Rosemount Manual: Rosemount 3410 Series Gas Ultrasonic Flow Meters Manuals & Guides

Installation manual
00825-0700-3104, Rev AA
April 2022
Rosemount™ 3410 Series Gas Ultrasonic Flow Meters
Model 3418
Installation manual April 2022
This Rosemount product complies with all applicable European directives when properly installed in accordance with the instructions in this manual. Refer to the EU declaration of conformity for directives that apply to this product. The EU declaration of conformity, with all applicable European directives, and the complete ATEX Installation Drawings and Instructions are available on the internet at
www.emerson.com or through your local Emerson support center.
Information affixed to equipment that complies with the Pressure Equipment Directive, can be found on the internet at http://www.emerson.com.
For hazardous installations in Europe, refer to standard EN 60079-14 if national standards do not apply.
Other information
Full product specifications can be found in the product data sheet. Troubleshooting information can be found in the user manual. Product data sheets and manuals are available from the Emerson website at
http://www.emerson.com.
Return policy
Follow Emerson procedures when returning equipment. These procedures ensure legal compliance with government transportation agencies and help provide a safe working environment for Emerson employees. Emerson will not accept your returned equipment if you fail to follow Emerson procedures. Return procedures and forms are available on our web support site at Emerson.com, or by phoning the Emerson Customer Service department.
Emerson Flow customer service
Email:
Worldwide: http://flow.support@emerson.com
Asia-Pacific: http://APflow.support@emerson.com
Telephone:
North and South America
United States 800 522 6277 U.K. 0870 240 1978 Australia 800 158 727
Canada +1 303 527 5200 The
Mexico +41 (0) 41 7686
Argentina +54 11 4837 7000 Germany 0800 182 5347 Pakistan 888 550 2682
Brazil +55 15 3413 8000 Italy 8008 77334 China +86 21 2892 9000
111
Europe and Middle East Asia Pacific
Netherlands
France 0800 917 901 India 800 440 1468
Central & Eastern
Russia/CIS +7 495 981 9811 South Korea +82 2 3438 4600
Egypt 0800 000 0015 Singapore +65 6 777 8211
Oman 800 70101 Thailand 001 800 441 6426
Qatar 431 0044 Malaysia 800 814 008
Kuwait 663 299 01
South Africa 800 991 390
Saudi Arabia 800 844 9564
+31 (0) 704 136 666
+41 (0) 41 7686 111
New Zealand 099 128 804
Japan +81 3 5769 6803
2 Installation manual
April 2022 Installation manual
North and South America Europe and Middle East Asia Pacific
UAE 800 0444 0684
Contents
Introduction.................................................................................................................................5
Mechanical installation...............................................................................................................29
Electrical installation.................................................................................................................. 47
Configuration.............................................................................................................................87
Engineering drawings.................................................................................................................96
Open source licenses..................................................................................................................98
Installation manual 3
Installation manual April 2022
4 Installation manual
April 2022 Installation manual

1 Introduction

1.1 General overview of Rosemount gas flow meters

Rosemount™ 3410 Series Ultrasonic Gas Flow Meters have various configurations that meet a broad range of customer requirements. Each meter comes fully assembled from Rosemount™ Measurement and Control, Inc.
Refer to the following documents for additional details:
00809-0100-7630 MeterLink™ Software for Gas and Liquid Ultrasonic
Flow Meters Quick Start Manual
00809-0700-3104 Rosemount 3410 Series Ultrasonic Gas Flow Meter
Maintenance and Troubleshooting Manual

1.2 Hazard messages

This document uses the following criteria for hazard messages based on ANSI standards Z535.6-2011 (R2017).
DANGER
Serious injury or death will occur if a hazardous situation is not avoided.
WARNING
Serious injury or death could occur if a hazardous situation is not avoided.
CAUTION
Minor or moderate injury will or could occur if a hazardous situation is not avoided.
NOTICE
Data loss, property damage, hardware damage, or software damage can occur if a situation is not avoided. There is no credible risk of physical injury.
Installation manual 5
Installation manual April 2022
Physical access
NOTICE
Unauthorized personnel can potentially cause significant damage and/or misconfiguration of end users' equipment. Protect against all intentional or unintentional unauthorized use. Physical security is an important part of any security program and fundamental to protecting your system. Restrict physical access to protect users' assets. This is true for all systems used within the facility.

1.3 Personnel qualifications

Read and follow all instructions, dangers, warnings, and cautions to avoid personal injury or property damage during system operation. Emerson is not responsible for damage or injury resulting from unsafe use of products, lack of maintenance, incorrect installation of equipment or system operation. If in doubt about any applications and safety precautions described in this document, contact Emerson.
Inform and train all personnel in the proper installation, operation, and maintenance of this product. To ensure safe and proper performance, only informed and trained personnel should install, operate, repair and maintain this product. For further questions about training requirements, contact your local Emerson representative.
Operations risk assessment must be used and followed in conjunction with this document when performing all online retrieval operations.
Ensure that all end user and installation specific safety requirements are read, understood and adhered to.
Ensure that any operator that is conducting work on the equipment, is following end user guidelines on the use of protective equipment including, but not limited to:
Safety helmet or hard hat
Steel-toed shoes
Safety glasses
Working gloves (suitable for mechanical operations)
Chemical resistant latex gloves or the equivalent
Long-sleeved, fire-retardant shirt and fire-retardant trousers or full-
length fire retardant coveralls
Additional PPE may be required depending on facility requirements and MSDS requirements, if applicable. Failure to comply may result in personnel injury.
6 Installation manual
April 2022 Installation manual
WARNING
RISK TO PERSONNEL AND EQUIPMENT Failure to follow the installation, operation or maintenance instructions for a Rosemount product could lead to serious injury or death from explosion or exposure to dangerous substances. To reduce the risk:
Comply with all information on the product, in this manual, and in any
local and national codes that apply to this product.
Do not allow untrained personnel to work with this product.
Use Rosemount parts and work procedures specified in this manual.
NOTICE
Observe all precautionary signs posted on the equipment to avoid serious injury.
WARNING
RISK TO PERSONNEL AND EQUIPMENT Operation of this product on pressurized lines may potentially imply operational risk for personnel and equipment from the potential escape of hot gas or liquid, which could result in serious injury.
Observe all precautionary signs on the equipment.
WARNING
RISK TO PERSONNEL AND EQUIPMENT The operation of the Rosemount product involves heavy equipment handling. Observe the following guidelines to avoid potentially serious injury:
Be aware of your limitations and ask for assistance if needed.
Do not attempt to lift weight beyond your capacity.
Lift with your legs, not your back.
Note
Mechanical lifting tools may also be used in some locations to reduce risk.
Installation manual 7
Installation manual April 2022
NOTICE
Attending the training course for this product is not considered sufficient for operating the tool on pressurized lines. Emerson requires a two-man crew with formal training. Additionally, at least one of the operators must have a record of extensive field experience and be certified for this work.
Emerson assumes no responsibility for incidents, or consequences of incidents, occurring as a result of the use of this product by others than Emerson or its designated personnel, and have no liability whatsoever for any such work.
Consult Emerson for more details on both training and certification.

1.4 Warranty restrictions

Visually inspect all components for shipping damage. If shipping damage is found, notify the carrier at once. Shipping damage is not covered by the warranty. The carrier is responsible for all repair and replacement costs resulting from shipment damage.

1.5 Assistance

The Emerson Global Service Center is organized through a network of service centers worldwide, and supports all service requirements or technical queries. For the Product Support Help Desk, go to: http://
www.emerson.com or contact your nearest Emerson service provider.
1.6
8 Installation manual

Typical applications of this product

Rosemount™ 8-path 3410 Series Ultrasonic Gas Flow Meters various configurations meet a broad range of customer requirements. Each meter comes fully assembled from Rosemount. The technology can be applied to custody transfer, allocation measurement, and check metering applications such as:
Custody transfer
Production and gathering
Offshore
Gas processing plants
Underground storage sites
Transmission pipelines
Power plants
Large and industrial users
April 2022 Installation manual

1.7 Features and benefits of the 3418 model meter

OIML Accuracy Class 0.5 with 5 diameters upstream pipe and no flow
conditioner
Best-in-class performance in compact installations
Reduce size, weight and capital costs of metering system designs
Configurable read-only serial ports
GERG-2008 and Detail AGA Methods
Proven long term stability
Field proven reliability
No line obstruction
No pressure loss
Low maintenance
Bi-directional measurement
Extensive self-diagnostics
Immediate alarm reporting
Continuous Flow AnalysisAbnormal profile
Blockage
Internal bore buildup
Liquids present in the gas meter
Reverse Flow
Speed of Sound comparison error
Auto-detected ASCII/RTU Modbus communications protocol
Low power consumption
Sophisticated noise reduction
Internet-ready communications
Ethernet access
On-board LED status indicators
Analog pressure and temperature inputs
API Chapter 21 compliant event and data logging (gas meters)
MeterLink™ (a Windows®- based interface software)
Installation manual 9
Installation manual April 2022
Local Display (optional)
Smart Meter Verification (4-Path and 8-Path meters)
For other features and benefits refer to the ultrasonic flow meter product datasheets: http://www.emerson.com.

1.8 Acronyms, abbreviations and definitions

Acronym or abbreviation Definition
° degree (angle)
°C degrees celsius (temperature unit)
°F degrees fahrenheit (temperature unit)
ADC analog-to-digital converter
AI Analog Input
AO Analog Output
ASCII MODBUS A Modbus protocol message framing format in
boolean A type of data point that can only take on values
bps Bits Per Second (baud rate)
cPoise centipoise (viscosity unit)
CPU Central Processing Unit
C T S Clear-to-Send; the RS-232C hand shaking signal
D A C Digital-to-Analog Converter
MeterLink
DI Digital Input
DO Digital Output
DHCP Dynamic Host Configuration Protocol
dm decimeter (10 -1 meters, length unit)
which ASCII characters are used to delineate the beginning and end of the frame. ASCII stands for American Standard Code for Information Interchange.
of TRUE or FALSE (generally TRUE is represented by a value of 1, FALSE is represented by a value of
0)
input to a transmitter indicating that it is okay to transmit data - i.e., the corresponding receiver is ready to receive data. Generally, the Request-to­Send (RTS) outputfrom a receiver is input to the Clear-to-Send (CTS) input of a transmitter.
Ultrasonic Meter interface software
10 Installation manual
April 2022 Installation manual
Acronym or abbreviation Definition
ECC Error Correction Code
EEPROM Electrically-Erasable, Programmable Read-Only
Flash non-volatile, programmable read-only memory
FODO output that is user configurable as either a
HART® Communication Protocol
hr hour (time unit)
Hz Hertz (cycles per second, frequency unit)
I/O Input/Output
IS Intrinsically Safe
K Kelvin (temperature unit)
kHz kilohertz (10 3 cycles per second, frequency unit)
LAN Local Area Network
LED Light-emitting Diode
m meter (length unit)
m 3/d cubic meters per day (volumetric flow rate)
m 3/h cubic meters per hour (volumetric flow rate)
m 3/s cubic meters per second (volumetric flow rate)
mA milliamp (current unit)
MAC Address Media Access Control (Ethernet Hardware
microinch (m inch) microinch (10-6 in)
micron micrometer (10-6 m)
MMU Memory Management Unit
MPa megapascal (equivalent to 10 6 Pascal) (pressure
N/A Not Applicable
Nm 3/h normal cubic meters per hour
NVRAM Non-Volatile Random Access Memory
Pa Pascal, equivalent to 1 newton per square meter
Memory
Frequency or Digital Output
Highway Addressable Remote Transducer communications protocol
Address -EHA)
unit)
(pressure unit)
Installation manual 11
Installation manual April 2022
Acronym or abbreviation Definition
Pa × s Pascal Second (viscosity unit)
PC Personal Computer
PFC Peripheral Field Connection (Board)
P/N Part Number
PS Power Supply (board)
psi pounds per square inch (pressure unit)
psia pounds per square inch absolute (pressure unit)
psig pounds per square inch gage (pressure unit)
R Radius of meter
rad radian (angle)
RAM Random Access Memory
RTS Request-to-Send; the RS-232C hand shaking
RTU MODBUS A Modbus protocol framing format in which
s second (time unit, metric)
SDRAM Synchronous Dynamic Random Access Memory
sec second (time unit, U.S. Customary)
TCP/IP Transmission Control Protocol/Internet Protocol
time_t seconds since Epoch (00:00:00 UTC Jan.1,1970)
UDP User Datagram Protocol
U.L. Underwriters Laboratories, Inc. - product safety
V Volts (electric potential unit)
W Watts (power unit)
signal output by a receiver when it is ready to receive data
elapsed time between received characters is used to separate messages. RTU stands for Remote Terminal Unit.
(time unit)
test in gand certification organization

1.9 MeterLink software

MeterLink software has robust features for setting communications parameters, configuring your meter, collecting logs and reports and
12 Installation manual
April 2022 Installation manual
monitoring the meter health and alarm statuses. MeterLink may be downloaded at no charge from: emerson.com/en-us/catalog/meterlink.
Figure 1-1: MeterLink download and registration
Refer to MeterLink Software for Gas and Liquid Ultrasonic Meters Quick Start Manual (00809-0100-7630) for installation instructions and setup for initial
communications. You may download the manual from the MeterLink web page: emerson.com/en-us/catalog/meterlink.

1.10 Design of Rosemount™ 3410 series meter

Rosemount 3410 Series Gas Ultrasonic Flow Meters are designed to accurately measure products in applications where reliable performance is critical, by measuring the difference in signal transit time with and against the flow across one or more measurement path(s). A signal transmitted in the flow direction travels faster than one transmitted against the flow direction. Each measurement path is defined by a transducer pair in which each transducer alternately acts as transmitter and receiver. The meter uses transit time measurements and transducer location information to calculate the mean velocity.
The 3418 combines the power of two interlocked 4-path British Gas design meters in one flowmeter body. The second set of chords is the mirror image of the first, which allows the meter to cancel out the effects of swirl and cross flow. The meter offers bidirectional measurement and superior low­flow capabilities, without the compromises associated with conventional technologies.
Installation manual 13
Installation manual April 2022
Figure 1-2: Rosemount 3418 Gas Ultrasonic Flow Meter design
A. Transmitter electronics enclosure (explosion-proof) Optional - Local Display with glass endcap (Figure 1-3)
B. Base electronics enclosure (intrinsically safe)
C. Meter body with transducer assemblies (T-21, T-22 or T-200) (intrinsically safe) covered by security shrouds
The Rosemount Gas Ultrasonic Flow Meter design is available with an optional glass end cap and a local display.
14 Installation manual
April 2022 Installation manual
Figure 1-3: Transmitter electronics enclosure with local display and glass endcap
All Rosemount ultrasonic flow meter's U.L. safety listing is accomplished through the combination of an explosion-proof transmitter electronics enclosure that houses the CPU module, Power Supply board, I.S. Barrier board, Backplane board and optional LCD Display board.
Note
The optional LCD Display requires firmware v1.04 or later and Uboot version, January 31, 2013.
The Base Electronics Enclosure that houses the Acquisition Module. Intrinsically safe transducers and cable assemblies are designed for Class 1, Division1, Groups C and D areas without need of further protection when installed in accordance with the field wiring diagram (refer to Rosemount drawing DMC-005324 see Engineering drawings).
1.11

Meter specifications for 3418 model

WARNING
CONTENTS MAY BE UNDER PRESSURE When the meter is under pressure, DO NOT attempt to remove or adjust the transducer holder of the T-Slot transducer assembly, or loosen the screws holding the T-200 transducer assembly.
Attempting to do so could release pressurized gases, resulting in serious injury or equipment damage.
Installation manual 15
Installation manual April 2022
WARNING
CONTENTS MAY BE HAZARDOUS The meter must be fully depressurized and drained before attempting to remove the T-200 transducer assembly. If gas or fluid begins to leak from the T-200 transducer stalk assembly, stop immediately and reinstall T-200 stalk assembly.
Failure to comply could cause serious injury or equipment damage.
A. Transducer holder
CAUTION
ESCAPING GASES OR FLUIDS HAZARD The purchaser of the meter is responsible for the selection of Rosemount components/seals and materials compatible with the chemical properties of gas flow measurement.
Failure to select the suitable meter component/seals may cause escaping gases or liquids, resulting in injury or equipment damage.
Consult your Emerson Flow sales and service representative to ensure you purchase the correct components and seals for your application. Specifications for Rosemount™ Gas Ultrasonic Flow Meter model 3418 are below:
16 Installation manual
April 2022 Installation manual
Table 1-1: Rosemount™ model 3418 meter specifications (part 1)
Rosemount 3418 meter specifications
Meter type Number of paths
3418: 8-path chordal design
Ultrasonic type
Transit-time based measurement
Spool piece with integral mount
transducers
Enclosure materials ASTM B26GrA356.0T6 Aluminum
100% conversion coated and
exterior coated with a polyurethane enamel
ASTM A351 GrCF8MStainless SteelPassivated
Optional Local Display with a glass endcap on transmitter enclosure
Meter performance
Flow specifications Model 3418 8-path chordal design
Flow calibrated accuracy is ±0.1% of
reading over entire flow calibration range
OIML Accuracy Class 0.5 with 5
diameters upstream pipe and no flow conditioner
Repeatibility ±0.05% of reading in the specified
velocity range from 5% to 100% (Q
)
max
Velocity range Nominal 0 to 30 m/s (0 to 100 fps)
with over-range performance exceeding 38 m/s (125 fp/s) on some sizes
Meter meets or exceeds AGA 9 2017
Edition / ISO 17089 performance specifications
Installation manual 17
Installation manual April 2022
Table 1-2: Performance specifications
Model 3418
AGA 9 / ISO 17089 Flow rate values (Metric units)
Meter size (DN)
Qmin (m/s) 0.5 0.5 0.5 0.5
Qt (m/s) 3.048 2.591 2.29 CF *
Qmax (m/s) 30.48 25.91 22.86 CF *
Model 3418
AGA 9 / ISO 17089 Flow rate values (US Customary Units)
Meter size (IN)
Qmin (ft/s) 1.7 1.7 1.7 1.7
Qt (ft/s) 10 8.5 7.5 CF *
Qmax (ft/s) 100 85 75 CF *
250 to 600 750 900 1050
10 to 24 30 36 42
(*) CF = consult factory
Table 1-3: Rosemount™ model 3418 meter specifications (part 2)
Body and Flange Sizes and Pressure rating range
18 Installation manual
U.S. Customary Units - Meter sizes 10, 12, 16, 20, 24, 30, 36 and 42 (inches)
ANSI pressure classes 300, 600, 900,
1050 and 2500 (per ANSI B16.5)
Carbon Steel
316 Stainless Steel
Metric Units - Meter sizes DN - 250, 300, 400, 500, 600, 750, 900 and 1050
PN 50, 100, 150, 200, 420
Carbon Steel
316 Stainless Steel
Maximum Pressures
Dependent on operating
temperature
Meter bore
Schedule 20, 30, 40, 60, 80, 100,
120, 140, 160, STD, XS, LW
April 2022 Installation manual
Table 1-3: Rosemount™ model 3418 meter specifications (part 2)
(continued)
Flanges types ANSI classes - 300, 600, 900, 1500 and
Specific gravity 0.35 to 1.50
Accuracy Limits Model 3418 is AGA 9 compliant with
Minimum operating pressure 100 psig (7 bar)
Electronic specifications
Power Meter
2500 (per ANSI B16.5)
accuracy limits
Flow calibrated accuracy is ±0.1% of
reading over entire flow calibration range
OIML Accuracy Class 0.5 with 5
diameters upstream pipe and no flow conditioner
10.4 VDC to 36 VDC
11 W power consumption (15 W
maximum)
Serial cable
Belden #9940 or equivalent (22
gauge)
Capacitance (pF/m) 121.397
(conductor to conductor)
Capacitance (pF/m) 219.827
(conductor to other conductor and shield)
Resistance (DC) DCR @ 20° C
(recommended)
Ethernet cable
Cat-5 Standard 100 Mbps
Frequency (see Table 1-2)
22 AWG wire characteristics areas
follows:
Capacitance = 20 pF/ft or 20 nF/
1000 ft (between two wires)
Resistance = 0.0168 Ohms/ft or
16.8 Ohms/1000 ft
Pull-up voltages 24 VDC
Installation manual 19
Installation manual April 2022
Table 1-4: Transducers, mounts and holders
Transducer specifications
Transducer type Temperature range Mount and holder type
1
T-21
2
T-22
T-41 -50° C to 100° C (-58° F to
T-200 -50 °C to +125 °C (-58°F to
1
T-21 and T-41 transducers use W-01 transformers
2
T-22 transducers use W-02 transformers
-20° C to +100° C (-4° F to 212° F)
-50° C to +100° C (-58° F to 212° F)
212° F)
257 °F)
Standard mounts/ Holders/NBR O-ring
Inconel mounts/316L Holders/NBR O-ring
Inconel Mounts/Inconel Holders/FKM O-ring
Inconel Mounts/316L Holders/FKM O-rings
Standard mounts/ Holders/NBR O-ring
Inconel mounts/316L Holders/NBR O-ring
Inconel Mounts/Inconel Holders/FKM O-ring
Inconel Mounts/316L Holders/FKM O-rings
Standard mounts/ Holders/NBR O-ring
Inconel mounts/316L Holders/NBR O-ring
Inconel Mounts/Inconel Holders/FKM O-ring
Inconel Mounts/316L Holders/FKM O-rings
Standard Stalk Assemblies Inconel Stalk Assemblies
Note
The process temperature must not exceed the operating temperature range of the transducers.
Note
T-21 and T-41 transducers are used for the direct paths of 16" and larger meters. T-22 and T-200 transducers are used for the direct paths of 12" and smaller meters.
20 Installation manual
April 2022 Installation manual
Table 1-4: Transducers, mounts and holders (continued)
Note
The ultrasonic transducers are not intended for use across boundary walls of different hazardous area classifications. The transmitter electronics cannot be remote mounted from Division 1 classification to a Division 2 area to meet an area classification.
Table 1-5: Rosemount™ model 3418 meter specifications (part 3)
Communications specifications
Connectivity protocols One serial RS-232/RS-485 port (115 kbps
baud rate) (Modbus RTU/ASCII)
(1) Serial Port A
(RS-232/RS-485 Full Duplex/RS-485
Half Duplex)
One Ethernet Port (TCP/IP) 100 Base
Up to 10 Mbps (internal connection)
100Mbps (external connection)
Modbus TCP, TCP/IP
Device compatibility Rosemount Ultrasonic flow meters are
Digital, analog, and frequency inputs
Digital Input(s) (1) Single polarity
compatible with nearly every commercially available flow computer. Examples: FloBoss 103, FloBoss S600 flow computer, ROC 107.
Note
DI1Mode must be set to Digital Input/ Calibration Input.
Installation manual 21
Installation manual April 2022
Table 1-5: Rosemount™ model 3418 meter specifications (part 3)
(continued)
Analog Input(s) (2) 4-20 mA
AI-1 Temperature
AI-2 Pressure
Note
The analog-to-digital conversion accuracy is within ±0.05% of full scale over the operating temperature range.
Note
AI-1 and AI-2 are electronically isolated and operate in sink mode. The input contains a series resistance so HART Communicators can be connected to configure sensors.
A regulated 24 Volt DC power output is available to provide power to the sensors.
Frequency/Digital Output(s) The outputs have user-configurable
selections as either a frequency output or digital status (FODO) (Also see
Frequency/Digital outputs).
Frequency/Digital Outputs
FODO1 (eight possible output
configurations)
FODO2 (eight possible output
configurations)
FODO3 (eight possible output
configurations)
FODO4 (eight possible output
configurations)
FODO5 (eight possible output
configurations)
FODO6 (eight possible output
configurations)
Note
Use of FODO6 requires DI1Mode set to Frequency/Digital Output 6. Digital Input will not be available.
®
22 Installation manual
April 2022 Installation manual
Table 1-5: Rosemount™ model 3418 meter specifications (part 3)
(continued)
Frequency or Digital Output parameter pairs (see Frequency/Digital outputs)
Frequency or Digital Outputs (FODO1, FODO2, FODO3, FODO4, FODO5, FODO6) source selections:
(FO1A, DO1A, FO1B, DO1B, FO2A,
DO2A, FO2B, DO2B)
Mode options:
Open Collector (requires external
excitation supply voltage and pull-up resistor)
TTL (internally powered by the meter
0-5 VDC signal)
Channel B Phase options:
Lag forward, Lead reverse (Phase B
lags Phase A while reporting forward flow, leads Phase A while reporting reverse flow)
Lead forward, Lag reverse (Phase B
leads Phase A while reporting forward flow, lags Phase A while reporting reverse flow)
Installation manual 23
Installation manual April 2022
Table 1-5: Rosemount™ model 3418 meter specifications (part 3)
(continued)
Phase A and Phase B output (based on flow direction)
Reverse flow - output only reports
flow in the reverse direction. For frequency outputs, Phase B of the output is 90 degrees out of phase with Phase A.
Forward flow - output only reports
flow in the forward direction. For frequency outputs, Phase B of the output is 90 degrees out of phase with Phase A.
Absolute - output reports flow in
both directions. For frequency outputs, Phase B of the output is 90 degrees out of phase with Phase A.
Bidirectional - output reports flow on
Phase A only in the forward direction and on Phase B only in the reverse direction.
Maximum frequency for the frequency outputs
1000Hz
5000Hz
Analog Output(s) (1) 4-20 mA independently
Optional Module Slot Inputs/Outputs RS-232 module
configurable analog output
(1) 4-20 mA independently
configurable analog output (conventional) - Type 2 CPU only
The analog output zero scale offset error is within ±0.1% of full scale and gain error is within ±0.2% of full scale. The total output drift is within ±50 ppm of full scale per °C.
RS-485 half duplex module
Expansion I/O module

1.12 Preinstallation considerations

Pipeline equipment code compliance, ANSI, ASME, etc.
24 Installation manual
April 2022 Installation manual
Proper Inlet/outlet meter tube piping for reasonable stable flow to the
settling chamber (first meter tube spool upstream of the meter).
Electrical safety compliance; UL, CSA, ATEX, IECEx etc.
Civil and structural good practices compliance
Contractual agreements or governmental compliance (or both)
In-situ performance test procedures
Field tested meter health check and flow dynamics diagnostics
Data collection and retention procedures

1.13 Safety considerations

The Rosemount™ 3410 Series Gas Ultrasonic Flow Meter is suitable for use in U.L. Class 1, Division 1, Group C and D hazardous locations.
NOTICE
An “X” signifies the user should contact Emeron for information on the dimensions of the flameproof joints.
Refer to the 3410 Series Systems Wiring Diagram, Sheet 3 (DMC-005324) for the certification tag (see 3410 Series engineering drawings ).
Rosemount 3410 Series GasUltrasonic Meters are INMETRO certified. Refer to the 3410 Series Gas Ultrasonic Flow Meter Tag, INMETRO Certification drawing DMC-006224.
Certificate number: UL-BR 16.0144X
Marking: Ex db ia IIB T4...T3 Gb
Electrical parameters: Refer to Meter specifications for 3418 model, 3410
Series engineering drawings.
Special conditions for safe use
Explosion proof joint dimensions are compliant with the Brazilian
Association of technical standard: ABNT NBR IEC 60079-1, Table 3.
The enclosure for the explosion proof transmitter and intrinsically safe
barrier must be remote mounted (refer to Table 1-3) if the operating temperature exceeds 140 °F (60 °C) (refer to Table 1-3).
Cable length (refer to Table 1-3).
Installation manual 25
Installation manual April 2022
WARNING
EXPLOSION OR FIRE HAZARD Conduit runs must have a sealing fitting within 18 inches (457 mm) of the enclosure to reduce the risk of an explosion or a fire.
During operation, keep covers tight.
During equipment maintenance, disconnect power before opening
transmitter or base electronics. Clean cover joints before replacing.
DO NOT substitute meter components. Component substituting may
compromise the intrinsic safety.
Failure to comply could result in severe injury to personnel or cause damage to the equipment.

1.14 Certifications and approvals for the Rosemount™ 3410 series

Rosemount™ 3410 Series Gas Ultrasonic Flow Meters have electrical, metrology, intrinsic safety and Pressure Equipment Directive certifications and approvals by the agencies listed below. Refer to the nameplate tag on the meter body, the wiring diagram (DMC-005324) in 3410 Series
engineering drawings and observe all safety precautions. Rosemount 3410
Series Gas Ultrasonic Flow Meters operate within the pressure and temperature range of the device (also see Meter specifications for 3418
model Design of Rosemount 3410 series meter). Rosemount 3410 Series Gas
Ultrasonic Flow Meters are approved to the ATEX Directive 94/9/EC.
Standards
US
Canada
Europe
Explosive Atmospheres (ATEX)
International Electrotechnical Commission (IECEx)
Pressure Equipment Directive (PED via BSI)
Electromagnetic Compatibility (EMC)
International Organization of Legal Metrology (OIML)
Approval agencies
UL
c-UL
26 Installation manual
April 2022 Installation manual
DEMKO
INMETRO
NEPSI
GOSTR
Important
Please consult Emerson Flow services for Rosemount products for the complete metrology approvals list.

1.15 FCC compliance

This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment.
This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
NOTICE
Changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment.
1.16
Installation manual 27

References

1. Gould Modbus Protocol Reference Guide, Rev. B, PI-MBUS-300
2. Measurement of Fuel Gas By Turbine Meters, American Gas Association, Transmission Measurement Committee Report No. 7, Second Revision, April 1996 (also referred to as AGA7)
3. Compressibility Factors of Natural Gas and Other Related Hydrocarbon Gases, American Gas Association, Transmission Measurement Committee Report No. 8, Second Edition, Second Printing, July 1994 (also referred to as AGA8)
4. Speed of Sound in Natural Gas and Other Related Hydrocarbon Gasses, Report 10, First Edition, May 2003 (also referred to as AGA10)
5. Manual of Petroleum Measurement Standards, Chapter 21 — Flow Measurement Using Electronic Metering Systems, Section 1 —
Installation manual April 2022
Electronic Gas Measurement, American Gas Association and American Petroleum Institute, First Edition, September 1993
6. AGA Report No. 9, Measurement of Gas by Multipath Ultrasonic Meters, Second Edition (April 2007)
28 Installation manual
April 2022 Installation manual

2 Mechanical installation

2.1 Meter piping, lifting and mounting

Refer to the following sections for piping recommendations, lifting with hoist rings and slings, mounting in heated or cooled pipelines and safety warnings and precautions.
CAUTION
SURFACE TEMPERATURE HAZARD The meter body and piping may be extremely hot or cold.
Wear appropriate personal protective equipment when coming in contact with the meter.
Failure to comply may result in injury.
WARNING
CUTTING HAZARD Sharp edges may be present on the transducer retaining ring.
Wear appropriate eye protection equipment when removing or installing the transducer retaining ring.
Failure to comply could cause serious injury.
CAUTION
TRANSPORTATION HAZARD When moving the meter, do not insert the forks of a forklift into the bore.
Inserting the forks may cause the meter to become unstable, resulting in injury or damage to the bore and sealing face.
CAUTION
TRIPPING HAZARD Clear all obstacles or obstructions from the work area when transporting, installing or removing the meter.
Failure to clear the work area may cause injury to personnel.
Installation manual 29
Installation manual April 2022
WARNING
CRUSHING HAZARD Do not remove flange stabilizers.
Attempting to do so could allow the meter to roll, resulting in serious injury or equipment damage.
A. Flange stabilizers
WARNING
CRUSHING HAZARD Before installation, do not rest the meter on a slope of greater than 10 degrees. Also ensure the surface is solid so that the flange stabilizers do not sink into the surface.
Failure to comply could allow the meter to roll, resulting in serious injury or equipment damage.
CAUTION
ESCAPING GASES OR FLUIDS HAZARD The purchaser of the meter is responsible for the selection of Rosemount components/seals and materials compatible with the chemical properties of gas flow measurement.
Failure to select the suitable meter component/seals may cause escaping gases or liquids, resulting in injury or equipment damage.
30 Installation manual
Loading...
+ 86 hidden pages