Rosemount Manual: OCX 8800 O2 / Combustibles Transmitter General Purpose with Remote Electronics-Rev 1.3 | Rosemount Manuals & Guides

Reference Manual
00809-0300-4880, Rev AA
July 2018
Rosemount
Combustibles Transmitter
General Purpose Probe with Remote Electronics
TM
Reference Manual
4880, Rev AA
July 2018
OCX 8800
TOC-2
00809-0300-
SECTION 1 Description and Specifications
SECTION 2 Installation
SECTION 3 Configuration and Startup
Table of Contents
Essential Instructions ........................................................................................ i
Preface ............................................................................................................... ii
Definitions .......................................................................................................... ii
Symbols .............................................................................................................. ii
Component Checklist ................................................................................... 1-1
System Overview .......................................................................................... 1-1
Specifications ..............................................................................................1-12
Mechanical
Installation ...................................................................................................... 2-2
Electrical Installation ..................................................................................... 2-8
Pneumatic Installation ................................................................................2-14
Initial Startup ................................................................................................2-20
Verify Installation ........................................................................................... 3-1
Initial Power Up ............................................................................................. 3-3
Set Test Gas Values .................................................................................... 3-4
OCX 8800 Reset Procedure ....................................................................... 3-4
SECTION 4 Using HART Communications
SECTION 5 Calibration
SECTION 6 Maintenance and Service
Overview ........................................................................................................ 4-1
Field Communicator Sig na l Conn ec tio ns .................................................. 4-1
Field Communicator PC Connections ........................................................ 4-4
HART Menu Tree .......................................................................................... 4-5
D/A Trim Procedures .................................................................................... 4-9
Overview ........................................................................................................ 5-1
Fully Automatic Calibration .......................................................................... 5-1
Operator - Initiated Autocalibration ............................................................ 5-3
Manual Calibration ........................................................................................ 5-3
Overview ........................................................................................................ 6-1
OCX 8800 Removal
and Installation .............................................................................................. 6-1
OCX with
Remote Electronics ................................................................................. 6-2
Repair Sensor Housing ................................................................................ 6-8
Sensor Housing Disassembly ............................................................... 6-8
Sensor Housing Assembly .................................................................. 6-18
Repair Electronics Housing ...................................................................... 6-28
Electronics Housing Disassembly ..................................................... 6-28
Reference Manual
July 2018
OCX 8800
00809-0300-4880, Rev AA
Electronics Housing Assembly ........................................................... 6-30
Replace Tube Fittings ................................................................................6-34
Remove Tube Fittings ..........................................................................6-34
Install Tube Fittings ...............................................................................6-35
SECTION 7 Troubleshooting
SECTION 8 Replacement Parts
APPENDIX A Safety Data
APPENDIX B SPA with HART Alarm
APPENDIX C Return of Materials
Overview ........................................................................................................ 7-1
Grounding ................................................................................................. 7-1
Electrical Noise ........................................................................................ 7-1
Electrostatic Discharge........................................................................... 7-1
Total Power Loss .................................................................................... 7-2
Diagnostic Alarms ......................................................................................... 7-2
Fault Isolation ................................................................................................ 7-3
Alarm Relay Events ....................................................................................7-11
Sensor Housing ............................................................................................. 8-2
Electronics Housing ...................................................................................... 8-6
O2 Cell and Heater Strut Assembly ........................................................... 8-9
Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-2
Safety Data Sheet for Ceramic Fiber Products . . . . . . . . . . . . . . . . . A-24
High Pressure Gas Cylinders . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-30
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-2
Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-2
Returning Material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .C-1
Reference Manual
4880, Rev AA
July 2018
OCX 8800
TOC-2
00809-0300-
ESSENTIAL INSTRUCTIONS
Rosemount OCX 8800 Oxygen and Combustibles Transmitter
Emerson designs, manufactures and tests its products to meet many national and international standards. Because these instruments are sophisticated technical products, you MUST properly install, use, and maintain them to ensure they continue to operate within their normal specifications. The following instructions MUST be adhered to and integrated into your safety program when installing, using, and maintaining Emerson’s Rosemount products. Failure to follow the proper instructions may cause any one of the following situations to occur: Loss of life; personal injury; property damage; damage to this instrument; and warranty invalidation.
Read all instructions prior to installing, operating, and servicing the product.
If you do not understand any of the instructions, contact your Emerson representative for clarification.
Follow all warnings, cautions, and instructions marked on and supplied with the product.
Inform and educate your personnel in the proper installation, operation, and maintenance of the product.
Install your equipment as specified in the Installation Instructions of the appropriate Instruction Manual and per applicable local and national codes. Connect all products to the proper electrical and
pressure sources.
To ensure proper performance, use qualified personnel to install, operate, update, program, and maintain the product.
When replacement parts are required, ensure that qualified people use replacement parts specified by Emerson. Unauthorized parts and procedures can affect the product's performance, place the safe operation of your process at risk, and VOID YOUR WARRANTY. Look-alike substitutions may result in fire, electrical hazards, or improper operation.
Ensure that all equipment doors are closed and protective covers are in place, except when maintenance is being performed by qualified persons, to prevent electrical shock and personal injury.
READ THIS PAGE BEFORE PROCEEDING!
The information contained in this document is subject to change without notice.
If a Model 275/375 Universal HART® Communicator is used with this unit, the software within the Model 275/375 may require modification. If a software modification is required, please contact your local Emerson Service Group or National Response Center at 1-800­654-7768.
Reference Manual
July 2018
OCX 8800
00809-0300-4880, Rev AA
PREFACE The purpose of this manual is to provide a comprehensive understanding of
the OCX 8800 components, functions, installation, and maintenance. We recommend that you thoroughly familiarize yourself with the Introduction
and Installation sections before installing your transmitter. The introduction presents the basic principles of the transmitter along with its
performance characteristics and components. The remaining sections contain detailed procedures and information necessary to install and service the transmitter.
Before contacting Emerson concerning any questions, first consult this manual. It describes most situations encountered in your equipment's operation and details necessary action.
DEFINITIONS The following definitions apply to WARNINGS, CAUTIONS, and NOTES
found throughout this publication.
Highlights an operation or maintenance procedure, practice, condition, statement, etc. If not strictly observed, could result in injury, death, or long-term health hazards of personnel.
SYMBOLS
Highlights an operation or maintenance procedure, practice, condition, statement, etc. If not strictly observed, could result in damage to or destruction of equipment, or loss of effectiveness.
NOTE
Highlights an essential operating procedure, condition, or statement.
: EARTH (GROUND) TERMINAL
: PROTECTIVE CONDUCTOR TERMINAL : RISK OF ELECTRICAL SHOCK : WARNING: REFER TO INSTRUCTION BULLETIN
NOTE TO USERS
The number in the lower right corner of each illustration in this publication is a manual illustration number. It is not a part number, and is not related to the illustration in any technical manner.
Reference Manual
4880, Rev AA
July 2018
OCX 8800
ii
00809-0300-
Section 1 Description and Specifications
Component Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1-1
System Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1-1
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1-12
COMPONENT CHECKLIST
SYSTEM OVERVIEW Scope
A typical OCX 8800 Oxygen/Combustibles Transmitter package should contain the items shown in Figure 1-1.
Use the product matrix in Table 1-1 at the end of this section to verify your order number. The first part of the matrix defines the model. The last part defines the various options and features of the OCX 8800. Check the model number against the transmitter features and options, making sure options specified by this number are on or included with the unit. Use this complete model number for any correspondence with Emerson. A list of accessories for use with the OCX 8800 is provided in Table 1-2.
This Instruction Manual supplies details needed to install, startup, operate, and maintain the OCX 8800. Signal conditioning electronics outputs separate 4-20 mA signals representing oxygen (O This information, plus additional details, can be accessed with the HART Model 275/375 handheld communicator or Rosemount AMS software.
) and combustibles (COe) values.
2
System Description
The OCX 8800 is designed to measure oxygen and combustible concentrations in flue gas temperatures up to 2600°F (1427°C). Electrical connections, power and communications are made through two 3/4 NPT ports in the flameproof electronics enclosure using fittings and cables provided by the customer. Cable installation must meet NEC, IEC and/or other applicable national or local codes for Class I, Zone 1, Group IIB +H2 T3/T6 permanently mounted equipment. The transmitter is close coupled to the process and requires minimal sample conditioning requirements.
Reference Manual
4880, Rev AA
July 2018
OCX 8800
1-2
1
4
6
MAN 4275A00
o
FISHER
-ROSEMOUNT
TM
2 3
37390076
Figure 1-1. Typical System Package
English
October 1994
HART Communicator
00809-0300-
5
1.
Instruction Manual
2.
Field Communicator Package (optional)
3.
Adapter Plate with Mounting Hardware and Gasket
4.
Reference Air and Calibration Set
5.
Blowback Hardware (optional)
6.
OCX 8800 with Remote Electronics
Reference Manual
July 2018
OCX 8800
1-3
00809-0300-4880, Rev AA
The equipment measures oxygen percentage by reading the voltage developed across a heated electrochemical cell, which consists of a small yttria-stabilized, zirconia disc. Both sides of the disc are coated with porous metal electrodes. When operated at the proper temperature, the millivolt output of the cell is given by the following Nernst equation:
EMF = KT log10 (P
Where:
1.
P2 is the partial pressure of the oxygen in the measured gas on one side of the cell.
2.
P1 is the partial pressure of the oxygen in the reference air on the opposite side of the cell.
3.
T is the absolute temperature.
4.
C is the cell constant.
5.
K is an arithmetic constant.
NOTE
For best results, use clean, dry instrument air (20.95% oxygen) as the reference air.
When the cell is at operating temperature and there are unequal oxygen concentrations across the cell, oxygen ions will travel from the high oxygen partial pressure side to the low oxygen partial pressure side of the cell. The resulting logarithmic output vo ltag e is approximately 50 mV per decade. The output is proportional to the inverse logarithm of the oxygen concentration. Therefore, the output signal increases as the oxygen concentration of the sample gas decreases. This characteristic enables the OCX 8800 to provide exceptional sensitivity at low oxygen concentrations.
1/P2
) + C
The OCX 8800 measures net oxygen concentration in the presence of all the products of combustion, including water vapor. Therefore, it may be considered an analysis on a "wet" basis. In comparison with older methods, such as the portable apparatus, which provides an analysis on a "dry" gas basis, the "wet" analysis will, in general, indicate a lower percentage of oxygen. The difference will be proportional to the water content of the sampled gas stream.
The OCX 8800 combustibles sensor is a catalytic sensor consisting of two Resistance Devices (RTD). One RTD is the reference element covered with an inert coating. The other RTD element is active, coated with a catalyst. As the sample gases flow by the sensor, the combustible gases oxidize on the surface of the active element. The oxidation that occurs produces heat and a temperature rise in the active element. The temperature difference produces a resistance relationship between the two elements that is directly proportional to the concentration of combustibles in the sample gases.
1-4
Reference Manual
July 2018
OCX 8800
00809-0300-4880, Rev AA
The catalyst is specifically designed to detect carbon monoxide (CO), but the sensor responds to other combustible gases. The sensor is calibrated using CO, thus the output should be expressed in terms of CO. However, since the sensor detects other combustible gases, the output cannot just be labeled CO. The response of the sensor to other combustible gases gives an output that is equivalent to the sensor detecting CO. The term COe is used in this manual to describe the sensor output. This term indicates that the sensor is calibrated in terms of CO, and that the sensor output is equivalent to CO but not specific to CO.
Dilution air is provided to the COe sensor to ensure there is adequate oxygen to fully oxidize any combustible gases regardless of the concentration of oxygen in the process.
System Configuration
Transmitters are available in four lengths, giving the user the flexibility to use a penetration appropriate to the size of the stack or duct. The length options are 18 in. (457 mm), 3 ft (0.91 m), 6 ft (1.83 m), or 9 ft (2.7 m). Probes are available in three material options, 316L stainless steel, inconel 600, and ceramic to accommodate higher temperatures.
The electronics are contained in a separate housing from the sensors. The electronics housing may be mounted up to 150 feet away from the sensor housing.
The electronics control both sensor temperatures and provide individual 4-20 mA isolated outputs that are proportional to the measured oxygen and combustibles concentrations. The power supply can accept voltages of 100 to 240 VAC and 50 to 60 Hz. The electronics accepts millivolt signals generated by the sensors and produces the outputs to be used by remotely connected devices. The outputs are isolated 4-20 mA linearized currents. Refer to Section 3, Configuration and Startup for specific instructions upon initial power up.
System Features
1.
The O2 cell output voltage and sensitivity increase as the oxygen concentration decreases.
2.
HART communication is standard. To use the HART capability, you must have either:
a.
Model 275/375 Field Communicator.
b.
AMS software for the PC.
3.
Oxygen cell and heater /t he rmocouple assembly are field replaceable.
4.
Electronics are automatically configured for line voltages from 100 to 240 VAC.
Reference Manual
July 2018
OCX 8800
1-5
00809-0300-4880, Rev AA
5.
An operator can calibrate and diagnostically troubleshoot the OCX 8800 using the HART Interface. Each of the OCX 8800's 4-20 mA output lines transmit an analog signal proportional to oxygen or combustible levels detected. The HART output is superimposed on the oxygen 4-20 mA output line only. This information can be accessed through the following:
Model 275/375 Handheld Communicator - The handheld communicator requires Device Description (DD) software specific to the OCX 8800. The DD software will be supplied with many Model 275/375 units, but can also be programmed into existing units at most Emerson service offices. Refer to Section 4, Using HART Communications, for additional information.
Personal Computer (PC) - The use of a personal computer requires AMS software available from Emerson.
Selected Distributed Control Systems - The use of distributed control systems requires input/output (I/O) hardware and AMS software which permit HART communications.
6.
Optional Blowback System. The blowback system periodically blows instrument air back throug h the sample line filter a nd o ut the s ample tube. This clears out particulate and keeps the sample line filter from clogging.
System Operation
Figure 1-2 shows the relationship between the components of the OCX 8800. The sensors and the electronics are contained in separate housings. The sensor housing and probe mounts to a duct or process wall so that the probe protrudes into the flue gas stream. An air powered eductor continuously pulls samples of the process flue gas through the probe to a chamber in front of the sensor housing where the sample passes the O the COe sensor. Dilution air is provided to the COe sensor and reference air to the O the COe sensor, it is drawn through the eductor where it mixes with the eductor air and exits through exhaust back into the system. The electronics housing contains the CPU and HART boards which convert the sensor inputs into 4-20 mA analog output signals. The CPU can also initiate and perform calibrations. Three test gasses and instrument air can be turned on and off by solenoids. Test gas flow to the sensors is regulated by a flow meter between the electronics and sensor housings. Instrument air is separated into eductor air, reference air, and dilution air. The instrument air solenoid does not allow air flow until the heaters are up to temperature. This minimizes the amount of sampled process flue gas being pulled into cold sensors causing condensation.
sensor. After the gas sample flows past the O2 sensor and through
2
sensor and continues on to
2
1-6
Reference Manual
July 2018
OCX 8800
Test Gas
37390001
Figure 1-2. System Operation Diagram
Probe
Combustibles
Sensor
Sample
Gas
Exhaust
SENSOR
HOUSING
COe
Sensor
O
2
Eductor
Reference Air
Flow Meter
7 scfh
ELECTRONICS
Instrument Air
Eductor Air
HOUSING
CPU
HART Board
Power
Supply
Optional Test Gas Solenoids
Solenoid
00809-0300-4880, Rev AA
Low O
2
High O
2
Test Gas
CO
Test Gas
Instrument
Air
Dilution Air
Flow Meter
50 cc/min.
(0.1 scfh)
Handling the OCX 8800
It is important that printed circuit boards and integrated circuits are handled only when adequate antistatic precautions have been taken to prevent possible equipment damage.
The OCX 8800 is designed for industrial application. Treat each component of the system with care to avoid physical damage. The probe may contain components made from ceramics, which are susceptible to shock when mishandled.
System Considerations
Prior to installing your OCX 8800, make sure you have all the components necessary to mak e the system installation. Ens ure al l t he c omponents are properly integrated to make the system functional.
Reference Manual
July 2018
OCX 8800
1-7
00809-0300-4880, Rev AA
After verifying that you have all the components, select mounting locations and determine how each component will be placed in terms of available line voltage, ambient temperatures, environmental considerations, convenience, and serviceability. Figure 1-3 shows a typical system wiring. Simplified installations for the OCX 8800 are shown in Figure 1-4. Figure 1-6 shows the dimensions for the optional sample tube support.
A source of instrument air is required at the OCX 8800 for reference air, dilution air, and eductor air. Since the OCX 8800 is equipped with an in-place calibration feature, provision should be made for connecting test gas tanks to the OCX 8800 when it is to be calibrated.
NOTE
The electronics module is designed to meet NEMA 4 (IP66) and the electronic components are rated to temperatures up to 185°F (8 5°C).
Retain packaging in which the unit arrived from the factory in case any components are to be shipped to another site. This packaging has been designed to protect the product.
Figure 1-3. OCX 8800 HART Connections and AMS Application
1-8
Reference Manual
July 2018
OCX 8800
37390064
Figure 1-4. Typical System Installation
Power Ca ble
[up to 150 ft (46 m)]
Signal Cable
[up to 150 ft (46 m)]
Figure 1-5. OCX 8800 HART
Heater
Gases
Stack
Dilution
Air
Flow
Meter
00809-0300-4880, Rev AA
Duct
Flow Meter
OCX 8800 with
REMOTE
ELECTRONICS
Test Gas
Pressure
Regulator
High O2 Test Gas Low O CO Test Gas
4-20 mA Outputs (2 Twisted Pairs)
Line Voltage
Instrument Air
Supply
(Reference Gas)
Test Gas
2
Reference Manual
July 2018
OCX 8800
1-9
00809-0300-4880, Rev AA
Connections and AMS Application
Reference Manual
July 2018
OCX 8800
1-10
Figure 1-6. Sample Tube Support
00809-0300-4880, Rev AA
Reference Manual
July 2018
OCX 8800
1-11
37390064
00809-0300-4880, Rev AA
Figure 1-7. Typical System Installation
Power Ca ble
[up to 150 ft (46 m)]
[up to 150 ft (46 m)]
Heater
Signal Cable
Gases
Stack
Dilution
Air
Flow
Meter
Duct
Flow Meter
OCX 8800 with
REMOTE
ELECTRONICS
Test Gas
Pressure
Regulator
High O2 Test Gas Low O CO Test Gas
4-20 mA Outputs (2 Twisted Pairs)
Line Voltage
Instrument Air
Supply
(Reference Gas)
Test Gas
2
Reference Manual
July 2018
OCX 8800
1-12
Blowback Air (optional) Clean, dry, instrument-quality air (20.95% O2), regulated to ≥ 60 psi
SPECIFICATIONS General Purpose OCX
Specifications
Net O2 Range 0-1% to 0-40% O2, fully field selectable Combustibles 0-1000 ppm to 0-5%, fully field selectable Accuracy
Oxygen ± 0.75% of reading or 0.05% O Combustibles ± 2% range
System Response to Test G as
Oxygen 10 sec T90 Combustibles 25 sec T90
Temperature Limits
Process 32°to 2600°F (0° to 1427°C) Sensors Housing -40°to 212°F (-40°to 100°C), ambient Electronics Housing -40°to 149°F (-40°to 65°C), ambient
Nominal and Approximate Shipping Weights
18 in. (457 mm) probe package
3 ft (0.91 m) probe package
6 ft (1.83 m) probe package
9 ft (2.74 m) probe package
Mounting and Mounting Positions
Sensors Housing Flange
Electronics Housing Wall/Pipe
Materials
Probes 316L stainless steel - 1300°F (704°C)
Enclosures Low-copper aluminum Calibration Semi-aut omatic or automatic Calibration Gas Mixtures
Recommended
(Ref. test gas bottles
kit #1A99119G04) Calibration Gas Flow 7 scfh (3.3 l/m) Reference Air 2 scfh (1 l/m), clean, dry instrument-quality air (20.95% O
Eductor Air 5 scfh (2.5 l/m), clean, dry, instrument-qualit y air 20.95% O
Dilution Air 0.1 scfh (0. 5 l/m), clean, dry, instrument-quality air (20.95% O
00809-0300-4880, Rev AA
(whichever is greater)
-40°to 185°F (-40°to 85°C), internal - operating temperature of electronics inside instrument housing, as measured by a HART communicator or AMS software
2
54 lbs (20 kg)
55 lbs (20.5 kg)
57 lbs (21 kg)
59 lbs (22 kg)
Inconel 600 - 1832°F (1000°C) Ceramic - 2600°F (1427°C)
0.4
% O2, Balance N2
8% O
, Balance N2
2
1000 ppm CO, Balance Air
regulated to 35 psi (241 kPa)
regulated to 35 psi (241 kPa)
regulated to 35 psi (241 kPa)
(413 kPa) or greater and ambient temperature of ≥ 0 °F (-18 °C)
Table continued on next page
),
2
),
2
)
2
Reference Manual
July 2018
OCX 8800
1-13
C
U
00809-0300-4880, Rev AA
Specifications
Sensors Housing NEMA 4, IP66 with fitting and pipe on reference exhaust port to clean, dry
atmosphere, two 3/4-14 NPT conduit ports (when reference vents are routed to a dry area).
Electronics Housing NEMA 4, IP66 with fitting and pipe on reference exhaust port to clean, dry
atmosphere, two 3/4-14 NPT conduit ports (when reference vents are routed to a dry area).
Electrical Noise EN 61326-1, Class A
Line Voltage Universal 100 to 240 VAC ±
jumpers required, 3/4-14 NPT conduit port
Pollution Degree 2
Over Voltage Category II
Relative Humidity 5 to 95% (non-condensing)
Isolated Output
Oxygen 4-20 mAdc, 950 ohm maximum, with HART capability
Combustibles 4-20 mAdc, 950 ohm maximum
Alarm Alarm output relay - dry contact, form C, 30mA, 30VDC capacity Power Consumption 750 W maximum Mounting and Mounting
Positions
Sensor Housing Flange
Electronics Housing
NOTE All static performance characteristics are with operating variables constant. Specifications subject to change without notice.
Wall/Pipe
Certifications
S
10%, 50 to 60 Hz, no switches or
Reference Manual
July 2018
OCX 8800
1-14
OCX88A
O2/Combustibles Transmitter
Code
Probe Length and Material
00
No Probe or Exhaust Tube
11
18 in. (457 mm) 316 SST
up to 1300°F (704°C)
(3)
21
18 in. (457 mm) Inconel 600
up to 1832°F (1000°C)
31
18 in. (457 mm) Ceramic
up to 2600°F (1427°C)
12
3 ft (0.91 m ) 316 SST
up to 1300°F (704°C)
22
3 ft (0.91 m) Inconel 600
up to 1832°F (1000°C)
(3)
32
3 ft (0.91 m) Ceramic
up to 2600°F (1427°C)
13
6 ft (1.83 m ) 316 SST
up to 1300°F (704°C)
23
6 ft (1.83 m) Inconel 600
up to 1832°F (1000°C)
(3)
14
9 ft (2.7 m) 316 SST
up to 1300°F (704°C)
24
9 ft (2.7 m) Inconel 600
up to 1832°F (1000°C)
(3)
Code
Probe Mounting Assembly
10
(ANSI 2 in. 150 lb) 6" dia. flange, 4.75" BC with 4 x 0.75" dia. holes
20
(DIN) 185 mm dia. flange, 145 mm BC with 4 x 18 mm dia. holes
Code
Mounting Hardware - Stac k Side
0 No Adapter Plate (“0” must be chosen under “Mounting Adapter - Probe Side” below)
1 New Installation - Square weld plate with studs
2 Model 218/240 Mounting Plate (with Model 218/240 Shiel d Removed)
3 Existing Model 218/240 Support Shield
4 Special Mounting
(1)
5 Model 132 Adapter Plate
Code
Mounting Hardware - Probe Side
0 No Adapter Plate
1 Probe Only (ANSI)
2 Probe Only (DIN)
Code
Electronics Housing - Communications
H1
HART Communications
H2
HART Communicatio ns with Local Operator Interface
H3
HART Communications with Calibration Solenoids
H4
HART Communications with Local Operator Interface and C alibrati on Solenoids
Code
Electronics Mounting
01
Integr al to Sensor H ousing
02
Remote Electronic s and no cable
03
Remote Electronics and 20 ft (6 m) cable
04
Remote Electronics and 40 ft (12 m) cable
05
Remote Electronics and 60 ft (18 m) cable
06
Remote Electronics and 80 ft (24 m) cable
07
Remote Electronics and 100 ft (30 m) cable
08
Remote Electronics and 150 ft (46 m) cable
Code
Accessories
00
None
01
Flow meters & Ref. Air Set
02
In-Situ Filte r (Stainless Steel only)
(2) 03
In-Situ Filter (SST), Flow meters & Ref. Air Set
(2)
11
Flow meters, and Ref. Air Set with Blowback
12
In-Situ Filter (SST) with Blowback
(2) 13
In-Situ Filter (SST), Flow meters & Ref. Air Set with Blowback
(2)
OCX88A
11
10 1 1
H3
06
02
Example
Plate with studs
Bolt circle diameter, number, and arrangement of studs, stud thread, stud height above mounting plate.
Plate without studs
Bolt circle diameter, number, and arrangement of holes, thread, depth of stud mounting plate with accessories.
00809-0300-4880, Rev AA
Table 1-1. Product Matrix - General Purpose OCX 8800
NOTES:
(1)
Provide details of the existi ng mo unti ng pl at e as foll o ws:
(2)
For use with stainless steel sample tube only.
(3)
For high temperature applications that require a filter, please order 1A99762H03 separately.
Reference Manual
July 2018
OCX 8800
1-15
PART NUMBER DESCRIPTION
00809-0300-4880, Rev AA
Table 1-2. Accessories
1A99119H01 Oxygen test gas bottle; 0.4% O2, balance N 1A99119H02 Oxygen test gas bottle; 8.0% O2, balance N
1A 99119H07 CO test gas bottle; 1000 ppm CO, balance air 1A99120H02 Regulator for Oxygen (may need 2) 1A99120H03 Regulator for CO test gas 1A99119G06 Wall mount bracket for test gas bottles 1A99119G05 Test gas regulators kit 1A99119G04 Test gas bottles kit
1A99292H01
1A99339H03 Blowback valve, air operated 1A99762H03 Hasteloy In Situ Filter, High Temperature
1A99784H02
6A00171G01 Power line filter kit 6A00288G01 Sample Tube Support, 18 in. (457 mm) 6A00288G02 Sample Tube Support, 3 Ft. (0.91 m) 6A00288G02 Sample Tube Support, 6 Ft. (1.83 m) 6A00288G04 Sample Tube Support, 9 Ft. (2.7 m) 6P00162H02 Flange Insulator
Moore Industries SPA for Low O Calibration Status, and Unit Fail
375 Field Communicator with 12 Megabyte buffer, model no. 375HR1EKLU
Alarm, High COe Alarm,
2
2 2
Reference Manual
July 2018
OCX 8800
00809-0300-4880, Rev AA
Section 2 Installation
Mechanical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-2
Electrical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-8
Pneumatic Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-14
Initial Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-20
Before installing this equipment, read the "Safety instructions for the wiring and installati on of this apparatus" in Appendix A: Safety Data. Failure to follow the safety instructions could result in serious injury or death.
The OCX88A can be installed in general purpose areas only. Do not install the OCX88A in hazardous areas.
Reference Manual
July 2018
OCX 8800
2-2
00809-0300-4880, Rev AA
MECHANICAL INSTALLATION
Selecting Location
1.
The location of the OCX 8800 in the stack or flue is most important for maximum accuracy in the oxygen analyzing process. The probe must be positioned so the gas it measures is representative of the process. Best results are normally obtained if the transmitter is positioned near the center of the duct (40-60% insertion). Longer ducts may require several transmitters since the oxygen and combustibles can vary due to stratification. A point too near the wall of the duct or the inside radius of a bend, may not provide a representative sample because of the very low flow conditions. The sensing point should be selected so the process gas temperature falls within the range of probe material used. Figure 2-1 through Figure 2-4 provide mechanical installation references. The ambient temperature inside the electronics housing must not exceed 185°F (85°C).
2.
Check the flue or stack for holes and air leakage. The presence of this condition will substantially affect the accuracy of the oxygen and combustibles readings. Therefore, either make the necessary repairs or install the transmitter up stream of any leakage.
3.
Ensure the area is clear of internal and external obstructions that will interfere with installation and maintenance access to the unit. Allow adequate clearance for the removal of the OCX 8800.
Do not allow the temperature of the electronics housing to exceed 185°F (85°C) or damage to the electronics may result.
Whenever a positive stack pressure exists at the installation site, be sure to connect all pneumatic lines prior to installing the OCX 8800 in the stack or ductwork. Failure to connect the pneumatic lines can allow the flow of contaminants into the OCX 8800 ports.
Installation
1.
Ensure all components are available to install the OCX 8800.
2.
The OCX 8800 may be installed intact as it is received.
3.
Weld or bolt adapter plate (Figure 2-2) onto the duct.
4.
Use the pipe or wall mounting hardware as shown in Figure 2-3 to mount the electronics housing. Choose a location not to exceed the length of the electronics cable ordered.
5.
Ensure the conduits drop vertically from the OCX 8800 and the conduit is routed below the level of the conduit ports on the housing to form a drip loop. Drip loops minimize the possibility that moisture will damage the electronics (Figure 2-4).
6.
Where a positive stack pressure exists at the installation site, connect all pneumatic lines prior to installing the OCX 8800 in the stack or ductwork.
Reference Manual
00809 July 2018
OCX 8800
2-3
-0300-4880, Rev AA
NOTE
If process temperatures will exceed 392°F (200°C), use anti-seize compound on stud threads to ease future removal of the OCX 8800.
7.
Insert sample and exhaust tubes through the opening in the mounting flange and bolt the unit to the flange.
Uninsulated stacks or ducts may cause ambient temperatures in the electronics housing to exceed 185°F (85°C) and damage the electronics.
8.
If insulation is removed to access the duct for OCX 8800 mounting, make sure to replace insulation afterward.
Enclosures
The OCX 8800 enclosures are designed to meet ingress conditions of IP66. Each enclosure cover is threaded to its base and sealed with an o-ring that isolates the threads from external contaminants.
Each cover is secured by a clip attached to the base that engages the cover between the ribs of the cover sidewall. The clip is held in place by an Allen head cap screw and lockwasher mounted in a recess. Cover removal and installation requires an Allen wrench to loosen and tighten the screw.
Reference Manual
July 2018
OCX 8800
4-2
Table 2. Installation/Removal
18
(457)
34
(864)
36
(914)
52
(1321)
72
(1829)
88
(2235)
108
(2743)
124
(3150)
0.06 In. Thick Gasket
ANSI
3535B18H02
DIN
3535B45H01
Heater
Po
wer Cab
le
Signal Cable
Signal Cable
Heater
Po
wer Cab
le
37390009
Table
1. Mounting
Flange
ANSI
DIN
5R10244H01
5R10244H02
Flange Dia.
6.00
7.28
(152)
(185)
Hole
0.75
0.71
Dia.
(19)
(18)
(4) Holes spaced on
(121)
(145)
B.C. dia
Figure 2-1. Installation, OCX 8800
NOTE
All dimensions are in inches with millimeters in parentheses. Insulate if exposed to adverse weather or extreme temperature
changes, install a protective housing and/or insulation around the unit.
See Table 1
See Table 2
SENSOR HOUSING
Probe Dim "A” Dim "B” 18 in.
Flange Dia.
B.C. Dia.
Hole Dia.
equally
Removal Envelope
Dim “B”
00809-0300-4880, Rev AA
4.75
5.71
Insertion Depth
Dim “A”
Optional
In Situ FIilter
8.3
(211)
3 ft 6 ft 9 ft
Allow 9 in.
(229 mm) for
Cover Removal
ELECTRONICS HOUSING
Reference Manual
00809 July 2018
OCX 8800
2-5
-0300-4880, Rev AA
Figure 2-2. Adapter Plate Installat ion
Reference Manual
July 2018
OCX 8800
6-2
37020021
Figure 2-3. Wall or Pipe Mounting of Electronics Housing
Note: * Indicates items are included
in mounting kit P/N 4851B40G01.
*Pipe
Mounting
Clamp
*Wall or Pipe
Mounting Bracket
and Screws
00809-0300-4880, Rev AA
Electronics
Housing
Wall Mounting Bolts
or Lag Screws
(4 each by customer)
1/4-20 UNC x 2 in. M-F Standoffs.
Recommended for rear piping
clearance when wall mounting.
(4 each by customer)
Reference Manual
00809 July 2018
OCX 8800
2-7
Conduit Drip Loops
Duct Wall
Conduit Drip Loop
Conduit Drip Loop
Duct Wall
37020004
-0300-4880, Rev AA
Figure 2-4. Installation with Drip Loops
Reference Manual
July 2018
OCX 8800
8-2
00809-0300-4880, Rev AA
ELECTRICAL INSTALLATION
All wiring must conform to local and national codes. For reference, factory wired solenoid power connections are shown in Figure 2-5.
Disconnect and lock out power before connecting the unit to the power supply. Failure to lock out power could result in serious injury or death.
Install all protective equipment covers and safety ground leads after installation. Failure to install covers and ground leads could result in serious injury or death.
To meet the Safety Requirements of IEC 1010 (EC requirement), and ensure safe operation of this equipment, connection to the main electrical power supply must be made through a circuit breaker (min 10 A) in close proximity and marked for this equipment which will disconnect all current-carrying conductors during a fault situation. This circuit breaker should also include a mechanically operated isolating switch. If not, then another external means of disconnecting the supply from the equipment should be located close by. Circuit breakers or switches must comply with a recognized standard such as IEC 947.
The OCX88A can be installed in general purpose areas only. Do not install the OCX88A in hazardous areas.
Reference Manual
00809 July 2018
OCX 8800
2-9
-0300-4880, Rev AA
NOTE
To maintain proper earth grounding, ensure a positive connection exists between the sensor housing, the electronics housing, and earth. The connecting ground wire must be 14 AWG minimum. Refer to Figure 2-5.
NOTE
Line voltage, signal, and relay wiring must be rated for at least 105ºC (221ºF).
Electrical Connections
Electrical connections, power and communications are made to the electronic enclosure. The connections are made through two 3/4 NPT ports in the enclosure using fittings and cables provided by the customer. Cable installation must meet NEC, IEC and/or other applicable national or local codes for Class I, Zone 1, IIB +H2 T3/T6 permanently mounted equipment.
Connect Line Voltage
The OCX 8800 operates on 100 to 240 VAC line voltage at 50 to 60 Hz. The power supply requires no setup. Connect the line (L wire) to the L terminal, and the neutral (N wire) to the N terminal on the AC power input terminal block in the electronics housing. Connect the ground (G wire) to the ground stud in the electronics housing as shown in Figure 2-5.
Connect 4-20 mA Signals
Connect the 4-20 mA current loop to the 4-20 mA signal output terminals in the electronics housing as shown in Figure 2-5. Use individual shielded twisted wire pairs. Terminate the shield at the electronics housing.
4-20 mA Signal
O
2
One 4-20 mA signal represents the O
value. Superimposed on the O
2
2
signal is the HART information accessible through a Model 275/375
Handheld Communicator or AMS software. The O
signal is at the AOUT 1
2
terminals.
COe 4-20 mA Signal
Another 4-20 mA signal at the AOUT 2 terminals represents the COe value. HART information is not available on the COe signal.
Alarm Output Relay
Connect any customer-supplied relay input to the alarm output relay terminal. Use shielded wire and terminate the shield at the electronics housing. The alarm output relay terminal is a set of dry, no. 2, form C, contacts with 30 mA, 30 VDC capacity.
Reference Manual
July 2018
OCX 8800
2-10
00809-0300-4880, Rev AA
Remote Electronics Connections to Sens or Housing
Make the following connections between the electronics and sensor housings with the electronics cable order ed with the pac k age (Fi gur e 2-6). Br a ide d cable is available in lengths up to 150 ft. (46 m).
NOTE
Interconnect wiring shown is for Rosemount supplied cables. For customer furnished interconnect wiring or cables, refer to Figure 2-7.
Signal Connections
Connect the electronics housing terminals to the corresponding terminals in the sensor housing. The twisted wire pairs are numbered on the inner plastic wrapper. Keep twisted pairs together and match the numbers and wire colors shown in Figure 2-6.
Heater Power Connections
Use the blue, white, orange black, red, and yellow stranded wires in the heater power cable to connect power to the three heaters in the sensor housing. Match the wire colors to the corresponding heater power terminal blocks in the sensor and electronics housings as shown in Figure 2-6.
Loading...
+ 130 hidden pages