Rosemount Manual: Rosemount 644 Head and Rail Mount Temperature Transmitters Manuals & Guides

Reference Manual
00809-0100-4728, Rev KA July 2010
Rosemount 644 Head and Rail Mount Temperature Transmitters
www.rosemount.com
Reference Manual
NOTICE
00809-0100-4728, Rev KA July 2010
Rosemount 644
Rosemount 644 Temperature Transmitters
Rosemount 644 Hardware Revision
®
Device Revision
HART Field Communicator Field Device Revision
OUNDATION
F
OUNDATION fieldbus Device Revision
F
Read this manual before working with the product. For personal and system safety, and for optimum product performance, make sure to thoroughly understand the contents before installing, using, or maintaining this product.
The United States has two toll-free assistance numbers and one international number.
Customer Central
1-800-999-9307 (7:00 a.m. to 7:00 P.M. CST)
National Response Center
1-800-654-7768 (24 hours a day) Equipment service needs
International
1-(952) 906-8888
The products described in this document are NOT designed for nuclear-qualified applications.
Using non-nuclear qualified products in applications that require nuclear-qualified hardware or products may cause inaccurate readings.
For information on Rosemount nuclear-qualified products, contact a Emerson Process Management Sales Representative.
fieldbus Hardware Revision
26
5.6 Dev v6, DD v1 5 1
www.rosemount.com
Reference Manual
00809-0100-4728, Rev KA July 2010
Table of Contents
Rosemount 644
SECTION 1 Introduction
SECTION 2 Installation
SECTION 3 HART Configuration
SECTION 4 Foundation fieldbus Configuration
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Return of Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-9
Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13
Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Field Communicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
AMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
Multidrop Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-18
Operation and Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-19
Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
General Block Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Foundation fieldbus function blocks . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
Operation and Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-14
APPENDIX A Specifications and Reference Data
APPENDIX B Product Certifications
APPENDIX C Foundation fieldbus Block Information
HART and Foundation Fieldbus Specifications . . . . . . . . . . . . . . . . . A-1
Foundation Fieldbus Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . A-4
4–20 mA / HART Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-6
Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-10
Ordering Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-12
Stainless Steel Housing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-18
Approved Manufacturing Locations . . . . . . . . . . . . . . . . . . . . . . . . . . B-1
European Union Directive Information . . . . . . . . . . . . . . . . . . . . . . . . B-1
Hazardous Locations Certificates . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-2
Installation Drawings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-10
Basic Setup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-1
Resource Block. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-1
Sensor Transducer Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-5
Analog Input (AI) Function Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-8
LCD Transducer Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-12
PID Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-13
TOC-1
Reference Manual
00809-0100-4728, Rev KA July 2010
Rosemount 644
TOC-2
Reference Manual
00809-0100-4728, Rev KA July 2010
Rosemount 644

Section 1 Introduction

Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1-1
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 1-2
Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 1-3
Return of Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1-4

SAFETY MESSAGES Instructions and procedures in this section may require special precautions to

ensure the safety of the personnel performing the operations. Information that potentially raises safety issues is indicated by a warning symbol ( ). Please refer to the following safety messages before performing an operation preceded by this symbol.
Warnings
Failure to follow these installation guidelines could result in death or serious injury.
• Make sure only qualified personnel perform the installation.
Explosions could result in death or serious injury.
• Do not remove the connection head cover in explosive atmospheres when the circuit is live.
• Before connecting HART or F make sure the instruments in the loop are installed in accordance with intrinsically safe or non-intrinsic field wiring practices.
• Verify that the operating atmosphere of the transmitter is consistent with the appropriate hazardous locations certifications.
• All connection head covers must be fully engaged to meet explosion-proof requirements.
Process leaks could result in death or serious injury.
• Do not remove the thermowell while in operation.
• Install and tighten thermowells and sensors before applying pressure
Electrical shock could cause death or serious injury.
• Use extreme caution when making contact with the leads and terminals.
OUNDATION fieldbus in an explosive atmosphere,
www.rosemount.com
Reference Manual
00809-0100-4728, Rev KA
Rosemount 644
OVERVIEW Manual This manual is designed to assist in the installation, operation, and
maintenance of Rosemount 644 head mount and 644 rail mount.
Section 1: Introduction
Transmitter and Manual Overview
Considerations
Return of Material
Section 2: Installation
Mounting
Installation
Wiring
Power Supply
Commissioning
Section 3: HART Configuration
Field Communicator
Configuration
Multidrop Communication
July 2010
Section 4: F
Calibration
Hardware Maintenance
Diagnostic Messaging
Appendix A: Specifications and Reference Data
Specifications
Dimensional drawings
Ordering Information
Biotechnology, Pharmaceutical Industries, and Sanitary Applications
Appendix B: Approvals
Product Certifications
Installation Drawings
Appendix C: Foundation fieldbus Block Information
Information regarding the Function Blocks
OUNDATION fieldbus Configuration
Transmitter Features of the Rosemount 644 include:
Accepts inputs from a wide variety of sensors
Configuration using HART protocol or F
Electronics that are completely encapsulated in epoxy and enclosed in a metal housing, making the transmitter extremely durable and ensuring long-term reliability
A compact size and two housing options allowing mounting flexibility for the control room or the field
OUNDATION fieldbus
1-2
Reference Manual
00809-0100-4728, Rev KA July 2010
Refer to the following literature for a full range of compatible connection heads, sensors, and thermowells provided by Emerson Process Management.
Temperature Sensors and Assemblies Product Data Sheet, Volume 1 (document number 00813-0100-2654)
Temperature Sensors and Assemblies Product Data Sheet, Volume 2 (document number 00813-0200-2654)
Rosemount 644
CONSIDERATIONS General Electrical temperature sensors such as RTDs and thermocouples produce
low-level signals proportional to their sensed temperature. The 644 converts the low-level sensor signal to a standard 4–20 mA dc, digital HART, or digital
OUNDATION fieldbus signal that is relatively insensitive to lead length and
F electrical noise. This signal is then transmitted to the control room via two wires.
Commissioning The transmitter can be commissioned before or after installation. It may be
useful to commission it on the bench, before installation, to ensure proper operation and to become familiar with its functionality. Make sure the instruments in the loop are installed in accordance with intrinsically safe, FISCO, or non-incendive field wiring practices.
Mechanical Location
When choosing an installation location and position, take into account the need for access to the transmitter.
Special Mounting
Special mounting hardware is available for mounting a 644 head mount transmitter to a DIN rail, or assembling a new 644 head mount to an existing threaded sensor connection head (former option code L1).
Electrical Proper electrical installation is necessary to prevent errors due to sensor lead
resistance and electrical noise. For best results, shielded cable should be used in electrically noisy environments.
Make wiring connections through the cable entry in the side of the connection head. Be sure to provide adequate clearance for cover removal.
Environmental The transmitter electronics module is permanently sealed within the housing,
resisting moisture and corrosive damage. Verify that the operating atmosphere of the transmitter is consistent with the appropriate hazardous locations certifications.
Temperature Effects
The transmitter will operate within specifications for ambient temperatures between –40 and 185 °F (–40 and 85 °C). Heat from the process is transferred from the thermowell to the transmitter housing. If the expected process temperature is near or beyond specification limits, consider the use of additional thermowell lagging, and extension nipple, or a remote mounting configuration to isolate the transmitter from the process.
Figure 1-1 provides an example of the relationship between transmitter housing temperature rise and extension length.
1-3
Rosemount 644
Housing Temperature Rise, Above
Ambient °C (°F)
3 4 5 6 7 8 9
0
60 (108)
50 (90)
40 (72)
30 (54)
20 (36)
10 (18)
3.6
22
Extension Length (in.)
815 °C (1500 °F) Oven Temperature
540 °C (1000 °F) Oven Temperature
250 °C (482 °F) Oven Temperature
Figure 1-1. 644 head mount Transmitter Connection Head Temperature Rise vs. Extension Length
Reference Manual
00809-0100-4728, Rev KA
July 2010
Example
The transmitter specification limit is 85 °C. If the ambient temperature is 55 °C and the process temperature to be measured is 800 °C, the maximum permissible connection head temperature rise is the transmitter specification limit minus the ambient temperature (moves 85 to 55 °C), or 30 °C.
In this case, an extension of 100 mm meets this requirement, but 125 mm provides a margin of 8 °C, thereby reducing any temperature effects in the transmitter.

RETURN OF MATERIALS To expedite the return process in North America, call the Emerson Process

Management National Response Center toll-free at 800-654-7768. This center, available 24 hours a day, will assist you with any needed information or materials.
The center will ask for the following information:
Product model
Serial numbers
The last process material to which the product was exposed
The center will provide
A Return Material Authorization (RMA) number
Instructions and procedures that are necessary to return goods that were exposed to hazardous substances
For other locations, please contact a Emerson Process Management sales representative.
NOTE
If a hazardous substance is identified, a Material Safety Data Sheet (MSDS), required by law to be available to people exposed to specific hazardous substances, must be included with the returned materials.
1-4
Reference Manual
00809-0100-4728, Rev KA July 2010
Rosemount 644

Section 2 Installation

Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-1
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-3
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-4
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-9
Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-13

SAFETY MESSAGES Instructions and procedures in this section may require special precautions to

ensure the safety of the personnel performing the operations. Information that potentially raises safety issues is indicated by a warning symbol ( ). Please refer to the following safety messages before performing an operation preceded by this symbol.
Warnings
Failure to follow these installation guidelines could result in death or serious injury.
• Make sure only qualified personnel perform the installation.
Explosions could result in death or serious injury.
• Do not remove the connection head cover in explosive atmospheres when the circuit is live.
• Before connecting a Field Communicator in an explosive atmosphere, make sure the instruments in the loop are installed in accordance with instrinsically safe or non-incendive field wiring practices.
• Verify that the operating atmosphere of the transmitter is consistent with the appropriate hazardous locations certifications.
• All connection head covers must be fully engaged to meet explosion-proof requirements.
Process leaks could result in death or serious injury.
• Do not remove the thermowell while in operation.
• Install and tighten thermowells and sensors before applying pressure
Electrical shock could cause death or serious injury.
• Use extreme caution when making contact with the leads and terminals.
www.rosemount.com
Rosemount 644
START
HERE
Bench
Calibration?
BASIC SETUP
Set Sensor Type
Set Number of Wires
Set Units
Set Range Values
Set Damping
VERIFY
Simulate Sensor Input
Within
Specifications?
Refer to Section 4: Foundation
fieldbus Configuration
FIELD INSTALL
Set Failure Mode
Switch
Mount Transmitter
Wire Transmitter
Power Transmitter
FINISHED
Does not apply to the 644 with F
OUNDATION fieldbus
Figure 2-1. Installation Flowchart
Reference Manual
00809-0100-4728, Rev KA
July 2010
2-2
Reference Manual
Transmitter
Mounting Hardware
Rail Clip
Transmitter
Mounting Hardware
Rail Clip
Kit includes replacement bracket and screws.
Existing Threaded Sensor Connection Head
(Former option code L1)
00809-0100-4728, Rev KA July 2010
Rosemount 644

MOUNTING Mount the transmitter at a high point in the conduit run to prevent moisture

from draining into the transmitter housing.
The 644 head mount installs
In a connection head or universal head mounted directly on a sensor assembly
Apart from a sensor assembly using a universal head
To a DIN rail using an optional mounting clip.
The 644 rail mount attaches directly to a wall or to a DIN rail.
Mounting a 644H to a DIN Rail
To attach a head mount transmitter to a DIN rail, assemble the appropriate rail mounting kit (part number 00644-5301-0010) to the transmitter as shown in Figure 2-2. Follow the procedure under “Rail Mount Transmitter and Sensor (HART only)”.
Figure 2-2. Assembling Rail Clip Hardware to a 644H
G-Rail (asymmetric) Top Hat Rail (symmetric)
Figure 2-3. Assembling 644H for Use in an Existing L1 Connection Head
Note: Kit includes Mounting Hardware and both types of Rail Kits.
Retrofitting a 644H for Use in an Existing Threaded Sensor Connection Head
To mount a 644H in an existing threaded sensor connection head (former option code L1), order the 644H retrofit kit (part number 00644-5321-0010). The retrofit kit includes a new mounting bracket and all associated hardware necessary to facilitate the installation of the 644H in the existing head. See Figure 2-3.
2-3
Rosemount 644
A
D
B
C
E
F

INSTALLATION

Reference Manual
00809-0100-4728, Rev KA
July 2010
Typical European Installation
Head Mount Transmitt er with DIN Plate Style Sensor (HART and F
OUNDATION fieldbus)
1. Attach the thermowell to the pipe or process container wall. Install
and tighten the thermowell before applying process pressure.
2. Verify the transmitter failure mode switch (HART only).
3. Assemble the transmitter to the sensor. Push the transmitter
mounting screws through the sensor mounting plate and insert the snap rings (optional) into the transmitter mounting screw groove.
4. Wire the sensor to the transmitter (see Figure 2-9 on page 2-11).
5. Insert the transmitter-sensor assembly into the connection head.
Thread the transmitter mounting screw into the connection head mounting holes.Assemble the extension to the connection head. Insert the assembly into the thermowell.
6. Attach a cable gland into the shielded cable.
7. Insert the shielded cable leads into the connection head through the
cable entry. Connect and tighten the cable gland.
8. Connect the shielded power cable leads to the transmitter power
terminals. Avoid contact with sensor leads and sensor connections.
9. Install and tighten the connection head cover. Enclosure covers must
be fully engaged to meet explosion-proof requirements.
A = 644H Transmitter D = Transmitter Mounting Screws B = Connection Head E = Integral Mount Sensor with Flying Leads C = Thermowell F = Extension
2-4
Reference Manual
A
B
C
D
E
00809-0100-4728, Rev KA July 2010
Rosemount 644
Typical North American Installation
Head Mount Transmitter with Threaded Sensor (HART and F
OUNDATION fieldbus)
1. Attach the thermowell to the pipe or process container wall. Install
and tighten thermowells before applying process pressure.
2. Attach necessary extension nipples and adapters to the thermowell.
Seal the nipple and adapter threads with silicone tape.
3. Screw the sensor into the thermowell. Install drain seals if required for
severe environments or to satisfy code requirements.
4. Verify the transmitter failure mode switch (HART only).
5. Pull the sensor wiring leads through the universal head and
transmitter. Mount the transmitter in the universal head by threading the transmitter mounting screws into the universal head mounting holes.
6. Mount the transmitter-sensor assembly into the thermowell. Seal
adapter threads with silicone tape.
7. Install conduit for field wiring to the conduit entry of the universal
head. Seal conduit threads with silicone tape.
8. Pull the field wiring leads through the conduit into the universal head.
Attach the sensor and power leads to the transmitter. Avoid contact with other terminals.
9. Install and tighten the universal head cover. Enclosure covers must
be fully engaged to meet explosion-proof requirements.
A = Threaded Thermowell D = Universal Head B = Threaded Style Sensor E = Conduit Entry C = Standard Extension
2-5
Rosemount 644
B
C
D
E
F
A
B
Reference Manual
00809-0100-4728, Rev KA
July 2010
Rail Mount Transmitter and Sensor (HART only)
1. Attach the transmitter to a suitable rail or panel.
2. Attach the thermowell to the pipe or process container wall. Install
and tighten the thermowell, according to plant standards, before applying pressure.
3. Attach the sensor to the connection head and mount the entire
assembly to the thermowell.
4. Attach and connect sufficient lengths of sensor lead wire from the
connection head to the sensor terminal block.
5. Tighten the connection head cover. Enclosure covers must be fully
engaged to meet explosion-proof requirements.
6. Run sensor lead wires from the sensor assembly to the transmitter.
7. Verify the transmitter failure mode switch.
8. Attach the sensor wires to the transmitter (see Figure 2-9 on
page 2-11).
A = Rail Mount Transmitter B = Sensor Leads with Cable Glands C = Integral Mount Sensor with Terminal Block D = Connection Head E = Standard Extension F = Threaded Thermowell
2-6
Reference Manual
A
D
E
C
B
00809-0100-4728, Rev KA July 2010
Rosemount 644
Rail Mount Transmitter with Threaded Sensor (HART only)
1. Attach the transmitter to a suitable rail or panel.
2. Attach the thermowell to the pipe or process container wall. Install
and tighten the thermowell before applying pressure.
3. Attach necessary extension nipples and adapters. Seal the nipple
and adapter threads with silicone tape.
4. Screw the sensor into the thermowell. Install drain seals if required for
severe environments or to satisfy code requirements.
5. Screw the connection head to the sensor.
6. Attach the sensor lead wires to the connection head terminals.
7. Attach additional sensor lead wires from the connection head to the
transmitter.
8. Attach and tighten the connection head cover. Enclosure covers must
be fully engaged to meet explosion-proof requirements.
9. Set the transmitter failure mode switch
10. Attach the sensor wires to the transmitter (see Figure 2-9 on
page 2-11).
A = Rail Mount Transmitter C = Standard Extension B = Threaded Sensor Connection Head D = Threaded Style Sensor
E = Threaded Thermowell
2-7
Reference Manual
644H
Captive Mounting Screws and Springs
Meter Spacer
LCD Display
10 pin Connector
00809-0100-4728, Rev KA
Rosemount 644
July 2010
LCD Display Installation The LCD display provides local indication of the transmitter output and
abbreviated diagnostic messages governing transmitter operation. Transmitters ordered with the LCD display are shipped with the meter installed. After-market installation of the meter can be performed the transmitter has a meter connector (transmitter revision 5.5.2 or later). After-market installation requires the meter kit (part number 00644-4430-0001), which includes:
LCD display assembly (includes LCD display, meter spacer, and 2 screws)
Meter cover with O-ring in place
Figure 2-4. Installing the LCD Display
Use the following procedure to install the meter.
1. If the transmitter is installed in a loop, secure the loop and disconnect
the power. If the transmitter is installed in an enclosure, remove the cover from the enclosure.
2. Decide meter orientation (the meter can be rotated in 90°
increments). To change meter orientation, remove the screws located above and below the display screen. Lift the meter off the meter spacer. Remove the 8-pin plug and re-insert it in the location that will result in the desired viewing orientation.
3. Reattach the meter to the meter spacer using the screws. If the meter
was rotated 90° from its original position it will be necessary to remove the screws from their original holes and re-insert them in the adjacent screws holes.
4. Line up the 10-pin connector with the 10-pin socket and push the
meter into the transmitter until it snaps into place.
5. Attach the meter cover; tighten at least one-third turn after the O-ring
contacts the transmitter housing. The cover must be fully engaged to meet explosion-proof requirements.
6. Use a Field Communicator, AMS software, or a F
OUNDATION fieldbus
Communication tool to configure the meter to the desired display. Refer to “LCD Meter Options ( 644H Only)” for information on configuring the LCD display.
2-8
NOTE
Observe the following LCD display temperature limits: Operating: –4 to 185 °F (–20 to 85 °C) Storage: –50 to 185 °F (–45 to 85 °C)
Reference Manual
Transmitter
No. 1
Transmitter
No. 2
R
Lead
R
Lead
R
Lead
Readout or
Controller No. 1
Readout or
Controller No. 2
To Additional Transmitters
dc
Power
Supply
Backup
Battery
Between 250 and 1100 if no load resistor.
00809-0100-4728, Rev KA July 2010
Rosemount 644
Multichannel Installations (HART)
In a HART installation, several transmitters can be connected to a single master power supply, as shown in Figure 2-5. In this case, the system may be grounded only at the negative power supply terminal. In multichannel installations where several transmitters depend on one power supply and the loss of all transmitters would cause operational problems, consider an uninterrupted power supply or a back-up battery. The diodes shown in Figure 2-5 prevent unwanted charging or discharging of the back-up battery.
Figure 2-5. Multichannel Installations

WIRING All power to the transmitter is supplied over the signal wiring. Use ordinary

copper wire of sufficient size to ensure that the voltage across the transmitter power terminals does not drop below 12.0 VDC for HART or 9 VDC for
OUNDATION fieldbus.
F
If the sensor is installed in a high-voltage environment and a fault condition or installation error occurs, the sensor leads and transmitter terminals could carry lethal voltages. Use extreme caution when making contact with the leads and terminals.
NOTE
Do not apply high voltage (e.g., ac line voltage) to the transmitter terminals. Abnormally high voltage can damage the unit. (Sensor and transmitter power terminals are rated to 42.4 VDC. A constant 42.4 volts across the sensor terminals may damage the unit.)
For multichannel HART installations, see above. The transmitters will accept inputs from a variety of RTD and thermocouple types. Refer to Figure 2-6 on page 2-10 when making sensor connections. Refer to Figure 2-8 on page 2-10 for F
OUNDATION fieldbus installations.
Use the following steps to wire the power and sensor to the transmitter:
1. Remove the terminal block cover (if applicable).
2. Connect the positive power lead to the “+” terminal. Connect the
negative power lead to the “–” terminal (see Figure 2-7).
3. Tighten the terminal screws. When tightening the sensor and power
wires, the max torque is 6-in.-lbs (0.7 N-m).
4. Reattach and tighten the cover (if applicable).
5. Apply power (see “Power Supply”).
2-9
Rosemount 644
1 2 3 4
Sensor
Terminals
Communication
Terminals
Power Terminals
Sensor Terminals
Power/ Configuration Terminals
Max torque is 6 in.-lbs (0/7 N-m)
250 RL  1100
Power
Supply
Field
Communicator
250 RL  1100
Power
Supply
Field Communicator
Power
Supply
6234 ft (1900 m) max
(depending upon cable characteristics)
Integrated Power
Conditioner and Filter
Terminators
(Spur)
(Spur)
(Trunk)
(The power supply,
filter, first
terminator, and
configuration
tool are typically
located in the
control room.)
Devices 1
through 16
F
OUNDATION
fieldbus
Configuration
Tool
Power/
Signal Wiring
Reference Manual
00809-0100-4728, Rev KA
July 2010
Figure 2-6. Transmitter Power, Communication, and Sensor Te rm i na l s
Figure 2-7. Connecting a HART Communication Tool to a Transmitter Loop
644H 644 Rail Mount
644H 644 Rail Mount
Figure 2-8. Connecting a F
OUNDATION fieldbus Host
System to a Transmitter Loop
2-10
Note: Signal loop may be grounded at any point or left ungrounded. Note: A Field Communicator may be connected at any termination point in the signal loop. The signal
Note: Max torque is 6 in.-lbs (0/7 N-m)
loop must have between 250 and 1100 ohms load for communications.
Reference Manual
2-wire
RTD and
3-wire RTD
and
4-wire RTD
and
T/C
and mV
*
1234
1234
1234
1234
00809-0100-4728, Rev KA July 2010
Rosemount 644
Sensor Connections The 644 is compatible with a number of RTD and thermocouple sensor types.
Figure 2-9 shows the correct input connections to the sensor terminals on the transmitter. To ensure a proper sensor connection, anchor the sensor lead wires into the appropriate compression terminals and tighten the screws.
Figure 2-9. Sensor Wiring Diagrams
* Emerson Process Management provides 4-wire sensors for all single element RTDs. Use these
RTDs in 3-wire configurations by leaving the unneeded leads disconnected and insulated withelectrical tape.
Thermocouple or Millivolt Inputs
The thermocouple can be connected directly to the transmitter. Use appropriate thermocouple extension wire if mounting the transmitter remotely from the sensor. Make millivolt inputs connections with copper wire. Use shielding for long runs of wire.
644 Sensor Connections Diagram
RTD or Ohm Inputs
The transmitters will accept a variety of RTD configurations, including 2-wire, 3-wire, 4-wire. If the transmitter is mounted remotely from a 3-wire or 4-wire RTD, it will operate within specifications, without recalibration, for lead wire resistances of up to 60 ohms per lead (equivalent to 6,000 feet of 20 AWG wire). In this case, the leads between the RTD and transmitter should be shielded. If using only two leads, both RTD leads are in series with the sensor element, so significant errors can occur if the lead lengths exceed three feet of 20 AWG wire (approximately 0.05 °C/ft). For longer runs, attach a third or fourth lead as described above.
Sensor Lead Wire Resistance Effect– RTD Input
When using a 4-wire RTD, the effect of lead resistance is eliminated and has no impact on accuracy. However, a 3-wire sensor will not fully cancel lead resistance error because it cannot compensate for imbalances in resistance between the lead wires. Using the same type of wire on all three lead wires will make a 3-wire RTD installation as accurate as possible. A 2-wire sensor will produce the largest error because it directly adds the lead wire resistance to the sensor resistance. For 2- and 3-wire RTDs, an additional lead wire resistance error is induced with ambient temperature variations. The table and the examples shown below help quantify these errors.
2-11
Rosemount 644
Basic Error
Imbalance of Lead Wires
PtRo

------------------------------------------------------------------=
Error due to amb. temp. variation
Cu
T
amb
 Imbalance of Lead Wires
Pt
Ro
-------------------------------------------------------------------------------------------------------------------------=
Basic error
0.5
0.00385 /  C100 
--------------------------------------------------------------------------------- - 1.3 C==
Error due to amb. temp. var. of 25 °C
0.0039 /  C25  C 0.5 
0.00385 /  C100
-------------------------------------------------------------------------------------------------------
0.1266 C==
Basic Error
Lead Wire Resistance
PtRo

----------------------------------------------------------=
Error due to amb. temp. variation
Cu
T
amb
 Lead Wire Resistance
Pt
Ro
-----------------------------------------------------------------------------------------------------------------=
Basic error
7.5
0.00385 /  C100 
--------------------------------------------------------------------------------- - 19.5 C==
Error due to amb. temp. var. of 25 °C
0.0039 /  C25  C 7.5 
0.00385 /  C100
-------------------------------------------------------------------------------------------------------
1.9 C==
Table 2-1. Examples of Approximate Basic Error
Reference Manual
00809-0100-4728, Rev KA
July 2010
Sensor Input Approximate Basic Error
4-wire RTD None (independent of lead wire resistance) 3-wire RTD ± 1.0 in reading per ohm of unbalanced lead wire resistance
(Unbalanced lead wire resistance = maximum imbalance between any two leads.)
2-wire RTD 1.0 in reading per ohm of lead wire resistance
Examples of Approximate Lead Wire Resistance Effect Calculations Given:
Total cable length: 150 m Imbalance of the lead wires at 20 °C: 1.5 Resistance/length (18 AWG Cu): 0.025 /m °C Temperature coefficient of Cu (Cu): 0.039 / °C Temperature coefficient of Pt(Pt): 0.00385 / °C Change in Ambient Temperature (T RTD Resistance at 0 °C (Ro): 100 (for Pt 100 RTD)
Pt100 4-wire RTD: No lead wire resistance effect.
Pt100 3-wire RTD:
): 25 °C
amb
Lead wire imbalance seen by the transmitter = 0.5
Pt100 2-wire RTD:
Lead wire resistance seen by the transmitter = 150 m × 2 wires ×
0.025
/m = 7.5
2-12
Reference Manual
4–20 mA dc
1322 1100
1000
750 500 250
0
1012.0 20 30 40 42.4
Load (Ohms)
Supply Voltage (VDC)
Operating
Region
00809-0100-4728, Rev KA July 2010

POWER SUPPLY HART Installation

To communicate with a transmitter, a 18.1 VDC minimum power supply is required. The power supplied to the transmitter should not drop below the transmitter lift-off voltage (see Figure 2-10). If the power drops below the lift-off voltage while the transmitter is being configured, the transmitter may interpret the configuration information incorrectly.
The dc power supply should provide power with less than 2 percent ripple. The total resistance load is the sum of the resistance of the signal leads and the load resistance of any controller, indicator, or related pieces of equipment in the loop. Note that the resistance of intrinsic safety barriers, if used, must be included.
Figure 2-10. Load Limits
Rosemount 644
Maximum Load = 40.8 x (Supply Voltage – 12.0)
OUNDATION fieldbus Installation
F
Powered over F
OUNDATION fieldbus with standard fieldbus power supplies.
The transmitter operates between 9.0 and 32.0 VDC, 11 mA maximum. Transmitter power terminals are rated to 42.4 VDC.
The power terminals on the 644 with F
OUNDATION fieldbus are polarity
insensitive.
2-13
Reference Manual
Sensor Wires
F
OUNDATION fieldbus segment
or 4–20 mA loop
Shield ground point
Connect shields together, electrically isolated from the transmitter.
Transmitter
00809-0100-4728, Rev KA
Rosemount 644
July 2010
Ground the Transmitter The transmitter will operate with the current signal loop either floating or
grounded. However, the extra noise in floating systems affects many types of readout devices. If the signal appears noisy or erratic, grounding the current signal loop at a single point may solve the problem. The best place to ground the loop is at the negative terminal of the power supply. Do not ground the current signal loop at more than one point.
The transmitter is electrically isolated to 500 V DC/AC rms (707 VDC), so the input circuit may also be grounded at any single point. When using a grounded thermocouple, the grounded junction serves as this point.
Neither side of the loop should be grounded on F
OUNDATION fieldbus devices.
Only the shield wire should be grounded.
NOTE
Do not ground the signal wire at both ends.
Ungrounded Thermocouple, mV, and RTD/Ohm Inputs
Each process installation has different requirements for grounding. Use the grounding options recommended by the facility for the specific sensor type, or begin with grounding Option 1 (the most common).
Option 1:
1. Connect signal wiring shield to the sensor wiring shield.
2. Ensure the two shields are tied together and electrically isolated from
the transmitter housing.
3. Ground shield at the power supply end only.
4. Ensure that the sensor shield is electrically isolated from the
surrounding grounded fixtures.
2-14
Option 2:
1. Connect sensor wiring shield to the transmitter housing (only if the
housing is grounded).
2. Ensure the sensor shield is electrically isolated from surrounding
fixtures that may be grounded.
3. Ground signal wiring shield at the power supply end.
Rosemount 644
Sensor Wires
Shield ground point
Transmitter
F
OUNDATION fieldbus segment
or 4–20 mA loop
Sensor Wires
Shield ground point
Transmitter
F
OUNDATION fieldbus segment
or 4–20 mA loop
Sensor Wires
Shield ground point
Transmitter
F
OUNDATION fieldbus segment
or 4–20 mA loop
Reference Manual
00809-0100-4728, Rev KA
July 2010
Option 3:
1. Ground sensor wiring shield at the sensor, if possible.
2. Ensure that the sensor wiring and signal wiring shields are electrically
isolated from the transmitter housing.
3. Do not connect the signal wiring shield to the sensor wiring shield.
4. Ground signal wiring shield at the power supply end.
Grounded Thermocouple Inputs
1. Ground sensor wiring shield at the sensor.
2. Ensure that the sensor wiring and signal wiring shields are electrically
isolated from the transmitter housing.
3. Do not connect the signal wiring shield to the sensor wiring shield.
4. Ground signal wiring shield at the power supply end.
2-15
Rosemount 644
Reference Manual
00809-0100-4728, Rev KA
July 2010
2-16
Reference Manual
00809-0100-4728, Rev KA July 2010

Section 3 HART Configuration

Rosemount 644
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 3-1
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-1
Field Communicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-3
Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-3
Multidrop Communication . . . . . . . . . . . . . . . . . . . . . . . . . page 3-18
Operation and Maintenance . . . . . . . . . . . . . . . . . . . . . . . . page 3-19

OVERVIEW This section provides information on configuring, troubleshooting, operating,

and maintaining the Rosemount 644 with HART protocol.

SAFETY MESSAGES Instructions and procedures in this section may require special precautions to

ensure the safety of the personnel performing the operations. Information that potentially raises safety issues is indicated by a warning symbol ( ). Please refer to the following safety messages before performing an operation preceded by this symbol.
Warnings
Failure to follow these installation guidelines could result in death or serious injury.
• Make sure only qualified personnel perform the installation.
Explosions could result in death or serious injury.
• Do not remove the connection head cover in explosive atmospheres when the circuit is live.
• Before connecting a Field Communicator in an explosive atmosphere, make sure the instruments in the loop are installed in accordance with instrinsically safe or non-incendive field wiring practices.
• Verify that the operating atmosphere of the transmitter is consistent with the appropriate hazardous locations certifications.
• All connection head covers must be fully engaged to meet explosion-proof requirements.
Process leaks could result in death or serious injury.
• Do not remove the thermowell while in operation.
• Install and tighten thermowells and sensors before applying pressure
Electrical shock could cause death or serious injury.
• Use extreme caution when making contact with the leads and terminals.
HART
www.rosemount.com
HART
Reference Manual
00809-0100-4728, Rev KA
Rosemount 644
July 2010
Surges/Transients The transmitter will withstand electrical transients of the energy level
encountered in static discharges or induced switching transients. However, high-energy transients, such as those induced in wiring from nearby lightning strikes, welding, heavy electrical equipment, or switching gears, can damage both the transmitter and the sensor. To protect against high-energy transients, install the transmitter into a suitable connection head with the Rosemount 470 Transient Protector. Refer to the 470 Transient Protector Product Data Sheet (document number 00813-0100-4191) for more information.

COMMISSIONING The 644 must be configured for certain basic variables to operate. In many

cases, all of these variables are pre-configured at the factory. Configuration may be required if the transmitter is not configured or if the configuration variables need revision.
Commissioning consists of testing the transmitter and verifying transmitter configuration data. 644 transmitters can be commissioned either before or after installation. Commissioning the transmitter on the bench before installation using a Field Communicator or AMS ensures that all transmitter components are in working order.
To commission on the bench, connect the transmitter and the Field Communicator or AMS as shown in Figure 2-7 on page 2-10. Make sure the instruments in the loop are installed according to intrinsically-safe or non-incendive field wiring practices before connecting a communication in an explosive atmosphere. Connect HART Communication leads at any termination point in the signal loop. For convenience, connect them to the terminals labeled “COMM” on the terminal block. Connecting across the “TEST” terminals will prevent successful communication. Avoid exposing the transmitter electronics to the plant environment after installation by setting all transmitter jumpers during the commissioning stage on the bench.
When using a Field Communicator, any configuration changes made must be sent to the transmitter by using the “Send” key (F2). AMS configuration changes are implemented when the “Apply” button is clicked.
For more information on using the Field Communicator with the 644 transmitter, see Section 3: HART Configuration.
Setting the Loop to Manual
When sending or requesting data that would disrupt the loop or change the output of the transmitter, set the process application loop to manual. The Field Communicator or AMS will prompt you to set the loop to manual when necessary. Acknowledging this prompt does not set the loop to manual. The prompt is only a reminder; set the loop to manual as a separate operation.
Failure Mode As part of normal operation, each transmitter continuously monitors its own
performance. This automatic diagnostics routine is a timed series of checks repeated continuously. If diagnostics detect an input sensor failure or a failure in the transmitter electronics, the transmitter drives its output to low or high depending on the position of the failure mode switch. Saturation levels are
3.90 mA for standard configuration (3.8 mA if configured for NAMUR­compliant operation) on the low end and 20.5 mA for standard or NAMUR­compliant configuration on the high end, if the sensor temperature is outside of range limits. These values are also custom configurable by the factory or using the Field Communicator.
3-2
Reference Manual
00809-0100-4728, Rev KA July 2010
Rosemount 644
The values to which the transmitter drives its output in failure mode depend on whether it is configured to standard, NAMUR-compliant, or custom operation. See “Hardware and Software Failure Mode” on page A-7 for standard and NAMUR-compliant operation parameters.
Changing Switch Positions
To change the failure mode on the 644 transmitter, follow the steps below.
1. If applicable, remove the enclosure cover.
2. Locate the orange failure mode switch. On the 644H the switch is located near the power terminals and located in the center of the front panel on the 644 rail mount (see Figure 2-6).
3. Move the switch to the desired alarm setting. To set the failure mode to high alarm, position the switch toward the “HI” mark on the terminal block. To set the failure mode to low alarm, position the switch in the opposite direction.
4. Replace the enclosure cover (if applicable). Enclosure covers must be fully engaged to meet explosion-proof requirements.

FIELD COMMUNICATOR The Field Communicator exchanges information with the transmitter from the

control room, the instrument site, or any wiring termination point in the loop. To facilitate communication, connect the Field Communicator in parallel with the transmitter (see Figure 2-11). Use the loop connection ports on the rear panel of the Field Communicator. The connections are non-polarized. Do not make connections to the serial port or the NiCad recharger jack in explosive atmospheres. Before connecting the Field Communicator in an explosive atmosphere, make sure the instruments in the loop are installed in accordance with intrinsically safe or non-incendive field wiring practices.
For more information regarding the Field Communicator, please see the Field Communicator Reference Manual.
HART

CONFIGURATION The 644 transmitter can be configured either on-line or off-line using a Field

Communicator or AMS. During on-line configuration, the transmitter is connected to a Field communicator. Data is entered in the working register of the communicator and sent directly to the transmitter. Off-line configuration consists of storing configuration data in a Field Communicator while it is not connected to a transmitter. Data is stored in nonvolatile memory and can be downloaded to the transmitter at a later time.
3-3
HART
The review menu lists all of the information stored in the 644. This includes device information, measuring element, output configuration, and software revision
1. TEST DEVICE
2. CALIBRATION
3. Write Protect
On-line Menu
1. Snsr 1 Digital Reading
2. Terminal Digital Reading
1. Snsr 1 Input Trim
2. Snsr 1 Trim-Fact
3. Active Calibrator
1. Loop Test
2. Self test
3. Master Reset
4. Status
1. SNSR 1 TRIM
2. D/A trim
3. Scaled D/A trim
1. Revision #s
2. Sensor Review
3. Dev Outputs Review
4. Device Information
5. Measurement Filtering
1. PROCESS VARIABLES
2. DIAGNOSTICS AND SERVICE
3. CONFIGURA TION
4. REVIEW
1. VARIABLE MAPPING
2. SENSOR CONFIGURATION
3. DEVICE OUTPUT CONFIGURATION
4. DEVICE INFORMATION
5. MEASUREMENT FILTERING
1. TRANSMITTER VARS
2. PV is
3. PV Digital Reading
4. PV AO
5. PV% rnge
6. PV LRV
7. PV URV
8. PV Lower Sensor Limits
9. PV Upper Sensor Limits
10.PV Damping
1. DEVICE SETUP
2. PV is
3. PV
4. PV AO
5. % RNGE
6. PV LRV
7. PV URV
1. PV is
2. SV is
3. TV is
4. QV is
5. Variable re-map
1. SENSOR 1
2. TERMINAL TEMP
1. Connections
2. SNSR 1 SETUP
3. CAL VANDUSEN
4. Sensor S/N
1. Terminal Units
2. Terminal Damp
3. Terminal LSL
4. Terminal USL
1. PV RANGE VALUES
2. ALARM SATURATION
3. HART OUTPUT
4. LCD METER OPTIONS
1. AO Alarm Type
2. Low Alarm
3. High Alarm
4. Low Sat.
5. High Sat.
1. Poll Addr
2. Num Req Preams
3. Burst Mode
4. Burst Option
1. Meter Configuration
2. Meter Decimal Pt
1. Tag
2. Date
3. Descriptor
4. Message
5. Final Assembly number
1. 50/60 Hz Filter
2. Active Calibrator
3. Open Sensor Holdoff
4. Intermit Detect
5. Intermit Thresh
1. 2-wire Offset
2. Snsr 1 Units
3. Snsr 1 Damp
4. Snsr LSL
5. Snsr USL
1. R0
2. Alpha
3. Delta
4. Beta
1. PV LRV
2. PV URV
3. PV Damping
4. PV Units
5. Apply Values
6. PV LSL
7. PV USL
8. PV Min. Span
These numbers are to be entered by the user.
When the hardware alarm switches are changed, the communicator should be power cycled to see new readings.
Reference Manual
00809-0100-4728, Rev KA
Rosemount 644
July 2010
HART Menu Tree Options listed in bold type indicate that a selection provides other options. For
ease of operation, changing calibration and setup, such as sensor type, number of wires, and range values, can be completed in several locations.
Figure 3-1. Field Communicator Menu Tree
3-4
Loading...
+ 112 hidden pages