Rosemount Manual: Sanitary Tank Spud Weld Guidelines | Rosemount Manuals & Guides

Reference Manual
00809-0100-4016, Rev DA September 2010
Sanitary Tank Spud
Sanit ary Tank Spud Weld Guidelines
This document is a welding guideline. Actual procedures and specifications vary based upon equipment and application.

TANK PREPARATION When preparing the tank, ensure an area wi th a minim um di amete r of 9 ¼-in.

is available to properly weld the tank spud, Figure 1-1 bullet 1. The center of the tank spud should be at least 1 ½-in. below the minimum measurement level, as shown in bullet 2 of Figure 1-1. In order to get a proper process fluid measurement, half of the remote seal diaphragm must be covered.
Figure 1-1. Tank Preparation
www.emersonprocess.com/rosemount
Bullet 3 shows the actual hole cut in the tank. Attempt to cut the hole as smoothly and as circular as possible. A torch cut is not recommended. The tank spud OD is 5.98-in. ±.010-in. When cutting the hole for the tank spud, the gap between the hole diameter and spud OD should be he ld to a min imum. It is recommended that the hole be no large r than 6.020-in. Anything larger than
6.020-in. could increase the amount of tank spud distortion. If a bevel(s) is required, an angle no larger than 37.5º is recommended; see
ASME B16.25 for more details. Bevels can be made on one or both sides of the tank. Do not grind or cut the bevel to a sharp point. Attempt to leave a flat area, as shown in Figure 1-2 below.
Sanitary Tank Spud
Figure 1-2. Bevel Example
Reference Manual
00809-0100-4016, Rev DA
September 2010
The flat area should be large enough to minimize spud distortion but small enough so that tank weld requirements can be met. Minimizing the bevel angle will decrease the amount of fill required during weld and minimize the number of weld passes. These best practices will decrease heat input and help mitigate distortion.

WELDING

Figure 1-3. O-ring Sealing Surfaces
Excessive heat will distort the tank spud. Allow adequate cooling time between passes.
Ensure spud is not assembled to transmitter and/or remote seal prior to welding.
Do not nick the sealing surfaces of the tank spud, the inner angled surfaces where the o-ring sits shown in Figure 1-3, as any irregularities may cause leaks.
1-2
Loading...
+ 2 hidden pages