio control, and others.
Signal Characterizer Block
Characterizes or approximates any function that defines an input/output relationship by configuring up to twenty X, Y coordinates. The block interpolates an output value for a given input value using the curve defined by the configured coordinates.
Integrator Block
Compares the integrated or accumulated value from one or two variables to pre-trip and trip limits and generates discrete output signals when the limits are reached. This block is useful for calculating total flow, total mass, or volume over time.
OUNDATION fieldbus Diagnostics Suite (Option Code D01)
F
The 3051C F Prevention (ASP) indication. The integral statistical process monitoring (SPM) technology calculates the mean and standard deviation of the process variable 22 times per second. The 3051C ASP algorithm uses these values and highly flexible configuration options for customization to many user-defined or application specific abnormal situations. The detection of plugged impulse lines is the first available predefined application.
OUNDATION fieldbus Diagnostics provide Abnormal Situation
A-29
Annubar Flowmeter Series
Reference Manual
00809-0100-4809, Rev CB
March 2012
Low Power (Output Code M)
Output
Three wire 1–5 Vdc or 0.8–3.2 Vdc (Option Code C2) user-selectable output. Also user selectable for linear or square root output configuration. Digital process variable superimposed on voltage signal, available to any host conforming to the HART protocol. Low-power transmitter operates on 6–12 Vdc with no load.
Power Consumption
3.0 mA, 18–36 mW
Minimum Load Impedance
100 k (V
Indication
Optional 5-digit LCD display
Overpressure Limits
Rosemount 3051CF
• Range 0: 750 psi (51,7 bar)
• Range 1: 2000 psig (137,9 bar)
• Ranges 2–5: 3626 psig (250 bar) 4500 psig (310,3 bar) for option code P9
Static Pressure Limit
Operates within specifications between static line pressures of 0.5 psia and 3626 psig.
Range 1: 0.5 psia and 2000 psig (3, 4 bar and 137, 9 bar)
wiring)
out
Burst Pressure Limits
Burst pressure on Coplanar process flange is 10000 psig (69 MPa).
Failure Mode Alarm
Output Code A
If self-diagnostics detect a gross transmitter failure, the analog signal will be driven either below 3.75 mA or to 21.75 mA to alert the user. NAMUR-compliant values are available, option code C4. High or low alarm signal is user-selectable by internal jumper.
Output Code M
If self-diagnostics detect a gross transmitter failure, the analog signal will be driven either below 0.94 V or above 5.4 V to alert the user (below 0.75 V or above 4.4 V for Option C2). High or low alarm signal is user-selectable by internal jumper.
Output Code F and W
If self-diagnostics detect a gross transmitter failure, that information gets passed as a status along with the process variable.
A-30