This manual is intended to be used as a supplement to the Rosemount 3051S Reference Manuals. Since
the Rosemount 3051S High Static Differential Pressure Transmitter (Rosemount 3051SHP) and
Rosemount 3051S utilize similar components, certain sections of this manual will be linked to the
corresponding Rosemount 3051S Reference Manual section. Any information that differs from the
Rosemount 3051S product will be covered within this manual.
The sections in this manual provide information on installing, operating, and maintaining the
Rosemount 3051SHP. The sections are organized as follows:
Section 1: Introduction provides an introduction to the pressure transmitter, how to use the manual,
models covered by this manual, and other support information for the transmitter.
Section 2: Installation contains instructions for mounting the transmitter, connecting it to the
process, and wiring the transmitter.
Section 3: Configuration provides instruction on commissioning and operating Rosemount
3051SHP transmitters from a bench computer or a hand held field device. Information on software
functions, configuration parameters, and on line variables are also included.
Section 4: Operation and Maintenance contains techniques to maintain the transmitter, and
disassembly/assembly directions.
Section 5: Troubleshooting provides troubleshooting techniques for the most common operating
issues.
Manual Supplement
00809-0100-4851, Rev AA
Section 6: Safety Instrumented Systems contains identification, commissioning, maintenance, and
operations information for the Rosemount 3051SHP SIS Safety Transmitter.
Section 7: Advanced HART Diagnostics contains procedures for installation, configuration, and
operation of the Rosemount 3051SHP HART Diagnostics option.
Section 8: Specifications and Reference Data supplies reference and specification data, as well as
Recycling of equipment and packaging should be taken into consideration and disposed of in accordance
with local and national legislation/regulations.
2
Rosemount 3051S High Pressure
Manual Supplement
00809-0100-4851, Rev AA
Section 2Installation
NOTICE
This section provides basic guidelines for Rosemount 3051SHP. It does not provide instructions for
configuration, diagnostics, maintenance, service, troubleshooting, Explosion-proof, Flameproof, or
intrinsically safe (I.S.) installations. This manual is also available electronically on
Emerson.com/Rosemount
Shipping considerations for wireless products
The unit was shipped to you without the power module installed. Remove the power module prior
to shipping the unit.
Each power module contains two “C” size primary lithium batteries. Primary lithium batteries are
regulated in transportation by the U.S. Department of Transportation, and are also covered by IATA
(International Air Transport Association), ICAO (International Civil Aviation Organization), and ARD
(European Ground Transportation of Dangerous Goods). It is the responsibility of the shipper to
ensure compliance with these or any other local requirements. Consult current regulations and
requirements before shipping.
.
Rosemount 3051S High Pressure
2017
Explosions could result in death or serious injury.
Installation of this transmitter in an explosive environment must be in accordance with the
appropriate local, national, and international standards, codes, and practices. Review “Product
Certifications” on page 52for any restrictions associated with a safe installation.
Before connecting a HART
®
-based communicator in an explosive atmosphere, make sure the
instruments in the loop are installed in accordance with intrinsically safe or non-incendive field
wiring practices.
In an Explosion-proof/Flameproof installation, do not remove the transmitter covers when power is
applied to the unit.
Process leaks may cause harm or result in death.
To avoid process leaks, ensure secure connection with coned-and-threaded connection.
Electrical shock can result in death or serious injury.
Avoid contact with the leads and the terminals. High voltage that may be present on leads can cause
electrical shock.
Conduit/cable entries
Unless marked, the conduit/cable entries in the transmitter housing use a
1
/2–14 NPT thread form.
Entries marked “M20” are M20 x 1.5 thread form. On devices with multiple conduit entries, all
entries will have the same thread form. Only use plugs, adapters, glands, or conduit with a
compatible thread form when closing these entries.
When installing in a hazardous location, use only appropriately listed or Ex certified flameproof/dust
plugs, adapters, or glands in cable/conduit entries.
Rosemount 3051S High Pressure
3
Rosemount 3051S High Pressure
2017
Wireless/power module considerations
The power module may be replaced in a hazardous area. The power module has surface
resistivity greater than one gigaohm and must be properly installed in the wireless device
enclosure. Care must be taken during transportation to and from the point of installation to
prevent electrostatic charge build-up.
This device complies with Part 15 of the FCC Rules. Operation is subject to the following
conditions. This device may not cause harmful interference. This device must accept any
interference received, including interference that may cause undesired operation. This device
must be installed to ensure a minimum antenna separation distance of 20 cm from all persons.
2.1System readiness
Note
The system readiness information is for the selectable HART 5/HART 7 Advanced Diagnostics (option code DA2)
version of the transmitter only.
Manual Supplement
00809-0100-4851, Rev AA
2.1.1Confirm HART Revision capability
If using HART based control or asset management systems, confirm the HART capability of those
systems prior to transmitter installation. Not all systems are capable of communicating with HART
Revision 7 Protocol. This transmitter can be configured for either HART Revision 5 or 7.
For instructions on how to change the HART revision of your transmitter, see the Rosemount 3051S
Reference Manual
.
2.1.2Confirm correct device driver
Verify the latest device driver (DD/DTM
communications.
Download the latest device driver at Emerson.com or FieldCommGroup.org.
Ta bl e 1 -1 provides the information necessary to ensure you have the correct device driver and
documentation for your device.
Table 1-1. Device Revisions and Files
Identify deviceFind device driver
Software
release
date
Apr-161.0.0207400809-0100-4801HART Revision 5 and 7
Oct-10N/A125300809-0100-4801Added Power Advisory,
NAMUR
software
revision
(1)
HART
software
revision
(2)
™
) is loaded on your systems to ensure proper
HART
universal
revision
53
Device
revision
(3)
Review
instructions
Manual
document
number
Review functionality
Changes to software
selectable
mA Output,
Power Consumption,
Coefficient of Variation
4
Rosemount 3051S High Pressure
Manual Supplement
00809-0100-4851, Rev AA
Table 1-1. Device Revisions and Files
Identify deviceFind device driver
May-07N/A75200809-0100-4801Update Statistical Process
Sep-06N/A4, 5, 65100809-0100-4801N/A
1. NAMUR sof tware revisio n is located on the hardware tag of the d evice. In accordance with NE53, revisions of the least significant level X (of
1.0.X) do not change functionality or operation of the device and will not be reflected in the review functionality column.
2. HART software revision can be read using a HART capable configuration tool.
3. Device driver file names use Device and DD Revision, e.g. 10_01. HART Protocol is designed to enable legacy device driver revisions to
continue to communicate with new HART devices. To access new functionality, the new device driver must be downloaded. It is
recommended to download new device driver files to ensure full functionality.
2.2Mount the transmitter
2.2.1Liquid flow applications
Rosemount 3051S High Pressure
Review
instructions
Review functionality
Monitoring Capability
2017
1.Place taps to the side of the line.
2.Mount beside or below the taps.
2.2.2Gas flow applications
1.Place taps in the top or side of the line.
2.Mount beside or above the taps.
Note
Bracket required to support the transmitter and the 1/4-in. tubing going into the transmitter.
Rosemount 3051S High Pressure
5
Rosemount 3051S High Pressure
2017
2.2.3Using a mounting bracket
The images below provide instructions on how to properly mount the transmitter using the Emerson™
provided mounting brackets. Use only bolts provided with the transmitter or sold as Emerson spare
parts. Bolts should be tightened to a torque of 125 in-lb.
Panel mountPipe mount
Manual Supplement
00809-0100-4851, Rev AA
Housings
PlantWeb
™
Junction boxRemote mount display
2.2.4Environmental seal for housing
Thread sealing (PTFE) tape or paste on male threads of conduit is required to provide a water/dust tight
conduit seal and meets requirements of NEMA
Protection ratings are required.
For M20 threads, install conduit plugs to full thread engagement or until mechanical resistance is met.
Note
IP 68 is not available with wireless output.
®
Type 4X, IP66, and IP68. Consult factory if other Ingress
2.2.5Installing high pressure coned and threaded connection
The transmitter comes with an autoclave connection designed for high pressure applications. Follow the
steps below to properly connect the transmitter to your process:
1.Apply a small amount of process-compatible lubricant to the gland nut threads.
2.Slip the gland nut onto the tube, then thread the collar onto the tube end (the collar is reverse
threaded).
3.Apply a small amount of process-compatible lubricant applied to the tube cone to help prevent
galling and facilitate sealing. Insert the tubing into the connection and tighten gland nut finger
tight.
6
Rosemount 3051S High Pressure
Manual Supplement
00809-0100-4851, Rev AA
4.Tighten the gland nut to a torque of 25 ft-lb.
Note
A weep hole has been designed into the transmitter for safety and leak detection. If fluid begins to leak from the
weep hole after torquing, isolate the process pressure, disconnect the transmitter, and reseal until the leak is
resolved.
All Rosemount 3051SHP Transmitters come with 316L SST tagging.
2.2.6Wireless considerations (if applicable)
Power up sequence
The power module should not be installed on any wireless device until the Emerson Smart Wireless
Gateway (Gateway) has been installed and functioning properly. See “Power up transmitter” on page 11
for more details.
Antenna position
Position the antenna vertically, either straight up or straight down (see Figure 1-1 on page 7). The
antenna should be approximately 3 ft. (1 m) from any large structure or building to allow clear
communication to other devices.
Rosemount 3051S High Pressure
2017
Figure 1-1. Antenna Position
High gain, remote antenna mounting instructions (WN wireless
option only)
The high gain, remote antenna option provides flexibility for mounting the transmitter based on wireless
connectivity, lightning protection, and current work practices (see Figure 1-2 on page 9).
Rosemount 3051S High Pressure
7
Rosemount 3051S High Pressure
2017
When installing the remote mount antenna for the transmitter, always use established safety
procedures to avoid falling or contact with high-power electrical lines.
Install remote antenna components for the transmitter in compliance with local and national
electrical codes and use best practices for lightning protection.
Before installing consult with the local area electrical inspector, electrical officer, and work area
supervisor.
The remote antenna option is specifically engineered to provide installation flexibility while
optimizing wireless performance and local spectrum approvals. To maintain wireless performance
and avoid non-compliance with spectrum regulations, do not change the length of cable or the
antenna type.
If the supplied remote mount antenna kit is not installed per these instructions, Emerson is not
responsible for wireless performance or non-compliance with spectrum regulations.
The high gain, remote mount antenna kit includes coaxial sealant for the cable connections for the
lightning arrestor and antenna.
Manual Supplement
00809-0100-4851, Rev AA
Find a location where the remote antenna has optimal wireless performance. Ideally this will be 15–25 ft.
(4,6–7,6 m) above the ground or 6 ft. (2 m) above obstructions or major infrastructure. To install the
remote antenna use the following procedure:
1.Mount the antenna on a 1.5- to 2-in. pipe mast using the supplied mounting equipment.
2.Connect the lightning arrestor directly to the top of the transmitter.
3.Install the grounding lug, lock washer, and nut on top of lightning arrestor.
4.Connect the antenna to the lightning arrestor using the supplied LMR-400 coaxial cable ensuring the
drip loop is not closer than 1 ft. (0,3 m) from the lightning arrestor.
5.Use the coaxial sealant to seal each connection between the wireless field device, lightning arrestor,
cable, and antenna.
6.Ensure the mounting mast and lightning arrestor are grounded according to local/national electrical
code.
Any spare lengths of coaxial cable should be placed in 12-in. (0,3 m) coils.
8
Rosemount 3051S High Pressure
Manual Supplement
A
B
D
C
00809-0100-4851, Rev AA
Figure 1-2. Rosemount 3051SHP with High Gain, Remote Antenna
Rosemount 3051S High Pressure
2017
A. Lightning arrestor
B. Antenna
C. Mounting mast
D. Drip loop
Note: Weather proofing is required!
The remote mount antenna kit includes coaxial sealant for weather proofing the cable connections for the lightning
arrestor, antenna, and the transmitter. Coaxial sealant must be applied to guarantee performance of the wireless
field network. See Figure 1-3 for details on how to apply coaxial sealant.
Figure 1-3. Applying Coaxial Sealant to Cable Connections
2.3Consider housing rotation
To improve field access to wiring or to better view the optional LCD display:
Rosemount 3051S High Pressure
1.Loosen the housing rotation set screw.
2.First rotate the housing clockwise to the desired location. If the desired location cannot be achieved
due to thread limit, rotate the housing counter clockwise to the desired location (up to 360° from
thread limit).
3.Retighten the housing rotation set screw up to 30 in-lb.
4.For wireless, consider access to the power module when selecting housing rotation.
9
Rosemount 3051S High Pressure
A
A
A
B
C
B
C
2017
Figure 1-4. Transmitter Housing Set Screw
PlantWebJunction box
A. Housing rotation set screw (3/32-in.)
Note
Do not rotate the housing more than 180° without first performing a disassembly procedure. Over-rotation may
sever the electrical connection between the sensor module and the feature board electronics.
2.4Set switches and jumpers
Manual Supplement
00809-0100-4851, Rev AA
If alarm and security adjustment option is not installed, the transmitter will operate normally with the
default alarm condition alarm “high” and the security “off”.
1.Do not remove the transmitter covers in explosive atmospheres when the circuit is live. If the
transmitters is live, set the loop to manual and remove power.
2.Remove the electronics compartment cover. On the PlantWeb housing the cover is opposite the
field terminals side, or on the junction box housing remove the terminal block cover. Do not remove
the housing cover in explosive environments.
3.On the PlantWeb housing, slide the security and alarm switches into the preferred position by using
a small screwdriver (an LCD display or an adjustment module must be in place to activate the
switches). On the junction box housing pull the pins out and rotate 90° into desired position to set
the security and alarm.
4.Reinstall the housing cover so that metal contacts metal to meet explosion-proof requirements.
Figure 1-5. Transmitter Switch and Jumper Configuration
PlantWebJunction box
A. Meter/adjustment module
B. Security
C. Alarm
10
Rosemount 3051S High Pressure
Manual Supplement
00809-0100-4851, Rev AA
Rosemount 3051S High Pressure
2.5Power up transmitter
This section provides the steps needed to power up transmitters. These steps are unique based on the
specific protocol used.
Steps for HART transmitters begin on page 11.
Steps for FOUNDATION
Steps for WirelessHART
2.5.1Connect wiring and power up for wired HART configuration
Use the following steps to wire the transmitter:
1.Remove and discard orange conduit plugs.
2.Remove the housing cover labeled “Field Terminals.”
3.Connect the positive lead to the “+” terminal, and the negative lead to the “–” terminal.
™
Fieldbus transmitters begin on page 17.
®
transmitter begin on page 18.
2017
Note
Do not connect the power across the test terminals. Power could damage the test diode in the test connection.
Twisted pairs yield best results. Use 24 AWG to 14 AWG wire and do not exceed 5,000 feet (1500 meters). For single
compartment housing (Junction Box housing), shielded signal wiring should be used in high EMI/RFI environments.
4.Ensure full contact with Terminal Block screw and washer. When using a direct wiring method, wrap
wire clockwise to ensure it is in place when tightening the terminal block screw.
Note
The use of a pin or ferrule wire terminal is not recommended as the connection may be more susceptible to
loosening over time or under vibration.
5.If the optional process temperature input is not installed, plug and seal the unused conduit
connection. If the optional process temperature input is being utilized, see “Install optional process
temperature input (Pt 100 RTD sensor)” on page 16 for more information.
Note
When the enclosed threaded plug is utilized in the conduit opening, it must be installed with a minimum thread
engagement in order to comply with explosion-proof requirements. For straight threads, a minimum of seven
threads must be engaged. For tapered threads, a minimum of five threads must be engaged.
6.If applicable, install wiring with a drip loop. Arrange the drip loop so the bottom is lower than the
conduit connections and the transmitter housing.
7.Reinstall the housing cover and tighten so the cover is fully seated with metal to metal contact
between the housing and cover in order to meet explosion proof requirements.
Figure 1-6 shows the wiring connections necessary to power a wired HART transmitter and enable
communications with a handheld Field Communicator.
Installation of the transient protection terminal block does not provide transient protection unless the transmitter
case is properly grounded.
Signal wiring grounding
Do not run signal wiring in conduit or open trays with power wiring, or near heavy electrical equipment.
Grounding terminations are provided on the sensor module and inside the terminal compartment.
These grounds are used when transient protection terminal blocks are installed or to fulfill local
regulations. See Step 2 below for more information on how the cable shield should be grounded.
1.Remove the field terminals housing cover.
2.Connect the wiring pair and ground as indicated in Figure 1-7. The cable shield should:
– Be trimmed close and insulated from touching the transmitter housing
– Continuously connect to the termination point
– Be connected to a good earth ground at the power supply end
12
Rosemount 3051S High Pressure
Manual Supplement
00809-0100-4851, Rev AA
Figure 1-7. Wiring
Rosemount 3051S High Pressure
2017
B
D
B
E
DP
A
C
A. Insulate shieldD. Trim shield and insulate
B. Minimize distanceE. Safety ground
C. Connect shield back to the power supply ground
B
3.Replace the housing cover. It is recommended the cover be tightened until there is no gap between
the cover and the housing.
Note
When the enclosed threaded plug is utilized in the conduit opening, it must be installed with a minimum thread
engagement in order to comply with explosion-proof requirements. For straight threads, a minimum of seven
threads must be engaged. For tapered threads, a minimum of five threads must be engaged.
4.Plug and seal unused conduit connections with the provided conduit plug.
Remote display wiring and power up (if applicable)
The remote mount display and Interface system consists of a local transmitter and a remote mount LCD
display assembly. The local transmitter assembly includes a junction box housing with a three-position
terminal block integrally mounted to a sensor module. The remote mount LCD display assembly consists
of a dual compartment PlantWeb housing with a seven position terminal block. See Figure 1-8 on
page 14 for complete wiring instructions. The following is a list of necessary information specific to the
remote mount display system:
Each terminal block is unique for the remote display system.
A 316 SST housing adapter is permanently secured to the remote mount LCD display PlantWeb
housing, providing an external ground and a means for field mounting with the provided mounting
bracket.
A cable is required for wiring between the transmitter and remote mount LCD display. The cable
length is limited to 100 ft.
50 ft. (option M8) or 100 ft. (option M9) cable is provided for wiring between the transmitter and
remote mount LCD display. Option M7 does not include cable; see recommended specifications.
Cable type
It is recommended that Madison AWM Style 2549 cable is used in this installation. Other comparable
cables may be used as long as it has independent dual twisted shielded pair wires with an outer shield.
The power wires must be 22 AWG minimum and the CAN communication wires must be 24 AWG
minimum.
Rosemount 3051S High Pressure
13
Rosemount 3051S High Pressure
A
B
C
(white) 24 AWG
(blue) 24 AWG
(black) 22 AWG
(red) 22 AWG
2017
Cable length
The cable length is up to 100 ft. depending upon cable capacitance.
Cable capacitance
The capacitance from the CAN communications line to the CAN return line as wired must be less than
5000 picofarads total. This allows up to 50 picofarads per foot for a 100 foot cable.
Intrinsic safety consideration
The transmitter assembly with remote display has been approved with Madison AWM Style 2549 cable.
Alternate cable may be used as long as the transmitter with remote display and cable is configured
according to the installation control drawing or certificate. Refer to appropriate approval certificate or
control drawing in the Rosemount 3051S Reference Manual
Important
Do not apply power to the remote communications terminal. Follow wiring instructions carefully to prevent damage
to system components.
Manual Supplement
00809-0100-4851, Rev AA
for remote cable IS requirements.
Figure 1-8. Remote Mount Display Wiring
A. Remote mount display
B. Junction box housing
C. 4–20 mA
Note
Wire colors provided on Figure 1-8 are per Madison AWM Style 2549 cable. Wire color may vary depending on cable
selected.
14
Madison AWM Style 2549 cable includes a ground shield. This shield must be connected to earth ground
at either the sensor module or the remote display, but not both.
Rosemount 3051S High Pressure
Manual Supplement
A
F
D
E
C
B
A
B
“+”
“
-”
00809-0100-4851, Rev AA
Quick connect wiring (if applicable)
As standard, the quick connect arrives properly assembled to the sensor module and is ready for
installation. Cordsets and field wireable connectors (in shaded area) are sold separately.
Figure 1-9. Rosemount Quick Connect Exploded View
Rosemount 3051S High Pressure
2017
A. Straight field wireable connector
B. Right angle field wireable connector
C. Quick connect housingF. Quick connect coupling nut
1. Order part number 03151-9063-0001.
2. Field wiring supplied customer.
3. Supplied by cordset vendor.
4. Order part number 03151-9063-0002.
(1)(2)
(2)
E. Coupling nut
D. Cordset
(4)
(3)
Important
If quick connect is ordered as a 300S spare housing or is removed from the sensor module, follow the instructions
below for proper assembly prior to field wiring.
1.Place the quick connect onto the sensor module. To ensure proper pin alignment, remove coupling
nut prior to installing quick connect onto the sensor module.
2.Place coupling nut over quick connect and wrench tighten to a maximum of 300 in-lb (34 N-m).
3.Tighten the set screw up to 30 in-lb using a
3
/32-in. hex wrench.
4.Install cordset/field wireable connectors onto the quick connect. Do not over tighten.
Figure 1-10. Quick Connect Housing Pin-Out
Rosemount 3051S High Pressure
A. Ground
B. No connection
Note
For other wiring details, refer to pin-out drawing and the cordset manufacturer’s installation instructions.
15
Rosemount 3051S High Pressure
Load (Ohms)
1387
1000
500
0
10.520
30
42.4
Operating
Region
Voltage (Vdc)
1322
1000
500
0
12.02030
42.4
Voltage (Vdc)
Load (Ohms)
Operating
Region
2017
Power supply
The DC power supply should provide power with less than two percent ripple. The total resistance load is
the sum of the resistance of the signal leads and the load resistance of the controller, indicator, and
related pieces. Note the resistance of intrinsic safety barriers, if used, must be included.
Figure 1-11. Load Limitation
Standard transmitter
Maximum Loop Resistance =
43.5 ⫻ (Power Supply Voltage – 10.5)
Manual Supplement
00809-0100-4851, Rev AA
HART diagnostic transmitter (option code DA2)
differential pressure and temperature transmitter
Maximum Loop Resistance =
43.5 ⫻ (Power Supply Voltage – 12.0)
The Field Communicator requires a minimum loop resistance of 250 Ω for communication.
2.5.2Install optional process temperature input
(Pt 100 RTD sensor)
Note
To meet ATEX/IECEx Flameproof certification, only ATEX/IECEx Flameproof cables (Temperature Input Code C30,
C32, C33, or C34) may be used.
1.Mount the Pt 100 RTD sensor in the appropriate location.
Note
Use shielded four-wire cable for the process temperature connection.
2.Connect the RTD cable to the transmitter by inserting the cable wires through the unused housing
conduit and connect to the four screws on the transmitter terminal block. An appropriate cable
gland should be used to seal the conduit opening around the cable.
3.Connect the RTD cable shield wire to the ground lug in the housing.
16
Rosemount 3051S High Pressure
Manual Supplement
00809-0100-4851, Rev AA
Figure 1-12. Transmitter RTD Wiring Connection
A
Red
Red
B
White
Rosemount 3051S High Pressure
2017
C
White
A. Pt 100 RTD sensor
B. RTD cable assembly wires
C. Ground lug
2.5.3Connect wiring and power up FOUNDATION Fieldbus transmitter
Cable connection
The segment cable can enter the transmitter through either conduit connection on the housing. Cable
entering the housing vertically should be avoided. Drip loops are recommended for installations where
moisture can accumulate and enter the terminal compartment.
Power supply
The transmitter requires between 9 and 32 Vdc (9 and 15 Vdc for FISCO) at the terminals to operate and
provide complete functionality.
Power conditioner
A fieldbus segment requires a power conditioner to isolate the power supply filter and decouple the
segment from other segments attached to the same power supply.
Signal termination
Every fieldbus segment requires terminators at each end of the segment. Failure to properly terminate
segments may cause communication errors with devices on the segment.
Transient protection
Transient protection devices require the transmitter be grounded for proper operation. Refer to
“Grounding” on page 18 for further information.
Rosemount 3051S High Pressure
17
Rosemount 3051S High Pressure
2017
Grounding
Grounding terminations are provided on the sensor module and inside the terminal compartment.
These grounds are used when transient protect terminal blocks are installed or to fulfill local regulations.
1.Remove the field terminals housing cover.
2.Connect the wiring pair and ground as indicated in Figure 1-13.
a.The terminals are not polarity sensitive.
b.The cable shield should:
– Be trimmed close and insulated from touching the transmitter housing
– Continuously connect to the termination point
– Be connected to a good earth ground at the power supply end
Figure 1-13. Wiring
Manual Supplement
00809-0100-4851, Rev AA
B
D
B
E
DP
A
C
A. Insulate shieldD. Trim shield and insulate
B. Minimize distanceE. Safety ground
C. Connect shield back to the power supply ground
B
FIELDBUS WIRING
3.Replace the housing cover. It is recommended the cover be tightened until there is no gap between
the cover and the housing.
4.Plug and seal the unused conduit connection with the provided conduit plug.
NOTICE
When installing in hazardous locations, the enclosed conduit plug must be installed in the unused
conduit opening per all local installation codes and standards.
2.5.4Connect the power module for WirelessHART transmitter
The power module should not be installed on any wireless device until the Gateway is installed and
functioning properly. This transmitter uses the black power module (order model number 701PBKKF).
Wireless devices should also be powered up in order of proximity from the Gateway, beginning with the
closest. This will result in a simpler and faster network installation. Enable active advertising on the
Gateway to ensure new devices join the network faster. For more information, see the Emerson Wireless
Gateway 1420 Reference Manual
.
18
Rosemount 3051S High Pressure
Loading...
+ 42 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.