Read this manual before working with the product. For personal and system safety, and for optimum product performance,
ensure you thoroughly understand the contents before installing, using, or maintaining this product.
For technical assistance, contacts are listed below:
Customer Central
Technical support, quoting, and order-related questions.
• United States - 1-800-999-9307 (7:00 am to 7:00 pm CST)
• Asia Pacific- 65 777 8211
North American Response Center
Equipment service needs.
• 1-800-654-7768 (24 hours a day — includes Canada)
• Outside of these areas, contact your local Emerson representative.
2
WARNING
Failure to follow safe installation and servicing guidelines could result in death or serious injury.
• Ensure the transmitter is installed by qualified personnel and in accordance with applicable code of practice.
• Use the equipment only as specified in this manual. Failure to do so may impair the protection provided by the equipment.
• Do not perform any services other than those contained in this manual unless you are qualified.
Explosions could result in death or serious injury.
• Verify that the operating atmosphere of the transmitter is consistent with the appropriate hazardous locations certifications.
• Before connecting a handheld communicator in an explosive atmosphere, ensure the instruments are installed in accordance
with intrinsically safe or non-incendive field wiring practices.
• Do not remove the gauge cover in explosive atmospheres when the circuit is alive.
• To prevent ignition of flammable or combustible atmospheres, disconnect power before servicing.
Process leaks could result in death or serious injury.
• Ensure that the transmitter is handled carefully. If the process seal is damaged, gas might escape from the tank if the
transmitter head is removed from the probe.
High voltage that may be present on leads could cause electrical shock.
• Avoid contact with the leads and terminals.
• Ensure the main power to the transmitter is off and the lines to any other external power source are disconnected or not
powered while wiring the transmitter.
• Probes covered with plastic and/or with plastic discs may generate an ignition-capable level of electrostatic charge under
certain extreme conditions. Therefore, when the probe is used in a potentially explosive atmosphere, appropriate measures
must be taken to prevent electrostatic discharge.
• Eliminate the risk of Electrostatic Discharge (ESD) discharge prior to dismounting the transmitter head. Probes may generate
an ignition-capable level of electrostatic charge under extreme conditions. During any type of installation or maintenance in a
potentially explosive atmosphere, the responsible person should ensure that any ESD risks are eliminated before attempting
to separate the probe from the transmitter head.
Electrical shock could cause death or serious injury.
• Use extreme caution when making contact with the leads and terminals.
Any substitution of non-recognized parts may jeopardize safety. Repair (e.g. substitution of components) may also jeopardize
safety and is not allowed under any circumstances.
• Unauthorized changes to the product are strictly prohibited as they may unintentionally and unpredictably alter performance
and jeopardize safety. Unauthorized changes that interfere with the integrity of the welds or flanges, such as making
additional perforations, compromise product integrity and safety. Equipment ratings and certifications are no longer valid on
any products that have been damaged or modified without the prior written permission of Emerson. Any continued use of
product that has been damaged or modified without the written authorization is at the customer’s sole risk and expense.
WARNING
Physical access
Unauthorized personnel may potentially cause significant damage to and/or misconfiguration of end users’ equipment. This could
be intentional or unintentional and needs to be protected against.
Physical security is an important part of any security program and fundamental to protecting your system. Restrict physical access
by unauthorized personnel to protect end users’ assets. This is true for all systems used within the facility.
3
CAUTION
Hot surfaces
The flange and process seal may be hot at high process temperatures. Allow to cool before servicing.
CAUTION
The products described in this document are NOT designed for nuclear-qualified applications. Using non-nuclear qualified
products in applications that require nuclear-qualified hardware or products may cause inaccurate readings. For information on
Rosemount nuclear-qualified products, contact your local Emerson Sales Representative.
CAUTION
This product is designed to meet FCC and R&TTE requirements for a non-intentional radiator. It does not require any licensing
whatsoever and has no tank restrictions associated with telecommunications issues.
CAUTION
This device complies with Part 15 of the FCC Rules. Operation is subject to the following conditions:
• This device may not cause harmful interference.
• This device must accept any interference received, including interference that may cause undesired operation.
4
Safety ManualContents
00809-1900-4530September 2020
Contents
Chapter 1Before you begin........................................................................................................7
1.1 About this document...................................................................................................................7
1.2 About this product.......................................................................................................................7
1.3 Related documents......................................................................................................................7
Chapter 2Installation and commissioning..................................................................................9
2.1 Safety Instrumented System (SIS) certification............................................................................ 9
4.3 Reset to factory settings............................................................................................................ 42
Appendix ATerms and definitions...............................................................................................43
Rosemount 5300:SIS Level Transmitter5
ContentsSafety Manual
September 202000809-1900-4530
6Safety Manual
Safety ManualBefore you begin
00809-1900-4530September 2020
1Before you begin
1.1About this document
This document provides information about how to install, commission, and proof-test a
Rosemount 5300 Level Transmitter to comply with Safety Instrumented Systems (SIS)
requirements.
Note
The following conditions must apply:
• The transmitter has been installed correctly and completely according to the
instructions in the Reference Manual and Quick Start Guide.
• The installation complies with all applicable safety requirements.
• The operator is trained in local and corporate safety standards.
1.2About this product
The Rosemount 5300 is a two-wire transmitter for continuous level measurements over a
broad range of liquids, slurries, and solids. The measurement principle is Time Domain
Reflectometry (TDR).
The Rosemount 5300 can be used as the level sensor in a BPCS or as a safety device in a
safety instrumented system.
1.2.1
Application examples
• Level range monitoring
• Dry-run prevention
• Overfill prevention
1.3Related documents
You can find all product documentation at Emerson.com/Rosemount.
For more information, see the following documents:
Table 1-1: Related Documentation
DocumentDocument type
00809-0100-4530Reference Manual
00813-0100-4530Product Data Sheet
00825-0100-4530Quick Start Guide
00809-0900-4530Manual Supplement: High Level Supervision
00809-1800-4530Manual Supplement: Cold Temperature Option Code BR5
Rosemount 5300:SIS Level Transmitter7
Before you beginSafety Manual
September 202000809-1900-4530
8Safety Manual
Safety ManualInstallation and commissioning
00809-1900-4530September 2020
2Installation and commissioning
2.1Safety Instrumented System (SIS) certification
For safety instrumented systems usage, the 4-20 mA analog output is used as the primary
safety variable. It is configured to activate the alarm function if an error occurs. If a
measured value goes beyond the measurement range, the transmitter enters saturation
mode (limit alarm is disabled) or alarm mode, depending on the current configuration.
The minimum time for the alarm condition is 200 ms.
The measurement signal used by the logic solver must be the analog 4-20 mA signal
proportional to the level generated. The HART® protocol can only be used for setup,
calibration, and diagnostic purposes, not for safety critical operation.
The Rosemount™ 5300 Level Transmitter is IEC 61508 certified accordingly:
• Low and high demand: Type B element
• SIL 2 for random integrity @ HFT=0
• SIL 3 for random integrity @ HFT=1
• SIL 3 for systematic capability
2.2Safety-certified identification
All Rosemount 5300 Level Transmitter must be identified as safety-certified before
installing into SIS systems. Table 2-1 lists the versions of the Rosemount 5300 Level
Transmitter that have been considered for the hardware assessment, to which this section
applies.
• Models with the QS option code are supplied with a manufacturer’s prior use certificate
of FMEDA data.
• Models with the QT option code are IEC 61508 certified by an accredited 3rd party
agency for use in safety instrumented systems up to SIL 3. (For single use (1oo1)
capable up to SIL 2 and for redundant use (1oo2 or 2oo3) capable up to SIL 3.)
Table 2-1: Rosemount 5300 Series Safety-Certified Option Model Codes
Rosemount 5300 4-20 mA HART Guided Wave Radar Level and Interface Transmitter
HardwareModel 5301HxxxxxxxxxxxxxxZZ
Model 5302HxxxxxxxxxxxxxxZZ
Model 5303HxxxxxxxxxxxxxxZZ
Note
Transmitters will be marked with “QS” or “QT”
at the end of the model number in place of ZZ
above.
Software/Firmware2.A1 or higher
Rosemount 5300:SIS Level Transmitter9
Installation and commissioningSafety Manual
September 202000809-1900-4530
2.2.1Identify a safety-certified transmitter
To identify a Rosemount 5300 Level Transmitter safety-certified transmitter:
Procedure
1. Verify the option code QS or QT in the model code, on the label affixed to the
outside of the transmitter head.
2. Check if a yellow label is affixed to the transmitter head for option code QT.
10Safety Manual
Safety ManualInstallation and commissioning
00809-1900-4530September 2020
2.3Installation
Refer to the Reference Manual for installation instructions. No special installation is
required in addition to the standard installation practices outlined in this manual.
The loop must be designed so that the terminal voltage does not drop below the
minimum input voltage when the transmitter output is 22.5 mA. See values in Power
supply.
Check that environmental conditions do not exceed the ratings provided in the
Rosemount 5300 Product Data Sheet.
Note
The Rosemount 5300 Level Transmitter is not safety-rated during maintenance work,
configuration changes, multidrop, loop test, proof-test, or other activity that affects the
safety function. Alternative means should be used to ensure process safety during such
activities.
It is assumed that the personnel installing, configuring, and operating the system have the
knowledge equal or greater than that of a qualified Instrument Technician familiar with
safety-related systems, process control applications, and general instrument use.
2.3.1
Power supply
Table 2-2: Minimum Input Terminal Voltage (Ui) at Different Currents
Use a HART-compliant master, such as Rosemount Radar Master, AMS Device Manager, or
a handheld communicator, to communicate with and verify configuration of the
Rosemount 5300 Level Transmitter.
A full review of configuration methods is available in Reference Manual.
2.4.1Make sure you are connected to the correct transmitter
Verify that the serial number on the label matches the one in your configuration tool.
Procedure
1. Write down the serial number from the transmitter label.
2. Verify the same serial number in your configuration tool.
Be sure to enable write protection as soon as you are finished.
12Safety Manual
Safety ManualInstallation and commissioning
00809-1900-4530September 2020
2.4.2Configure device using Guided Setup
Follow the Guided Setup wizard for transmitter configuration. When configuring
parameters not included in the Guided Setup, it may be necessary to do additional
verification.
Configure using Rosemount Radar Master
Procedure
1. Start Rosemount Radar Master.
2. Connect to the desired transmitter.
3. In the Guided Setup window, click Run Wizard for guided setup and follow the
instructions.
4. In the Guided Setup window, continue with steps 2 to 5.
5. Click View live values from device to verify that the transmitter works correctly.
Configure using AMS Device Manager or handheld
communicator
Connect to device using AMS Device Manager
Procedure
1. Start AMS Device Manager.
2. Select View→Device Connection View.
3. In the Device Connection View, double-click the modem icon.
4. Double-click the device icon.
Rosemount 5300:SIS Level Transmitter13
Installation and commissioningSafety Manual
September 202000809-1900-4530
Connect to device using a handheld communicator
Procedure
Turn on the handheld communicator and connect to the device.
Configure HART® devices
Procedure
1. Select Configure→Guided Setup.
2. Select Level Measurement Setup and follow the instructions.
3. Select Device Specific Setup.
4. Run Verify Level to check your level measurement.
5. (Optional) Select Volume Setup.
6. (Optional) Select Display Setup.
2.4.3
2.4.4
2.4.5
Damping
User adjusted damping will affect the transmitter’s ability to respond to process changes.
Therefore, the damping values + response time should not exceed the loop requirements.
For further information on damping, see Reference Manual.
Write protection
A Rosemount 5300 Level Transmitter safety-certified transmitter should always be
protected from unintentional configuration changes by a password protected function. It
is recommended to use write protection described in Reference Manual.
Alarm and saturation levels
DCS or safety logic solver should be configured to handle both High alarm and Low alarm.
In addition, the transmitter must be configured for High or Low alarm.
Note
In certain cases, the transmitter does not go into the user defined alarm state. For
example, in case of a short circuit, the transmitter goes into High Alarm state even if Low
Alarm has been configured.
Figure 2-2 identifies the alarm levels available and their operation values.
14Safety Manual
Loading...
+ 32 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.