Rosemount Manual: Rosemount 485 Annubar® Flow Handbook Manuals & Guides

Reference Manual
00809-0100-1191, Rev CB May 2006

Rosemount 485 Annubar® Flow Handbook

www.rosemount.com
Reference Manual
00809-0100-1191, Rev CB May 2006
Rosemount 485 Annubar

SECTION 1 Fluid Flow Theory

SECTION 2 Annubar Primary Element Flow Calculations

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Physical Fluid Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Density, Specific Weight, Specific Gravity . . . . . . . . . . . . . . . . . . . 1-4
Viscosity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
Nature of Fluid Flow in Pipes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
Flow Patterns . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
Average Velocity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-7
Reynolds Number. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-8
Bernoulli's Theorem . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-9
Actual and Standard Volumetric Flowrate for Gases . . . . . . 1-12
Actual and Standard Volumetric Flowrate for Liquids . . . . . . . . 1-15
Annubar Primary Element Flow Equations . . . . . . . . . . . . . . . . . . . . . 2-1
Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
Flow Coefficient Reynolds Number Dependency . . . . . . . . . . . . . 2-9
Flow Coefficient Theory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-9
Signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-9
Shape Differential . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-9
Blockage Differential. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
The Importance of the Flow Coefficient, or K vs. B Theory . . . . . 2-10
Operating Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-11
Flow Calculation Examples: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12

SECTION 3 Installation and Operational

Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Alignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Upstream Flow Disturbance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Instrument Lines and Connections Leakage . . . . . . . . . . . . . . . . . . . 3-4
Flow Parameter Changes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Dirt Accumulation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Gas Entrapment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
Flow Parameter Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
www.rosemount.com
Rosemount 485 Annubar
Reference Manual
00809-0100-1191, Rev CB
May 2006
APPENDIX A Fluid Properties and Pipe Data
APPENDIX B Pipe Data
APPENDIX C Unit and Conversion Factors
APPENDIX D Related Calculations
APPENDIX E Flow Turndown and Differential Pressure Requirements
Fluid Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
Ideal and Real Specific Gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .D-1
Derivation of Annubar primary element flow equations . . . . . . . . . . . .D-3
Flow Turndown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .E-1
Differential Pressure (DP Turndown). . . . . . . . . . . . . . . . . . . . . . . . . .E-2
Accuracy and Flow Turndown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .E-2
Flow Measurement System Turndown . . . . . . . . . . . . . . . . . . . . . . . .E-2
Percent of Value and Percent of Full Scale accuracy . . . . . . . . . . . . . E-2
Annubar Turndown Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E-3
Minimum measurable differential pressure . . . . . . . . . . . . . . . . . . . . .E-4
Putting it all together: The flow system turndown . . . . . . . . . . . . . . . . E-4
APPENDIX F References
APPENDIX G Variable List
TOC-2
Reference Manual
00809-0100-1191, Rev CB May 2006
Rosemount 485 Annubar

Section 1 Fluid Flow Theory

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 1-1
Physical Fluid Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 1-1
Nature of Fluid Flow in Pipes . . . . . . . . . . . . . . . . . . . . . . . . . .page 1-6
INTRODUCTION The Emerson Process Management DP-Flow Engineering Department has
prepared this book to provide all of the information necessary to accurately measure fluid flow using the Rosemount 485 Annubar primary element.
Fluid flow measurement involves many variables. In this handbook fluid properties that affect flow measurement are discussed and defined. We hope this will bring all readers to a point where they are comfortable with the flow equations which follow. The flow equations are developed from Bernoulli's Theorem, which is the application of the law of conservation of energy to fluid flow. These equations are then developed and modified for use with 485 Annubar Flow Sensors. After all the terms have been defined and the equations developed, you are then ready to do the precise flow calculations necessary to apply an Annubar and an associated secondary readout instrument to your flow situation.
We realize that many intricacies of fluid flow have been neglected in this book. We feel that we have presented enough theory and data for you to accurately measure fluid flow using the Annubar Flow Sensor. For difficult flow measurement problems, contact your local Emerson Process Management representative for assistance.
PHYSICAL FLUID PROPERTIES
Pressure Pressure is the force exerted by a fluid per unit area. The most common unit
To solve any flow problem a knowledge of the physical properties of the fluid is required. Appendix A gives fluid property data for the most common fluids. Definitions and descriptions of the most common properties are given below.
2
of pressure measurement is pounds force per square inch (lbf/in English system of units and pascal or kilopascal (Pa or kPa) in the SI system of units.
In most flow problems (especially gas flow problems), the absolute pressure must be used in the calculations. However, most pressure gages measure a pressure that is referenced to atmospheric pressure (atmospheric pressure = 0 psig or 0 kPa g). To obtain absolute pressure, the atmospheric pressure must be added to the gage pressure. Vacuum gages measure a pressure that is lower than atmospheric pressure. To obtain absolute pressure, the vacuum pressure must be subtracted from the atmospheric pressure. All of these pressure terms are described in detail below and the relationship between these pressures is shown graphically in Figure 1-1.
or psi) in the
www.rosemount.com
Rosemount 485 Annubar
Figure 1-1. Pressure Relationships
Absolute pressure that
is greater than
atmospheric pressure
Absolute zero pressure, or a perfect vacuum, would exist if all molecules were removed from an enclosed space. In reality, this is impossible to achieve, but it does serve as a convenient reference for pressure measurement.
Atmospheric pressure is the amount of pressure exerted by the atmosphere above absolute zero pressure. The “standard” atmospheric pressure used in this handbook is 14.696 psia (101.325 kPa). It is important to realize that atmospheric pressure at any one location varies with day to day weather conditions. More important, the atmospheric pressure changes rapidly with elevation above sea level. The following table gives the U.S. Standard Atmosphere (1962) for various altitudes above sea level.
Barometer reads
atmospheric pressure
Reference Manual
00809-0100-1191, Rev CB
May 2006
Pressure above atmospheric pressure
Ordinary pressure gauge measures pressure above atmospheric pressure
Atmospheric pressure
Ordinary vacuum gauge measures pressure below atmospheric pressure
Pressure less than atmospheric pressure
Absolute pressure that is less than atmospheric pressure
Perfect vacuum
Table 1-1. Atmospheric Pressure by Altitude
Altitude Atmospheric Pressure
feet meters psia bar
0 0 14.696 1.01
500 152.4 14.433 0.995 1000 304.8 14.173 0.977 1500 457.2 13.917 0.959 2000 609.6 13.664 0.942 2500 762.0 13.416 0.925 3000 914.4 13.171 0.908 3500 1066.8 12.930 0.891 4000 1219.2 12.692 0.875 4500 1371.6 12.458 0.859 5000 1524.0 12.227 0.843 6000 1828.8 11.777 0.812 7000 2133.6 11.340 0.782 8000 2438.4 10.916 0.753 9000 2743.2 10.505 0.724
10000 3048.0 10.106 0.697 15000 4572.0 8.293 0.572 20000 6096.0 6.753 0.466
1-2
Reference Manual
00809-0100-1191, Rev CB May 2006
Rosemount 485 Annubar
Example:
A manometer at an elevation of 5,000 feet above sea level measures 10 inches of mercury vacuum. Express this pressure in absolute terms (psia).
Solution:
From Table 1-1 on page 1-2, the average atmospheric pressure at 5,000 feet elevation is 12.227 psia.
10 inches of mercury = 4.912 psia.
(2.036" Hg @ 0°C = 1 psi - see Appendix B Unit and Conversion Factors)
Absolute pressure = 12.227 - 4.912 = 7.315 psia.
Differential pressure is just what the name implies, a difference between two pressures. Frequently, a differential pressure is measured with a pressure transmitter or a manometer which contains water, mercury, alcohol, oil, or other fluids. The differential pressure can be calculated by the relation:
ΔP ρh=
where:
ΔP = differential pressure in lbf/ft ρ = density of the fluid in lbm/ft
h = elevation difference of the fluid in feet
2
3
Figure 1-2. Differential Pressure
Fluid
h
Commercial instruments used for indicating or recording the differential pressure operate using various principles; such as variable reluctance, capacitance, or strain gage. These instruments generally give the true differential pressure without the need for additional corrections.
1-3
Reference Manual
00809-0100-1191, Rev CB
Rosemount 485 Annubar
May 2006
Temperature Although temperature is a property which is familiar, an exact definition is
difficult. Temperature is a measure of the degree of hotness or coldness of a substance. Temperature scales are defined such that the temperature of boiling water at standard atmospheric pressure is 212 °F (100 °C) and the freezing temperature of water is 32 °F (0 °C).
Most flow problems require that the temperature be expressed in absolute units. The absolute temperature of a substance is the measure of the temperature intensity of the substance above the datum known as “absolute zero.” According to kinetic theory, all molecular activity ceases at absolute zero. The Rankine and Kelvin temperature scales are based on absolute zero.
Absolute zero temperature is -459.69 °F (-273.15 °C).
Thus:
Density, Specific Weight, Specific Gravity
°R = °F + 459.69
Where:
°R = degrees Rankine °F = degrees Fahrenheit
°K = °C + 273.15
Where:
°K = degrees Kelvin °C = degrees Celsius
In most engineering work, the value of 459.69 is rounded off to 460 so that degrees Rankine is approximated as:
°R = °F + 460
It is important that absolute temperatures be used in gas flow problems.
Density is defined as the mass of a substance per unit volume. Density is usually expressed in pounds-mass-per cubic foot (lbm/ft cubic meter (kg/m
3
).
3
) or kilograms per
Specific Weight is defined as the weight, due to the gravitational pull of the earth, of a substance per unit volume. Specific weight is expressed in pounds-force per cubic foot (lbf/ft
3
) or Newtons per cubic meter (N/m3). As can be seen, specific weight and density are not synonymous terms. Only at locations where the local acceleration of gravity is equal to the standard acceleration of gravity (g
= 32.1740 ft/s2 or gc = 9.807 m/s2) does the
c
numerical value of specific weight equal the numerical value of density.
Specific Gravity is defined as the ratio of the density of one substance to the density of a second or reference substance. The reference substance depends on whether the flowing media is liquid or gas.
1-4
For liquids, water at either 60 °F (15°C) or 77 °F (25 °C) is used as the reference substance. The density of distilled water at 60 °F is 62.3707 lbm/ft The density of distilled water is 25 °C is 997 kg/m
3
.
3
The determination of the specific gravity of a liquid can be made by comparing the weights of equal volumes of the liquid and water. If the quality of the work justifies it, these weights may be corrected for the buoyancy of air as well as for temperature effects. For most commercial work, the specific gravities of liquids are obtained with hydrometers. The scales of hydrometers are graduated to read directly in specific gravities, in degrees Baume or in degrees API (American Petroleum Institute). The relationship between specific gravity and degrees Baume is defined by the following formulas:
.
Reference Manual
00809-0100-1191, Rev CB May 2006
Rosemount 485 Annubar
⎛⎞ ⎜⎟
1. For liquids heavier than water:
2. For liquids lighter than water:
°B 145
⎛⎞ ⎜⎟
°B
--------------------------- -
⎜⎟
SpGr60
⎜⎟
⎛⎞
----------------------
⎝⎠
⎝⎠
3. For use in the American petroleum industry, the following relation between degrees API and specific gravities is used:
⎛⎞ ⎜⎟
API
141.5
--------------------------- -
⎜⎟
SpGr60
⎜⎟
⎛⎞
----------------------
⎝⎠
⎝⎠
60° F
131.5=
In the above equations, the term “Sp Gr 60/60” means that the specific gravity value to be used is that which exists when the temperatures of the reference liquid (water) and of the oil, or other liquid, are both at 60 °F.
For gases, air is used as the reference fluid. However, instead of a ratio of densities, the ideal specific gravity of a gas is defined as the ratio of the molecular weight of the gas of interest to the molecular weight of air. The molecular weight of air is 28.9644.
145
--------------------------- -
=
⎜⎟
SpGr60
⎜⎟
⎛⎞
----------------------
⎝⎠
⎝⎠
60° F
140
60° F
130=
The reason for not using the ratio of the densities is that the effects of pressure and temperature on the densities of gases vary from one gas, or gas mixture, to another. Thus, even though the densities may be determined at very nearly identical ambient conditions and the resulting values adjusted to a common basis of pressure and temperature, an error may be incurred when the resulting ratio is used at a state differing from the common basis. The magnitude of this error is likely to increase as the state of use departs further and further from the common starting basis. On the other hand, so long as the composition of the gas used undergoes no change, the ratio of molecular weights will remain the same regardless of changes of pressure, temperature, and location.
For a more complete discussion or real and ideal specific gravities, see Appendix C Related Calculations.
Viscosity Absolute viscosity may be defined simply as the temporary resistance to flow
of a liquid or gas. It is that property of a liquid or gas which tends to prevent one particle from moving faster than an adjacent particle. The viscosity of most liquids decreases with an increase in temperature, but the viscosity of gases increases with an increase in temperature.
In the English System of units, the absolute viscosity has units of lbm/ft-sec. However, it is common practice to express the value of the viscosity in poise or centipoise (1 poise = 100 centipoise). The poise has units of dyne seconds per square centimeter or of grams per centimeter second. Less confusion will exist if the centipoise is used exclusively for the unit of viscosity. For this reason, all viscosity data in this handbook are expressed in centipoise, which is given the symbol µ
cp
.
1-5
Rosemount 485 Annubar
If it is necessary to express the viscosity in the English System of units, the following conversion factors should be used.
Poise x 0.067197 = lbm/ft-sec
Centipoise x 0.00067197 = lbm/ft-sec
The Annubar primary element is a head-type meter and requires fluid to convey the DP signal to the meter. For this reason a practical viscosity limit of 50 centipoise should be followed.
Kinematic viscosity or kinetic viscosity is the absolute viscosity divided by the density of the fluid at the same temperature.
ν
cs
(36.13 converts to lbm/ft
Like the units of absolute viscosity, the units of kinematic viscosity are usually expressed in metric units. To be consistent and to reduce confusion, the kinematic viscosities used in this handbook will have units of centistokes
2
/sec) and will be denoted υcs.
(cm
μ
cp
------------------=
36.13ρ
ν
cs
3
to gm/cm3)
Reference Manual
00809-0100-1191, Rev CB
May 2006
μ
cp
-------- -=
ρ
There is no name for kinematic viscosities in the English System of units, but the following conversion factor can be used:
υ
x 0.00001076 = υ(ft2/s)
cs
NATURE OF FLUID FLOW IN PIPES
In the foregoing sections on the physical properties of fluids, subjects were discussed that had to do with the type of fluid being used. However, one property of fluid flow which is independent of the type of fluid is velocity.
Flow Patterns Depending upon the magnitude of the velocity, three distinct flow regimes can
be encountered. These three types of flows are known as laminar, transition, and turbulent.
The classic experiment of introducing dye into a flowing stream was first conducted by Reynolds in 1883. The experiment consists of injecting a small stream of dye into a flowing liquid and observing the behavior of the dye at different sections downstream of the injection point. Figure 1-3 shows the three possible types of flow with the dye injected.
1-6
Reference Manual
00809-0100-1191, Rev CB May 2006
Figure 1-3. Types of Flow Development
Rosemount 485 Annubar
Laminar occurs when the velocity is small and the dye remains in a straight line.
Dye Filament
Needle
Ta nk
Transition occurs at a slightly higher velocity than laminar flow. The dye does not remain in a straight line and does not spread throughout the pipe.
Dye Filament
Needle
Tank
Turbulent occurs at velocities above transition flow. The dye spreads throughout the pipe as shown below. It is this type of flow which is important to the general user. Turbulent flow is, by far, the most common type of flow encountered in pipes.
Dye Filament
Needle
Ta nk
Average Velocity Unless it is stated otherwise, the term velocity will refer to the average velocity
in the pipe. The average velocity is determined by the continuity equation for steady state flow.
lbm
W = ρAV
⎛⎞
----------
⎝⎠
⎛⎞ ⎝⎠
kg
------
s
s
⎛⎞
=
⎝⎠
kg
⎛⎞
-------
=
⎝⎠
m
This equation states that for steady state flow, the mass rate of flow lbm/sec (kg/s) at any point in the pipeline can be calculated from the product of the density lbm/ft
3
(kg/m3), the cross-sectional area of the pipe ft2 (m2), and the
average velocity ft/s (m/s).
lbm
----------
ft
3
3
2
()
ft
2
⎛⎞
()
m
⎝⎠
ft
⎛⎞
---
⎝⎠
s
m
---- -
s
1-7
Reference Manual
00809-0100-1191, Rev CB
Rosemount 485 Annubar
May 2006
Reynolds Number The work that Osborne Reynolds accomplished in the late 1800's led to a flow
parameter that now carries his name, e.g. the Reynolds Number. His work showed that the nature of flow in a pipe depends on the pipe diameter (D), the density (ρ), viscosity, and the velocity of the fluid.
m
ft
lbm
⎛⎞
⎛⎞
---
ft()
----------
⎝⎠
⎝⎠
3
s
Dνρ
R
-----------
D
---------------------------------- -==
μ
ft
lbm
⎛⎞
---------- -
⎝⎠
ft s
Dνρ
-----------
R
D
m()
---------------------------------- -==
μ
As can be seen, the Reynolds Number has no dimensions and it may be considered as the ratio of dynamic forces to viscous forces.
For the three types of flow previously discussed, it has been found that generally laminar flow exists below a Reynolds Number of 2000. Transition flow generally exists between a Reynolds Number range of 2000 to 4000. However, the values of 2000 and 4000 are not precisely fixed. The laminar flow range can terminate between a Reynolds Number range of 1200 to 13000 depending on the smoothness of the pipe. If heat is added to the pipe, laminar flow can be extended to even higher Reynolds Numbers. The turbulent flow exist above pipe Reynolds numbers from 4,000 to 13,000.
kg
⎛⎞
⎛⎞
---- -
-------
⎝⎠
⎝⎠
3
s
m
kg
⎛⎞
------------
⎝⎠
ms
Since the product is dimensionless, the numerical value will be the same for any given set of conditions, so long as all the separate factors are expressed in a consistent system of units. This makes the Reynolds Number an ideal correlating parameter. Therefore, the flow coefficient of flow meters are generally expressed as functions of Reynolds Number.
Although the combination DVρ / µ is the classical expression for the Reynolds Number, there are several other equivalent combinations. First, the ratio ρ/ µ may be replaced by 1 /υ giving:
DV
--------=
R
D
υ
3
Also, the volume rate of flow (ft
/s or m3/s) is Q = π(D2/4)V, thus another
alternate combination for Reynolds Number is:
4Qρ
R
-------------- -= R
D
πD
μ
ft
4Qρ
--------------- -=
D
πD
μ
m
Also, the mass rate of flow (lbm/s or kg/s) is W = Qρ so that a third alternate combination is:
4W
R
-------------- -= R
D
πD
μ
ft
4W
--------------- -=
D
πD
μ
m
If the viscosity (µ) is given in centipoise, the last combination for Reynolds Number becomes:
1895W
R
------------------ -= R
D
D
ftμcp
D
1298W
------------------ -=
D
mμcp
1-8
The pipe Reynolds Number (R following equations:
Liquid:
3160 G PM G⋅⋅
-----------------------------------------= R
R
D
D μ
cp
) can be calculated by using any of the
D
21230 L PM G⋅⋅
-------------------------------------------=
D
D μ
cp
Reference Manual
00809-0100-1191, Rev CB May 2006
Rosemount 485 Annubar
Gas:
0.4831 S CF H G⋅⋅
-------------------------------------------------= R
R
D
D μ
cp
432 N CM H G⋅⋅
------------------------------------------ -=
D
D μ
cp
Liquid, Gas and Steam:
lbm
⎛⎞
----------
6.316
⎝⎠
R
-----------------------------------= R
D
D μ
hr
cp
353.6
------------------------------- -=
D
D μ
kg
⎛⎞
------
⎝⎠
hr
cp
where: G = specific gravity of flowing fluid (air = 1.0, water = 1.0) GPM = U.S. gallons per minute kg/hr = flowrate of fluid in kilograms per hour LPM = flowrate of fluid in liters per minute NCMH = flowrate of gas in normal cubic meters per hour SCFH = flowrate of gas in standard cubic feet per hour
Bernoulli's Theorem Bernoulli's Theorem is a means of expressing the application of The Law of
Conservation of Energy to the flow of fluids in a pipe. The total energy at any location in the pipe, above some arbitrary datum, is equal to the sum of the elevation head, the velocity head, and the pressure head.
Figure 1-4. Bernoulli's Theorem
2
V
/2g
2
Constant Energy Line
2
/2g
V
2
P
/ρ
1
P2/ρ
12
Flow
Z
Z
1
Arbitrary Datum Plane
2
In a steady incompressible flow, without friction, the sum of the velocity head, pressure head, and elevation head is a constant along any streamline (see Figure 1-4). Assuming that the elevation difference between two measuring points is negligible (Z
= Z2), Bernoulli's Equation can then be written:
1
Equation 1-1.
2
V
⎛⎞
1
---------
+
⎜⎟
2g
⎝⎠
P
1
⎛⎞
------
⎝⎠
ρ
2
V
⎛⎞
2
---------
+=
⎜⎟
2g
⎝⎠
P
2
⎛⎞
------
⎝⎠
ρ
where,
V = velocity, ft/s (m/s) g = gravitation constant, ft/s P = pressure, lbf/ft ρ = density, lbm/ft A = area, ft
2 (m2
3
)
2
(kg/m3)
(kPa)
2
(m/s2)
1-9
Rosemount 485 Annubar
Since Bernoulli's Theorem states that the flow is steady, the continuity equation must apply. The continuity equation states that the mass rate of flow between two points must be constant.
Equation 1-2.
ρ1A1V1ρ2A2V
=
Reference Manual
00809-0100-1191, Rev CB
May 2006
2
since the flow is incompressible (ρ
Equation 1-3.
A
=
1V1A2V2
solving for V
in Equation 1-4:
1
Equation 1-4.
A2V
2
------------- -=
V
1
A
1
and substituting into Equation 1-1:
1
------ -
2g
2
A
⎛⎞
2V2
------------- -
⎜⎟ ⎝⎠
+
A
1
2
V
⎛⎞
1
2
------ -
------ -
⎜⎟
2g
2g
⎝⎠
2
V
⎛⎞
2
------ - 1
⎜⎟
2g
⎝⎠
2
2g
V
2
P
V
⎛⎞
1
2
1
2
A
⎛⎞
2
------
⎜⎟
A
⎝⎠
1
1P2
ρ
2
---------
⎜⎟
2g
⎝⎠
⎛⎞ ⎝⎠
------------------------=
⎛⎞
------
⎝⎠
ρ
A
2V2
------------- -
A
P
⎛⎞
-------------------
⎝⎠
1
2
P
1
------
ρ
P
-------------------=
= ρ2), Equation 1-3 reduces to:
1
P
2
⎛⎞
------
+=
⎝⎠
ρ
P
2
⎛⎞
------
+=
⎝⎠
ρ
1P2
ρ
1
2
A
⎛⎞
2
------
⎜⎟
A
⎝⎠
1
1-10
P
1P2
2g
-------------------
ρ
V
2
------------------------=
1
1
A
⎛⎞
------
⎜⎟
A
⎝⎠
2
2
1
Again, using the continuity equation, the theoretical mass rate of flow would be:
Equation 1-5.
1
W
theoρA2
V=
A22gρ P1P2–()
2
------------------------=
1
A
⎛⎞
------
⎜⎟
A
⎝⎠
2
2
1
The theoretical equation for volumetric flow is:
Equation 1-6.
Q
theoA2
2gρ P1P2–()
V=
2
----------------------------------- -
A
2
ρ
------------------------=
1
1
A
⎛⎞
------
⎜⎟
A
⎝⎠
2
2
1
Reference Manual
00809-0100-1191, Rev CB May 2006
Rosemount 485 Annubar
By definition the discharge coefficient of a flow meter is the ratio of the actual rate of flow to the theoretical rate of flow.
Equation 1-7.
W
C
actual
------------------------------- -
W
theoretical
Therefore, the actual volumetric flow for liquid is:
Equation 1-8.
actual
QA2C==
Q
By defining the flow coefficient K of an Annubar primary element as:
C
---------------------------- -=
K
A
⎛⎞
2
1
------
⎜⎟
A
⎝⎠
1
The volumetric flow Equation 1-8 reduces to:
Q
------------------------------ -==
Q
theoretical
2gρ P
----------------------------------- -
2
actual
()
1P2
ρ
1
------------------------
A
⎛⎞
2
1
------
⎜⎟
A
⎝⎠
1
2
Equation 1-9.
2g P
()
1P2
=
------------------------------- -
2
ρ
QKA
In a like manner, the mass rate of flow reduces to:
Equation 1-10.
W
WKA
== 2gρ P1P2–()
actual
2
By using consistent units Equation 1-9 can be checked as follows:
2
Qft
=
lbf
⎛⎞
------ -
ft
⎝⎠
2
ft
------------------ -
2
lbf
⎛⎞
------ -
s
⎝⎠
ft
3
ft
------=
s
3
Qm
=
m()
2
------------------------
s
kgf
⎛⎞
--------
⎝⎠
2
m
2
kgf
⎛⎞
--------
⎝⎠
3
m
3
m
-------=
s
Likewise, Equation 1-10 is:
2
Wft
=
ft
lbm
lbf
-----
----------
2
s
ft
lbm
------ -
----------= Wm
3
2
s
ft
2
m
kgm
kgf
=
-----
----------- -
2
3
s
m
--------
m
kgm
----------- -=
2
s
NOTE:
In the above units conversion, lbf is set equal to lbm. This is only true at standard gravity (g surface of the earth, the assumption of lbf = lbm is fairly good.
= 32.174 ft/sec2). However, for measurements on the
c
It is also interesting to note that this assumption leads to the historical name “head-type meters”. By using the following:
lbf
------ -
2
ft
h
---------- ft== h lbm
----------
3
ft
kgf
--------
2
m
----------- - m== kgm
----------- -
3
m
Where h is feet (meters) of head of flowing fluid, equation (2-9) can be written as:
⎛⎞ ⎝⎠
QKA2g
--------------- - KA 2gh==
⎛⎞ ⎝⎠
lbf
------ -
ft
lbm
----------
ft
2
QKA2g
3
kgf
⎛⎞
--------
⎝⎠
2
m
----------------- KA 2gh== kgm
⎛⎞
----------- -
⎝⎠
3
m
1-11
Rosemount 485 Annubar
Reference Manual
00809-0100-1191, Rev CB
May 2006
Actual and Standard Volumetric Flowrate for Gases
The equation will be recognized as the well known hydraulic
QKA2gh=
equation for liquids.
The most common unit of volumetric measurement in English Units is the cubic foot. The most common unit in SI units is the cubic meter. Many others exist, such as the cubic inch, the gallon (231 cubic inches), and the barrel (42 gallons); but these are generally defined as portions of a cubic foot.
3
In Equation 1-9 the volumetric flow (Q) can be calculated in ft
/s (m3/s) if all the other parameters have the consistent set of units shown. The most important aspect of this equation is that the volumetric flow is given in actual units.
Example:
Suppose a flowmeter is operating according to Equation 1-10, and that the equation shows that the flowrate is 5 ft
3
/s. Also suppose that the fluid can be poured or dumped into one (1) cubic foot containers. At the end of one second, five containers would be full of fluid. In other words, the equation gave the flowrate in actual cubic feet per second.
For gases, especially fuel gases, the cubic foot is still the unit of measurement. However, a cubic foot of gas has no absolute or comparative value unless the pressure and temperature of the gas are specified. Common sense tells us that the amount of matter within a one cubic foot space at a pressure of 1000 psia is greater than the amount of matter within that space if the pressure is atmospheric. Since the fuel gas industry is interested in selling energy, which is the amount of heat that can be generated by that cubic foot of gas, and that the amount of energy is directly proportional to the number of molecules (matter) within the cubic foot space, it is easy to see why the pressure and temperature of the gas are specified.
Table 1-2. Standard Conditions
Since it is the amount of matter (mass) that is required to be measured as the gas flows along the pipeline, the actual volumetric flowrate terms do not lend themselves to this task easily.
Example:
Suppose a gas in a pipeline at 140 kPa abs and 5 °C is flowing at 50 actual m flow through a pipeline at 5100 kPa abs and 30.8 °C if the flowrate was
1.54 actual m
3
/s; it is not obvious that the same amount of matter (mass) would
3
/s.
Because of the inability to compare the amounts of mass of a gas in actual volumetric terms, the standard volumetric term was developed. The most common unit of gaseous measurement is the amount of a gas that would be contained in a one cubic foot enclosure at standard conditions. Standard conditions can be defined as any combination of temperature and pressure. Some common standard sets are provided in the table below.
Temperature Pressure
60 °F 14.73 psia 68 °F 14.73 psia 0 °C 101.393 kPa abs
The approximate conversion from actual volumetric flowrate to standard volumetric flowrate is accomplished by the BOYLES-CHARLES law. These laws state the following:
1-12
Reference Manual
Q
Q
00809-0100-1191, Rev CB May 2006
Rosemount 485 Annubar
1. If an ideal gas were contained within an enclosure at constant
temperature, the pressure would increase in proportion to the volume decrease. Example: the pressure would double if the volume was reduced by half. The equation takes the form of:
P1V1P2V
=
2
Which states that the product of the pressure and volume at one condition must equal the product of the pressure and volume at any other condition provided the temperature is the same at both conditions.
2. Again, if an ideal gas were contained within an enclosure of constant
volume, the pressure would increase in proportion to the absolute temperature increase. The equation for this process takes the form:
P
P
1
2
------
------=
T
T
1
2
Which states that the ratio of the pressure and temperature at any one condition must equal the ratio of the pressure and temperature at any other conditions provided the volume of the container has not changed.
Both of these laws can be combined to form a single equation:
P
------------- -
1V1
T
1
P
------------- -=
2V2
T
2
If, instead of considering actual volumes, the flowrate (actual volume per unit time) is used, the equation becomes:
P
-------------- -
V
1
------= Q
Q
Since and where t is a common unit of time (hours, minutes
1
t
V
2
------=
2
t
1Q1
T
1
P
-------------- -=
2Q2
T
2
or seconds).
Now, if P conditions of 14.73 psia and 60°F (101.393 kPa A and 0 °C), the flowrate Q is the standard volumetric flowrate Q
and T1 are always considered to be at the standard specified
1
.
14.73
---------------------- -
460 60+
P
s
fQA
---------------------= Tf460+
s
101.325
-----------------------------
273.15 0+
P
s
----------------------------- -=
Tf273.15+
fQA
1
This equation allows the standard volumetric flowrate (Qs) to be calculated from any actual volumetric flowrate (QA) where the pressure and temperature are known.
P
460 60+
f
-------------- -
---------------------- - Q
Q
s
⋅⋅= Q
T
14.73
460+
f
A
s
P
f
---------------------
101.325
273.15 0+
----------------------------- - Q
⋅⋅=
T
273.15+
f
A
In an example on page 1-12, two actual volumetric flowrates were given, and it was stated that the amount of mass flowing was the same. To check this, the standard volumetric can be calculated for each flowrate:
1-13
Rosemount 485 Annubar
Reference Manual
00809-0100-1191, Rev CB
May 2006
Flowrate #1:
3
ft
QA50
P
T
Q
Q
------=
s
20psia=
f
40° F=
f
20
460 60+
-------------- -
s
s
---------------------- - 50⋅⋅=
14.73
460 40+
70.6S CF S= Qs67.8NMCS=
Q
A
P
f
T
f
Q
s
m
-------=
50
s
140kPaabs=
5° C=
140
---------------------
101.325
3
273.15 0+
--------------------------- - 50⋅⋅=
273.15 5+
Flowrate #2
3
ft
Q
P
T
f
Q
Q
------=
1.5
A
f
s
s
s
750p si a=
102.5° F=
460 60+
750
------------------------------ - 1.5⋅⋅=
-------------- -
460 102.5+
14.73
70.6S CF S= Qs67.8N MC S=
Q
A
P
f
T
f
Q
s
1.54
5100k Pa A=
39.2° C=
5100
---------------------
101.325
m
-------=
s
3
----------------------------------- - 1.54⋅⋅=
273.15 39.2+
273.15 0+
As can be seen, the two actual volumetric flowrates are identical in terms of standard volumetric flowrates. However, only ideal gases have been considered so far. Real gases deviate from the Boyles-Charles relationships. The amount of deviation depends upon pressure, temperature, and type or composition of the gas. The deviation is known as the compressibility factor of the gas. For most flow conditions, the conversion to standard volumetric flowrate using only the Boyles-Charles relationship will be accurate within a few percent. To be correct, the Boyles-Charles relationship must be modified as follows:
1V1
P
2V2
------------- -=
ZfT
1
2
P
------------- -
ZaT
Where Z is the compressibility factor at each pressure and temperature condition. This modification leads to the following:
P
460 60+
Q
f
---------------------- -
⋅⋅= Q
-------------- -
s
14.73
Z
b
------ Q
T
f
A
Z
f
s
P
f
---------------------
101.325
273.15 0+
--------------------------- -
⋅⋅=
Z
b
------ Q
T
f
A
Z
f
Where:
1-14
=compressibility factor at base or standard conditions and is generally
Z
b
considered to be unity (Z
=compressibility factor at Pf and Tf.
Z
f
=1.000).
b
More discussion on compressibility factors can be found in “Ideal and Real Specific Gravity” on page D-1.
Reference Manual
00809-0100-1191, Rev CB May 2006
Rosemount 485 Annubar
Actual and Standard Volumetric Flowrate for Liquids
In general, liquid flowrates are not converted into standard volumetric flowrates. They are usually expressed in actual volumetric terms.
However, some industries do convert actual liquid flows to standard liquid flows. The petroleum industry is probably the largest industry which does convert its actual volumes to standard volumes. This is done primarily because that industry is concerned with the selling and buying of energy. The energy content of a barrel of oil at 1000 °F is less than the energy content of a barrel of oil at 60 °F because the oil expands with temperature. Since the energy content is directly proportional to the amount of matter (mass) within the barrel, the temperature (thermal) expansion is considered.
Industries which convert liquids to standard volumetric flows have generally established 60 °F as the reference temperature. To convert actual volumetric flow to standard volumetric flows, the following equation can be used.
ρ
QsQ
A
------=
A
ρ
s
Where,
= standard volumetric flowrate
Q
S
= actual volumetric flowrate
Q
A
= density of fluid at actual flowing conditions
ρ
A
= density of fluid at standard or base conditions
ρ
S
As can be seen, the conversion to standard volumetric flow can be accomplished simply by multiplying the density ratio. One alternate that is commonly encountered is that the conversion is accomplished by multiplying by the ratio of the specific gravities. That is:
G
Q
sQA
f
------ -=
G
s
Where,
=specific gravity at flowing conditions
G
f
=specific gravity at base conditions
G
S
Since specific gravity is defined as the ratio of the density of the fluid to the density of the fluid to the density of water at 60°F, these conversions are identical.
1-15
Reference Manual
00809-0100-1191, Rev CB May 2006
Rosemount 485 Annubar
1-16
Reference Manual
00809-0100-1191, Rev CB May 2006
Rosemount 485 Annubar
Section 2 Annubar Primary Element Flow
Calculations
Annubar Primary Element Flow Equations . . . . . . . . . . . . . . . page 2-1
Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 2-6
ANNUBAR PRIMARY ELEMENT FLOW EQUATIONS
The Annubar primary element flow equations are all derived from the hydraulic equations which are shown on page 1-11. For a detailed example of a derivation of an Annubar primary element equation, see the Rosemount 485 Annubar Flow Test Data Book (document number 00821-0100-4809).
Equation 2-1. : Volume rate of flow - Liquids (Actual Conditions)
2
Q
a
QaC' hw⋅=
OR
⎛⎞
-------
h
=
w
⎝⎠
C'
where:
C' F
na
KD2F
aa
1
----- -⋅⋅ ⋅ ⋅=
G
f
NOTE:
For description of standard volumetric flow equations, see page 1-12.
Equation 2-2. : Mass rate of flow - Liquids
2
W
WC' hw⋅= h
OR
⎛⎞
-----
=
w
⎝⎠
C'
where:
C' FnaKD2Faaρ
⋅⋅ ⋅ ⋅=
f
Equation 2-3. : Mass rate of flow - Gas and Steam
2
W
WC' hw⋅= h
OR
⎛⎞
-----
=
w
⎝⎠
C'
www.rosemount.com
where:
C' FnaKD2YaF
⋅⋅ ⋅ =
aa
ρ
f
Equation 2-4. : Volume rate of flow - Gas (Standard Conditions)
QsC' hwPf⋅= h
OR
w
-----
P
=
⎝⎠
f
------ -
C'
2
Q
1
s
⎛⎞
where:
C' FnaKD2YaFpbFtbFtfFgFpvF⋅⋅⋅⋅⋅⋅
⋅⋅ ⋅=
aa
Rosemount 485 Annubar
Equation 2-5. : Volume rate of flow - Gas (Actual Conditions)
QaC' hw⋅= h
where:
For a detailed description of each term in the above equations, see “Nomenclature” on page 2-6. Please note that each of the above equations has a C' constant. It is not intended that the C' constant of one equation is equal to the C' constant of another equation. The numerical value of any C' constant is the product of the appropriate factors for that equation only.
The following tabulations of the flow equations will serve as handy work pads. Also, the table numbers where the necessary information can be found are given in the headings of these tabulations. Several completed examples of flow calculations are given beginning on page 2-11.
NOTE
The 485 Annubar primary element needs no correction for the Reynolds Number.
OR
C' FnaKD2YF
aa
w
⎛⎞
=
⎝⎠
1
----⋅⋅ ⋅ = ρ
f
Q
-------
Reference Manual
00809-0100-1191, Rev CB
May 2006
2
a
C'
2-2
Reference Manual
00809-0100-1191, Rev CB May 2006
w
h
Differential Pressure
Flowing Specific
Gravity
.
1
----- -
G
...
O at 68 °F
2
inch H
f
O at 68 °F
O at 68 °F
O at 68 °F
2
2
inch H
inch H
inch H
O at 68 °F
2
2
inch H
Rosemount 485 Annubar
O at 68 °F
O at 68 °F
O at 68 °F
O at 68 °F
kPa
kPa
kPa
kPa
kPa
kPa
2
inch H
inch H
2
2
inch H
2
inch H
kPa
aa
F
I
Thermal Expansion
Factor (Table A-11)
Internal Pipe
Diameter
.
2
D
Annubar Flow Constant C
K
Annubar Flow
Coefficient
na
F
Unit Conversion
Factor
Rate of Flow
Table 2-1. Equation for Liquid – Volume Rate of Flow
=
a
Q
2
2
2
2
2
2
/H 4.0005E-03 (mm)
3
m
/M 6.6675E-05 (mm)
3
m
2
/s 1.1112E-06 (mm)
3
m
2
2
2
2
2
2
2
2
2
/D 9.6012E-02 (mm)
GPM 5.6664 (in)
GPH 339.99 (in)
GPD 8159.7 (in)
BPH (42 gal) 8.0949 (in)
BPD (42 gal) 194.28 (in)
3
/min 0.75749 (in) ft
CFH 45.4494 (in)
CFM 0.7575 (in)
LPH 4.00038 (mm)
lmp. GPM 4.7183 (in)
LPM 6.6673E-02 (mm)
LPS 1.1112E-03 (mm)
3
m
2-3
Rosemount 485 Annubar
Reference Manual
00809-0100-1191, Rev CB
May 2006
w
h
Differential Pressure
f
ρ
Flowing Specific
Gravity
aa
F
I
Thermal Expansion
Factor (Table A-11)
2
D
Internal Pipe
Diameter
Annubar Flow Constant C
O at 68 °F
O at 68 °F
2
2
inch H
inch H
2
2
O at 68 °F
O at 68 °F
2
2
inch H
inch H
2
2
kPa
2
2
kPa
2
kPa
kPa
2
2
kPa
Differential Pressure
Flowing
Specific
Gravity
Thermal
Expansion
Factor (Table A-11)
I
Annubar
Expansion
Factor
Annubar Flow Constant C
Internal Pipe
Diameter
w
h
.
f
ρ
aa
F
. .Y
a
.
2
D
O at 68 °F
O at 68 °F
2
2
inch H
inch H
2
2
O at 68 °F
O at 68 °F
2
2
inch H
inch H
2
2
kPa
2
kPa
2
2
kPa
2
kPa
kPa
2
2-4
K
Annubar Flow
Coefficient
Unit Conversion
Factor
. . . . .
na
=
WF
PPD 8614.56 (in)
Rate of Flow
Table 2-2. Liquid – Mass Rate of Flow
PPH 358.94 (in)
PPS 0.0997 (in)
PPM 5.9823 (in)
kg/D 3.03471 (mm)
T(met)/hr 1.2645E-04 (mm)
Kg/H 0.12645 (mm)
kg/M 2.1074E-03 (mm)
kg/S 3.5124E-05 (mm)
K
Annubar
Flow
Coefficient
Unit
Conversion
Factor
. .
na
=
WF
PPD 8614.56 (in)
Table 2-3. Gas and Steam– Mass Rate of Flow
Rate of Flow
PPH 358.94 (in)
PPS 0.0997 (in)
PPM 5.9823 (in)
kg/D 3.03471 (mm)
T(met)/hr 1.2645E-04 (mm)
Kg/H 0.12645 (mm)
kg/M 2.1074E-03 (mm)
kg/S 3.5124E-05 (mm)
Reference Manual
00809-0100-1191, Rev CB May 2006
Rosemount 485 Annubar
Pressure
Differential
Gravity
Flowing
Specific
w
h
0 @ 68° F
2
H
.
f
ρ
0 @ 68° F
0 @ 68° F
2
2
H
H
kPa
kPa
kPa
kPa
kPa
.
aa
I
Annubar Flow Constant C
F
pv
F
. .
g
F
.
tf
F
.
tb
F
.
pb
F
a
Y
. .
2
2
2
2
2
2
2
D
2
2
Thermal
Expansion
Factor (Table 9)
Factor
(Table 8)
Supercomp
Factor
Gravity
Specific
Factor
Flowing
Temperature
Base
Factor
Temperature
Base
Factor
Pressure
Factor
Annubar
Expansion
Diameter
Internal Pipe
.
Flow
Annubar
Coefficient
Unit
Factor
Conversion
Flow
Rate of
Table 2-4. Volume Rate of Flow at STD Conditions - Gas
K
.
na
F
=
/D 0.27234 (mm)
/H 1.1347E-02 (mm)
/M 1.8912E-04 (mm)
3
3
NM
NM
3
NM
NL/H 11.34700 (mm)
a
SCFD 8116.1 (in)
Q
SCFH 338.17 (in)
NL/M 0.18912 (mm)
SCFM 5.6362 (in)
2
3
kPa
/S 3.1520E-06 (mm)
NM
Pressure
Differential
w
0 @ 68° F
2
H
0 @ 68° F
0 @ 68° F
2
2
H
H
kPa
kPa
.
f
l
---- h
Gravity
Flowing
Specific
Thermal
Expansion
Factor (Table 9)
ρ
aa
F
. .
I
a
Factor
Annubar
Expansion
Y
.
2
2
2
Diameter
Internal Pipe
Annubar Flow Constant C
2
2
2
D
2
.
Annubar
Flow Coefficient
K
.
na
Factor
Unit Conversion
F
=
a
Q
ACFD 8614.56 (in)
ACFH 358.94 (in)
Rate of Flow
Table 2-5. Volume Rate of Flow at Act Conditions
ACFM 5.9823 (in)
AL/H 126.4434 (mm)
AL/M 2.10739 (mm)
3
kPa
/D 3.03473 (mm)
Am
kPa
2
/H 0.12645 (mm)
3
Am
2
3
kPa
/M 2.1074E-03 (mm)
Am
kPa
2
/S 3.5124E-05 (mm)
3
Am
2-5
Rosemount 485 Annubar
NOMENCLATURE
D Internal diameter of pipe, inches (mm)
F
aa
F
g
F
na
F
pb
Thermal Expansion Factor. This factor corrects for the flowing area change of the pipe at the Annubar location due to temperature effects. For 316 stainless steel Annubar primary elements mounted in carbon steel pipe, Faa =
1.0000 for temperatures between 31 and 106 °F. See Table B-1 on page B-3 which includes thermal expansion factors for various pipe materials at several temperatures.
Specific Gravity Factor. This factor corrects the flow equation whenever the gas is not air. The factor can be calculated as:
1
----=
F
g
G
where, G = specific gravity of flowing gas, air = 1.000. For a more complete description of specific gravity, see “Density, Specific Weight, Specific Gravity” on page 1-4 and Appendix D: Related Calculations.
Units Conversion Factor. This factor is used to convert the flow rate to the desired set of units. Appendix D: Related Calculations shows an example of how the numerical value of Fna is derived from the hydraulic equation for a given set of input units.
Pressure Base Factor. The Pressure Base Factors are calculated to give gas volumes at a pressure base of 14.73 psia (101.325 kPa abs). The pressure base factor can be calculated as:
F
pb
14.73
-- -=
base pressure, psia
OR
F
-- -=
pb
base pressure, kPa abs
Reference Manual
00809-0100-1191, Rev CB
May 2006
101.325
F
pv
Supercompressibility Factor. The Supercompressibility Factor accounts for the deviation from the “ideal gas” laws. In the flow equations, gas volumes are assumed to vary with pressure and temperature in accordance with Boyle’s and Charles' laws (the “ideal gas” laws). Actually, the volume occupied by individual gases deviate, by a slight degree, from the volumes which the “ideal gas” laws indicate. The amount of deviation is a function of the composition of the gas and varies primarily with static pressure and temperature. The actual deviation may be obtained by a laboratory test conducted on a sample of the gas, carefully taken at line conditions of pressure and temperature.
The National Bureau of Standards, Circular 564, gives the compressibility factor (Z) of air and other pure gases. The relationship between supercompressibility factor and compressibility factor is as follows:
1
F
---=
pv
Z
Table A-9 on page A-12 gives an abbreviated listing of the supercompressibility factors for air. Practical relationships have been established by which this deviation can be calculated and tabulated for natural gases containing normal mixtures of hydrocarbon components, considering the presence of small quantities of carbon dioxide and nitrogen and also relating the deviation to the heating value of gas. The A.G.A. manual (NX-19), “Determination of Supercompressibility Factors for Natural Gas”, should be used for determination of F
F
tb
Temperature Base Factor. The Temperature Base Factors are calculated to give gas volumes at a base temperature of 60 °F (520°R) for English Units. In order to adapt the flow equation for use in SI units, the factor is calculated
.
pv
similarly at 16 °C (289.15 K). The factor can be calculated as:
temperature base (°F) + 460
Ftb-- -=
F
tf
Flowing Temperature Factor. The units conversion factor (FNA) for volumetric flow of gases at standard conditions has been calculated assuming that the gas temperature flowing around the Annubar primary element is 60 °F (520
520
OR
temperature base (°C) + 273.15
F
-- -=
tb
288.15
°R) or 16 °C (289 K). If measurement is made at any other flowing temperature, then the flowing temperature factor must be applied. The factor can be found in Table A-8 on page A-11 or calculated as:
520
F
--------- -=
tf
flowing temperature (°F) + 460
520
OR
520
F
--------- -=
tf
273.15 + flowing temperature (°C)
288.15
G Specific Gravity of Flowing Liquid. Ratio of the density of the flowing fluid to the density of water at 60°F which is
63.3707 lbm/ft
h
w
Differential pressure produced by the Annubar primary element. For this handbook, the differential pressure is expressed as the height, in inches, of a water column at 68 °F at standard gravity (gc = 32.174 ft/sec2). In SI Units,
3
. See Table A-4 on page A-6 for specific gravities of various liquids.
the differential pressure is expressed in kPa.
h
= inches H2O at 68 °F (kPa)
w
K Flow Coefficient. Equation 2-8 on page 2-9 defines the flow coefficient of an Annubar primary element. It is related to
the diameter of the pipe and is generally expressed as a function of Reynolds Number. See “Reynolds Number” on page 1-8 for an explanation of Reynolds Number.
2-6