Rosemount Manual: Rosemount 3095FT Manuals & Guides

Model 3095FT HART® Flow Transmitter
00809-0100-4015
English
R
Product Manual
Model 3095FT HART
®
Flow Transmitter
Model 3095FT Software: 64 Model 3095FT User Interface Software: 2.02
NOTICE
Read this manual before working with the product. For personal and system safety, and for optimum product performance, make sure you thoroughly understand the contents before installing, using, or maintaining this product.
Within the United States, Rosemount Inc. has two toll-free assistance numbers. Customer Central: 1-800-999-9307 (
Technical support, quoting, and order-related questions.
North American 1-800-654-7768 ( Response Center: Equipment service needs.
For equipment service or support needs outside the United States, contact your local Rosemount representative.
7:00 a.m. to 7:00 p.m. CST)
24 hours a day – Includes Canada)
Rosemount Inc. Measurement Division
8200 Market Boulevard Chanhassen, MN 55317 USA Tel 1-800-999-9307 Telex 4310012 Fax (612) 949-7001
Publication Number 00809-0100-4015 © Rosemount Inc., 1995, 1996. Printed in the USA
The products described in this document are NOT designed for nuclear­qualified applications.
Using non-nuclear qualified products in applications that require nuclear­qualified hardware or products may cause inaccurate readings.
For information on Rosemount nuclear-qualified products, contact your local Rosemount Sales Representative.
Rosemount and the Rosemount logotype are registered trademarks of Rosemount Inc. Coplanar and Multivariable are trademarks of Rosemount Inc. HART is a registered trademark of the HART Communication Foundation. Hastelloy C is a registered trademark of Cabot Corp. Monel is a registered trademark of International Nickel Company. Teflon is a registered trademark of I.E. du Pont de Nemours & Co. MS-DOS and Windows are registered trademarks of Microsoft Corp. Flow-Cal is a trademark of Coastal Flow Measurement, Inc.
Fisher-Rosemount satisfies all obligations coming from legislation to harmonize product requirements in the European Union.
SNF-0004

Table of Contents

SECTION 1 Introduction
SECTION 2 Initial Checkout and Field Installation
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Using This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
System Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Unpacking The Model 3095FT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Becoming Familiar With The Model 3095FT . . . . . . . . . . . . . . . . . . 2-2
Initial Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Bench Configuration and Calibration . . . . . . . . . . . . . . . . . . . . . 2-4
Write Protect (WP) / Real-Time Clock (RTC) Switches . . . . . . . 2-4
General Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
Mechanical Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
Taps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
Impulse Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
Environmental Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
Access Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
Process Flange Orientation . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
Housing Rotation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
Terminal Side of Electronics Housing . . . . . . . . . . . . . . . . . . 2-9
Circuit Side of Electronics Housing . . . . . . . . . . . . . . . . . . . 2-9
Process Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-9
Mounting Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
Mounting Brackets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
Mounting Pressure Effect . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
Bolt Installation Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-11
Electrical Consideration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14
Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14
Hazardous Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-15
Field Installation Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-15
Field Installation Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-16
1. Review InstallationConsiderations . . . . . . . . . . . . . . . . . . . . . 2-16
2. Mount Transmitter and Install Bolts . . . . . . . . . . . . . . . . . . .2-16
3. Make Process Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-16
4. Install RTD Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-17
5. Check for Leaks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-17
6. Field Wiring (Power and Signal) . . . . . . . . . . . . . . . . . . . . . . .2-18
7. Install Grounds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-19
Field Wiring Ground . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-19
Ground the Transmitter Case . . . . . . . . . . . . . . . . . . . . . . . . 2-19
8. Field Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-20
9. Replace Cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-20
SECTION 3 Options and Accessories
LCD Meter (03095-0392-0001) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Installing the Meter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
SST Mounting Brackets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Transient Protection Terminal Block . . . . . . . . . . . . . . . . . . . . . . . . 3-5
Installation Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
Custom Configuration (Option Code C1) . . . . . . . . . . . . . . . . . . . . . . 3-6
i
Flange Adapters (Option Code DF) . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
Model 3095FT User Interface Software . . . . . . . . . . . . . . . . . . . . . . . 3-7
Remote Power Supply (03095-5000-101x) . . . . . . . . . . . . . . . . . . . . . 3-7
Installation Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
Check Battery Voltage Level . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
Sunlight Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
Mount Solar Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
Mount Remote Power Supply Enclosure . . . . . . . . . . . . . . . 3-10
Remote Power Supply Wiring Connections . . . . . . . . . . . . . 3-10
Recharging the Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-12
Backup Power Supply (03095-5000-200x) . . . . . . . . . . . . . . . . . . . . . 3-14
Mount Remote Power Supply Enclosure . . . . . . . . . . . . . . . 3-14
Battery Backup Wiring Connections . . . . . . . . . . . . . . . . . . 3-14
SECTION 4 Using the Model 3095FT User Interface Software
Install the Model 3095FT User Interface Software . . . . . . . . . . . . . 4-1
System Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
MInimum Equipment and Software . . . . . . . . . . . . . . . . . . . 4-1
Recommended Equipment and Software . . . . . . . . . . . . . . . 4-1
Installation Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Establish Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
Connect a Personal Computer to a Model 3095FT . . . . . . . . . . . 4-4
Connect a Personal Computer to a Remote Power Supply . . . . . 4-6
Sample Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-8
Menu Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-8
Menu Categories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-9
Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-9
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-9
Sys Admin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-9
Logs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-9
Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-9
Windows . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-9
Exit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-9
Screen Components and Conventions . . . . . . . . . . . . . . . . . . . . . . . . 4-9
Screen Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-9
Title Bar Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-10
Status Bar Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-10
Hot Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-10
Toolbar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-10
Path Name Convention . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-11
OK and Cancel Buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-11
Automatic Error Messages . . . . . . . . . . . . . . . . . . . . . . . . . . 4-11
Sample Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-12
Bench Configuration (Standard) . . . . . . . . . . . . . . . . . . . . . . . . .4-12
Bench Configuration (Option Code C1) . . . . . . . . . . . . . . . . . . . .4-12
Bench Calibration Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-13
Field Calibration Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-13
Collect New Log Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-13
Collect All Log Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-13
Collect Log Data per System Defaults . . . . . . . . . . . . . . . . . . . . 4-13
ii
User Interface Software Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-14
Configuration Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-14
Configuration
Flow
Flow Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-14
Gas Properties (CO2) . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-17
Gas Properties (N2) . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-18
Gas Properties (Detail) . . . . . . . . . . . . . . . . . . . . . . . . . . 4-20
Configuration
Audit Trail
Audit Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-22
Logged Variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-23
Configuration
LCD Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-24
Read Config File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-25
Save Config File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-25
Coefficient Calculation . . . . . . . . . . . . . . . . . . . . . . . . . . .4-26
Send Xmtr . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-26
Recv Xmtr . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-26
Maintenance Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-27
Maintenance
Transmitter
Sensor Trim . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-27
Damping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-30
PV Default Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-30
Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-31
Matls of Const . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-31
Multidrop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-32
Change Address . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-32
Change Connection . . . . . . . . . . . . . . . . . . . . . . . . 4-33
Self Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-34
Revision . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-34
EEPROM Info . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-35
Maintenance
Clock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-35
Maintenance Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-36
Sys Admin Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-38
Sys Admin
Comm Statistics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-38
Login . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-38
Change Passwords . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-39
Disable Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-40
Clear Logs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-41
Factory Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-41
Test Calc . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-42
Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-43
Communication Options . . . . . . . . . . . . . . . . . . . . . . . 4-43
Log Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-43
About 3095UI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-44
iii
Log Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-44
View Archive Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-44
View Transmitter Data
Default . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-45
New . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-45
All . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-45
Limited . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-45
Previous . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-45
Collect Batch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-46
Collect Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-47
Save to Archive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-47
Print to File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-47
Close all Windows . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-48
Interpreting Variable and Daily Logs . . . . . . . . . . . . . . . . . .4-48
Importing files into a spreadsheet . . . . . . . . . . . . . . . . . . . . 4-48
Importing a file into edit.com . . . . . . . . . . . . . . . . . . . . . . . .4-48
Output Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-49
Output
Read Current Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-49
Read Current Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-49
Windows Selections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-49
Exit Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-49
SECTION 5 Troubleshooting and Maintenance
Maintenance Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Off-line Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
On-line Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Model 3095FT Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
Transmitter Does Not Communicate With the Model 3095FT
User Interface Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
Poor Communication Between the Model 3095FT User Interface
Software and the Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
Interpreting Model 3095FT Alarms and Events . . . . . . . . . . . . 5-3
Unexpected Process Variable (PV) Readings . . . . . . . . . . . . . . . 5-6
Symptom High PV Reading . . . . . . . . . . . . . . . . . . . . . . . . . . 5-6
Symptom: Erratic PV Reading . . . . . . . . . . . . . . . . . . . . . . . 5-7
Symptom: Low PV Reading or No PV Reading . . . . . . . . . . 5-8
Symptom: Sluggish Output Response/Drift . . . . . . . . . . . . . 5-9
Disassembly Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-10
Process Sensor Body . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-10
Electrical Housing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-11
Removing the Sensor from the Electrical Housing . . . . . . . . . . .5-13
Reassembly Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-14
Connecting the Electrical Housing to the Sensor . . . . . . . . . . . .5-15
Reassembling the Process Sensor Body . . . . . . . . . . . . . . . . . . .5-15
Return Of Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-16
Battery Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-17
Replacing the Real-time Clock Battery . . . . . . . . . . . . . . . .5-17
Replacing the Remote Power Supply Battery . . . . . . . . . . . 5-18
iv
SECTION 6 Theory of Operation
Transmitter Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Multivariable Sensor Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
Capacitive Differential Pressure Sensor . . . . . . . . . . . . . . . . . . . 6-2
Piezoresistive Absolute Pressure Sensor . . . . . . . . . . . . . . . . . . 6-2
Process Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
Sensor Microprocessor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3
Electronics Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4
Flow/Output Microprocessor . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4
Nonvolatile Memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4
RAM
(Random Access Memory) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4
HART Digital Communication . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4
Personal Computer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4
SECTION 7 Specifications and Reference Data
Model 3095FT Functional Specifications . . . . . . . . . . . . . . . . . . . . . 7-1
Model 3095FT Performance Specifications . . . . . . . . . . . . . . . . . . . . 7-3
Model 3095FT Physical Specifications . . . . . . . . . . . . . . . . . . . . . . . 7-4
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-6
Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-7
Remote Power Supply Assembly (Included with Part No.
03095-5000-101x and 03095-5000-200x) . . . . . . . . . . . . . . . . . . . 7-7
General Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-7
Solar Panel Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-8
Battery Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-8
Battery Backup Specifications
(Applies to Part No. 03095-5000-200x) . . . . . . . . . . . . . . . . . . . . 7-8
Temperature Sensor Assemblies . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-9
Series 68 RTD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-9
Platinum Element and Lead Wire Configurations . . . . . . . 7-9
Series 78 RTD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-10
Platinum Element and Lead Wire Configurations . . . . . . .7-10
Flat Cover Connection Assemblies . . . . . . . . . . . . . . . . . . . . . . . . . .7-12
Configuration Data Sheet CDS 4015A00 . . . . . . . . . . . . . . . . . . . . . 7-13
Model 3095FT Spare Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-17
v
APPENDIX A
Model 3095FT Explosion-Proof Installation Drawing, Factory Mutual (Drawing Number 03095-1025, Rev G).
APPENDIX B
APPENDIX C
APPENDIX D
APPENDIX E
APPENDIX F
APPENDIX G
Index of I.S. F.M. for 3095 and Index of I.S. F.M. for 03095-5000 (Drawing Numbers 03095-1020 and 03095-1030).
Model 3095FT Explosion-Proof Installation Drawing, Canadian Standards Association (Drawing Number 03095-1024, Rev D).
Index of I.S. CSA for 3095 and Index of I.S. CSA for 03095-5000 (Drawing Numbers 03095-1021 and 03095-1031).
Software Error Messages
Flow-Cal™ Import Information
Model 3095FT Flow Transmitter HART Commands
vi
Section
1 Introduction
OVERVIEW
USING THIS MANUAL Section 2
Section 3
Section 4
Section 5
This manual provides installation, configuration, calibration, troubleshooting, and maintenance instructions for the Rosemount Model 3095FT HART Flow Transmitter and for its operation with the Model 3095FT User Interface Software.
Initial Checkout and Field Installation explains how to install the Model 3095FT. This includes testing the transmitter, reviewing transmitter configuration data, installation considerations, and field installation.
Options and Accessories presents options such as the LCD meter, mounting brackets, transient protection terminal block, custom configuration, and the remote power supply.
Using the Model 3095FT User Interface Software describes how to use the configuration software. This includes installing the software onto a personal computer, establishing communications with the Model 3095FT, configuring the flow transmitter, creating a configuration file, calibrating the flow transmitter, and retrieving log data from the Model 3095FT. This section also explains each configuration software menu.
Troubleshooting and Maintenance provides troubleshooting instructions for dealing with potential mechanical or electrical difficulties.
®
Section 6
Section 7
Appendices A and B Appendices C and D
Appendix E
Appendix F
Appendix G
Theory of Operation discusses the basic operating principles of the
transmitter.
Specifications and Reference Data includes specification data for the Model 3095FT, the Model 3095FT configuration data sheet (CDS 4015), and spare parts information.
These appendices illustrate Factory Mutual (FM) certified drawings.
These appendices illustrate Canada Standards Association (CSA) certified drawings.
Software Error Messages identifies and explains error messages that might occur while using the Model 3095FT User Interface Software.
Flow-Cal™Import Information explains how to import Model 3095FT logged data into the Flow-Cal software.
Model 3095FT Flow TransmitterHART Commands identifies the HART commands that a control system can use to monitor or configure the Model 3095FT Flow Transmitter.
1-1
Rosemount Model 3095FT HART Flow Transmitter
SYSTEM DESCRIPTION
The Model 3095FT HART Flow Transmitter is an advanced compact electronic gas measurement (EGM) device. Where traditional transmitters measure just one process variable, the Model 3095FT measures three variables simultaneously: differential pressure, absolute pressure, and process temperature. The Multivariable
module incorporates a high-accuracy capacitance sensor for measuring differential pressure, a high-accuracy piezoresistive sensor for measuring absolute pressure, and a four-wire RTD input for process temperature measurement. In addition, the sensor electronics convert the process variables directly into digital format for further correction and compensation within the sensor module.
The Model 3095FT performs American Gas Association flow calculations per A.G.A. Report No. 3 (API MPMS Chapter 14.3 — GPA 8185-92) and A.G.A. Report No. 8 (API MPMS Chapter 14.2), and stores all relevant data in nonvolatile memory in accordance with American Petroleum Institute electronic flow measurement standards (API ­Manual of Petroleum Measurement Standards, Chapter 21.1, “Electronic Gas Measurement”). The three process variables and the
®
flow rate are available at all times via the HART
protocol on a single
two-wire system. Configuring the Model 3095FT is accomplished by using the Model
3095FT User Interface Software, an easy-to-use software package which runs on a DOS-based personal computer (386 and above) running Microsoft
®
Windows.® This software package can include a modem to connect a computer to the Model 3095FT, and provides both configuration capabilities and retrieval capabilities for the Model 3095FT logged data.
FIGURE 1-1. Model 3095FT System.
Solar
Panel
Remote
Power Supply
Enclosure
Personal Computer
(not included)
Finally, the Model 3095FT can be installed in remote locations using a solar power and battery system. Figure 1-1 shows the components of the Model 3095FT system.
Model 3095FT
Model 3095FT
RTD Assembly
RTD Cable
1-2
Section
2 Initial Checkout and
FIGURE 2-1. Model 3095FT Installation Flowchart.
START
Field Installation
This section contains an installation flowchart, information on the Model 3095FT system, installation considerations, and a field installation procedure. The suggested sequence of Model 3095FT installation and wiring is shown in Figure 2-1.
B
FIELD
INSTALLATION
A
Unpackthe Model
3095FT
Review the M odel
3095FT Product
Manual
Hazardous
Location
?
No
Non-
Incendive
Location
?
No
Bench
Configure
?
No
B
Yes
Yes
Yes
Review Rosemount
drawing 03095-1025
or 03095-1024
Review Rosemount
drawings 03095-1020
or 03095-1021
A
BENCH
CONFIGURE
Connect Bench
Power Supply
(Pages 2-14, 2-18)
Connect Personal
Computer
(4-4)
Perform Bench
Configuration
Tasks (4-10)
(Optl.) Perform
BenchCalibration
Tasks (4-11)
B
Review Installation
Considerations
(Pages 2-6 — 2-15)
Mount
Transmitter and
Install Bolts (2-16)
(Optional) Install
RTD Assembly
(2-17)
Remote
Power
Supply
?
No
Make Field Wiring
Connections (2-18 — 2-20)
Bench
Configuration
Performed
?
Yes
Yes
No
Install Remote
Power Supply
(3-7 — 3-13)
Perform
Configuration
Tasks (4-10)
(Optl.) Perform
Field Calibration
Tasks (4-11)
DONE
2-1
Rosemount Model 3095FT HART Flow Transmitter
UNPACKING THE MODEL 3095FT
BECOMING FAMILIAR WITH THE MODEL 3095FT
Depending on the system ordered, the Model 3095FT may arrive in four different shipping containers:
Model 3095FT
This box contains the Model 3095FT. If ordered, this package also contains an RTD cable and optional mounting hardware. One Model 3095FT Flow Transmitter Product Manual is included with each order of transmitters.
User Interface Software Package (Accessory)
The complete user interface package includes one 3.5-in. floppy disk containing the User Interface Software, one HART modem, one set of modem cables, and the Model 3095FT Flow Transmitter Product Manual. User interface components may also be ordered separately.
RTD Assembly (Optional)
This box contains the optional Series 68 or Series 78 RTD Assembly and the Sensor Wiring Instruction Sheet.
Remote Power Supply (Optional)
If the Remote Power Supply package is ordered, this box contains a remote power supply enclosure, battery, and solar panel. If the Battery Backup package is ordered, this box contains the remote power supply enclosure and battery.
Figure 2-2 illustrates a typical Model 3095FT installation site, and Figure 2-3 illustrates the exploded view of the Model 3095FT. Major components of the Model 3095FT System and the Model 3095FT Flow Transmitter are identified in these figures.
FIGURE 2-2. Typical Model 3095FT Installation Site.
Model
3095FT
RTD Connector
Process
Connections
RTD Cable
Solar Panel
Remote Power Supply Enclosure
Remote Power Supply Battery
2-in Pipe Stand (Not Included)
2-2
RTD Assembly
3095-DATAA02A
Initial Checkout and Field Installation
FIGURE 2-3. Exploded View of Model 3095FT Flow Transmitter.
Housing
Terminal Block
O-ring
Cover
Certification Label
Electronics Board
Real Time Clock Battery
Nameplate
Module O-ring
Housing
Locking Screw
RTD Connector
Process Flange O-ring
Flange Adapter O-ring
Flange Adapters
Bolts
Sensor Module
Drain/Vent Valve
Coplanar Flange
3095-3095-A08B
2-3
Rosemount Model 3095FT HART Flow Transmitter
INITIAL INSPECTION
Bench Configuration and Calibration
Write Protect (WP) / Real-Time Clock (RTC) Switches
1. Place the shipping containers on a secure bench and open them, taking care not to damage the contents.
2. Review the packing list to verify that all equipment was received.
3. Inspect the equipment and report any shipping damage to the carrier.
Before mounting the Model 3095FT in the field, the flow transmitter should be configured on the bench using a personal computer and the Model 3095FT User Interface Software.
This software provides advanced configuration capabilities, including flow parameters (such as meter tube bore, orifice bore, orifice plate material, contract hour, DP cut-off, and static pressure type), gas properties (for example, A.G.A. 8 GrHvCO2), and audit trail configuration (such as configuration log, event log, and hourly and daily quantity transaction record).
After bench configuration, the Model 3095FT may be bench calibrated. These procedures include absolute pressure sensor offset and slope trim, and differential pressure sensor offset and slope trim.
For information concerning Model 3095FT bench configuration and Model 3095FT bench calibration, see pages 4-10 and 4-11.
Once the transmitter has been configured, the configuration data can be protected by moving the write protection (WP) switch. When this switch is set to “ON,” the transmitter will not allow any changes to its configuration memory, and will not allow the transmitter to be placed into any Maintenance Mode.
The real-time clock switch (RTC) determines whether the battery powers the real-time clock during power outages. This switch should always be set to “ON” because the real-time clock battery is required for maintaining the internal Model 3095FT clock if transmitter power is interrupted.
When shipped from the factory, the write protect switch is set to “OFF,” and the real-time clock switch is set to “ON” (see Figure 2-4).
NOTE
Setting the real-time clock switch to “OFF” may result in inaccurate time-stamps if power to the Model 3095FT is interrupted. Therefore, always set the real-time clock switch to “ON.”
2-4
Initial Checkout and Field Installation
Use the following steps to change the switch settings:
Explosions can cause death or serious injury. Do not remove the instrument cover in explosive atmospheres when the circuit is alive.
1. If the transmitter is installed, secure the loop, and remove power.
2. Remove the housing cover opposite the field terminal side.
3. Remove the LCD meter if present.
4. Locate the switches on the output electronics board (see Figure 2-4), then move the switch to the desired setting.
Explosions can cause death or serious injury. Both transmitter covers must be fully engaged to meet explosion­proof requirements.
FIGURE 2-4. Write Protect and Real-Time Battery Switches.
5. Reattach the transmitter cover. Metal to metal contact is preferred.
6. If the transmitter is installed, reapply power.
ON OFF
40
WP
RTC
1
ON K
OUTPUT ELECTRONICS BOARD
NOTE Default switch settings are shown.
2-5
Rosemount Model 3095FT HART Flow Transmitter
GENERAL CONSIDERATIONS
MECHANICAL CONSIDERATIONS
The accuracy of a flow or pressure measurement depends to a great extent on proper installation of the transmitter and impulse piping. The piping between the process and transmitter must accurately transmit process pressure to the transmitter. Mount the flow transmitter close to the process and use a minimum of impulse piping to achieve best accuracy. Keep in mind, however, the need for easy access, safety of personnel, practical field calibration, and a suitable transmitter environment. In general, install the transmitter so as to minimize vibration, shock, and temperature fluctuations.
For installations using the Remote Power Supply option, be sure the mounting location is in an area that allows the Remote Power Supply to receive full sun.
The Rosemount Model 3095FT may be panel-mounted, wall-mounted, or attached to a two-inch pipe with an optional mounting bracket. Figure 2-5 illustrates Model 3095FT mounting configurations.Figure 2-6 shows the transmitter dimensions, and Figure 2-6 illustrates example installations.
NOTE
When the transmitter is oriented on its side, the Coplanar
flange may be mounted to ensure proper venting or draining. Mount the flange as shown in Figure 2-6 so that the drain/vent connections are on the bottom half of the flange.
FIGURE 2-5. Mounting Configurations.
6.15
(156)
2.82 (72)
2.81 (71)
4.73
(120)
4.15
(105)
The following paragraphs discuss the factors necessary for a successful transmitter installation.
6.63
(168)
1.28 (33)
3.27 (83)
5.98
(152)
2-6
FIGURE 2-6. Dimensional Drawings of Model 3095FT.
Initial Checkout and Field Installation
Meter Cover
(Optional)
0.75 (19)
Clearance for
Cover Removal
Transmitter
Circuitry
This Side
Nameplate
Drain/Vent
Valve
4.82
(122)
4.15
(105)
6.4
(163)
½–14 NPT on Optional Mounting
Adapters. Adapters Can Be
Rotated to Give Connection Centers
of 2.00 (51), 2.125 (54), or 2.25 (57).
½–14 NPT Conduit
Connection (2 Places)
0.75 (19)
Clearance for
Cover Removal
Transmitter
Connections
This Side
Housing Rotation
Set Screw
3.77 (96)
3.20 (81)
¼–18 NPT on Coplanar Flange
for Pressure Connection
without the Use of
Mounting Adapters
Certification
Label
6.63
(168)
8.08
(198)
3095-3095A05A, B05A
NOTE Dimensions are in inches (millimeters).
FIGURE 2-6. Example Installations.
NOTE Drain vents should be located on lower half of transmitter.
Flow
Flow
3095-3095B03A, D03A
2-7
Rosemount Model 3095FT HART Flow Transmitter
Taps
Impulse Piping
For gas flow measurement, place taps in the top or side of the line and mount the transmitter beside or above the taps so liquid will drain into the process line.
The piping between the process and the transmitter must accurately transfer the pressure to obtain accurate measurements. In this pressure transfer, three possible sources of error can occur: leaks, friction loss, and liquid in the impulse line.
Consider the following general rules in determining flow transmitter location and placement of impulse piping:
• Keep impulse piping as short as possible.
• Slope the impulse piping at least one inch per foot (8 centimeters per meter) downward from the transmitter toward the process connection.
• Avoid low points in gas lines.
• Use impulse piping large enough to avoid friction effects and prevent blockage.
• Keep corrosive or hot (above 185 °F (85 °C)) process material out of direct contact with the sensor module and flanges.
• Prevent sediment deposits in the impulse piping.
• Avoid conditions that might allow process fluid to freeze within the process flange.
Environmental Considerations
Access Requirements
Process Flange Orientation The process flanges must be oriented to enable process connections to
Housing Rotation The electronics housing may be rotated to improve field access to the
Mount the transmitter to minimize ambient temperature changes. Section 7 - Specifications and Reference Data lists the transmitter temperature operating limits. Mount the transmitter to avoid vibration and mechanical shock, and to avoid external contact with corrosive materials.
When choosing an installation location and position, take into account the need for access to the transmitter.
be made. In addition, consider the possible need for a testing or calibration input.
Drain/vent valves must be oriented so that process fluid is directed away from technicians when the valves are used.
two compartments. To rotate the housing less than 90 degrees, release the housing rotation set screw and turn the housing not more than 90 degrees from the orientation shown in Figure 2-6 on Page 2-7. To rotate the housing greater than 90 degrees, follow steps 1–6 of the disassembly procedure on page 5-10.
2-8
Rotating the housing greater than 90 degrees without performing the disassembly procedure may damage the Model 3095FT sensor module.
Initial Checkout and Field Installation
Terminal Side of Electronics Housing
Circuit Side of Electronics Housing
Process Considerations
Wiring connections are made through the conduit openings on the top side of the housing. The field terminal side is marked on the electronics housing. Mount the transmitter so that the terminal side is accessible. A 0.75-inch clearance is required for cover removal. Install a conduit plug on the unused side of the conduit opening.
The circuit compartment should not routinely need to be opened when the unit is in service; however, provide 0.75 inches clearance if possible to allow access. A 3-inch clearance is required for cover removal if a meter is installed. See Section 3 - Options.
Model 3095FT process connections on the transmitter flange are 1/4–18
1
NPT. Flange adapter unions with
/2–14 NPT connections are supplied as options. These are Class 2 threads; use your plant-approved lubricant or sealant when making the process connections. The process
1
connections on the transmitter flange are on 2
/8-inch (54-mm) centers
to allow direct mounting to a three- or five-valve manifold. By rotating
1
one or both of the flange adapters, connection centers of 2, 2
/8, or 21/4
inches (51, 54, or 57 mm) may be obtained.
Failure to install proper flange adapter O-rings can cause process leaks, which can result in death or serious injury.
There are two styles of Rosemount flange adapters, each requiring a unique O-ring, as shown below. Each flange adapter is distinguished by its unique groove.
MODEL 3051/2024/3001/3095
Flange Adapter
O-ring
Unique O-ring
Grooves
Flange Adapter
O-ring
MODEL 1151
Use only the O-ring designed to seal with the corresponding flange adapter. Refer to the Spare Parts List on Page 7-17 for the correct part numbers of the flange adapters and O-rings designed for the Model 3095FT Flow Transmitter.
®
When compressed, Teflon
O-rings tend to cold flow, which aids in their sealing capabilities. Whenever flanges or adapters are removed, visually inspect the Teflon O-rings. Replace them if there are any signs of damage, such as nicks or cuts. If they are undamaged, they may be reused. If the O-rings are replaced, the flange bolts may need to be retorqued after installation to compensate for cold flow. Refer to the process sensor body reassembly procedure on page 5-15.
2-9
Rosemount Model 3095FT HART Flow Transmitter
Mounting Considerations
The Model 3095FT Flow Transmitter total weight varies depending on the components ordered (see Table 2-1). This weight must be securely supported.
TABLE 2-1. Transmitter Weight.
Component Weight
Model 3095FT Without Options 6 lb (2.7 kg)
LCD Meter for Aluminum Housing 0.5 lb (0.2 kg)
SST Mounting Bracket for Coplanar Flange 1.0 lb (0.5 kg)
12 ft (3.66 m) cable 0.5 lb (0.2 kg)
24 ft (7.32 m) cable 2.2 lb (1.0 kg)
Remote Power Supply 20 lb (9 kg)
Mounting Brackets Optional mounting brackets available with the Model 3095FT facilitate
mounting to a panel, wall, or 2-inch pipe. The bracket option for use with the Coplanar flange is 316 SST with 316 SST bolts. Figure 2-7 shows bracket dimensions and mounting configurations for this option.
When installing the transmitter to one of the mounting brackets, torque the bolts to 125 in-lb.
Mounting Pressure Effect The transmitter is calibrated in an upright position at the factory. If
this orientation is changed during mounting, the resulting mounting pressure effects can be corrected by using the field calibration procedure described on page 4-29.
2-10
Initial Checkout and Field Installation
Bolt Installation Guidelines
The following guidelines have been established to ensure a tight flange, adapter, or manifold seal. Use only bolts supplied with the transmitter or sold by Rosemount Inc. as a spare part to the Model 3095FT transmitter.
The Model 3095FT is shipped with the Coplanar flange installed with four 1.75-inch flange bolts. The following bolts also are supplied to facilitate other mounting configurations:
• Four 2.25-inch manifold/flange bolts for mounting the Coplanar flange on a three-valve manifold. In this configuration, the 1.75­inch bolts may be used to mount the flange adapters to the process connection side of the manifold.
• (Optional) If flange adapters are ordered, four 2.88-inch flange/ adapter bolts for mounting the flange adapters to the Coplanar flange.
Figure 2-7 shows the optional mounting bracket and mounting configurations. Figure 2-8 shows mounting bolts and bolting configuration for the Model 3095FT with the coplanar flange.
Stainless steel bolts supplied by Rosemount Inc. are coated with a lubricant to ease installation. Carbon steel bolts do not require lubrication. No additional lubricant should be applied when installing either type of bolt. Bolts supplied by Rosemount Inc. are identified by their head markings:
Steel Head Markings (CS)
teel Head Markings (SST)
316
B7M
316
R
B8M
STM
316 316
SW 316
2-11
Rosemount Model 3095FT HART Flow Transmitter
FIGURE 2-7. Optional Mounting Bracket and Mounting Configurations.
5
/16 x11/2 Bolts
forPanel Mounting
2.81 (71)
3
/8-16x11/4 Bolts
for Mounting
to Transmitter
3.35 (85)
(Not Supplied)
2-Inch U-Bolt
for Pipe Mounting
3051-3051D04A, E04A
2.82 (72)
4.15
(105)
6.15
(156)
2.81 (71)
4.73
(120)
PANEL MOUNT CONFIGURATION
NOTE Dimensions are in inches (millimeters).
6.63
(168)
1.28 (33)
3.27 (83)
5.98
(152)
OPTIONAL MOUNTING BRACKET (OPTION CODE B4) SHOWN IN TYPICAL
MOUNTING CONFIGURATION
3051A04A, B04A, C04A
2-12
FIGURE 2-8. Coplanar Mounting Bolts and Bolting Configurations for Coplanar Flange.
1.75 (44) x 4 TRANSMITTER WI TH
FLANGE BOLTS
Description Qty.
Flange bolts Flange/adapter bolts Manifold/flange bolts
4 4 4
Initial Checkout and Field Installation
Size in. (mm)
1.75 (44)
2.88 (73)
2.25 (57)
2.88 (73) x 4
TRANSMITTER WITH OPTIONAL FLANGE ADAPTERS AND FLANGE/ADAPTER BOLTS
NOTE Dimensionsare in inches (millimeters).
2.25 (57) x 4
1.75 (44) x 4
TRANSMITTER WITH 3-VALVE MANIFOLD
MANIFOLD/FLANGE BOLTS
FLANGE ADAPTERS
AND FLAN GE/ADAPTER BOLTS
3095-3095D05A, 3095E05A, 3095B29A
2-13
Rosemount Model 3095FT HART Flow Transmitter
ELECTRICAL CONSIDERATION
Power Supply
The signal terminals are located in a compartment of the electronics housing separate from the transmitter electronics. Figure 2-9 illustrates power supply load limitations for the transmitter.
The dc power supply should provide power with less than 2% ripple. The total resistance load is the sum of the resistance of the signal leads and the load resistance of the controller, indicator, and related pieces. Note that the resistance of intrinsic safety barriers, if used, must be included.
NOTE
A minimum loop resistance of 250 ohms is required to communicate with a personal computer. With 250 ohms of loop resistance, the transmitter requires a minimum of 11.0 volts.
If a single power supply is used to power more than one Model 3095FT transmitter, the power supply used, and circuitry common to the transmitters, should not have more than 20 ohms of impedance at 1200 Hz.
If the Remote Power Supply enclosure is installed, a 250 ohm resistor is factory installed — do not add additional loop resistance.
1964
Load (Ohms)
250
0
7.5 11.0
Maximum loop resistance is de termined by the voltage of the external power supply, as described by
:
Max. Loop Resistance
Communication requires a minimum loop resistance of 250 ohms.
Operating Region
Power Supply Voltage
35
Power Supply Voltage 7.5
-------------------------------------------------------------------
0.014
2-14
Initial Checkout and Field Installation
Inductive-based transient protectors, including the Rosemount Model 470, can adversely affect the output of the Model 3095FT. Do not use the Model 470 for transient protection with the Model 3095FT. If transient protection is desired, install the Transient Protection Terminal Block as explained on Page 3-5.
HAZARDOUS LOCATIONS
FIELD INSTALLATION EQUIPMENT
The Model 3095FT was designed with an explosion-proof housing and circuitry suitable for intrinsically safe and non-incendive operation. Individual transmitters are clearly marked with a tag indicating the certifications they carry. See Section 7 - Specifications and Reference Data for specific approval categories, and see Appendices A through D for approval drawings.
The following equipment and tools are not provided with the Model 3095FT. Be sure to review this list before field installing the transmitter.
• Installation tools
• Field wire between the power supply and the Model 3095FT
• Barriers or seals required for non-incendive or hazardous locations
•Conduit
• 2-in. mounting pipe or saddles
• Power supply (unless the Remote Power Supply was ordered)
• 3- or 5-valve manifolds
• Impulse piping
•Tie wraps
• Lock for the remote power supply enclosure.
2-15
Rosemount Model 3095FT HART Flow Transmitter
FIELD INSTALLATION PROCEDURE
1. Review Installation Considerations
2. Mount Transmitter and Install Bolts
For explosion-proof installations, installation location must be made in accordance with Rosemount drawing 03095­1025 or 03095-1024.
For instrinsically safe installations, installation location must be made in accordance with Rosemount drawings 03095-1020 and 03095-1030; or 03095-1021 and 03095-1031.
1. Review the installation considerations described on pages 2-6 through 2-15 in this chapter to determine the location for the Model 3095FT. If the installation includes the Remote Power Supply, also review the sunlight considerations described on page 3-8.
2. Mount the Model 3095FT in the desired location, and install flange or flange/adaptor bolts.
TABLE 2-2. Bolt Installation Torque Value s.
3. Make Process Connections
Only use bolts supplied with the Model 3095FT or sold by Rosemount Inc. as a spare part to the Model 3095FT. Unauthorized parts can affect product performance and may render the instrument dangerous.
a.Finger-tighten the bolts. b.Torque the bolts to the initial torque value using a cross-pattern
(see Table 2-2).
c. Torque the bolts to the final torque value using the same cross-
pattern.
Bolt Material Initial TorqueValue Final Torque Value
Carbon Steel (CS) 300 in-lb 650 in-lb
Stainless Steel (SST) 150 in-lb 300 in-lb
When installing the transmitter to one of the mounting brackets, torque the mounting bracket bolts to 125 in-lb.
3. Connect the transmitter to the process.
2-16
Process leaks can cause death or serious injury. All four flange bolts must be installed and tight before applying pressure, or process leakage will result. When properly installed, the flange bolts will protrude through the top of the module housing. Attempting to remove the flange bolts while the transmitter is in service will result in leakage of the process fluid.
Initial Checkout and Field Installation
4. Install RTD Assembly
FIRST FULLY ENGAGE THE BLACK CABLE CONNECTOR
SCREW IN AND TIGHTEN THE CABLE ADAPTER UNTIL METAL TO METAL CONTACT OCCURS
4.(Optional) Install the Series 68 or Series 78 RTD Assembly. a.Mount the RTD Assembly in the desired location in accordance
ith AGA Report No. 3/API MPMS Chapter 14.3, Part 2.
b.Connect the RTD cable to the Model 3095FT RTD connector as
illustrated in the following photos.
SCREW IN AND TIGHTEN THE STRAIN RELIEF CLAMP
Compression Fitting
¾ to ½–in. NPT Adapter (Screws into RTD Connection Head)
c. (Optional) If using an armored, shielded cable, install the
armored cable compression seal as illustrated below, and use a pliers to tighten the cap onto the compression fitting.
Rubber Bushing (Slide stop to edge of armored cable)
Washer
Cap
RTD Cable Adapter and Connector (Connects to Model 3095FT)
3095-069AB, 068AB, 067AB
3095-0020D01A
2-17
Rosemount Model 3095FT HART Flow Transmitter
d.Make all necessary wiring connections inside the RTD Flat
Connection Head as explained in the Sensor Wiring Instructions included with the RTD.
NOTE
If you are using two- or three-wire RTD connections, jump together the extra RTD wires.
5. Check for Leaks
6. Field Wiring (Po wer and Signal)
5. Check all process penetrations for leaks.
NOTE
If the installation includes either the Remote Power Supply (Part No. 03095-5000-101x) or the Battery Backup (Part No. 03095-5000-200x), do not perform Steps 6 through 9 that follow. Instead, complete installation as explained in Section 3 (Remote Power Supply—see pages 3-7 through 3-12; Battery Backup—see pages 3-14 through 3-16).
6. Make field wiring connections (see Figure 2-10). These connections provide both power and signal wiring.
For explosion-proof installations, wiring connections must be made in accordance with Rosemount drawing 03095­1025 or 03095-1024.
For instrinsically safe installations, wiring connections must be made in accordance with ANSI/ISA-RP12.6, and Rosemount drawings 03095-1020 or 03095-1031.
For ALL installations, wiring connections must follow the National Electric Code.
2-18
NOTES
• Do not run field wiring in conduit or open trays with other power wiring, or near heavy electrical equipment.
• Field wiring need not be shielded, but twisted pairs should be used for best results.
• To ensure communication, wiring should be 24 AWG or larger and not exceed 5,000 feet (1,500 meters).
• For connections in ambient temperatures above 140 °F (60 °C), use wiring rated for at least 194 °F (90 °C).
Incorrect field wiring connections may damage the Model 3095FT. Do not connect field wiring to the “TEST +” terminals.
Loading...
+ 154 hidden pages