Configure the Meter for Custom Output . . . . . . . . . . . . . . . .23
FIGURE 1. Model 3051C with the Optional LCD Meter.
2
BEFORE YOU INSTALL THE METER KIT
This document contains installation and operation information for
six different meter kits. Review Table 1 and Figure 2 carefully to
ensure that you are installing the appropriate meter kit.
TABLE 1. Descriptions of the Meter Kits.
Part NumberDescription
03031-0193-0101Meter kit – for use with improved style
aluminum housing
03031-0193-0111Meter kit – for use with improved style
stainless steel housing
03031-0193-1101Meter kit – for use with previous style
aluminum housing
03031-0193-1111Meter kit – for use with previous style
stainless steel housing
03031-0193-0103Meter only – for use with improved style
aluminum or stainless steel housings
03031-0193-1103Meter only – for use with previous style
aluminum or stainless steel housings
3
FIGURE 2. Improved and Previous Styles of the Model 3051
Transmitter Housing.
IMPROVED HOUSING
4.0 in.
(105 mm)
PREVIOUS HOUSING
3.2 in.
(80 mm)
4
OVERVIEW
The LCD meter provides local indication of the output, and
abbreviated diagnostic messages governing transmitter
operation. The meter is located on the electronics board side of
the transmitter, and receives its output information directly from
the electronics board microprocessor. An extended cover is
required to accommodate the meter.
The meter features a two-line display that accommodates five
digits for reporting the process variable on the top line, and six
characters for displaying engineering units on the bottom line.
And in addition to units of pressure, the new LCD meter is
capable of displaying flow and level units. The meter uses both
lines to display diagnostic messages. You can configure the
meter to display the following information:
䡲 Engineering Units
䡲 Percent of Range
䡲 User-Configurable LCD Scale
䡲 Alternating between any two of the above
The user-configurable scale is a new feature that enables you to
configure the LCD meter to a custom scale for flow or level. You
can configure the meter using a Model 275 HART Communicator
or AMS. With the user configurable scale feature, you can define
the decimal point position, the upper range value, the lower range
value, the engineering units, and the transfer function.
The user-configurable meter scale transfer function is independent
of the transmitter analog output transfer function, which allows the
meter to display square root flow output while the analog output
remains linear with the pressure input.
5
SAFETY MESSAGES
Procedures and instructions in this manual may require special
precautions to ensure the safety of the personnel performing the
operations. Information that raises potential safety issues is indicated
by a warning symbol ( ). Refer to the following safety messages
before performing an operation preceded by this symbol.
Explosions can result in death or serious injury.
• Do not remove the transmitter covers in explosive
atmospheres when the circuit is alive.
• Both transmitter covers must be fully engaged to meet
explosionproof requirements.
• Before connecting a communicator in an explosive
atmosphere, make sure the instruments in the loop are
installed in accordance with intrinsically safe or nonincendive
field wiring practices.
6
INSTALLATION PROCEDURES
The installation procedures vary depending on the style of
housing and the meter kit. Examine your meter part numbers
closely to ensure that you perform the appropriate procedure.
Part Numbers 03031-0193-0101
and 03031-0193-0111
The meter kit includes:
䡲 one LCD meter display
䡲 one extended cover with O-ring
䡲 two captive screws
䡲 one ten-pin interconnection header
Use the following procedure and Figure 3 to install the LCD meter.
NOTE
The LCD meter and the electronics board are
electrostatically sensitive; observe handling precautions for staticsensitive components.
7
FIGURE 3. Exploded View of the Transmitter and LCD Meter.
Interconnection Header
Jumpers (top and bottom)
LCD Meter
Extended Cover
1. If the transmitter is installed in a loop, secure the loop and
disconnect power.
2. Rotate the electronics housing up to 180 degrees (left or
right) to improve field access to the two compartments or
to better view the LCD meter. To rotate the housing,
release the housing rotation set screw and turn the
housing not more than 180 degrees from the orientation
shown in Figure 1 on page 2. To rotate the housing greater
than 180 degrees, refer to the Model 3051 product
manual, publication number 00809-0100-4001.
3051-3031A05A
NOTE
Do not rotate the housing greater than 180 degrees without first
referring to the Model 3051 product manual. Rotating the housing
greater than 180 degrees will damage the sensor module and
void the Rosemount warranty.
See “Safety Messages” on page 6 for complete warning information.
8