Rosemount Manual: Rosemount 644 Temperature Transmitter with PROFIBUS PA Manuals & Guides

Reference Manual
00809-0300-4728, Rev AA January 2011
Rosemount 644 Temperature Transmitter with Profibus PA
www.rosemount.com
Reference Manual
NOTICE
00809-0300-4728, Rev AA January 2011
Rosemount 644
Rosemount 644 Temperature Transmitter with Profibus PA
Rosemount 644 Hardware Revision 9
Read this manual before working with the product. For personal and system safety, and for optimum product performance, make sure to thoroughly understand the contents before installing, using, or maintaining this product.
The United States has two toll-free assistance numbers and one international number.
Customer Central
1-800-999-9307 (7:00 a.m. to 7:00 p.m. CST)
National Response Center
1-800-654-7768 (24 hours a day) Equipment service needs
International
1-(952) 906-8888
The products described in this document are NOT designed for nuclear-qualified applications.
Using non-nuclear qualified products in applications that require nuclear-qualified hardware or products may cause inaccurate readings.
For information on Rosemount nuclear-qualified products, contact an Emerson Process Management Sales Representative.
www.rosemount.com
Reference Manual
00809-0300-4728, Rev AA January 2011
Table of Contents
Rosemount 644
SECTION 1 Introduction
SECTION 2 Configuration
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Using This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Transmitter Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Device Revision . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Considerations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Mechanical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Environmental. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Return of Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Configuration Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Profile 3.02 Identification Number Adaptation Mode . . . . . . . . . . . 2-3
Block Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Configuration Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Basic Setup Tasks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Device Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Assign Address. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Default Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Transmitter Setup Using Class 2 Master . . . . . . . . . . . . . . . . . . . . . . . 2-4
Basic Transmitter Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Process Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Simulation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
Transmitter Online Setup with DD or DTM . . . . . . . . . . . . . . . . . . . . . 2-6
Basic Transmitter Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
Process Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
LCD Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
Simulation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
SECTION 3 Hardware Installation
SECTION 4 Electrical Installation
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Typical European Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Typical North American Installation . . . . . . . . . . . . . . . . . . . . . . . . 3-4
LCD Display Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Sensor Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
Ground the Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
TOC-1
Rosemount 644
Reference Manual
00809-0300-4728, Rev AA
January 2011
SECTION 5 Calibration
SECTION 6 Troubleshooting
APPENDIX A Specifications and Reference Data
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Sensor Transducer Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Diagnostics Identification and Recommendation. . . . . . . . . . . . . . . . . 6-2
Extended Diagnostics Identification with class one master . . . . . . 6-4
PlantWeb and NE107 Diagnostics. . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-6
Alert Messages and Fail Safe Type Selection . . . . . . . . . . . . . . . . . . . 6-6
Profibus PA Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
Functional . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
Physical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-2
Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-3
Function Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-3
Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-7
Ordering Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-9
Tagging. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-12
Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-12
Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-14
Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-15
APPENDIX B Product Certifications
APPENDIX C Profibus Block Information
Approved Manufacturing Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1
European Union Directive Information. . . . . . . . . . . . . . . . . . . . . . . . . B-1
Hazardous Locations Certificates . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-2
Rosemount 644 with Profibus PA. . . . . . . . . . . . . . . . . . . . . . . . . . B-2
IECEx Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-4
Russian GOST Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-6
Kazakhstan GOST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-6
Ukraine GOST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-6
Installation Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-7
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-1
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .C-1
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-1
Resource Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .C-2
Condensed Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .C-7
TOC-2
Reference Manual
00809-0300-4728, Rev AA January 2011
Rosemount 644

Section 1 Introduction

Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1-1
Using This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1-2
Transmitter Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1-2
Device Revision . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1-3
Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 1-3
Return of Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1-4

SAFETY MESSAGES Instructions and procedures in this section may require special precautions to

ensure the safety of the personnel performing the operations. Information that potentially raises safety issues is indicated by a warning symbol ( ). Please refer to the following safety messages before performing an operation preceded by this symbol.
Warnings
Failure to follow these installation guidelines could result in death or serious injury.
• Make sure only qualified personnel perform the installation.
Explosions could result in death or serious injury.
• Do not remove the connection head cover in explosive atmospheres when the circuit is live.
• Before connecting Profibus devices in an explosive atmosphere, make sure the instruments in the loop are installed in accordance with intrinsically safe or non-intrinsic field wiring practices.
• Verify that the operating atmosphere of the transmitter is consistent with the appropriate hazardous locations certifications.
• All connection head covers must be fully engaged to meet explosion-proof requirements.
Process leaks could result in death or serious injury.
• Do not remove the thermowell while in operation.
• Install and tighten thermowells and sensors before applying pressure
Electrical shock could cause death or serious injury.
• Use extreme caution when making contact with the leads and terminals.
www.rosemount.com
Reference Manual
00809-0300-4728, Rev AA
Rosemount 644
January 2011

USING THIS MANUAL The sections in this manual provide information on installing, operating, and

maintaining the Rosemount 644 with Profibus PA protocol. The sections are organized as follows:
Section 2: Configuration provides instruction on commissioning and operating the Rosemount 644 PA transmitter. Information on software functions, configuration parameters, and online variables is also included.
Section 3: Hardware Installation contains mechanical mounting and installation instructions, and field upgrade options.
Section 4: Electrical Installation contains electrical installation instructions, with wiring and power considerations.
Section 5: Calibration contains techniques for calibration and troubleshooting
Appendix A: Specifications and Reference Data supplies reference and specification data, as well as ordering information.
Appendix B: Product Certifications contains intrinsic safety approval information, European ATEX directive information, and approval drawings.
Appendix C: Profibus Block Information contains Profibus block and parameter information.

TRANSMITTER OVERVIEW

Features of the Rosemount 644 with Profibus PA include:
Accepts inputs from a wide variety of sensors (T/C, RTD, Ohm, mV)
Configuration using Siemens SIMATIC PDM
Electronics that are completely encapsulated in epoxy making the transmitter extremely durable and ensuring long-term reliability
A compact size and a variety of housing options allowing mounting flexibility for the control room or the field
Refer to the following literature for a full range of compatible connection heads, sensors, and thermowells provided by Emerson Process Management.
Temperature Sensors and Assemblies Product Data Sheet, Volume 1 (document number 00813-0100-2654)
Temperature Sensors and Assemblies Product Data Sheet, Volume 2 (document number 00813-0200-2654)
Rosemount 1067 compact sensor and 1097 Thermowell Product Data Sheet (00813-0100-4951)
Rosemount 65Q and 65B Resistance Temperature Sensors for Hygienic and Sanitary Applications Product Data Sheet (00813-0100-4827)
NOTE
For Rosemount 644 with HART Product Manual 00809-0100-4728.
®
or FOUNDATION™ fieldbus, see Rosemount
1-2
Reference Manual
00809-0300-4728, Rev AA January 2011
Rosemount 644

DEVICE REVISION

Table 1-1. Device Revisions (NE53)
Date
11/ 10 1.01.016 3.02 New
Software Revision
Profibus Profile
Changes to Software
Product
Compatible Files
644 GSD: EPM1039.gsd Profile:3.02 GSD: pa139700.gsd DD: see Rosemount.com DTM: see Rosemount.com
Manual Revision
AA
CONSIDERATIONS General Electrical temperature sensors such as RTDs and thermocouples produce
low-level signals proportional to their sensed temperature. The 644 converts the low-level sensor signal to digital Profibus PA signal that is relatively insensitive to lead length and electrical noise. This signal is then transmitted to the control room via two wires.
Commissioning The transmitter can be commissioned before or after installation. It may be
useful to commission it on the bench, before installation, to ensure proper operation and to become familiar with its functionality. Make sure the instruments in the loop are installed in accordance with intrinsically safe, FISCO, or non-incendive field wiring practices.
Mechanical Location
When choosing an installation location and position, take into account the need for access to the transmitter.
Special Mounting
Special mounting hardware is available for mounting a 644 head mount transmitter to a DIN rail, or assembling a new 644 head mount to an existing threaded sensor connection head (former option code L1).
Electrical Proper electrical installation is necessary to prevent errors due to sensor lead
resistance and electrical noise. For best results, shielded cable should be used in electrically noisy environments.
Make wiring connections through the cable entry in the side of the connection head. Be sure to provide adequate clearance for cover removal.
Environmental The transmitter electronics module is permanently sealed within the housing,
resisting moisture and corrosive damage. Verify that the operating atmosphere of the transmitter is consistent with the appropriate hazardous locations certifications.
Temperature Effects
The transmitter will operate within specifications for ambient temperatures between –40 and 185 °F (–40 and 85 °C). Heat from the process is transferred from the thermowell to the transmitter housing. If the expected process temperature is near or beyond specification limits, consider the use of additional thermowell lagging, and extension nipple, or a remote mounting configuration to isolate the transmitter from the process.
1-3
Rosemount 644
Housing Temperature Rise, Above
Ambient °C (°F)
3 4 5 6 7 8 9
0
60 (108)
50 (90)
40 (72)
30 (54)
20 (36)
10 (18)
3.6
22
Extension Length (in.)
815 °C (1500 °F) Oven Temperature
540 °C (1000 °F) Oven Temperature
250 °C (482 °F) Oven Temperature
Figure 1-1. 644 head mount Transmitter Connection Head Temperature Rise vs. Extension Length
Reference Manual
00809-0300-4728, Rev AA
January 2011
Figure 1-1 provides an example of the relationship between transmitter housing temperature rise and extension length.
Example
The transmitter specification limit is 85 °C. If the ambient temperature is 55 °C and the process temperature to be measured is 800 °C, the maximum permissible connection head temperature rise is the transmitter specification limit minus the ambient temperature (moves 85 to 55 °C), or 30 °C.
In this case, an extension of 100 mm meets this requirement, but 125 mm provides a margin of 8 °C, thereby reducing any temperature effects in the transmitter.

RETURN OF MATERIALS To expedite the return process in North America, call the Emerson Process

Management National Response Center toll-free at 800-654-7768. This center, available 24 hours a day, will assist you with any needed information or materials.
The center will ask for the following information:
Product model
Serial numbers
The last process material to which the product was exposed
The center will provide
A Return Material Authorization (RMA) number
Instructions and procedures that are necessary to return goods that were exposed to hazardous substances
For other locations, please contact an Emerson Process Management sales representative.
1-4
NOTE
If a hazardous substance is identified, a Material Safety Data Sheet (MSDS), required by law to be available to people exposed to specific hazardous substances, must be included with the returned materials.
Reference Manual
00809-0300-4728, Rev AA January 2011
Rosemount 644

Section 2 Configuration

Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-1
Configuration Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-3
Basic Setup Tasks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 2-3
Transmitter Setup Using Class 2 Master . . . . . . . . . . . . .page 2-4
Transmitter Online Setup with DD or DTM . . . . . . . . . . . .page 2-6

SAFETY MESSAGES Instructions and procedures in this section may require special precautions to

ensure the safety of the personnel performing the operations. Information that potentially raises safety issues is indicated by a warning symbol ( ). Please refer to the following safety messages before performing an operation preceded by this symbol.
Warnings
Failure to follow these installation guidelines could result in death or serious injury.
• Make sure only qualified personnel perform the installation.
Explosions could result in death or serious injury.
• Do not remove the connection head cover in explosive atmospheres when the circuit is live.
• Before connecting Profibus devices in an explosive atmosphere, make sure the instruments in the loop are installed in accordance with intrinsically safe or non-incendive field wiring practices.
• Verify that the operating atmosphere of the transmitter is consistent with the appropriate hazardous locations certifications.
• All connection head covers must be fully engaged to meet explosion-proof requirements.
Process leaks could result in death or serious injury.
• Do not remove the thermowell while in operation.
• Install and tighten thermowells and sensors before applying pressure.
Electrical shock could cause death or serious injury.
• Use extreme caution when making contact with the leads and terminals.
www.rosemount.com
Rosemount 644
START
HERE
Bench
Calibration?
BASIC SETUP
Set Sensor Type
Set Number of Wires
Set Units
Set Range Values
Set Damping
VERIFY
Simulate Sensor Input
Within
Specifications?
Refer to Section 2: Configuration
FIELD INSTALL
Mount Transmitter
Wire Transmitter
Power Transmitter
FINISHED
Figure 2-1. Configuration Flowchart
Reference Manual
00809-0300-4728, Rev AA
January 2011
2-2
Reference Manual
00809-0300-4728, Rev AA January 2011
Rosemount 644

CONFIGURATION GUIDELINES

Profile 3.02 Identification Number Adaptation Mode
To configure on the bench, required equipment includes a power supply, a class 2 master with DP/PA coupler, proper cable, and terminators. Verify that the Security hardware jumper is set to the OFF position in order to proceed with configuration. See Figure 4-2 for jumper location.
Setup for the Rosemount 644 can be done via Siemens SIMATIC software or any other DD or DTM based Class 2 master.
Rosemount 644 Profibus Profile 3.02 devices are set to Identification Number Adaptation Mode when shipped from the factory. This mode allows the transmitter to communicate with any Profibus class 1 master with either the generic Profile GSD (9700) or Rosemount 644 specific GSD (1039).
®
PDM
Block Modes When configuring a device with a class 2 master, it is best practice to set
blocks to OOS when downloading parameters that affect the transmitter output. However, the 644 will allow configuration changes made in AUTO to be downloaded to the device. This prevents the class one master from seeing a jump in output without a status change. Setting the blocks OOS and back into Auto is done automatically when using the class two master configuration wizards within the Rosemount 644 DD or DTM. This is done so no additional action is required when configuring the device.
Configuration Tools The Rosemount 644 can be configured through the factory at order entry or
using a class 2 master. The C1 option code must be ordered to obtain addressing and configuration of the device at the factory.
Class 2 masters require either DD or DTM files for configuration. These files can be found at www.rosemount.com or by contacting your local Emerson Process representative.
The remainder of this section will cover the configuration tasks using the Class 2 master configuration tool.
NOTE
Instructions in this section use the terminology found in the class 2 master. See Appendix C: Profibus Block Information to cross reference parameters between the class2 master, and the Profibus specification.
BASIC SETUP TASKS Device Description Before configuring the device, ensure the host has the appropriate Device
Description file revision for this device. The device descriptor can be found on www.rosemount.com. The initial release of the Rosemount 644 with Profibus PA protocol is device revision 1.
Assign Address The Rosemount 644 is shipped with a temporary address of 126. This must
be changed to a unique value between 1 and 125 in order to establish communication with the class 1 master. Usually, addresses 1-2 are reserved for masters, therefore transmitter addresses between 3 and 125 are recommended for the device.
Address can be set using either:
Factory Configuration (C1 option code)
Class 2 master – see respective class 2 master manual for setting instrument addresses
2-3
Reference Manual
00809-0300-4728, Rev AA
Rosemount 644
January 2011
Default Configuration Unless otherwise specified, the Rosemount 644 will be shipped with the
following settings:
Table 2-1. Temperature configuration defaults

TRANSMITTER SETUP USING CLASS 2 MASTER

Basic Transmitter Setup
Table 2-2. Basic Transmitter Configuration using Class 2 master
Device Address: 126 Sensor Type: RTD, Pt 100 (= 0.00385, 4 wire) Damping: 5 sec. Units of Measurement: °C Alarm Limits:
• HI-HI: Infinity
• HI: Infinity
• LO: - Infinity
• LO-LO: Infinity Local Display (when installed): Engineering Units of Temperature Measurement Range: 0 °C to 100 °C
Desired Action Menu >> Parameter >> Value
Set Sensor Type Primary Value>>Sensor>>Sensor Type Set Connection Type (Number of Wires) Primary Value>>Sensor>>Sensor Connection Set Units Set Upper Range Value Primary Value>>Process Value Scale>>Upper Value Set Lower Range Value Primary Value>>Process Value Scale>>Lower Value Set Damping Value Primary Value>>Sensor>>Damping Value
* Please see “Basic Transmitter Configuration using DD or DTM” on page 2-6 for considerations when changing units.
*
Primary Value>>Sensor>>Primary Value Unit
Process Alarms Process alarms activate an output alarm status when the configured alarm
point is exceeded. A process alarm will be transmitted continuously if the output set points are exceeded. The alarms will reset once the value returns within range.
Process Alarm parameters are defined as follows
HI-HI Alarm: Changes Output Status to Good – Critical Alarm – Hi Limit
HI Warning: Changes Output Status to Good – Advisory Alarm – Hi Limit
LO Warning: Changes Output Status to Good – Advisory Alarm – Lo Limit
LO-LO Alarm: Changes Output Status to Good – Critical Alarm – Lo Limit
Alarm Hysteresis: Amount the output value must pass back into range before alarm is cleared.
Example: Upper Alarm = 100 °C. Alarm Hysteresis = 0.5 °C. After activation at 100 °C, the alarm will clear once the output goes below
99.5 °C = 100 - 0.5 °C.
Process Alerts can be set using,
2-4
Class 2 master – see Table 2-3 for configuration
Reference Manual
00809-0300-4728, Rev AA January 2011
Rosemount 644
Table 2-3. Process Alarm Configuration using Class 2 master
Desired Action Menu Path
Enter Process Alarm Levels Output>>Output Limits>>LO-LO Alarm
Output>>Output Limits>>LO Warning Output>>Output Limits>>HI Warning Output>>Output Limits>>HI- HI Alarm
Simulation Simulation is in the AI block and used to verify the output from the transducer
block. The Rosemount 644 has a simulation jumper located on the transmitter puck top cover that must be set to the ON position in order to simulate.
NOTE
This jumper position is ignored when the transmitter is initially powered. The jumper position must be changed while the transmitter is powered to activate simulation. If power is removed and restored, the simulation mode will be OFF regardless of jumper position.
With simulation enabled, the actual measurement value has no impact on the OUT value or the status. The OUT value will equal the simulated value from the transducer block plus any scaling or linearization effects performed in the AI block.
Table 2-4. Simulation configuration using Class 2 master
Once the simulation jumper is set to on, simulation mode can be activated Using a Class 2 master see Table 2-4.
Desired Action Menu >> Parameter >> Value
Enable Simulate Main Setup>>Human Interface>>
Simulation Status>>State>> Select Enabled Enter Simulation Value Select Simulation Status>>Press “Download to device” icon
Disable Simulate Main Setup>>Human Interface>>
Simulation Status>>State>> Select Disabled Press “Download to device” icon
2-5
Rosemount 644

TRANSMITTER ONLINE SETUP WITH DD OR DTM

Basic Transmitter Setup
Reference Manual
00809-0300-4728, Rev AA
January 2011
Table 2-5. Basic Transmitter Configuration using DD or DTM
Using Guided Setup
Desired Action Menu >> Category >> Method
Set Sensor Type Configure>>Guided Setup>>Configure Sensor Method Set Connection Type Configure>>Guided Setup>>Configure Sensor Method Set Units Configure>>Guided Setup>>Configure Sensor Method Set Damping Configure>>Guided Setup>>Configure Sensor Method
Using Manual Setup
Desired Action Menu >> Category >> Tab >> Value
Set Sensor Type Configure>>Manual Setup>>Sensor>>Sensor Type Set Connection Type
(Number of Wires) Set Units Configure>>Manual Setup>>Classic
Set Damping Configure>>Manual Setup>>Sensor>>Damping Value Set Upper Range Value Configure>>Manual Setup>>Classic View>>Analog
Set Lower Range Value Configure>>Manual Setup>>Classic View>>Analog
Configure>>Manual Setup>>Sensor>>Sensor Connection
View>>Transducer Block>>Primary Value Unit
Input Block>>Analog Input Block_1>>Lower Range
Input Block>>Analog Input Block_1>>Upper Range
NOTE Changes made to the PRIMARY_VALUE_UNIT parameter through Manual Setup>>Classic View are only reflected in the Transducer Block parameters.
To change the AI OUT units the PV Scale and OUT Scale need to be updated
to mirror the upper and lower sensor limits in the desired units.
2-6
Example: (All values are arbitrary)
The default configuration of the device is:
4-wire PT100_A_385 AI.OUT = 23 °C PRIMARY_VALUE_UNIT = °C PV_SCALE = 100, 0 PV.VALUE = 23 °C OUT_SCALE = 100,0, °C SV.VALUE = 23 °C USL = 850 °C LSL = -200 °C
If the user desires to change the units to °F, only the parameters in Bold will change with the PRIMARY_VALUE_UNIT. The AI.OUT will stay in °C until the
PV_SCALE and OUT_SCALE are configured to match each other. (This can
be with the measurement range or the sensor limits.
4-wire PT100_A_385 AI.OUT = 23 °C
PRIMARY_VALUE_UNIT = °C PV_SCALE = 212, 32 PV.VALUE = 73 °C OUT_SCALE = 100,0, °C SV.VALUE = 73 ° C USL = 1562 °C LSL = -328 °C
So the following change is needed:
PV_SCALE = 1562,-328 (make the same as USL and LSL) OUT_SCALE = 1562,-328, °F (make the same as PV_SCALE)
Reference Manual
00809-0300-4728, Rev AA January 2011
Rosemount 644
Process Alarms Process Alarms can be set using a DD or DTM – see Table 2-6 for
configuration.
Table 2-6. Process Alarm Configuration using DD or DTM
Desired Action Menu Path
Enter Process Alert Levels Configure>>Alarm Setup>>LO-LO>>[Value]
Configure>>Alarm Setup>>LO>>[Value] Configure>>Alarm Setup>>HI >>[Value] Configure>>Alarm Setup>>HI-HI >>[Value]
LCD Display The LCD display connects directly to the top of the transmitter puck and uses
a 10-pin connector to directly connect to the electronics board. A display cover is provided to accommodate the display.
The display always indicates the transmitter output temperature as well as abbreviated diagnostic status when applicable. When turned on, the display will alternate between the selected variables.
For LCD display configuration using a DD or DTM see Table 2-7.
Table 2-7. LCD Display Configuration using DD or DTM
Desired Action Menu >> Parameter >> Value
Select Display Parameters Configure>>Manual Setup>>Display Tab>>Select
Parameters to display
Simulation Once the simulation jumper is set to on, simulation mode can be activated
Using DD or DTM see Table 2-8.
Table 2-8. Simulation Configuration using DD or DTM
Desired Action Menu >> Parameter >> Value
Enable Simulate Service Tools>>Simulate>>Select Enabled State
Enter Simulation Value Select Simulation Status>>Press Transfer button
Disable Simulate Service Tools>>Simulate>>Select Disabled State
>>Press Transfer button
2-7
Rosemount 644
Reference Manual
00809-0300-4728, Rev AA
January 2011
2-8
Reference Manual
00809-0300-4728, Rev AA January 2011
Rosemount 644

Section 3 Hardware Installation

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 3-1
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-1
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-2
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-3

OVERVIEW The information in this section covers installation considerations for the

Rosemount 644. A Quick Installation Guide is shipped with every transmitter to describe pipe-fitting, wiring procedures, and basic configuration for initial installation.

SAFETY MESSAGES Procedures and instructions in this section may require special precautions to

ensure the safety of the personnel performing the operations. Information that raises potential safety issues is indicated by a warning symbol ( ). Refer to the following safety messages before performing an operation preceded by this symbol.
Warnings
Explosions could result in death or serious injury:
Installation of this transmitter in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices. Please review the approvals section of this reference manual for any restrictions associated with a safe installation.
• In an Explosion-Proof/Flameproof installation, do not remove the transmitter covers when power is applied to the unit.
Process leaks may cause harm or result in death.
• Install and tighten process connectors before applying pressure.
Electrical shock could cause death or serious injury.
• Avoid contact with the leads and terminals. High voltage that may be present on leads can cause electrical shock.
Individual transmitters are clearly marked with a tag indicating the approvals they carry. Transmitters must be installed in accordance with all applicable codes and standards to maintain these certified ratings. Refer to ““Hazardous Locations Certificates” on page B-2 for information on these approvals.
www.rosemount.com
Reference Manual
Transmitter
Mounting Hardware
Rail Clip
Transmitter
Mounting Hardware
Rail Clip
00809-0300-4728, Rev AA
Rosemount 644
January 2011

MOUNTING Mount the transmitter at a high point in the conduit run to prevent moisture

from draining into the transmitter housing.
The 644 head mount installs
In a connection head or universal head mounted directly on a sensor assembly
Apart from a sensor assembly using a universal head
To a DIN rail using an optional mounting clip.
The 644 rail mount attaches directly to a wall or to a DIN rail.
Mounting a 644H to a DIN Rail
To attach a head mount transmitter to a DIN rail, assemble the appropriate rail mounting kit (part number 00644-5301-0010) to the transmitter as shown in Figure 3-1.
Figure 3-1. Assembling Rail Clip Hardware to a 644
G-Rail (asymmetric) Top Hat Rail (symmetric)
Note: Kit includes Mounting Hardware and both types of Rail Kits.
Retrofitting a 644H for Use in an Existing Threaded Sensor Connection Head
To mount a 644 in an existing threaded sensor connection head (former option code L1), order the 644H retrofit kit (part number 00644-5321-0010). The retrofit kit includes a new mounting bracket and all associated hardware necessary to facilitate the installation of the 644H in the existing head. See Figure 3-2.
3-2
Reference Manual
Kit includes replacement bracket and screws.
Existing Threaded Sensor Connection Head
(Former option code L1)
A
D
B
C
E
F
00809-0300-4728, Rev AA January 2011
Figure 3-2. Assembling 644H for Use in an Existing L1 Connection Head

INSTALLATION

Rosemount 644
Typical European Installation
Head Mount Transmitter with DIN Plate Style Sensor
1. Attach the thermowell to the pipe or process container wall. Install
and tighten the thermowell before applying process pressure.
2. Assemble the transmitter to the sensor. Push the transmitter
mounting screws through the sensor mounting plate and insert the snap rings (optional) into the transmitter mounting screw groove.
3. Wire the sensor to the transmitter (see Figure 4-3 on page 4-3).
4. Insert the transmitter-sensor assembly into the connection head.
Thread the transmitter mounting screw into the connection head mounting holes. Assemble the extension to the connection head. Insert the assembly into the thermowell.
5. Attach conduit or a cable gland to the open connection head entry.
6. Insert the shielded cable leads into the connection head through the
conduit or cable entry. Seal the entry properly.
7. Connect the shielded power cable leads to the transmitter power
terminals. Avoid contact with sensor leads and sensor connections.
8. Install and tighten the connection head cover. Enclosure covers must
be fully engaged to meet explosion-proof requirements.
A = 644H Transmitter D = Transmitter Mounting Screws B = Connection Head E = Integral Mount Sensor with Flying Leads C = Thermowell F = Extension
3-3
Rosemount 644
A
B
C
D
E
Reference Manual
00809-0300-4728, Rev AA
January 2011
Typical North American Installation
Head Mount Transmitter with Threaded Sensor
1. Attach the thermowell to the pipe or process container wall. Install
and tighten thermowells before applying process pressure.
2. Attach necessary extension nipples and adapters to the thermowell.
Seal the nipple and adapter threads with silicone tape.
3. Screw the sensor into the thermowell. Install drain seals if required for
severe environments or to satisfy code requirements.
4. Pull the sensor wiring leads through the universal head and
transmitter. Mount the transmitter in the universal head by threading the transmitter mounting screws into the universal head mounting holes.
5. Mount the transmitter-sensor assembly into the thermowell. Seal
adapter threads with silicone tape.
6. Install a cable gland or conduit for field wiring to the conduit entry of
the universal head. Seal threads with silicone tape.
7. Pull the field wiring leads through the conduit into the universal head.
Attach the sensor and power leads to the transmitter. Avoid contact with other terminals.
8. Install and tighten the universal head cover. Enclosure covers must
be fully engaged to meet explosion-proof requirements.
3-4
A = Threaded Thermowell D = Universal Head B = Threaded Style Sensor E = Conduit Entry C = Standard Extension
Reference Manual
644H
Captive Mounting Screws and Springs
Meter Spacer
LCD Display
10 pin Connector
00809-0300-4728, Rev AA January 2011
Rosemount 644
LCD Display Installation The LCD display provides local indication of the transmitter output and
abbreviated diagnostic messages governing transmitter operation. Transmitters ordered with the LCD display are shipped with the meter installed. After-market installation requires the meter kit (part number 00644-4430-0001), which includes:
LCD display assembly (includes LCD display, meter spacer, and 2 screws)
Meter cover with O-ring in place
Figure 3-3. Installing the LCD Display
Use the following procedure to install the meter.
1. If the transmitter is installed in a loop, secure the loop and disconnect
the power. If the transmitter is installed in an enclosure, remove the cover from the enclosure.
2. Decide meter orientation (the meter can be rotated in 90°
increments). To change meter orientation, remove the screws located above and below the display screen. Lift the meter off the meter spacer. Remove the 10-pin plug and re-insert it in the location that will result in the desired viewing orientation.
3. Reattach the meter to the meter spacer using the screws. If the meter
was rotated 90° from its original position it will be necessary to remove the screws from their original holes and re-insert them in the adjacent screws holes.
4. Line up the 10-pin connector with the 10-pin socket and push the
meter into the transmitter until it snaps into place.
5. Attach and tighten the universal head cover. Enclosure covers must
be fully engaged to meet explosion-proof requirements.
6. Use a Profibus Class 2 master to configure the meter to the desired
display parameters.
NOTE
Observe the following LCD display temperature limits: Operating: –4 to 185 °F (–20 to 85 °C) Storage: –50 to 185 °F (–45 to 85 °C)
3-5
Rosemount 644
Reference Manual
00809-0300-4728, Rev AA
January 2011
3-6
Reference Manual
00809-0300-4728, Rev AA January 2011
Rosemount 644

Section 4 Electrical Installation

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 4-1
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-1
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-2

OVERVIEW The information in this section covers installation considerations for the

Rosemount 644. A Quick Installation Guide is shipped with every transmitter to describe pipe-fitting, wiring procedures, and basic configuration for initial installation.

SAFETY MESSAGES Procedures and instructions in this section may require special precautions to

ensure the safety of the personnel performing the operations. Information that potentially raises safety issues is indicated by a warning symbol ( ). Please refer to the following safety messages before performing an operation preceded by this symbol.
Warnings
Failure to follow these installation guidelines could result in death or serious injury.
• Make sure only qualified personnel perform the installation.
Explosions could result in death or serious injury.
• Do not remove the connection head cover in explosive atmospheres when the circuit is live.
• Before powering Profibus devices segment in an explosive atmosphere, make sure the instruments in the loop are installed in accordance with intrinsically safe or non-incendive field wiring practices.
• Verify that the operating atmosphere of the transmitter is consistent with the appropriate hazardous locations certifications.
• All connection head covers must be fully engaged to meet explosion-proof requirements.
Process leaks could result in death or serious injury.
• Do not remove the thermowell while in operation.
• Install and tighten thermowells and sensors before applying pressure.
Electrical shock could cause death or serious injury.
• Use extreme caution when making contact with the leads and terminals.
www.rosemount.com
Reference Manual
1 2 3 4
Sensor
Terminals
Communication
Terminals
Power Terminals
00809-0300-4728, Rev AA
Rosemount 644
January 2011

WIRING All power to the transmitter is supplied over the signal wiring. Use ordinary

copper wire of sufficient size to ensure that the voltage across the transmitter power terminals does not drop below 9 Vdc for Profibus PA. If the sensor is installed in a high-voltage environment and a fault condition or installation error occurs, the sensor leads and transmitter terminals could carry lethal voltages. Use extreme caution when making contact with the leads and terminals.
NOTE
Do not apply high voltage (e.g., ac line voltage) to the transmitter terminals. Abnormally high voltage can damage the unit. (Sensor and transmitter power terminals are rated to 42.4 Vdc. A constant 42.4 volts across the sensor terminals may damage the unit.)
The transmitters will accept inputs from a variety of RTD and thermocouple types. Refer to Figure 4-1 when making sensor connections. Refer to Figure 4-2 for Profibus installations.
Use the following steps to wire the power and sensor to the transmitter:
1. Connect the positive power lead to the .+. terminal. Connect the negative power lead to the .-. terminal.
2. Tighten the terminal screws. When tightening the sensor and power wires, the max torque is 6-in.-lbs (0.7 N-m).
3. Apply power.
Figure 4-1. Transmitter Power, Communication and Sensor Te rm i na l
644H
4-2
Reference Manual
Profibus DP
Profibus PA
MBP-IS at 31.25KBd
Terminator
6234 ft (1900m) max
(Depending on cable characteristics)
DP/PA
Coupler
PROFIBUS
Class 2
Master
(Configurati
on Tool)
RS-485 up to 12 MBD
Profibus Transmitter
Power/
Signal
Wiring
2-wire
RTD and
3-wire RTD
and
4-wire RTD
and
T/C
and mV
*
1234
1234
1234
1234
00809-0300-4728, Rev AA January 2011
Figure 4-2. Typical connection of a Profibus configuration host to a transmitter loop
Rosemount 644
NOTE
1. Each Segment in a Profibus trunk must be terminated at both ends.
2. Some DP/PA couplers contain the power supply, one terminator, and the power conditioner within the coupling device.
3. The configuration tool is typically located in the control room.
Sensor Connections The 644 is compatible with a number of RTD and thermocouple sensor types.
Figure 4-3 shows the correct input connections to the sensor terminals on the transmitter. To ensure a proper sensor connection, anchor the sensor lead wires into the appropriate compression terminals and tighten the screws.
Figure 4-3. Sensor Wiring Diagrams
* Emerson Process Management provides 4-wire sensors for all single element RTDs. Use these
RTDs in 3-wire configurations by leaving the unneeded leads disconnected and insulated with electrical tape.
Thermocouple or Millivolt Inputs
The thermocouple can be connected directly to the transmitter. Use appropriate thermocouple extension wire if mounting the transmitter remotely from the sensor. Make millivolt input connections with copper wire. Use shielding for long runs of wire.
644 Sensor Connections Diagram
4-3
Loading...
+ 61 hidden pages