STANDARD CONFIGURATION
ALARM LEVELS
Unless otherwise specified, the transmitter is shipped with the following configuration:
Sensor Type: RTD, Pt 100, a = 0.00385 Number of Wires: 4 4 mA Value: 0 °C (32 °F) 20 mA Value: 100 °C (212 °F) Damping: 5 seconds Failure Mode: High/Upscale Output: Linear with Temperature Line Voltage Filter: 50 Hz Software Tag: Blank
Death or serious injury could result if the alarm levels of the Model 244EH or 244ER transmitter are not compatible with the alarm monitoring and detection systems.
Before installing the Model 244EH or 244ER transmitter in a control loop, verify that the upscale (high) and downscale (low) alarm levels are compatible with the alarm monitoring and detection system
Note of the following alarm levels before installing the Models 244EH or 244ER.
Table S-1. Standard vs. NAMUR-compliant specifications
Linear Output: 3.9 ≤ I ≤ 20.5 3.8 ≤ I ≤ 20.5 Fail High: 21 ≤ I ≤ 23 (default) 21 ≤ I ≤ 23 (default) Fail Low: I ≤ 3.75 I ≤ 3.6
(1) Measured in milliamperes
www.rosemount.com
Standard
(1)
NAMUR- Compliant
(1)
Manual Supplement
00809-0200-4737, Rev CA
Models 244EH and 244ER
December 2002
ATTACHING THE HEAD MOUNT TRANSMITTER
Integral Mount Sensor These sensors are available through the Temperature Sensors and
Accessories (Volume 2) Product Data Sheet (document number 00813-0200-2654).
To attach the transmitter to a integral mount sensor, use M2.5 4.0 mm-long flat head screws. Do not overtighten the screws.
Wall Panel or Other Integral Mount Sensor
To determine the correct screw length for attaching the transmitter to a wall panel or an integral mount sensor from a supplier other than Emerson Process Management, insert a
4.0 mm-long screw through the sensor plate and measure the distance that the screw extends from the plate surface (Length A in the diagram below).
If A 2.5 mm, use 4.0-mm long flat head screws. If A < 2.5 mm, use 5.0 mm-long flat head screws. Do not overtighten the screws.
Model 244EH
Transmitter
Length A
Sensor
(2) M2.5
Flat Head
Screw
MODEL 244EC CONFIGURATION SOFTWARE UPGRADE
The Model 244EC Configuration Software is compatible with Microsoft® Windows
®
95, 98, NT, and 2000.
The most recent version of the Model 244EC Configuration Software is v.04.00.000. Visit the following website to download the free software revision upgrade. The upgrade instructions are provided on the page that contains the upgrade files.
http://www.rosemount.com/products/temperature/m244cfg.html
Or, perform the following steps to download the free software revision upgrade:
1. Go to http://www.rosemount.com
2. Click on “Products.”
3. Click on “Temperature.”
4. Click on “Model 244EH and 244ER Programmable Temperature Transmi t t ers.”
5. Scroll to the bottom of the page and click “Upgrade to v.04.00.000,” located under “Model 244EC Configuration Software Tool.”
Rosemount and the Rosemount logotype are registered trademarks of Rosemount Inc. Microsoft and Windows are registered trademarks of Microsoft Inc. All other marks are the property of their respective owners.
Emerson Process Management
Rosemount Inc.
8200 Market Boulevard Chanhassen, MN 55317 USA T (U.S.) 1-800-999-9307 T (International) (952) 906-8888 F (952) 949-7001
www.rosemount.com
Rosemount Temperature GmbH
Frankenstrasse 21 63791 Karlstein Germany T 49 (6188) 992 0 F 49 (6188) 992 112
Emerson Process Management Asia Pacific Private Limited
1 Pandan Crescent Singapore 128461 T (65) 777 8211 F (65) 777 0947 AP.RMT-Specialist@emersonprocess.com
¢00809-0200-4737n¤
© 2002 Rosemount Inc. All rights reserved.
Loading...