Rosemount Manual: 1181-T Two-Wire Toroidal Transmitter | Rosemount Manuals & Guides

Model 1181T
Two-Wire Toroidal Conductivity Transmitter
Instruction Manual
PN 51-1181T/rev.C April 2003
DANGER
HAZARDOUS AREA INSTALLATION
Installations in hazardous area locations must be carefully evaluated by qualified on site safety per­sonnel. Transmitter and Sensor alone are not Intrinsically safe. To secure and maintain an intrin­sically safe installation, a certified safety barrier must be used and the installation must comply with the governing approval agency (FM, CSA or BASEEFA/CENELEC) installation drawing require­ments (see Section 2.0 - Installation).
EXPLOSION-PROOF INSTALLATION
Caution: Sensors are not explosion-proof. If the sensor must be installed in a hazardous location an intrinsically safe system must be implemented.
To maintain the explosion-proof rating of the trans­mitter, the following conditions must be met:
Discontinue power supply before removing enclosure covers.
Transmitter covers must be properly installed during power on operation.
Explosion proof "Y" fittings must be properly installed with sealing compound prior to apply­ing power to the transmitter.
Serial tag cover over the external Zero and Span adjustments must be in place.
See Installation Section for details.
Proper installation, operation and servicing of this instrument in a Hazardous Area Installation is entirely the responsibility of the user.
ESSENTIAL INSTRUCTIONS
READ THIS PAGE BEFORE PROCEEDING!
Rosemount Analytical designs, manufactures, and tests its products to meet many national and international standards. Because these instruments are sophisticated technical products, you must properly install, use, and main­tain them to ensure they continue to operate within their normal specifica­tions. The following instructions must be adhered to and integrated into your safety program when installing, using, and maintaining Rosemount Analytical products. Failure to follow the proper instructions may cause any one of the following situations to occur: Loss of life; personal injury; property damage; damage to this instrument; and warranty invalidation.
• Read all instructions prior to installing, operating, and servicing the prod­uct. If this Instruction Manual is not the correct manual, telephone 1-800­654-7768 and the requested manual will be provided. Save this Instruction Manual for future reference.
• If you do not understand any of the instructions, contact your Rosemount representative for clarification.
• Follow all warnings, cautions, and instructions marked on and supplied with the product.
• Inform and educate your personnel in the proper installation, operation, and maintenance of the product.
• Install your equipment as specified in the Installation Instructions of the appropriate Instruction Manual and per applicable local and national codes. Connect all products to the proper electrical and pressure sources.
• To ensure proper performance, use qualified personnel to install, operate, update, program, and maintain the product.
• When replacement parts are required, ensure that qualified people use replacement parts specified by Rosemount. Unauthorized parts and pro­cedures can affect the product’s performance and place the safe opera­tion of your process at risk. Look alike substitutions may result in fire, electrical hazards, or improper operation.
• Ensure that all equipment doors are closed and protective covers are in place, except when maintenance is being performed by qualified per­sons, to prevent electrical shock and personal injury.
Emerson Process Management
Liquid Division
2400 Barranca Parkway Irvine, CA 92606 USA Tel: (949) 757-8500 Fax: (949) 474-7250
http://www.raihome.com
© Rosemount Analytical Inc. 2003
About This Document
This manual contains instructions for installation and operation of Model 1181T Two-wire Toroidal Conductivity Transmitter. The following list provides notes concerning all revisions of this document.
Rev
. Level Date Notes
0 5/00 The initial release of the product manual. The manual has been reformatted to
reflect the Emerson documentation style and updated to reflect any changes in the product offering.
A 7/01 Added CE addendum info to page 6.
B 7/02 Updated drawing on page 7.
C 4/03 Updated CE cert reference on page 1.
MODEL 1181T
TWO-WIRE TRANSMITTER
TABLE OF CONTENTS
Section Title Page
1.0 GENERAL DESCRIPTION AND SPECIFICATIONS ........................... 1
1.1 Features and Applications.................................................................... 1
1.2 Physical Specifications – General........................................................ 1
1.3 Performance Specifications – General................................................. 2
1.4 Performance Specifications at 25°C .................................................... 3
1.5 Ordering Information............................................................................. 3
2.0 INSTALLATION..................................................................................... 4
2.1 Unpacking and Inspection .................................................................... 4
2.2 Mechanical Installation ......................................................................... 4
2.3 Hazardous Locations-Explosion-Proof Installation............................... 4
2.4 Wiring – General .................................................................................. 6
2.5 Hazardous Locations-Intrinsically Safe Installation.............................. 6
3.0 DESCRIPTION OF CONTROLS.......................................................... 15
3.1 Description of Controls ......................................................................... 15
4.0 CONFIGURATION................................................................................ 19
4.1 General................................................................................................. 19
4.2 Range Selection ................................................................................... 19
4.3 Digital Display....................................................................................... 21
4.4 Temperature Slope Adjustment ............................................................ 22
5.0 START UP AND CALIBRATION........................................................... 23
5.1 Calibration Using a Conductivity Standard or Process Sample........... 23
5.2 In-Situ Calibration by Grab Sample Analysis ....................................... 24
5.3 Full Scale Calibration Using a Decade Box or Resistors..................... 25
6.0 THEORY OF OPERATION................................................................... 26
6.1 Theory of Operation ............................................................................. 26
6.2 Circuit Description ................................................................................ 28
7.0 DISASSEMBLY/REASSEMBLY PROCEDURE ................................... 30
7.1 Disassembly Procedure........................................................................ 30
7.2 Reassembly Procedure ........................................................................ 30
8.0 TROUBLESHOOTING ......................................................................... 31
8.1 General................................................................................................. 31
8.2 Troubleshooting.................................................................................... 31
9.0 SPARE PARTS ..................................................................................... 32
9.1 Spare Parts........................................................................................... 32
10.0 RETURN OF MATERIAL...................................................................... 34
i
MODEL 1181T TABLE OF CONTENTS
ii
TABLE OF CONTENTS (CONT'D)
LIST OF FIGURES
Number Title Page
2-1 Mounting and Dimensional Drawing......................................................... 5
2-2 Transmitter Wiring..................................................................................... 7
2-3 Schematic System, F.M. I.S. Approved 1181T (1 of 3) ............................ 8
2-3 Schematic System, F.M. I.S. Approved 1181T (2 of 3) ............................ 9
2-3 Schematic System, F.M. I.S. Approved 1181T (3 of 3) ............................ 10
2-4 Schematic System, 1181T (CSA) ............................................................. 11
2-5 Intrinsically Safe Operation 1181T (CENELEC) ....................................... 12
2-6 FM Approved Explosion Proof Installation................................................ 13
3-1 External Span and Zero............................................................................ 16
3-2 Model 1181T PCB Stack........................................................................... 16
3-3 Temperature Circuit Board ........................................................................ 17
3-4 Driver Circuit Board .................................................................................. 17
3-5 Transmitter Circuit Board.......................................................................... 17
3-6 Signal Input Circuit Board......................................................................... 18
4-1 Model 1181T Matrix Cover........................................................................ 20
4-2 Digital Display ........................................................................................... 21
5-1 1181T Calibration Setup ........................................................................... 25
6-1 Toroidal Conductivity Principle .................................................................. 26
6-2 Model 1181T Operation Block Diagram.................................................... 27
6-3 Model 1181T Schematic ........................................................................... 29
9-1 Model 1181T Two Wire Transmitter Parts ................................................ 33
LIST OF TABLES
Number Title Page
4-1 Full Scale Readings of the 1181T With Various
Probe Constants in Microsiemens/cm ...................................................... 19
4-2 Operational Limits vs. Slope..................................................................... 22
8-1 Troubleshooting Guide.............................................................................. 31
9-1 Model 1181T Two-Wire Transmitter Spare Parts ..................................... 32
MODEL 1181T TABLE OF CONTENTS
1
MODEL 1181T SECTION 1.0
GENERAL DESCRIPTION AND SPECIFICATIONS
1.1 FEATURES AND APPLICATIONS
The Rosemount Analytical Two-Wire field mounted transmitters, with the appropriate sensors, are designed to continuously measure the pH, ORP, Conductivity, Dissolved Oxygen, or Free Residual Chlorine in industri­al processes.
The Model 1181 Transmitters include all the circuitry necessary for the measurement and transmission of an isolated 4-20 mA linear signal. Measurement range selection is made through internal range switches that are easily accessed by removing a housing cover. No further disassembly is required. A matrix is provided which conveniently indicates the proper switch position. Range selection can be made without the use of the instruction manual. Fine calibration of the 4-20 mA sig­nal is accomplished with the 20-turn external Zero and Span potentiometers.
The electronic printed circuits are protected from the environment by the NEMA 4X weatherproof, corrosion resistant enclosure. The printed circuit cards plug into a moisture barrier which is isolated from the field wiring and calibration terminals. Routine field calibration does not require exposing the electronics to harsh industrial environments. All PCBs are conformal coated for maxi­mum protection. The PCBs are removed as a unit and may be individually replaced. The transmitter housing covers are sealed with large cross sectional O-rings and need not be replaced each time the cover is removed.
The Model 1181 is available blind or with an analog or digital display. The digital display may be calibrated in engineering units and the analog display features multi­ple scales in engineering units.
The transmitters are certified explosion-proof, NEMA 7B, and intrinsically safe when installed with an approved barrier and sensor. Hazardous area certificates are pro­vided by BASEEFA to CENELEC regulations, FM, CSA, SAA, SEV, and TUV. CSA has determined that the mois­ture barrier qualifies as Factory Sealed which means Explosion Proof Y fittings and sealing compound are not required for installation when this approval is selected.
Accessory items are available for the two-wire transmit­ters. The Model 515 Isolated Power Supply provides power for up to 20 transmitters. Two transmitters may be
wired directly to the power supply. For more than two transmitters, junction boxes are available, each accom­modating wiring for a maximum of ten transmitters. Remote alarms are available with independently adjustable set points and hysteresis. Contacts of the Model 230A may be specified for high/low, high/high, or low/low operation. The impedance of the Model 230A Alarm Module is less than 100 ohms. For further infor­mation on the Models 515 and 230A, please refer to their respective product data sheet.
1.2 PHYSICAL SPECIFICATIONS – GENERAL
Enclosure: NEMA 4X, weatherproof and corrosion-
resistant
NEMA 7B, explosion proof
Hazardous Area Classification:
Explosion Proof:
FM: Class I, Groups B, C, & D, Div. 1
Class II, Groups E, F, & G, Div. 1 Class III 60°C Maximum
CSA: Class I, Groups C & D
Class II, Groups E, F, & G Class III Class I, Groups A, B, C, & D, Div. 2 Encl. Type 4, Factory Sealed
Intrinsic Safety:
FM: Class I, II, & III, Div. 1
Temperature Code T4
CSA: Class I, Groups A, B, C, & D, Encl 4
Temperature Code T4
CENELEC: Ex ia IIB T4
Display:
Analog: plug in, 90 degree, 2.5 inch diameter
1181T: single scale, 0-100%
Digital: 3.5 digit, LCD, adjustable range in
engineering units
EMI/RFI: EN-61326
SECTION 1.0
GENERAL DESCRIPTION AND SPECIFICATIONS
2
MODEL 1181T SECTION 1.0
GENERAL DESCRIPTION AND SPECIFICATIONS
Recommended Cable: Transmitter to Power Supply Two Wire, 18 AWG,
shielded, Belden 8760 or equal (Rosemount Analytical P/N 9200001)
Weight/Shipping Weight:
Blind: 1.8 kg/2.25 kg (4.0 lbs/5.0 lbs) Analog/Digital: 2.48 kg/2.93 kg (5.5 lbs/6.5 lbs)
1.3 PERFORMANCE SPECIFICATIONS – GENERAL
Power Supply Requirements: (See Load/Supply
Chart)
Lift Off Voltage:
Blind & Analog: 10 VDC Digital: 12.5 VDC
Maximum Operating Power: 40 milliwatts
Output: Blind & Analog: Isolated 4-20 mA into
700 ohms at 24 VDC
Digital: Isolated 4-20 mA into 575 ohms at
24 VDC
Input/Output Isolation: 600 Volts
Ambient Temperature: –25° to 70°C
Relative Humidity: 0-99%
Digital Display Accuracy: 0.1% reading ±1.0 count
Analog Display Accuracy: ±2.0%
External Zero: ±25%
External Span: ±50%
Shock: 10G maximum for 10 milliseconds
Vibration: 0.025 inches double amplitude
5 to 50 Hz for 2 hours
The Model 1181T Toroidal Transmitter measures con- ductivity over the range of 0-50 µS/cm to 0-1000 mS/cm. The Model 1181T uses an inductive principal of meas­urement and employs the use of toroidal or electrode­less conductivity sensors. Toroidal conductivity sensors have no exposed electrodes to the measured solution, which practically eliminates routine sensor maintenance in applications where electrode fouling may occur. A unique feature of the Model 1181T is the 0-4% tempera­ture slope adjustment which provides greater accuracy in chemical concentration control. The 0-4% tempera­ture slope adjustment eliminates the need for special temperature compensation circuits required for the cali­bration to a specific acid, base, or salt over a specific operating temperature range.
BLIND & ANALOG DISPLAY
LOAD/POWER SUPPLY REQUIREMENTS
+45 VDC @ 600 OHMS MIN. 1750 OHMS MAX.
10 VDC 24 VDC 33 VDC @ ZERO LOAD 45 VDC
LIFT OFF NOMINAL MAXIMUM
POWER SUPPLY VOLTAGE
1750 OHMS @ 45 VDC
600 OHMS @ 45 VDC
LOAD RESISTANCE REQUIRED
1.8 –
1.7 –
1.6 –
1.5 –
1.4 –
1.3 –
1.2 –
1.1 –
1.0 –
0.9 –
0.8 –
0.7 –
0.6 –
0.5 –
0.4 –
0.3 –
0.2 –
0.1 –
0.0 –
OPERATING
REGION
DIGITAL DISPLAY
LOAD/POWER SUPPLY REQUIREMENTS
+45 VDC @ 600 OHMS MIN. 1750 OHMS MAX.
12.5 VDC 24 VDC 35.5 VDC @ ZERO LOAD 45 VDC LIFT OFF NOMINAL MAXIMUM
POWER SUPPLY VOLTAGE
1750 OHMS @ 45 VDC
600 OHMS @ 45 VDC
LOAD RESISTANCE REQUIRED
1.8 –
1.7 –
1.6 –
1.5 –
1.4 –
1.3 –
1.2 –
1.1 –
1.0 –
0.9 –
0.8 –
0.7 –
0.6 –
0.5 –
0.4 –
0.3 –
0.2 –
0.1 –
0.0 –
OPERATING
REGION
3
RECOMMENDED TOROIDAL SENSORS:
FULL SCALE
Minimum Maximum
Model 222 Sensor 0-500 µS/cm 0-1000 mS/cm Model 225 Sensor 0-250 µS/cm 0-1000 mS/cm Model 226 Sensor 0-80 µS/cm 0-160 mS/cm Model 228 Sensor 0-250 µS/cm 0-1000 mS/cm
MODEL
1181 TWO-WIRE TRANSMITTER
CODE INPUT (Required Selection)
T Toroidal Conductivity
CODE DISPLAY (Required Selection)
01 FM and CSA approved analog display
02 Blind, without indication
03 FM, CSA and CENELEC approved analog display
06 CSA, & CENELEC approved digital display
CODE OPTIONS
07 Two-inch pipe/wall mounting bracket (order as P/N 2002577)
11 Stainless steel nameplate (specify marking) (order as P/N 9240591)
CODE AGENCY APPROVALS
67 FM Explosion proof and Intrinsically Safe
69 CSA Explosion proof and Intrinsically Safe
73 CENELEC Intrinsically Safe
1181 T 01 07-11 67 EXAMPLE
1.5 ORDERING INFORMATION
Model 1181 Two Wire Transmitter is housed in a NEMA 7B explosion-proof, 4X weatherproof, corrosion-resistant
enclosure and includes all the circuitry necessary for measurement and transmission of an isolated 4-20 mA signal. The transmitter may be selected with or without an analog or digital display.
MODEL 1181T SECTION 1.0
GENERAL DESCRIPTION AND SPECIFICATIONS
1.4 PERFORMANCE SPECIFICATIONS @ 25°C
Measurement Range: 0-80 µS/cm minimum
0-1000 mS/cm maximum
Internal Range Select: Multipliers X500, X1000,
X10,000 with jumper selectable span X1 & X10 and internal span adjust
Accuracy: ±0.5% full scale
Stability: ±0.1%/month, non-cumulative
Repeatability: ±0.1% full scale
Temperature Coefficient: 0.05% of F.S./°C
Temperature Slope Adjust: 0-4%/°C
Automatic Temperature Compensation: 0-200°C
4
MODEL 1181T SECTION 2.0
INSTALLATION
SECTION 2.0
INSTALLATION
2.1 UNPACKING AND INSPECTION
Before opening the shipping carton, inspect the outside of the carton for any damage. If damage is detected, contact the carrier immediately. If there is no apparent damage, open the carton and inspect the instrument and hardware. Make sure all the items in the packing list are present and in good condition. Notify the factory if any part is missing. If the instrument appears to be in satis­factory condition, proceed to the transmitter installation.
NOTE
Save the original packing cartons and materials as most carriers require proof of damage due to mishandling, etc., also, if it is necessary to return the instrument to the factory, you must pack the instrument in the same manner as it was received. (refer to Section 8 for return instructions).
2.2 MECHANICAL INSTALLATION
IMPORTANT
Do not attempt to install and operate the Model 1181T without first reading this manual.
2.2.1 General. The transmitter may be installed in harsh environments. However, it should be installed in an area where sources of extreme temperature fluctuation, vibra­tion and shock are at a minimum or non-existent. Select an installation site that (1) permits the use of the standard cable lengths of 20 feet (6.1 m) or 10 feet (3.0 m); (2) is easily accessed by operating and maintenance person­nel; (3) is at least 12 inches (300 mm) from sources of high voltage.
2.2.2 Mounting. The Transmitter may be mounted on a flat surface using the two threaded mounting holes locat­ed on the bottom of the transmitter or through the use of an optional 2-inch pipe/wall mounting bracket, Code 07 (Figure 2-1).
2.3 HAZARDOUS LOCATIONS–EXPLOSION PROOF INSTALLATIONS
In order to maintain the explosion proof rating for the installed transmitter, the following conditions must be met:
1. The transmitter enclosure covers must be on hand
tight and the threads must not be damaged.
NOTE
These covers seat on o-rings which serve to provide a dust proof enclosure for Class II and Class III installations.
2. Explosion proof "Y" fittings must be properly installed
and plugged with a sealing compound to prevent explosive gases from entering the transmitter. CSA has determined that the transmitter housing is "Factory Sealed". Installation of "Y" fittings and the use of sealing compound is not required for CSA approved Explosion Proof installations.
NOTE
Do not install sealing compound until all field wiring is complete.
3. If one of the conduit connections on the housing is
not used, it must be closed with a threaded metal plug with at least five threads engaged.
4. The serial tag cover on the external ZERO and SPAN
adjustments must be in place.
5. Explosion proof installation must be in accordance
with drawing number 1400155 (See Figure 2-6).
6. Due to the nature of the measurement, sensors can-
not be designed to meet explosion proof certification. If the sensors must be installed in hazardous area locations, Rosemount Analytical Inc. recommends that an intrinsically safe system be installed.
CAUTION
Sealing compound must be installed prior to applying power to the transmitter.
5
FIGURE 2-1. Mounting and Dimensional Drawing
MODEL 1181T SECTION 2.0
INSTALLATION
6
MODEL 1181T SECTION 2.0
INSTALLATION
2.4 WIRING– GENERAL
The transmitter is equipped with two 1¼2-inch conduit openings, one on each side of the housing. One is for the power supply/signal wiring and the other is for the sensor wiring.
The use of waterproof cable glands or conduit is recom­mended to prevent moisture from entering the housing. If conduit is used, it should be positioned to prevent con­densation from draining into the housing.
Twisted pairs are recommended for the signal cable. The twisted pairs should also be shielded and grounded. The transmitter case shall be grounded.
Signal or sensor wiring should never be run in the same conduit or open tray with AC power, or relay actuated sig­nal cables. Keep signal or sensor wiring at least 12 inch­es from heavy electrical equipment.
NOTE
For best EMI/REI protection the power supply/signal cable should be shielded and enclosed in an earth grounded rigid metal con­duit. Connect the cable’s outer shield to the earth ground terminal near TB1, Figure 2-2.
The sensor cable should also be shielded. The cable’s outer shield shall be connected to the earth ground terminal provided near TB1, Figure 2-2. If the outer shield is braided an appropriate metal cable gland fitting may be used to connect the braid to earth ground via the instrument case.
A new addition to the suite of tests done to ensure CE compliance is IEC 1000-4-5. This is a surge immunity test that simulates overvoltages due to switching and lightning transients.
In order to meet the requirements of this test, additional protection must be added to the instrument in the form of a Transient Protector such as the Rosemount Model 470D. This is a 3½-inch tube with ½-inch MNPT threads on both ends. Inside the tube are gas discharge and zener diode devices to limit surges to the trans­mitter from the current loop. No additional pro­tection is needed on the sensor connections.
2.4.3 Sensor Wiring. The Sensor wiring terminals are located on the side of the housing designated TERM SIDE on the serial label. Remove the housing cover from the TERM SIDE to gain access to the terminals desig­nated TB2. Remove the optional Analog or Digital dis­play. The plug in analog display is held in by a spring clip and the digital display is held in by a locking screw. Connect the sensor wiring to TB2 terminals 1 through 4 as shown on drawing 40118121 (Figure 2-2).
NOTE
Sensors are supplied with a standard cable length of 20 feet (6.1 m) or 10 feet (3.0 m). If the standard cable length is not sufficient for the planned installation, the use of a junction box with extension cable is strong­ly recommended. Cutting or extending the cable may reduce performance and will void warranty.
2.4.2 Power and Signal Wiring. The power and signal
wiring terminals are located directly above the Sensor wiring terminals and are designated TB1. TB1 also provides for plugging in the optional Analog display or wiring of the optional digital display.
2.5 HAZARDOUS LOCATIONS–
INTRINSICALLY SAFE INSTALLATION
To secure and maintain intrinsically safe installation for the appropriate approval agency, the following con­ditions must be met:
1. Code 73 must be specified when ordering CENELEC
units and installation must be performed in accor­dance with Drawing Number 6-012-BO26 (Figure 2-
5).
2. Code 69 must be specified when ordering CSA
(Canadian Standards Association) units. Installation must be performed in accordance with Drawing Number 1400150 (Figure 2-4).
3. Code 67 must be specified when ordering F.M. units.
Installation must be accordance with Drawing Number 1400128 (Figure 2-3).
CAUTION
Do not exceed 100 feet (30.5m) distance of total cable length between the Transmitter and the Sensor.
7
MODEL 1181T SECTION 2.0
INSTALLATION
FIGURE 2-2. Transmitter Wiring
DWG. NO. REV.
40118121 J
8
MODEL 1181T SECTION 2.0
INSTALLATION
FIGURE 2-3. Schematic System, F.M. I.S. Approved 1181T (1 of 3)
DWG. NO. REV.
1400128 L
Loading...
+ 28 hidden pages