The purpose of this document is to provide guidelines on how to change from other manufacturer’s
devices to Rosemount equipment by exchanging gauges. When a gauge is replaced with a Rosemount
gauge, it is necessary to configure the Rosemount 2410 Tank Hub for emulation.
The Rosemount field devices, for example Rosemount 5900 Radar Level Gauge and Rosemount 2240S
Temperature Transmitter, are connected to the tank hub using the intrinsically safe Tankbus as usual.
Emulation is done in the tank hub only. Each tank hub can emulate up to 10 tanks (10 separate
gauges)
(1)
.
Figure 1. Rosemount Devices Replacing Old Gauges in an Existing Sakura System
1.Tank hub version “Multiple tanks” can emulate up to 10 tanks (10 gauges). Tank hub version “Single tank” can emulate up to 2 tanks (2 gauges).
Rosemount 2410 Tank Hub
July 2017
1.1Emulation capabilities
Emulation enables the replacement of old devices with Rosemount devices in another vendor’s existing
tank gauging system. The Rosemount device will perform just like the replaced gauge, using the other
vendor’s protocol to communicate.
By using the other vendor’s field and control room communication protocol with modern Rosemount
tank gauging devices, the legacy system can be modernized step-by-step. The legacy system can be
upgraded while tanks are in operation and existing wiring can be re-used.
Tank hub acting as slave
When an old gauge from another vendor is replaced with a tank hub connected to a Rosemount field
device, the tank hub will act as a slave answering requests and sending data upwards towards the host.
A stepwise “bottom-up” upgrade is done by replacing legacy gauges to begin with, and changing the
complete control system at a later occasion.
Figure 2. Tank Hub Slave Emulation
Manual Supplement
00809-0800-2410, Rev AA
1.2Sakura system characteristics
Sakura protocol overview
The tank hub supports two versions of the Sakura protocol: Sakura MDP and Sakura V1, each supporting
all 10 tank positions. The tank hub automatically detects which protocol to use, based on the received
requests from the Sakura host.
The Sakura MDP protocol is sometimes also called “old Sakura protocol” or Sakura binary. The Sakura
MDP protocol includes one request type.
The Sakura V1 protocol is sometimes called “new Sakura protocol” or Sakura ASCII. The Sakura V1
protocol includes several request types. The tank hub identifies the request type, and replies with the
corresponding response type.
2
Rosemount 2410 Tank Hub
Manual Supplement
00809-0800-2410, Rev AA
Sakura response data
Rosemount 2410 Tank Hub
July 2017
The tank hub can emulate up to 10 tank positions
(1)
. Ta bl e 1 shows supported response data for the
Sakura MDP and Sakura V1 protocols.
Table 1. Sakura Protocol Response Data
Sakura MDPSakura V1
Level
Ullage
Average liquid temperature
Average vapor temperature
Sixteen spot temperatures
Free water level
Pressure (Vapor, middle or liquid)
Alarm status
Observed density
1. Max 3 tank positions.
(1)
Electrical interface and protocol
Table 2. Sakura Electrical Interface and Protocol Options
ProtocolElectrical interface
Sakura MDP
Sakura V1
Sakura Non-IS 2-wire bus
1.Tank hub version “Multiple tanks” can emulate up to 10 tanks (10 gauges). Tank hub version “Single tank” can emulate up to 2 tanks (2 gauges).
Rosemount 2410 Tank Hub
3
Rosemount 2410 Tank Hub
Ta nk M as t er™ PC
Primary bus:
TRL2/(RS485 Modbus)
Secondary bus:
Sakura MDP/V1
FBM/
(RS485 converter)
Sakura
converter
Sakura host
Tank hub with configuration on primary field bus and
Sakura emulation on secondary field bus
July 2017
1.3Rosemount 2410 Tank Hub communication
The tank hub has slots for two independent communication boards, primary and secondary field bus, for
TRL2 Modbus
The Sakura interface can be connected to the Rosemount 2410 secondary field bus.
The primary bus can be used for regular TRL2 or RS485 Modbus communication. Configuration is
performed with a TRL2 modem, like the Rosemount 2180 Field Bus Modem (FBM), or a RS485 converter
connected to the primary field bus.
Figure 3. Sakura Emulation on Secondary Field Bus
®
, RS485 Modbus, emulation or wireless communication.
Manual Supplement
00809-0800-2410, Rev AA
4
Rosemount 2410 Tank Hub
Manual Supplement
Secondary field bus
Primary field bus
00809-0800-2410, Rev AA
2.0Electrical installation
Rosemount 2410 Tank Hub
July 2017
Rosemount 2410 Tank Hub connections
(1)
Figure 4. Terminal Block in the Explosion-Proof/Flameproof Compartment
Table 3. Terminal Assignment for Non-Intrinsically Safe Side
11S Bus BSecondary communication bus - (Sakura X-wire)
12S Bus ASecondary communication bus + (Sakura Y-wire)
PEPEPower supply protective ground
GND_1GND_1Housing chassis/shield Primary bus
GND_2GND_2Housing chassis/shield Secondary bus
1.Consult the Sakura Electrical Installation Drawing (D7000003-779) for further information.
Rosemount 2410 Tank Hub
5
Rosemount 2410 Tank Hub
July 2017
3.0Configuration
The Rosemount 2410 Tank Hub is configured by using the TankMaster WinSetup configuration
program
well as advanced configuration and service functions.
Configuration of the Rosemount 2410 Sakura emulation function can be performed with the WinSetup
program using the FBMor a RS485 converter, depending on the tank hub configuration.
3.1Set up Modbus communication protocol
This section describes how to configure the Modbus Master protocol channel for communication.
To specify PC communication port and the standard communication parameters, do the following:
1.Open the Protocols folder in the Workspace window.
2.Select the Modbus Master icon.
(1)
. WinSetup is a user-friendly software package that includes basic configuration options as
Manual Supplement
00809-0800-2410, Rev AA
3.Right click the proper MBMaster icon and select Properties to configure the protocol channel.
4.Select the Communication tab.
1.See the Rosemount Tank Gauging System Configuration Manual for more information on how to use the TankMaster WinSetup software to configure the
Rosemount 2410 Tank Hub.
6
Rosemount 2410 Tank Hub
Manual Supplement
00809-0800-2410, Rev AA
5.Set the communication parameters:
Rosemount 2410 Tank Hub
July 2017
FBMRS485 converter
Port
Baud rate
Stop bits
Parity
Modem
Handshaking
Reply timeout
Retries
Description
The COM port the FBM is
connected to
48009600
11
NoneNone
FBM 2180RS-485
NoneRTS/CTS
1000 ms1000 ms
33
Text describing the configured
channel
The COM port the converter is
connected to
Text describing the configured
channel
6.Select the Enable Channel check box to activate the protocol channel.
7.Select OK to store the current configuration and close the configuration window.
3.2Install Rosemount 2410 Tank Hub in WinSetup
The TankMaster WinSetup wizard is the recommended tool for installing the tank hub. The installation
wizard manages basic configuration of the tank hub.
Perform the following steps to start the installation wizard in TankMaster WinSetup:
1.In the Workspace window select the Devices folder.
2.Right click and select Install New or, from the Service menu, select the Devices/Install New option.
The Select Device window opens.
Rosemount 2410 Tank Hub
7
Rosemount 2410 Tank Hub
July 2017
3.From the Device Type drop-down list, select the 2410 Tank Hub option.
4.Type a name on the 2410 HUB Tag field.
The 2410 Hub Tag will be used as an identifier for the tank hub in various windows and dialogs.
5.Select Next. The 2410 Tank Hub Communication window opens.
Manual Supplement
00809-0800-2410, Rev AA
6.Ensure TankMaster communicates directly with the tank hub and that the proper communication