Rosemount Manual: Rosemount 3051S Series of Instrumentation – Section 6: Advanced Pressure Diagnostics for Foundation Fieldbus Manuals & Guides

Reference Manual
00809-0200-4801, Rev CA July 2010
Rosemount 3051S
Section 6 Advanced Pressure Diagnostics
for F
Statistical Process Monitoring Technology . . . . . . . . . . . page 6-2
SPM Configuration and Operation . . . . . . . . . . . . . . . . . . page 6-6
Plugged Impulse Line Detection Technology . . . . . . . . . page 6-17
Configuration of Plugged Impulse Line Detection . . . . . page 6-25
OUNDATION fieldbus
OVERVIEW The 3051S FOUNDATION fieldbus Pressure Transmitter with Advanced
Diagnostics Suite is an extension of the Rosemount 3051S Scalable Pressure transmitter and takes full advantage of the architecture. The 3051S SuperModule™ Platform generates the pres sur e mea su rem en t. The Foundation fieldbus Feature Board is mounted in the PlantWeb housing and plugs into the top of the SuperModule. The Advanced Diagnostics Suite is a licensable option on the Foundation fieldbus feature board, and designated by the option code “D01” in the model number.
The Advanced Diagnostics Suite has two distinct diagnostic functions, Statistical Process Monitoring (SPM) and Plugged Impulse Line Detection (PIL), which can be used separately or in conjunction with each other to detect and alert users to conditions that were previously undetectable, or provide powerful troubleshooting tools. Figure 6-1 illustrates an overview of these two functions within the Fieldbus Advanced Diagnostics Transducer Block.
Figure 6-1. Advanced Diagnostics Transducer Block Overview
www.rosemount.com
Rosemount 3051S
Reference Manual
00809-0200-4801, Rev CA
July 2010
Statistical Process Monit oring (SPM)
The Advanced Diagnostics Suite features SPM technology to detect changes in the process, process equipment or installation co nditions of the tr ansmitter. This is done by modeling the process noise signature (using the statistical values of mean and standard deviation) under normal conditions and then comparing the baseline values to current values over time. If a significant change in the current values is detected, the transmitter can generate an alert. The SPM can perform its statistical processing on either the primary value of the field device (e.g. pressure measurement) or any other process variable available in one of the device’s other Fieldbus function blocks (e.g. the device sensor temperature, control signal, valve position, or measurement from another device on the same fieldbus segment). SPM has the capability of modeling the noise signatures for up to four process variables simultaneously (SPM1-SPM4). When SPM detects a change in the process statistical characteristics, it generates an alert. The statistical values are also available as secondary variables from the transmitter via AI or MAI Function Blocks if a user is interested in their own analysis or generating their own alarms.
Plugged Impulse Line (PIL) Diagnostics
STATISTICAL PROCESS MONITORING TECHNOLOGY
The Advanced Diagnostics Suite also implements a plugged impulse line detection algorithm. PIL leverages SPM technolo gy and adds some additional features that apply SPM to directly detect plugging in pressure measurement impulse lines. In addition to detecting a change in the process noise signature, the PIL also provides the ability to automatically relearn new baseline values if the process condition changes. When PIL detects a plug, a “Plugged Impulse Line Detected” PlantWeb alert is generated. Optionally, the user can configure the PIL to, when a plugged impulse line is detected, change the pressure measurement status quality to “Uncertain”, to alert an operator that the pressure reading may not be reliable.
IMPORTANT
Running the Advanced Diagnostics Block could affect other block execution times. We recommend the device be configured as a basic device versus a Link Master device if this is a concern.
Emerson has developed a unique technolog y, Statistical Process Monitoring, which provides a means for early detection of abnormal situations in a process environment. The technology is based on the premise that virtually all dynamic processes have a unique noise or variation signature when operating normally. Changes in these signatures may signal that a significant change will occur or has occurred in the process, process equipment, or transmitter installation. For example, the noise source may be equipment in the process such as a pump or agitator, the natural variation in the DP value caused by turbulent flow, or a combination of both.
6-2
Reference Manual
00809-0200-4801, Rev CA July 2010
Figure 6-2. Changes in process noise or variability and affect on statistical parameters
Rosemount 3051S
The sensing of the unique signature begins with the combination of a high speed sensing device, such as the Rosemount 3051S Pressure Transmitter, with software resident in a F statistical parameters that characterize and quantify the noise or variation. These statistical parameters are the mean and stand ard deviation of the inp ut pressure. Filtering capability is provided to separate slow changes in the process due to setpoint changes from the process noise or variation of interest. Figure 6-2 shows an example of how the standard deviation value () is affected by changes in noise level while the mean or average value () remains constant. The calculation of the statistical parameters within the device is accomplished on a parallel software path to the path used to filter and compute the primary output signal (e.g. the pressure measurement used for control and operations). The primary output is not affected in any wa y by this additional capability.
OUNDATION fieldbus Feature Board to compute
The device can provide the statistical information to the user in two ways. First, the statistical parameters can be made available to the host system directly via Foundation fieldbus communication protocol or FF to other protocol converters. Once available, the system may make use of these statistical parameters to indicate or detect a change in proce ss conditions. In the simplest example, the statistical values may be stored in the DCS historian. If a process upset or equipment problem occurs, these values can be examined to determine if changes in the values foreshadowed or indicated the process upset. The statistical values can then be made available to the operator directly, or made available to alarm or alert software.
Second, the device has internal software that can be used to baseline the process noise or signature via a learning process. Once the learning process is completed, the device itself can detect significant changes in the noise or variation, and communicate an alarm via PlantWeb alert. Typical applications are change in fluid composition or equipment related problems.
6-3
Reference Manual
00809-0200-4801, Rev CA
Rosemount 3051S
July 2010
SPM Functionality A block diagram of the Statistical Process Monitoring (SPM) diagnostic is
shown in Figure 6-3. Note from Figure 6-1 that the 3051S FF has four Statistical Process Monitoring blocks (SPM1-SPM4). Figure 6-3 illustrates just one of the SPM blocks. The process variable (which could be either the measured pressure or some other vari able from the fieldbus segment) is input to a Statistical Calculations Module where basic high pass filtering is performed on the pressure signal. The mean (or ave rage) is calculated on the unfiltered pressure signal, the standard deviation calculated from the filtered pressure signal. These statistical values are available via handheld communication devices like the 375 Field Communicator or asset management software like Emerson Process Management’s AMS Manager, or distributed control systems with Foundation fieldbus, such as DeltaV.
Figure 6-3. Diagram of 3051S FF Statistical Process Monitoring
Device
SPM also contains a learning module that establishes the baseline values for the process. Baseline values are established under user control at conditions considered normal for the process and installation . These baseline values are made available to a decision module that compar es the baseline values to the most current values of the mean and standard deviation. Based on sensitivity settings and actions selected by the user via the control input, the diagnostic generates a device alert when a significant change is detected in either mean or standard deviation.
6-4
Reference Manual
00809-0200-4801, Rev CA July 2010
Figure 6-4. Flow Chart of 3051S FF Statistical Process Monitoring
Rosemount 3051S
Further detail of the operation of the SPM diagnostic is shown in the Figure 6-4 flowchart. This is a simplified version showing operation using the default values. After configuration, SPM calculates mean and standard deviation, used in both the learning and the monitor ing modes. Once enabled, SPM enters the learning/verification mode. The baseline mean and standard deviation are calculated over a period of time controlled by the user (SPM Monitoring Cycle; default is 15 minutes). The status will be “Learning”. A second set of values is calculated and compared to the original set to verify that the measured process is stable and repeatable. During this period, the status will change to “Verifying”. If the process is st able, the diagnostic will use the last set of values as baseline values and move to “Monitoring” status. If the process is unstable, the diagnostic will continue to verify until stability is achieved.
In the “Monitoring” mode, new mean and standard deviation values are continuously calculated, with new values available every few seconds. The mean value is compared to the baseline mean value, and the standard deviation is compared to the baseline standard deviation value. If either the mean or the standard deviation has changed more than user-defined sensitivity settings, an alert is generated via F may indicate a change in the process, equipment, or transmitter installation.
OUNDATION fieldbus. The alert
6-5
Rosemount 3051S
Reference Manual
00809-0200-4801, Rev CA
July 2010
NOTE:
The Statistical Process Monitoring diagnostic capability in the Rosemount 3051S F significant changes in statistical parameters derived from the input process variable. These statistical parameters relate to the variability of and the noise signals present in the process variable. It is difficult to predict specifically which noise sources may be present in a given measurement or control application, the specific influence of those noise sources on the statistical parameters, and the expected changes in the noise source s at any tim e. Therefore, Rosemount cannot absolutely warrant or guarantee that Statistical Process Monitoring will accurately detect each specific condition under all circumstances.
OUNDATION fieldbus Pressure Transmitte r calculates and detects
SPM CONFIGURATION AND OPERATION
SPM Configuration for Monitoring Pressure
The following section describes the process of configuring and using the Statistical Process Monitoring diagnostic.
Most Advanced Diagnostics Applications require using the device’s pressure measurement as the SPM input. To configure the first SPM Block (SPM1) to monitor the pressure set the following parameters:
SPM1_Block_Tag = TRANSDUCER
NOTE:
By default, as shipped from the factory, the tag of the sensor transducer block is “TRANSDUCER”. DeltaV does not change the transducer block tags when the device is installed and commissioned. However, it is possible that other Fieldbus host systems may change the transducer block tags. If this h appens, SPM#_Block_Tag must be set to whatever tag was assigned by the host.
SPM1_Block_Type = TRANSDUCER Block SPM1_Parameter_Index = Pressure (inH SPM1_User_Command = Learn (optional) SPM_Monitoring_Cycle = [1 – 5] minutes (see “Other SPM
Settings” on page 6- 7) (optional) SPM_Bypass_Verification = [Yes/No] (see page 6-7) Apply all of these above changes to the device. Finally, set
O @ 68 °F)
2
6-6
SPM_Active = Enabled with 1st-order HP Filter After SPM is enabled, it will spend the first 5 (whatever the
SPM_Monitoring_Cycle is set to) minutes in the learning phase, and then another 5 minutes in the verification phase. If a steady pro cess is detected at the end of the verification phase, the SPM will move into the monitoring phase. After 5 minutes in the monitoring phase, SPM will have the current statistical values (e.g. current mean and standard deviation), and will begin comparing them against the baseline values to determine if an SPM Alert is detected.
Reference Manual
00809-0200-4801, Rev CA July 2010
Rosemount 3051S
SPM Configuration for Monitoring Other Process Variables
Advanced users may wish use SPM to monitor other Fieldbus parameters available within the pressure transmitter . Exam ples of such p arameters would include module sensor temperature, PID control output, valve position, or a process measurement from another device on the same Fieldbus segment. Configuration of SPM for other process variables is similar to what is done for pressure, except that the Block Tag, Block Type, and Parameter Index parameters are different.
Note that # should be replaced by the num ber of the SPM block which yo u are configuring (1, 2, 3, or 4).
SPM#_Block_Tag
The tag of the Fieldbus transducer or function block that contains the parameter to be monitored. Note that the tag must be entered manually – there is no pull-down menu to select the tag. SPM can also monitor “out” parameters from other devices. To do this, link the “out” parameter to an input parameter of a function block that resides in the device, and se t up SPM to monitor the input parameter.
SPM#_Block_Type
The type of block which was entered into SPM#_Block_Tag. This could be either a Transducer block, or one of the function blocks.
SPM#_Parameter_Index
The parameter (e.g. OUT, PV, FIELD_VAL) of the transducer or function block which you want to monitor.
See “Example Configuration of SPM using Function Block” on page 6-12 for an example of this using DeltaV.
Other SPM Settings Additional information on other SPM settings is shown below:
SPM_Bypass_Verification
If this is set to “Y es”, SPM will skip the verification process, and the first mean and standard deviation from the learning phase will be taken as the baseline mean and standard deviation. By skippi ng the verification, the SPM can move into the monitoring phase more quickly. This parameter should only be set to “Yes” if you are certain that the process is at a steady-state at the time you start the Learning. The default (and recommended) setting is “No”.
SPM_Monitoring_Cycle
This is the length of the sample window over which mean and standard deviation are computed. A shorter sample window means that the statistical values will respond faster when there are process changes, but there is also a greater chance of generating false detections. A longer sample window means that mean and standard deviation will take longer to respond when there is a process change. The default value is 15 minutes. For most applications a Monitoring Cycle ranging from 1 to 10 minutes is appropriate. The allowable range is 1 to 1440 minutes (for software revisions 2.0.x or earlier, the minimum SPM Monitoring Cycle is 5 minutes).
Figure 6-5 illustrates the effect of the SPM Monitoring Cycle on the Statistical Calculations. Notice how with a shorter sampling window there is more variation (e.g. the plot looks noisier) in the trend. With the longer sampling window the trend looks smoother because the SPM uses process data averaged over a longer period of time.
6-7
Rosemount 3051S
Figure 6-5. Effect of the SPM Monitoring Cycle on the Statistical Values
Reference Manual
00809-0200-4801, Rev CA
July 2010
SPM#_User_Command
Select “Learn” after all the parameters have been configured to beg in the Learning Phase. The monitoring phase will start automatically after the learning process is complete. Select “Quit” to stop th e SPM . “Det ec t” m ay be selected to return to the monitoring phase.
SPM_Active
The SPM_Active parameter starts the Statistical Process Monitoring when “Enabled”. “Disabled” (default) turns the diagnostic monitoring off. Must be set to “Disabled” for configuration. Only set to “Enabled” after fully co nfiguring the SPM. When Enabling SPM, you may select one of two options:
Enabled with 1st-Order HP Filter
Applies a high-pass filter to the pre ssu re me asur eme nt prio r to calcu lating standard deviation. This removes the effect of slow or gradual process changes from the standard deviation calcul ation while preserving the higher-frequency process fluctuations. Using the high-pass filter reduces the likelihood of generating a false detection if there is a normal process or setpoint change. For most diagnostics applications, you will want to use the filter.
Enabled w/o Filter
This enables SPM without applying the high-pass filter. Without the filter, changes in the mean of the process variable will cause an increase in the standard deviation. Use this option only if there are very slow process changes (e.g. an oscillation with a long period), which you wish to monitor using the standard deviation.
Configuration of Alerts In order to have SPM generate a PlantWeb alert, the alert limits must be
configured on the mean and/or standard deviation. The three alert limits available are:
6-8
SPM#_Mean_Lim
Upper and lower limits for detecting a Mean Change
SPM#_High_Variation_Lim
Upper limit on standard deviation for detecting a High Variation condition
Reference Manual
00809-0200-4801, Rev CA July 2010
Rosemount 3051S
SPM#_Low_Dynamics_Lim
Lower limit on standard deviation for detecting a Low Dynamics condition (must be specified as a negative number)
All of these limits are specified as a percent change in the statistical value from its baseline. If a limit is set to 0 (the default setting) then the corresponding diagnostic is disabled. Fo r ex am p le, if SPM#_High_Variation_Limit is 0, then SPM# does not detect an increase in standard deviation.
Figure 6-6 illustrates an example of the standard deviation, with its baseline value and alert limits. During the monitoring phase, the SPM will continuously evaluate the standard deviation and compare it against the baseline value. An alert will be detected if the standard deviation either goes above the upper alert limit, or below the lower alert limit.
In general, a higher value in any of these limits leads to the SPM diagnostic being less sensitive, because a greater change in m ean or st andard d eviation is needed to exceed the limit. A lower value makes the diagnostic more sensitive, and could potentially lead to false detections.
Figure 6-6. Example Alerts for Standard Deviation
SPM Operations During operation, the following values are updated for each SPM Block (e.g.
SPM1-SPM4)
SPM#_Baseline_Mean
Baseline Mean (calculated average) of the process variable, determined during the Learning/Verification process, and representing the normal operating condition
SPM#_Mean
Current Mean of the process variable
SPM#_Mean_Change
Percent change between the Baseline Mean and the Current Mean
SPM#_Baseline_StDev
Baseline Standard Deviation of the process variable, determined during the Learning/Verification process, and representing the normal operating condition
6-9
Rosemount 3051S
Reference Manual
00809-0200-4801, Rev CA
July 2010
SPM#_StDev
Current Standard Deviation of the process variable
SPM#_StDev_Change
Percent change between the Baseline Standard Deviation and the Current Standard Deviation
SPM#_Timestamp
Timestamp of the last values and status for the SPM
SPM#_Status
Current state of the SPM Block. Possible values for SPM Status are as follows:
Status Value Description
Inactive User Command in “Idle”, SPM not Enabled, or the function block is
not scheduled.
Learning Learning has been set in the User Command, and the initial
baseline values are being calculated
Verifying Current baseline values and previous baseline values or being
compared to verify the process is stable. Monitoring Monitoring the process and no detections are currently active. Mean Change Detected Alert resulting from the Mean Change exceeding the Threshold
Mean Limit. Can be caused by a set point change, a load change
in the flow, or an obstruction or the removal of an obstruction in the
process. High Variation Detected Alert resulting from the Stdev Change exceeding the Threshold
High Variation value. This is an indicator of increased dynamics in
the process, and could be caused by increased liquid or gas in the
flow, control or rotational problems, or unstable pressure
fluctuations. Low Dynamics Detected Alert resulting from the Stdev Change exceeding the Threshold
Low Dynamics value. This is an indicator for a lower flow, or other
change resulting in less turbulence in the flow. Not Licensed SPM is not currently purchased in this device.
In most cases, only one of the above SPM status bits will be active at one time. However, it is possible for “Mean Change Detected” to be active at the same time as either “High Variation Detected” or “Low Dynamics Detected” is active.
PlantWeb Alert When any of the SPM detections (Mean Change, High Variation, or Low
Dynamics) is active, a Fieldbus PlantWeb alert in the device “Process Anomaly Detected (SPM)” will be generated and sent to the host system. However, note that there is just one SPM PlantWeb alert, and it applies to all the detections on all four SPM blocks.
Trending Statistical V a lues in Control System
6-10
SPM Mean and St andard Deviation values may be viewed and/or trended in a Fieldbus host system through the AI or MAI function blocks.
An Analog Input (AI) block may be used to read either the mean or the standard deviation from any one of the SPM Blocks. To use the AI block to trend SPM data, set the CHANNEL parameter to one of the following values:
Loading...
+ 22 hidden pages