Rosemount Manual: Rosemount 3051S Electronic Remote Sensors Manuals & Guides

Reference Manual
00809-0100-4804, Rev DA
May 2018
Rosemount™ 3051S Electronic Remote Sensor
(ERS)
System
Reference Manual
00809-0100-4804, Rev DA
Contents
1Section 1: Introduction
2Section 2: Installation
Contents
May 2018
1.1 Using this manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.2 Product recycling/disposal. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
2.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.2 Safety messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.3 Models covered . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.4 Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.4.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.4.2 Mechanical. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.4.3 Environmental. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.5 Installation procedures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.5.1 Identify Rosemount ERS Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.5.2 Mount each Rosemount ERS Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.5.3 Process connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.5.4 Consider housing orientation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.5.5 Configure security and alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2.5.6 Connect wiring and power up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.5.7 Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
2.6 Rosemount manifolds. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
2.6.1 Rosemount 305 Manifold installation procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
2.6.2 Rosemount 304 Manifold installation procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
2.6.3 Rosemount 306 Manifold installation procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
2.6.4 Manifold valve configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
3Section 3: Configuration
3.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
3.2 Safety messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Content s
3.2.1 Setting the loop to manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
3.3 Wiring diagrams. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
3.4 Basic setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
3.4.1 Device tagging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
3.4.2 Units of measure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
3.4.3 Damping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Contents
May 2018
Reference Manual
00809-0100-4804, Rev DA
3.4.4 Variable mapping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
3.4.5 Analog output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
3.4.6 Alarm and saturation levels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
3.5 Additional configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
3.5.1 Local display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
3.5.2 Burst mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
3.5.3 Multidrop communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
3.5.4 Scaled variable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
3.5.5 Module assignments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
3.5.6 Process alerts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
3.6 HART menu trees. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
4Section 4: Operation and Maintenance
4.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
4.2 Safety messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
4.3 Calibration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
4.3.1 Calibration overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
4.3.2 PHI and PLO sensor calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
4.3.3 DP calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
4.3.4 Analog output trim . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
4.3.5 Recall factory trim . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
4.4 Functional tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
4.4.1 Find device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
4.5 Field upgrades and replacements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
4.5.1 Disassembly considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
4.5.2 Labeling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
4.5.3 Remove the terminal block. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
4.5.4 Removing the electronics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
4.5.5 Remove the SuperModule from the housing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
4.5.6 Attach the SuperModule to the housing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
4.5.7 Install electronics assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
4.5.8 Install the terminal block. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
4.5.9 Reassemble the process flange . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
5Section 5: Troubleshooting
5.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
5.2 Device overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
ii
Contents
Reference Manual
00809-0100-4804, Rev DA
6Section 6: Safety Instrumented Systems Requirements
AAppendix A: Reference Data
Contents
May 2018
5.2.1 HART host diagnostics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
5.2.2 LCD display diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
5.3 Measurement quality status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
5.4 Service support. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
6.1 Safety Instrumented Systems (SIS) Certification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
6.1.1 Rosemount ERS Systems safety certified identification . . . . . . . . . . . . . . . . . . . . . . . . . . 61
6.1.2 Installation in SIS applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
6.1.3 Configuring in SIS applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
6.1.4 Rosemount 3051S SIS operation and maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
6.1.5 Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
A.1 Product Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
A.2 Ordering Information, Specifications, and Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Content s
iii
Contents
May 2018
Reference Manual
00809-0100-4804, Rev DA
iv
Contents
Reference Manual
NOTICE
00809-0100-4804, Rev DA
Rosemount™ 3051S Electronic Remote Sensor (ERS)™ System
Read this manual before working with the product. For personal and system safety, and for optimum product performance, make sure you thoroughly understand the contents before installing, using, or maintaining this product.
For technical assistance, contacts are listed below:
Customer Central
Technical support, quoting, and order-related questions.
Americas 1 800 999 9307
Europe +41 (0) 41 768 6111
Middle east +971 4 811 8100
Asia +65 6777 8211
North American Response Center
Equipment service needs.
1-800-654-7768 (24 hours—includes Canada)
Outside of these areas, contact your local Emerson
representative.
Title Page
May 2018
Title Page
The products described in this document are NOT designed for nuclear-qualified applications. Using non-nuclear qualified products in applications that require nuclear-qualified hardware or products may cause inaccurate readings.
For information on Rosemount nuclear-qualified products, contact your local Emerson Sales Representative.
v
Title Page
May 2018
Reference Manual
00809-0100-4804, Rev DA
Failure to follow these installation guidelines could result in death or serious injury.
Make sure only qualified personnel perform the installation.
Explosions could result in death or serious injury.
Do not remove the housing covers in explosive atmospheres when the circuit is live. Before connecting a Field Communicator in an explosive atmosphere, make sure the instruments in
the loop are installed in accordance with intrinsically safe or non-incendive field wiring practices.
Both housing covers must be fully engaged to meet flameproof/explosion-proof requirements. Verify the operating atmosphere of the transmitter is consistent with the appropriate hazardous
location certifications.
Electrical shock could cause death or serious injury.
If the Rosemount ERS System is installed in a high-voltage environment and a fault or installation
error occurs, high voltage may be present on the sensor leads and terminals.
Use extreme caution when making contact with the leads and terminals.
Process leaks could result in death or serious injury.
Install and tighten all four flange bolts before applying pressure. Do not attempt to loosen or remove flange bolts while the Rosemount ERS System is in service. Replacement equipment or spare parts not approved by Emerson for use as spare parts could reduce
the pressure retaining capabilities of the transmitter and may render the instrument dangerous.
Use only bolts supplied or sold by Emerson as spare parts.
Improper assembly of manifolds to traditional flange can damage the device.
For the safe assembly of the manifold to the sensor flange, bolts must break the back plane of the flange web (i.e. bolt hole) but must not contact the sensor module.
Static electricity can damage sensitive components.
Observe safe handling precautions for static-sensitive components.
vi
Title Page
Reference Manual
00809-0100-4804, Rev DA

Section 1 Introduction

1.1 Using this manual

Introduction
May 2018
The sections in this manual provide information on installing, operating, and maintaining a Rosemount™ 3051S Electronic Remote Sensor (ERS)™ System with HART organized as follows:
Section 2: Installation contains mechanical and electrical installation instructions, and field upgrade
options.
Section 3: Configuration provides instruction on commissioning and operating a Rosemount ERS
System. Information on software functions, configuration parameters, and online variables is also included.
Section 4: Operation and Maintenance contains operation and maintenance techniques.
Section 5: Troubleshooting provides troubleshooting techniques for the most common operating
problems.
Section 6: Safety Instrumented Systems Requirements contains all certification and operation
information for SIS applications.
Appendix A: Reference Data supplies reference and specification data as well as ordering information.

1.2 Product recycling/disposal

Recycling of equipment and packaging should be taken into consideration and disposed of in accordance with local and national legislation/regulations.
®
protocol. The sections are
Introduction
1
Introduction
May 2018
Reference Manual
00809-0100-4804, Rev DA
2
Introduction
Reference Manual
00809-0100-4804, Rev DA

Section 2 Installation

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3
Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3
Models covered . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4
Installation procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 8
Rosemount manifolds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 21

2.1 Overview

This section covers installation considerations for the Rosemount™ 3051S Electronic Remote Sensor
(ERS)
System. A Quick Start Guide is shipped with every Rosemount 3051S ERS Transmitter to describe basic installation, wiring, configuration, and startup procedures. Dimensional drawings for each Rosemount 3051S ERS Transmitter are included in Product Data Sheet
Installation
May 2018
.

2.2 Safety messages

Procedures and instructions in this section may require special precautions to ensure the safety of personnel performing the operation. Information that raises potential safety issues is indicated with a
warning symbol ( ). Refer to the following safety messages before performing an operation preceded by this symbol.
Failure to follow these installation guidelines could result in death or serious injury.
Make sure only qualified personnel perform the installation.
Explosions could result in death or serious injury.
Do not remove the housing covers in explosive atmospheres when the circuit is live. Before connecting a Field Communicator in an explosive atmosphere, make sure the instruments in
the loop are installed in accordance with intrinsically safe or non-incendive field wiring practices.
Both housing covers must be fully engaged to meet flameproof/explosion-proof requirements. Verify the operating atmosphere of the transmitter is consistent with the appropriate hazardous
location certifications.
Electrical shock could cause death or serious injury.
If the Rosemount ERS System is installed in a high-voltage environment and a fault or installation
error occurs, high voltage may be present on the sensor leads and terminals.
Use extreme caution when making contact with the leads and terminals.
Installation
3
Installation
May 2018
Reference Manual
00809-0100-4804, Rev DA
Process leaks could result in death or serious injury.
Install and tighten all four flange bolts before applying pressure. Do not attempt to loosen or remove flange bolts while the Rosemount ERS System is in service. Replacement equipment or spare parts not approved by Emerson
reduce the pressure retaining capabilities of the transmitter and may render the instrument dangerous.
Use only bolts supplied or sold by Emerson as spare parts.
Improper assembly of manifolds to traditional flange can damage the device.
For the safe assembly of the manifold to the sensor flange, bolts must break the back plane of the flange web (i.e. bolt hole) but must not contact the sensor module.
Static electricity can damage sensitive components.
Observe safe handling precautions for static-sensitive components.
for use as spare parts could

2.3 Models covered

The Rosemount ERS System is a flexible, 2-wire HART® architecture that calculates differential pressure (DP) electronically, using two pressure sensors. The pressure sensors are linked together with an electrical cable and synchronized to create a single Rosemount ERS System. The sensors used in the Rosemount ERS System can consist of any combination of Rosemount 3051SAM and 3051SAL models. One of the sensors is required to be a “Primary” and the other is required to be a “Secondary.”
The Primary sensor contains the 4–20 mA loop termination and optional LCD display. The Secondary sensor is made up of a pressure sensor module and junction box housing that is connected to the primary sensor, using a standard instrument cable.
Rosemount 3051SAM Scalable™ ERS Measurement Transmitter
Coplanar and In-Line sensor module platformsVariety of process connections including NPT, flanges, manifolds, and Rosemount 1199 Remote
Diaphragm Seals
Rosemount 3051SAL Scalable ERS Level Transmitter
Integrated transmitter and remote diaphragm seal in a single model numberVariety of process connections including flanged, threaded, and hygienic remote diaphragm seals
Rosemount 300ERS Housing Kit
Upgrade and convert an existing Rosemount 3051S Transmitter into a Rosemount 3051S ERS
Transmitter.
Easily order replacement housings and electronics for an existing Rosemount ERS System.
4
Installation
Reference Manual
Rosemo unt
3051SAM In-Line
(Secondary)
Rosemount 3051SAL Coplanar
with FF Seal (Primary)
Rosemount 3051SAM
In-Line (Primary)
Rosemount 3051SAL Coplanar
with FF Seal (Secondary)
Rosemo unt
3051SAM In-Line
(Secondary)
Rosemount 3051SAL Coplanar with
FF Seal and Remote Display
(Primary)
00809-0100-4804, Rev DA
Figure 2-1. Rosemount ERS Models and Possible Configurations

2.4 Considerations

Installation
May 2018
2.4.1 General
Measurement performance depends upon proper installation of each transmitter and impulse piping. Mount each Rosemount 3051S ERS Transmitter close to the process and use minimum piping to achieve best performance. Also, consider the need for easy access, personnel safety, practical field calibration, and a suitable environment. Install each sensor to minimize vibration, shock, and temperature fluctuation.
Note
Install the enclosed pipe plugs (found in the box) in any unused conduit openings. For proper straight and tapered thread engagement requirements, see the appropriate approval drawings in Product Data
Sheet. For material compatibility considerations, see Material Selection Technical Note.
2.4.2 Mechanical
For dimensional drawing information, refer to Product Data Sheet.
For steam service or for applications with process temperatures greater than the limits of each Rosemount 3051S ERS Transmitter, do not blow down impulse piping through either sensor. Flush lines with the blocking valves and refill lines with water before resuming measurement.
If a Rosemount 3051S ERS Transmitter is mounted on its side, position the flange/manifold to ensure proper venting or draining.
Field terminal side of housing
Installation
Mount each Rosemount ERS Sensor so the terminal side is accessible. Clearance of 0.75-in. (19 mm) is required for cover removal.
Electronics side of housing
Provide 0.75-in. (19 mm) of clearance for units without an LCD display. Three inches of clearance is required for cover removal if an LCD display is installed.
5
Installation
A
B
May 2018
Reference Manual
00809-0100-4804, Rev DA
Cover installation
Always ensure a proper seal by installing the housing covers so that metal contacts metal in order to prevent performance degradation due to environmental effects. For replacement cover O-rings, use Rosemount O-rings (part number 03151-9040-0001).
Conduit entry threads
For NEMA® 4X, IP66, and IP68 requirements, use thread seal (PTFE) tape or paste on male threads to provide a watertight seal.
Cover jam screw
For housings shipped with a cover jam screw (as shown in Figure 2-2), the screw should be properly installed once the Rosemount ERS System has been wired and powered up. The cover jam screw is intended to prevent the removal of the housing covers in flameproof environments without the use of tools. Follow these steps to install the cover jam screw:
1. Verify the cover jam screw is completely threaded into the housing.
2. Install the housing covers and verify that metal contacts metal in order to meet
flameproof/explosion-proof requirements.
3. Using an M4 hex wrench, turn the jam screw counterclockwise until it contacts the housing cover.
4. Turn the jam screw an additional
excessive torque may strip the threads.
5. Verify the covers cannot be removed.
Figure 2-2. Cover Jam Screw
Plantweb
A. 2 Cover jam screw (one per side) B. Cover jam screw
housing Junction Box housing
1
/2 turn counterclockwise to secure the cover. Application of
2.4.3 Environmental
Access requirements and cover installation can help optimize transmitter performance. Mount each transmitter to minimize ambient temperature changes, vibration, mechanical shock, and to avoid external contact with corrosive materials.
6
Installation
Reference Manual
START HERE
Device Tagging
No
Bench
Commissioning?
Yes
Field Installation
Run “Basic Setup”
Wizard
Units of Measure and
Damping
Variable Mapping
4 and 20 mA Range
Points
Alarm and Saturation
Levels
Ver ify
Review Rosemount
ERS System
Configuration
Verif y PHI and PLO
Designations
Apply Pressure
No
Bench
Commissioning?
Yes
Refer to Section 4:
Operation and
Maintenance
Identify PHI and PLO
Rosemount ERS
Sensors
Mount Each
Rosemount ERS
Sensor
Consider Housing
Rotation
Set Switches
Connect Wiring and
Apply Power
Tri m R ose mo un t E RS
System for Mounting
Effects
Finish
00809-0100-4804, Rev DA
Note
The Rosemount ERS System contains additional electrical protection that is inherent to the design. As a result, ERS Systems cannot be used in applications with floating electrical grounds greater than 50 Vdc (such as Cathodic Protection). Consult an Emerson Sales Representative for additional information or considerations on use in similar applications.
Figure 2-3. Rosemount 3051S ERS Installation Flowchart
Installation
May 2018
Installation
7
Installation
OR
May 2018

2.5 Installation procedures

2.5.1 Identify Rosemount ERS Sensors
A complete Rosemount ERS System contains two pressure sensors. One is mounted on the high-pressure (P
connection. An optional remote display and interface may also be included if ordered.
1. Look at the wire-on tag on the Rosemount 3051S ERS Transmitter to identify whether it is configured
as the P
2. Locate the second sensor that will be used in the Rosemount ERS System:
For new installations or applications, the second Rosemount ERS Sensor may have been shipped in a
separate box.
If servicing or replacing part of an existing Rosemount ERS System, the other sensor may already be
installed.
Note
Rosemount 3051S ERS Transmitters are shipped from the factory preconfigured such that the primary unit (4–20 loop termination and optional LCD display) is assigned as the P unit (junction box housing) is assigned as the P transmitter is installed on the P may switched electronically using a HART Communicator (see “Local display” on page 30).
HI
) process connection, and the other is mounted on the low-pressure (PLO) process
HI
or PLO sensor (see Figure 2-4).
sensor. In installations where there the primary
process connection (such as at the top of a tank), these designations
LO
LO
Reference Manual
00809-0100-4804, Rev DA
sensor and the secondary
HI
Figure 2-4. Rosemount ERS PHI and PLO Wire-On Tags
2.5.2 Mount each Rosemount ERS Sensor
Mount the PHI and PLO sensors at the correct process connections for the application. Common Rosemount ERS installations are shown in Figure 2-5.
Vertical installation
In a vertical installation such as on a vessel or distillation column, the PHI sensor should be installed at the bottom process connection. The P
8
sensor should be installed at the top process connection.
LO
Installation
Reference Manual
A
B
B
A
Pressure Drop
00809-0100-4804, Rev DA
Horizontal installation
In a horizontal installation, the PHI sensor should be installed at the upstream process connection. The
sensor should be installed downstream.
P
LO
Figure 2-5. Vertical and Horizontal Rosemount ERS Installations
Installation
May 2018
Installation
A. PLO sensor B. P
sensor
HI
Mounting brackets
Mounting brackets are available to facilitate mounting the transmitter to a 2-in. pipe or to a panel. The B4 SST bracket option is for use with coplanar and in-line process connections. Figure 2-6 on page 11 shows dimensions and mounting configuration for the B4 bracket. Other bracket options are listed in
Ta bl e 2 -1 .
When installing a Rosemount 3051S ERS Transmitter to one of the optional mounting brackets, torque the bolts to 125 in-lb. (0,9 N-m).
Table 2-1. Mounting Brackets
Options Description Mounting type Bracket material Bolt material
B4 Coplanar flange bracket 2-in. pipe/panel SST SST
B1 Traditional flange bracket 2-in. pipe Painted carbon steel Carbon steel
B2 Traditional flange bracket Panel Painted carbon steel Carbon steel
B3 Traditional flange flat bracket 2-in. pipe Painted carbon steel Carbon steel
B7 Traditional flange bracket 2-in. pipe Painted carbon steel SST
9
Installation
Carbon Steel (CS) Head Markings
B7M
316
B8M
F
Stainless Steel (SST) Head Markings
* The last digit in the F593_ head marking may
be any letter between A and M.
F593_*
KM
660
CL A
Alloy K-500 Head Marking
May 2018
Reference Manual
00809-0100-4804, Rev DA
Table 2-1. Mounting Brackets
Options Description Mounting type Bracket material Bolt material
B8 Traditional flange bracket Panel Painted carbon steel SST
B9 Traditional flange flat bracket 2-in. pipe Painted carbon steel SST
BA Traditional flange bracket 2-in. pipe SST SST
BC Traditional flange flat bracket 2-in. pipe SST SST
Flange bolts
An Rosemount 3051S ERS Transmitter can be shipped with a coplanar flange or a traditional flange installed with four 1.75-in. flange bolts. Mounting bolts and bolting configurations for the coplanar and traditional flanges can be found on Tabl e 2-2 . Stainless steel bolts supplied by Emerson are coated with a lubricant to ease installation. Carbon steel bolts do not require lubrication. No additional lubricant should be applied when installing either type of bolt. Bolts supplied by Emerson are identified by their head markings:
Bolt installation
Only use bolts supplied with the Rosemount 3051S ERS Transmitter or sold by Emerson as spare parts. Use the following bolt installation procedure:
1. Finger-tighten the bolts.
2. Torque the bolts to the initial torque value using a crossing pattern. For initial torque values, see
Ta bl e 2 - 2.
3. Torque the bolts to the final torque value using the same crossing pattern. For final torque values, see
Ta bl e 2 - 2.
Torque values for the flange and manifold adapter bolts are as follows:
Table 2-2. Bolt Installation Torque Values
Bolt material Option code Initial torque value Final torque value
CS-ASTM-A449 Standard 300 in.-lb (34 N-m) 650 in.-lb (73 N-m)
316 SST Option L4 150 in.-lb (17 N-m) 300 in.-lb (34 N-m)
ASTM-A-193-B7M Option L5 300 in.-lb (34 N-m) 650 in.-lb (73 N-m)
Alloy K-500 Option L6 300 in.-lb (34 N-m) 650 in.-lb (73 N-m)
ASTM-A-453-660 Option L7 150 in.-lb (17 N-m) 300 in.-lb (34 N-m)
ASTM-A-193-B8M Option L8 150 in.-lb (17 N-m) 300 in.-lb (34 N-m)
10
Installation
Reference Manual
A
B
C
A
D
A
B
C
D
00809-0100-4804, Rev DA
Figure 2-6. Common Rosemount 3051S ERS Transmitter/Flange Assemblies
Installation
May 2018
Transmitter with coplanar
flange
A. 1.75 in. (44 mm) ⫻ 4 B. 1.75 in. (44 mm) ⫻ 2
Transmitter with coplanar
flange and flange adapters
C. 2.88 in. (73 mm) ⫻ 2 D. 1.5 in. (38 mm) ⫻2
Transmitter with traditional flange
and flange adapters
2.5.3 Process connections
The process connection size on a Rosemount 3051S ERS Transmitter flange is 1/4–18-in. NPT. Flange adapters with a plant-approved lubricant or sealant when making the process connections. For other level flange type connection options, reference the Rosemount 1199 Reference Manual
Install and tighten all four flange bolts before applying pressure to avoid leakage. When properly installed, the flange bolts will protrude through the top of the sensor module isolator plate. See
Figure 2-7. Do not attempt to loosen or remove the flange bolts while the transmitter is in service.
Figure 2-7. Sensor Module Isolator Plate
A. Bolt B. Sensor module isolator plate C. Coplanar flange D. Flange adapters
1
/4–18 NPT to 1/2–14 NPT connection are available with the D2 option. Use a
.
Installation
11
Installation
May 2018
Reference Manual
00809-0100-4804, Rev DA
To install adapters to a coplanar flange, perform the following procedure:
1. Remove the flange bolts.
2. Leaving the flange in place, move the adapters into position with the O-rings installed.
3. Attach the adapters and the coplanar flange to the transmitter sensor module assembly using the
longer of the bolts supplied.
4. Tighten the bolts. Refer to Table 2-2 on page 10 for torque specifications.
Use only the O-rings included with the flange adapter for the Rosemount 3051S ERS Transmitter. Failure to install proper fitting flange adapter O-rings may cause process leaks, which can result in death or serious injury.
When removing flanges or adapters, visually inspect the PTFE O-rings. Replace them if there are any
signs of damage such as nicks or cuts. If replacing O-rings, re-torque the flange bolts after installation to compensate for seating of the PTFE O-ring.
Impulse piping
The piping between the process and each Rosemount 3051S ERS Transmitter must accurately transfer the pressure to obtain accurate measurements. There are many possible sources of error: pressure transfer, leaks, friction loss (particularly if purging is used), trapped gas in a liquid line, liquid in a gas line, and plugged impulse lines.
The best location for each Rosemount 3051S ERS Transmitter depends on the process itself. Use the following guidelines to determine sensor location and placement of impulse piping:
Keep impulse piping as short as possible.For liquid service, slope the impulse piping at least 1 inch per foot (8 cm per m) upward from the
transmitter toward the process connection.
For gas service, slope the impulse piping at least 1 inch per foot (8 cm per m) downward from the
transmitter toward the process connection.
Avoid high points in liquid lines and low points in gas lines. When purging, make the purge connection close to the process tap and purge through equal lengths
of the same size pipe. Avoid purging through either Rosemount 3051S ERS Transmitter.
Keep corrosive or hot (above 250 °F or 121 °C) process material out of direct contact with the sensor
module process connection and flanges.
Prevent sediments from depositing in the impulse piping.
Note
Take necessary steps to prevent process fluid from freezing with the process flange to avoid damage to each Rosemount 3051S ERS Transmitter.
12
Note
Verify the zero point on each Rosemount 3051S ERS Transmitter after installation. To reset the zero trim, refer to “Calibration overview” on page 44.
Installation
Reference Manual
A
A
00809-0100-4804, Rev DA
2.5.4 Consider housing orientation
Housing rotation
The housing can be rotated to improve access to wiring or to better view the LCD display (if ordered). To rotate the housing, perform the following procedure:
1. Loosen the housing set screw.
2. Turn the housing up to 180° to the left or right of its original (as shipped) position.
Note
Do not rotate the housing more than 180° from its original position without first performing a disassembly procedure (see page 49). Over rotation may sever the electrical connection between the sensor module and the electronics feature board.
3. Retighten the housing rotation set screw.
Figure 2-8. Housing Rotation
Plantweb housing Junction box housing
Installation
May 2018
Installation
A. Housing rotation set screw (3/32-in.)
LCD display rotation
In addition to rotating the housing, the optional LCD display on the primary Rosemount ERS Sensor can be rotated in 90° increments by squeezing the two tabs, pulling out the display, rotating, and snapping the display back into place.
Note
If the LCD display pins are inadvertently removed from the electronics feature board, re-insert the pins before snapping the LCD display back into place.
13
Installation
B
A
May 2018
2.5.5 Configure security and alarm
Security switch
Changes to the Rosemount ERS System configuration can be prevented with the security (write protect) switch, which is located on the electronics feature board of the Rosemount 3051S ERS Primary Transmitter. See Figure 2-9 for the location of the switch. Position the switch in the “ON” position to prevent accidental or deliberate change to the Rosemount ERS System configuration.
If the write protect switch is in the “ON” position, the Rosemount ERS System will not accept any “writes” to its memory. Configuration changes, such as digital trim and reranging, cannot take place when the security switch is set to “ON.”
Alarm direction
The alarm direction of the analog output of the Rosemount ERS System is set by repositioning the alarm switch, which is located on the electronics feature board of the primary transmitter. Position the switch in the “HI” position to have the Rosemount ERS System go to high alarm in a fail condition, or position the switch in the “LO” position to have the system go to low alarm in a fail condition. See “Alarm and
saturation levels” on page 29 for more information on alarm and saturation levels.
Switch configuration procedure
Reference Manual
00809-0100-4804, Rev DA
To reposition the hardware switches, follow the procedure below:
1. Do not remove the housing covers in explosive atmospheres when the circuit is live. If the Rosemount
3051S ERS System is live, set the loop to manual and remove power.
2. On the Rosemount 3051S ERS Primary Transmitter, remove the housing cover opposite the field
terminal side.
3. Reposition the alarm and security switches as desired, by using a small screwdriver.
4. Reinstall the housing cover. Covers must be fully engaged so the metal contacts metal in order
to meet flameproof/explosion-proof requirements.
Figure 2-9. Alarm and Security Switches
A. Security switch B. Alarm switch
14
Installation
Reference Manual
00809-0100-4804, Rev DA
2.5.6 Connect wiring and power up
Typical Rosemount ERS System
1. Remove the housing cover labeled “Field Terminals” on both Rosemount 3051S ERS Transmitter.
2. Using the Rosemount ERS Madison Cable (if ordered) or an equivalent 4-wire shielded assembly per
the specifications detailed on page 16, connect the 1, 2, A, and B terminals between the two sensors per Figure 2-10. Maintain uniform twist in wires as close as possible to the screw terminals.
3. Connect the Rosemount ERS System to the control loop by wiring the “+” and “–” PWR/COMM
terminals of the Rosemount 3051S ERS Primary Transmitter to the positive and negative leads, respectively.
4. Plug and seal all unused conduit connections.
5. If applicable, install wiring with a drip loop. Arrange the drip loops so the bottom is lower than the
conduit connections and the transmitter housings.
6. Reinstall and tighten the housing covers on both sensors so metal contacts metal to meet
explosion-proof requirements.
Rosemount 3051S ERS System with optional remote display and interface
Installation
May 2018
1. Remove the housing cover labeled “Field Terminals” on both Rosemount ERS Sensors and the remote
housing.
2. Using the Rosemount ERS Madison Cable (if ordered) or an equivalent 4-wire shielded assembly per
the specifications detailed on page 16, connect the 1, 2, A, and B terminals between the two sensors and remote housing in a “tree” (Figure 2-11) or daisy-chain (Figure 2-12) configuration. Maintain uniform twist in wires as close as possible to the screw terminals.
3. Connect the Rosemount ERS System to the control loop by wiring the “+” and “–” PWR/COMM
terminals of the remote housing to the positive and negative leads, respectively.
4. Plug and seal all unused conduit connections.
5. If applicable, install wiring with a drip loop. Arrange the drip loops so the bottom is lower than the
conduit connections and the transmitter housings.
6. Reinstall and tighten all housing covers so metal contacts metal to meet explosion-proof
requirements.
Note
I.S. barriers with inductive loads greater than 1 mH should not be used with the Rosemount ERS System and may cause the device to not function properly.
Installation
15
Installation
May 2018
Reference Manual
00809-0100-4804, Rev DA
Rosemount 3051S ERS System cable specifications
Cable type: Recommend gray Madison 04ZZXLF015 cable, blue Madison 04ZZXLF021 cable, and
Southwire HLX-SPOS two pairs armor cable. Other comparable cable may be used as long as it has independent dual twisted shielded pair wires with an outer shield. The power wires (pin terminals 1 and 2) must be 22 AWG minimum and the communication wires (pin terminals A and B) must be 24 AWG minimum.
Maximum cable length: The total length of cable used to connect the ERS primary transmitter,
secondary transmitter, and remote display (if ordered) should not exceed maximum lengths below.
Madison (gray cable): up to 500 ft. (152,4 m) for non-IS applications and 225 ft. (68,58 m) for IS
applications; consult Emerson for applications requiring beyond 500 ft.
Madison (blue cable): up to 225 ft. (68,58 m) for IS applicationsArmored cable: up to 125 ft. (38,1 m)
For SIS maximum lengths see “Rosemount ERS Systems safety certified identification” on page 61Cable capacitance: The capacitance between the communication lines as wired must be less than
5000 pF total. This allows up to 50 pF per ft. (164 pF/m) for a 100-ft. cable.
Gray and blue cable outside diameter: 0.270-in. (6.86 mm)
Armor cable outside diameter: 0.76-in. (19.3 mm)
For armored cable, cable glands are included with the packaging
4–20 mA loop wiring specifications
It is recommended to use twisted pair wiring. To ensure proper communication, use 24 to 14 AWG wire, and do not exceed 5000 ft. (1500 m).
Note
There are four connections plus shield, which require correct configuration for operation. There is no mechanism that can result in re-sequencing of messages from the physical connections.
Surges/transients
The Rosemount 3051S ERS System will withstand electrical transients of the energy level usually encountered in static discharges or induced switching transients. However, high-energy transients, such as those induced in wiring from nearby lightning strikes, can damage the Rosemount ERS System.
Optional transient protection terminal block
The transient protection terminal block can be ordered as an installed (option code T1) or as a spare part to retrofit an existing Rosemount ERS System in the field. A lightning bolt symbol on a terminal block identifies it as having transient protection.
Note
The transient terminal block is only available as an option on the primary Rosemount 3051S ERS Transmitter. When ordered and installed, a primary Rosemount 3051S ERS Transmitter with the transient terminal block will protect the entire Rosemount ERS Assembly including the secondary Rosemount 3051S ERS Transmitter.
16
Power supply requirements
The DC power supply should provide power with less than two percent ripple. The total loop resistance is the sum of the resistance from the signal leads and the load resistance of the controller, indicator, and related pieces. Note that the resistance of intrinsically safe barriers, if used, must be included.
Installation
Loading...
+ 56 hidden pages