8200 Market Boulevard
Chanhassen, MN USA
55317
T (US) (800) 999-9307
T (Intnl) (952) 906-8888
F (952) 949-7001
Rosemount 8742C/8700 Series
Emerson Process
Management
Groeneveldselaan 6-8
3903 AZ Veenendaal
The Netherlands
Tel 31 (0) 318 549 549
Fax 31 (0) 318 549 559
Tel 0800-966 180 (U.K. only)
Fax 0800-966 181 (U.K. only)
Emerson Process
Management Asia Pacific
Private Limited
1 Pandan Crescent
Singapore 128461
T (65) 6777 8211
F (65) 6777 0947/65 6777 0743
IMPORTANT NOTICE
This installation guide provides basic guidelines for the
Rosemount
configuration, diagnostics, maintenance, service, troubleshooting,
explosion-proof, flameproof, or intrinsically safe (I.S.) installations.
Refer to the 8742C reference manual (document number
00809-0100-4793) for more instructions. The manual and this QIG
are also available electronically on www.rosemount.com.
®
8742C. It does not provide instructions for detailed
WARNING
Failure to follow these installation guidelines could result in
death or serious injury:
Installation and servicing instructions are for use by qualified
personnel only. Do not perform any servicing other than that
contained in the operating instructions, unless qualified. Verify that
the operating environment of the flowtube and transmitter is
consistent with the appropriate FM, CSA, or CENELEC approval.
Do not connect a 8742C to a non-Rosemount flowtube that is
located in an explosive atmosphere.
FINAL
Quick Installation Guide
00825-0100-4793, Rev BA
July 2003
Rosemount 8742C/8700 Series
WARNING
The flowtube liner is vulnerable to handling damage. Never place
anything through the flowtube for the purpose of lifting or gaining
leverage. Liner damage can render the flowtube useless.
To avoid possible damage to the flowtube liner ends, do not use
metallic or spiral-wound gaskets. If frequent removal is anticipated,
take precautions to protect the liner ends. Short spool pieces
attached to the flowtube ends are often used for protection.
Correct flange bolt tightening is crucial for proper flowtube operation
and life. All bolts must be tightened in the proper sequence to the
specified torque limits. Failure to observe these instructions could
result in severe damage to the flowtube lining and possible flowtube
replacement.
STEP 1: PRE-INSTALLATION
Before installing the Rosemount 8742C Magnetic Flowmeter
Transmitter, there are several pre-installation steps that should be
completed to make the installation process easier. They include
identifying the options and configurations that apply to your
application, setting the hardware switches if necessary, and
consideration of physical requirements.
The mounting site for the Rosemount 8742C should provide enough
room for secure mounting, easy access to the conduit ports, and full
opening of the transmitter covers.
To ensure maximum transmitter life, avoid excessive heat and
vibration. Typical problem areas include high-vibration lines with
integrally mounted transmitters, warm-climate installations in direct
sunlight, and outdoor installations in cold climates. To avoid potential
problems, remotely mounted transmitters may be installed in the
control room. This protects the electronics from the harsh environment
and provides easy access for configuration or service.
FINAL
Quick Installation Guide
00825-0100-4793, Rev BA
July 2003
Hardware Switches
The Rosemount 8742C electronics board is equipped with two
user-selectable hardware switches. These switches set Simulate
Enable and Transmitter Security. The standard configurations for
these switches when shipped from the factory are as follows:
Simulate Enable: Off
Transmitter Security: Off
The switches are located on the outerboard of the electronics
transmitter stack.
Figure 1. Hardware Switches
Simulate
Enable
Transmitter
Security
Rosemount 8742C/8700 Series
FINAL
Changing Hardware Switch Settings
In most cases, it is not necessary to change the setting of the
hardware switches. If you need to change the switch settings,
complete the steps outlined in the manual.
Quick Installation Guide
00825-0100-4793, Rev BA
July 2003
Rotate Transmitter Housing
The electronics housing can be rotated on the flowtube in 90°
increments by loosening the four mounting bolts on the bottom of the
housing, rotating the housing, and reinstalling the bolts. When the
housing is returned to its original position, be sure the surface is clean
and there is no gap between the housing and the flowtube.
Rosemount 8742C/8700 Series
STEP 2: HANDLING
Handle all parts carefully to prevent damage. Whenever possible,
transport the system to the installation site in the original shipping
containers. Teflon
protect it from both mechanical damage and normal unrestrained
distortion. Remove the end covers just before installation.
Figure 2. Rosemount 8705 Flowtube Support for Handling
®
-lined flowtubes are shipped with end covers that
FINAL
½- through 4-Inch
Flowtubes
6-Inch and Larger
Flowtubes
8732-0281B02A, C02A
Quick Installation Guide
00825-0100-4793, Rev BA
July 2003
Rosemount 8742C/8700 Series
STEP 3: MOUNTING
Upstream/Downstream Piping
To ensure specification accuracy over widely varying process
conditions, install the flowtube a minimum of five straight pipe
diameters upstream and two pipe diameters downstream from the
electrode plane (see Figure 3).
Figure 3. Upstream and Downstream Straight Pipe Diameters
5 Pipe Diameters
Flow
Flow Direction
The flowtube should be mounted so the FORWARD end of the flow
arrow, shown on the flowtube identification tag, points in the direction
of flow through the tube.
Flowtube Orientation
The flowtube should be installed in a position that ensures the
flowtube remains full during operation. Vertical installation allows
upward process fluid flow and keeps the cross-sectional area full,
regardless of flow rate. Horizontal installation should be restricted to
low piping sections that are normally full. In these cases, orient the
electrode plane to within 45 degrees of horizontal.
FINAL
2 Pipe Diameters
8732-0281G02A
Quick Installation Guide
00825-0100-4793, Rev BA
July 2003
Figure 4. Flowtube Orientation
A
Rosemount 8742C/8700 Series
FLOW
FLOW
The electrodes in the Rosemount 8705 flowtube are properly
orientated when the two measurement electrodes are in the 3 and 9
o’clock positions, as shown on the right of Figure 4.
The electrodes in the Rosemount 8711 are properly orientated when
the top of the flowtube is either vertical or horizontal, as shown in
Figure 5. Avoid any mounting orientation that positions the top of the
flowtube at 45° from the vertical or horizontal position.
Figure 5. Rosemount 8711 Mounting Position
45° Electrode Plane
FINAL
45° Electrode Plane
8732-0005A01A, 8732-0005A01C
8711-8711-E01A, 8711-8711-F01A
Quick Installation Guide
00825-0100-4793, Rev BA
July 2003
Rosemount 8742C/8700 Series
STEP 4: INSTALLATION (FLANGED FLOWTUBE)
Gaskets
The flowtube requires a gasket at each of its connections to adjacent
devices or piping. The gasket material selected must be compatible with the
process fluid and operating conditions. Metallic or spiral-wound gaskets
can damage the liner. Gaskets are required on each side of the
grounding ring. All other applications (including flowtubes with lining
protectors or a grounding electrode) require only one gasket on each
end connection.
Flange Bolts
Suggested torque values by flowtube line size and liner type are listed
in Table 1 for ASME B16.5 (ANSI) and Table 2 for DIN flanges.
Consult the factory if the flange rating of the flowtube is not listed.
Tighten flange bolts on the upstream side of the flowtube in the
incremental sequence shown in Figure 6 to 20% of the suggested
torque values. Repeat the process on the downstream side of the
flowtube. For flowtubes with more or less flange bolts, tighten the bolts
in a similar crosswise sequence. Repeat this entire tightening
sequence at 40%, 60%, 80%, and 100% of the suggested torque
values or until the leak between the process and flowtube flanges
stop.
If leakage has not stopped at the suggested torque values, the bolts
can be tightened in additional 10% increments until the joint stops
leaking, or until the measured torque value reaches the maximum
torque value of the bolts. Practical consideration for the integrity of the
liner often leads the user to distinct torque values to stop leakage due
to the unique combinations of flanges, bolts, gaskets, and flowtube
liner material.
Check for leaks at the flanges after tightening the bolts. Failure to use
the correct tightening methods can result in severe damage.
Flowtubes require a second tightening 24 hours after the initial
installation. Over time, flowtube liner materials may deform under
FINAL
Quick Installation Guide
00825-0100-4793, Rev BA
July 2003
pressure.
Figure 6. Flange Bolt Torquing Sequence
Table 1. Suggested Flange Bolt Torque Values for
Rosemount 8705 and 8707 High-Signal Flowtubes
Size
Code
005
0101 inch (25 mm)812-015 1
0202 inch (50 mm)19171411
0303 inch (80 mm)34352323
040 4 inch (100 mm)26501732
0606 inch (150mm)45503037
080 8 inch (200 mm)60824255
100 10 inch (250 mm)55804070
120 12 inch (300 mm)6512555105
140 14 inch (350 mm)851107095
160 16 inch (400 mm)8516065140
180 18 inch (450 mm)12017095150
200 20 inch (500 mm)11 017590150
240 24 inch (600 mm)165280140250
300 30 inch (750 mm)195415165375
360 36 inch (900 mm)280575245525
Line Size
1
/2-inch (15 mm)88--
1
/2 inch (40 mm)1325718
Rosemount 8742C/8700 Series
8-bolt
Polyurethane/Neoprene/
Teflon/Tefzel/PFA liners
Class 150
(pound-feet)
Class 300
(pound-feet)
Linatex liner
Class 150
(pound-feet)
(pound-feet)
FINAL
Class 300
8742f_01a.eps
Quick Installation Guide
00825-0100-4793, Rev BA
July 2003
Rosemount 8742C/8700 Series
Table 2. Flange Bolt Torque and Bolt Load Specifications for 8705
Teflon/Tefzel liner
(Newton-
meter)
104400104400
20101002010100
50161005016100
60201006020100
50168005016800
50178007019600
902470013028700
(Newton)
(Newton-
meter)
(Newton)
(Newton-
meter)
Size
Code
Line Size
005 0.5-inch
(15 mm)
0101 inch
(25 mm)
015 1.5 inch
(40 mm)
0202 inch
(50 mm)
0303 inch
(80 mm)
0404 inch
(100 mm)
0606 inch
(150mm)
0808 inch
(200 mm)
100 10 inch
(250 mm)
120 12 inch
(300 mm)
140 14 inch
(350 mm)
160 16 inch
(400 mm)
180 18 inch
(450 mm)
200 20 inch
(500 mm)
240 24 inch
(600 mm)
PN10PN 16PN 25PN 40
(Newton-
meter)
(Newton)
1303520090197001302920017034400
10028000130283001903800025044800
12032000170384001903860027047700
16043800220495003205720041068100
22050600280562004106810061092900
19043200340684003305510042064000
23051100380689004407330052073900
290586005709360059090100850112000
FINAL
(Newton)
Quick Installation Guide
00825-0100-4793, Rev BA
July 2003
Rosemount 8742C/8700 Series
Polyurethane, Linatex, and Neoprene Liners
(Newton-
meter)
(Newton)
(Newton)
207040207040
30107003010700
40134004013400
30111 003011100
40117005013200
60164009019200
(Newton-
meter)
(Newton)
(Newton-
meter)
(Newton)
Size
Code
Line Size
0101 inch
(25 mm)
015 1.5 inch
(40 mm)
0202 inch
(50 mm)
0303 inch
(80 mm)
0404 inch
(100 mm)
0606 inch
(150mm)
0808 inch
(200 mm)
100 10 inch
(250 mm)
120 12 inch
(300 mm)
140 14 inch
(350 mm)
160 16 inch
(400 mm)
180 18 inch
(450 mm)
200 20 inch
(500 mm)
240 24 inch
(600 mm)
PN 10PN 16PN 25PN 40
(Newton-
meter)
90234006013100901940011022800
7018600801880 01302540017029900
80213001102550013025800180319 00
11029100150330002103820028045400
15033700190374002804540041062000
13028700230456002203680028042700
15034100260459003004880035049400
20039200380624003906010056074400
FINAL
STEP 4: INSTALLATION (WAFER FLOWTUBE)
Gaskets
The flowtube requires a gasket at each of its connections to adjacent
devices or piping. The gasket material selected must be compatible with the
process fluid and operating conditions. Metallic or spiral-wound gaskets
can damage the liner. Gaskets are required on each side of the
grounding ring. All other applications (including flowtubes with lining
protectors or a grounding electrode) require only one gasket on each
end connection.
Quick Installation Guide
00825-0100-4793, Rev BA
July 2003
Alignment and Bolting
1. On 11/2 - through 8-inch (40 through 200 mm) line sizes, place
centering rings over each end of the flowtube. The smaller line
sizes, 0.15- through 1-inch (4 through 25 mm), do not require
centering rings. On the 4- and 6-inch PN 10–16, insert the flowtube
with rings first and then insert the studs. The slots on this ring
scenario are located on the inside of the ring.
2. Insert studs for the bottom side of the flowtube between the pipe
flanges. Stud specifications are listed in Table 3. Using carbon
steel bolts on smaller line sizes, 0.15- through 1-inch
(4 through 25 mm), rather than the required stainless steel
bolts, will degrade performance.
3. Place the flowtube between the flanges. Make sure that the
centering rings are properly placed in the studs. The studs should
be aligned with the markings on the rings that correspond to the
flange you are using.
4. Insert the remaining studs, washers, and nuts.
5. Tighten to the torque specifications shown in Table 1. Do not
overtighten the bolts or the liner may be damaged.
Rosemount 8742C/8700 Series
Class 1 threaded mounted studs
FINAL
Quick Installation Guide
00825-0100-4793, Rev BA
July 2003
Figure 7. Gasket Placement with Centering Rings
Installation, Studs Nuts
and Washers
Rosemount 8742C/8700 Series
Customer-supplied
Gasket
Centering Rings
FLOW
8732-0002A1A
Flange Bolts
Tighten flange bolts in crosswise sequence. Always check for leaks at
the flanges after tightening the flange bolts. All flowtubes require a
second torquing 24 hours after initial flange bolt tightening.
Table 4.
Size CodeLine SizePound-feetNewton-meter
15F0.15 inch (4 mm)511
30F0.30 inch (8 mm)511
005
0101 inch (25 mm)109
0151
0202 inch (50 mm)2521
0303 inch (80 mm)4020
0404 inch (100 mm)3045
0606 inch (150 mm)5077
0808 inch (200 mm)7061
FINAL
1
/2-inch (15 mm)511
1
/2 inch (40 mm)1514
Quick Installation Guide
00825-0100-4793, Rev BA
July 2003
Rosemount 8742C/8700 Series
STEP 4: INSTALLATION (SANITARY FLOWTUBE)
Gaskets
The flowtube requires a gasket at each of its connections to adjacent
devices or piping. The gasket material selected must be compatible
with the process fluid and operating conditions. Gaskets are supplied
between the IDF fitting and the process connection fitting, such as a
Tri-Clamp fitting, on all 8721 Sanitary flowtubes except when the
process connection fittings are not supplied and the only connection
type is an IDF fitting.
Alignment and Bolting
Standard plant practices should be followed when installing a
magmeter with sanitary fittings. Unique torque values and bolting
techniques are not required.
Figure 8. Rosemount 8721 Sanitary Installation
User supplied clamp
Note:
User supplied gasket
FINAL
If ordered manufacturer
supplied clamp and gasket
8721_a_06.eps
Quick Installation Guide
00825-0100-4793, Rev BA
July 2003
Rosemount 8742C/8700 Series
STEP 5: GROUNDING
Use Table 5 to determine which grounding option to follow for proper
installation. The flowtube case should always be earth grounded in
accordance with national and local electrical codes. Failure to do so
may impair the protection provided by the equipment. The Internal
Ground Connection (Protective Ground Connection) located in side
the junction box is the Internal Ground Connection screw. This screw
is identified by the ground symbol.
Table 5. Grounding Installation
Grounding Options
No
Grounding
Type of Pipe
Conductive
Unlined Pipe
Conductive
Lined Pipe
Non-Conduc
tive Pipe
Figure 9. No Grounding Options or Grounding Electrode in Lined Pipe
Options
See Figure 9 Not Required Not RequiredSee Figure 10
Insufficient
Grounding
Insufficient
Grounding
Grounding
Rings
See Figure 10 See Figure 9See Figure 10
See Figure 11 See Figure 12See Figure 11
Grounding
Electrodes
Lining
Protectors
FINAL
Earth
Ground
8705-0040C
Quick Installation Guide
00825-0100-4793, Rev BA
July 2003
Figure 10. Grounding with Grounding Rings or Lining Protectors
Figure 11. Grounding with Grounding Rings or Lining Protectors
Rosemount 8742C/8700 Series
Earth
Ground
Grounding Rings or Lining
Protectors
8705-038C
FINAL
Earth
Ground
Grounding Rings
8711-0360a01b
Quick Installation Guide
00825-0100-4793, Rev BA
July 2003
Figure 12. Grounding with Grounding Electrodes
Rosemount 8742C/8700 Series
Earth
Ground
8711-0360a01a
STEP 6: WIRING
Conduit Ports and Connections
Both the flowtube and transmitter junction boxes have ports for ¾-inch
NPT conduit connections. These connections should be made in
accordance with local or plant electrical codes. Unused ports should
be sealed with metal plugs. Proper electrical installation is necessary
to prevent errors due to electrical noise and interference. Separate
conduits are not necessary for the two cables, but a dedicated conduit
line between each transmitter and flowtube is required. Shielded cable
must be used for best results in electrically noisy environments.
Conduit Cables
Run the appropriate size cable through the conduit connections in your
magnetic flowmeter system. Run the power cable from the power
source to the transmitter. Run the coil drive and electrode cables
between the flowmeter and transmitter. Prepare the ends of the coil
drive and electrode cables as shown in Figure 13. Limit the unshielded
wire length to 1-inch on both the electrode and coil drive cables.
Excessive lead length or failure to connect cable shields can create
electrical noise resulting in unstable meter readings.
FINAL
Quick Installation Guide
00825-0100-4793, Rev BA
July 2003
Figure 13. Cable Preparation Detail
Cable Shield
Step 6.1 Transmitter Coil Input
This wiring section covers supplying power to the flowtube coils
through the transmitter. The transmitter coil input power sends a
pulsed DC frequency to the flowtube.
Wire the transmitter according to local electrical requirements. Ground
the transmitter cage via the threaded conduit connection. For ac power
applications, connect ac Neutral to terminal N and connect ac Line to
terminal L1. For dc power applications, properly connect the positive
and negative terminals. Units powered by 15-50 V dc power supply
may draw up to 1 amp of current. In addition, follow the supply wire
and disconnect requirements below:
Rosemount 8742C/8700 Series
1.00
(26)
NOTE
Dimensions are in
inches (millimeters).
FINAL
8705/0041a.eps
Quick Installation Guide
00825-0100-4793, Rev BA
July 2003
Figure 14. Power Supply Current
1.0
0.75
0.5
0.25
0
Supply Current (Amps)
I = 10/V
I = Supply current requirement (Amps)
V = Power supply voltage (Volts)
Supply Wire Requirements
Use 12 to 18 AWG wire rated for the proper temperature application.
For connections in ambient temperatures above 140 °F (60 °C), use a
wire rated for 176 °F (80 °C). For ambients greater than 176 °F (80
°C), use a wire rated for 230 °F (110 °C).
Disconnects
Connect the device through an external disconnect or circuit breaker.
Clearly label the disconnect or circuit breaker and locate it near
the transmitter and per local electrical control.
Rosemount 8742C/8700 Series
15
20
30
Power Supply (Volts)
40
FINAL
50
Installation Category
The installation category for the 8742C is (Overvoltage) Category II.
Quick Installation Guide
00825-0100-4793, Rev BA
July 2003
Rosemount 8742C/8700 Series
Overcurrent Protection
The 8742C Flowmeter Transmitter requires overcurrent protection of
the supply lines. Maximum ratings of overcurrent devices are as
follows:
Power
System
110 V ac250 V; 1 Amp, Quick ActingBussman AGCI or Equivalent
220 V ac250 V; 0.5 Amp, Quick ActingBussman AGCI or Equivalent
Fuse RatingManufacturer
Step 6.2 Transmitter Communication Input
The FOUNDATION fieldbus communication requires a minimum of
9 V dc and a maximum of 32 V dc at the transmitter communication
terminals. Do not exceed 32 V dc at the transmitter
communication terminals. Do not apply ac line voltage to the
transmitter communication terminals. Improper supply voltage can
damage the transmitter.
Power Conditioning
Each fieldbus power supply requires a power conditioner to decouple
the power supply output from the fieldbus wiring segment.
Field Wiring
Power independent of the coil power supply must be supplied for
OUNDATION fieldbus communications. Use shielded, twisted pair for
F
best results.In order to get maximum performance in new applications,
twisted pair cable specifically designed for fieldbus communications
should be used. The number of devices on a fieldbus segment is
limited by the power supply voltage, the resistance of the cable, and
the amount of current drawn by each device.
Table 6. Ideal Cable Specifications for Fieldbus Wiring
The communication terminals are polarity insensitive: the polarity of
the dc power leads does not matter when connecting to the power
terminals. When wiring to screw terminals, crimped lugs are
recommended. Tighten the terminals to ensure adequate contact. Both
transmitter covers must be fully engaged to meet explosion proof
requirements. Do not remove the transmitter covers in an explosive
atmosphere when the transmitter is powered.
Figure 15. Power Connections
(The power supply, filter,
first terminator, and
configuration tool are
typically located in the
control room.)
Integrated
Conditioner
and Filter
Power
6234 ft (1900 m) max
(depending upon cable characteristics)
Terminators
(Spur)
Fieldbus
Segment
FINAL
(Spur)
(Trunk)
* Intrinsically safe installations may
allow fewer devices per I.S. barrier.
Devices 1 through 11*
Step 6.3 Transmitter to Flowtube Wiring
A single dedicated conduit run for the coil drive and electrode cables is
needed between a flowtube and a remote transmitter. Bundled cables
in a single conduit are likely to create interference and noise problems
in your system. Use one set of cables per conduit run.
8742-8742_01A
Quick Installation Guide
00825-0100-4793, Rev BA
July 2003
Rosemount 8742C/8700 Series
Figure 16. Conduit Preparation
Power
Outputs
Table 7. Cable Requirements
DescriptionLengthPart Number
Signal Cable (20 AWG) Belden
8762, Alpha 2411 equivalent
(1) Combination signal and coil drive cable is not recommended for
WrongRight
Coil Drive
and
Electrode
Power
Outputs
high-signal magmeter system. For remote mount installations, combination
signal and coil drive cable should be limited to less than 100 ft. (30 m).
Cables
(1)
FINAL
Power
Outputs
Power
Outputs
ft
m
ft
m
ft
m
Coil Drive
and
Electrode
Cables
08712-0061-0001
08712-0061-0003
08712-0060-0001
08712-0060-0013
08712-0752-0001
08712-0752-0003
Remote transmitter installations require equal lengths of signal and
coil drive cables. Integrally mounted transmitters are factory wired and
do not require interconnecting cables.
Lengths from 5 to 1,000 feet (1.5 to 300 meters) may be specified, and
will be shipped with the flowtube.
8705/0000a01a, 0000a01b.eps
Quick Installation Guide
00825-0100-4793, Rev BA
July 2003
Rosemount 8742C/8700 Series
Flowtube to Remote Mount Transmitter Connections
Figure 17. Remote Mount Wiring Diagram
Do not connect ac
power to the flowtube
or to terminals 1 and 2
of the transmitter, or
replacement of the
electronics board will
be necessary.
Flowtube to Integral Mount Transmitter Connections
Figure 18. Integral Mount Wiring Diagram
Electronics
Board
FINAL
Do not connect
ac power to the
flowtube or to
terminals 1 and 2
of the transmitter,
or replacement of
the electronics
board will be
necessary.
8742b_07a,8742/8742_07.eps
8732-8732B01A,8742/8742_08
Quick Installation Guide
00825-0100-4793, Rev BA
July 2003
Rosemount 8742C/8700 Series
Step 7: Basic Configuration
Quick Start-Up
Once the magnetic flowmeter system is installed and communication
is established, configuration of the transmitter must be completed. The
standard transmitter configuration, without Option Code C1, Custom
Configuration, is shipped with the following parameters:
Engineering Units: ft/s
Tube Size: 3-in.
Flowtube Calibration Number: 100000501000000
Assigning Device Tag and Node Address
The 8742C Magnetic Flowmeter Transmitter is shipped with a blank
tag and a temporary address to allow a host to automatically assign an
address and a tag. If the tag or address need to be changed, use the
features of the configuration tool. The tools do the following:
• Change the tag to a new value.
• Change the address to a new address.
When the device is at a temporary address, only the tag and address
can be changed or written to. The resource, transducer, and function
blocks are all disabled.
FINAL
Quick Installation Guide
00825-0100-4793, Rev BA
July 2003
Flow-Specific Block Configuration
AI Block
The Analog Input (AI) function block provides the primary interface of
the measurement to the control and/or monitoring systems. To
properly configure the device, three parameters must be set in order to
correctly interface between the AI block and transducer block.
1. The CHANNEL parameter defines which transducer block
measurement is used by the AI block. In the 8742C Magnetic
Flowmeter Transmitter, only one channel is available:
AI1.CHANNEL = 1 (Flow).
2. The second parameter is the XD_SCALE.UNITS_INDX. The
default configuration is feet per second (ft/s).
3. Finally, since the flow measurement from the transducer block is in
the correct units, L_TYPE is configured as Direct. L_TYPE can be
either Direct or Indirect.
General Block Configuration
In general, only the transducer block and AI block have configurations
for flow-specific parameters. All other function blocks are configured
by linking the AI block to other blocks to be used for control and/or
monitoring applications.
NOTE
Refer to the F
00809-0100-4783, for more details on configuring and troubleshooting
the AI block.
OUNDATION fieldbus Block product manual, document
Rosemount 8742C/8700 Series
FINAL
Quick Installation Guide
00825-0100-4793, Rev BA
July 2003
Rosemount 8742C/8700 Series
Product Certifications
Approved Manufacturing Locations
Rosemount Inc. — Chanhassen, Minnesota, USA
Fisher-Rosemount Technologias de Flujo, S.A. de C.V. —
Chihuahua, Chihuahua, Mexico
European Directive Information
The EC declaration of conformity for all applicable European directives
for this product can be found on our website at www.rosemount.com.
A hard copy may be obtained by contacting our local sales office.
ATEX Directive
Rosemount Inc. complies with the ATEX Directive.
Flame-Proof enclosure Ex d protection type in
accordance with EN50 018
• Transmitters with Flame-Proof enclosure type protection shall only
be opened when power is removed.
• Closing of entries in the device must be carried out using the
appropriate EEx d metal cable gland or metal blanking plug.
• Do not exceed the energy level, which is stated on the approval
label.
Type n protection type in accordance with EN50 021
• Closing of entries in the device must be carried out using the
appropriate EExe or EExn metal cable gland and metal blanking
plug or any appropriate ATEX approved cable gland and blanking
plug with IP66 rating certified by an EU approved certification
body.
FINAL
Quick Installation Guide
00825-0100-4793, Rev BA
July 2003
European Pressure Equipment Directive (PED) (97/23/EC)
Rosemount 8705 Magnetic Flowmeter flowtubes in line size and
flange combinations:
Line Size: 1 1/2 inch / Flange Type ANSI 600, ANSI 900
Line Size: 2 inch / Flange Type ANSI 300, ANSI 600, ANSI 900
Line Size: 3 inch / Flange Type PN40, ANSI 300, ANSI 600, ANSI 900
Line Size: 4 inch / Flange Type PN 40, ANSI 300, ANSI 600, ANSI 900
Line Size: 6 inch / all Flange Types
Line Size: 8 inch / PN16, PN25, PN40, ANSI 150,
ANSI300, ANSI 600, ANSI900
Line Size: 10, 12, 14, 16, 18, 20, 24, 30, 36 inch / all Flange Types
QS Certificate of Assessment - EC No. PED-H-20
Module H Conformity Assessment
Rosemount 8711 Magnetic Flowmeter Flowtubes
Line Sizes: 1.5, 2, 3, 4, 6, and 8 inch
QS Certificate of Assessment - EC No. PED-H-20
Module H Conformity Assessment
All other Rosemount 8705/8711 Flowtubes —
Sound Engineering Practice
Flowtubes that are SEP or Category I with Explosion-Proof protection
are outside the scope of PED and cannot be marked for compliance
with PED.
Mandatory CE-marking for flowtubes in accordance with Article 15 of
the PED can be found on the flowtube body (CE 0434).
Flowtube categories I – IV, use module H for conformity assessment
procedures.
Rosemount 8742C/8700 Series
FINAL
Quick Installation Guide
00825-0100-4793, Rev BA
July 2003
Electro Magnetic Compatibility (EMC) (89/336/EEC)
All Models EN 50081-1: 1992, EN 50082-2: 1995, EN 61326-1: 1997
Installed signal wiring should not be run together and should not be in
the same cable tray as AC power wiring.
Device must be properly grounded or earthed according to local
electric codes.
To improve protection against signal interference, shielded cable is
recommended, see “Connect Wiring and Power Up” on page 16 for
more information.
Low Voltage Directive (93/68/EEC)
All Models 8742
EN 61010-1: 1995
Other important guidelines
Only use new, original parts.
To prevent the process medium escaping, do not unscrew or remove
process flange bolts, adapter bolts or bleed screws during operation.
Maintenance shall only be done by qualified personnel.
Hazardous Location Certifications
Equivalent Hazardous Location Certifications for flowtube and
transmitter must match in integrally-mounted magnetic flowmeter
systems. Remote-mounted systems do not require matched
hazardous location certification option codes.
Rosemount 8742C/8700 Series
FINAL
Quick Installation Guide
00825-0100-4793, Rev BA
July 2003
Rosemount 8742C/8700 Series
Transmitter Approval Information
TABLE 8. Transmitter Option Codes
Approval CodesFieldbus OutputI.S. fieldbus Output
N0•
N5•
E5•
ED•
K0••
K5••
(1)
KD
(1) Refer to Table 10 on page 36 for relation between ambient temperature,
process temperature, and temperature class.
North American Certifications
Factory Mutual (FM)
N0Division 2 Approval
Class I, Division 2, Groups A, B, C, D
Temp Code – T4 at 60°C
Dust-Ignition proof Class II/III, Division 1, Groups E, F, G
Temp Code – T6 at 60°C
Enclosure Type 4X
Rosemount 8742 Transmitter
••
FINAL
Quick Installation Guide
00825-0100-4793, Rev BA
July 2003
N5Division 2 Approval for flowtubes with IS electrodes only
Class I, Division 2, Groups A, B, C, D
Temp Codes – T4 at 60°C
Dust-Ignition proof Class II/III, Division 1, Groups E, F, G
Temp Code – T6 at 60°C
Enclosure Type 4X
E5Explosion-Proof Approval
Explosion-Proof for Class I, Division 1, Groups C, D
Temp Code – T6 at 60°C
Dust-Ignition proof Class II/III, Division 1, Groups E, F, G
Temp Code – T6 at 60°C
Class I, Division 2, Groups A, B, C, D
Temp Codes – T4 at 60°C,
Enclosure Type 4X
K0Division 2 Approval with Intrinsically Safe Output
Reference Rosemount Control Drawing 08742-1051
Class I, Division 2, Groups A, B, C, D with IS output for Class I,
Division 1, Groups A, B, C, D. Temp Code – T4 at 60°C
Dust-Ignition proof Class II/III, Division 1, Groups E, F, G
Temp Code – T6 at 60°C
Enclosure Type 4X
K5Explosion-Proof Approval with Intrinsically Safe Output
Reference Rosemount Control Drawing 08742-1051
Explosion-Proof for Class I, Division 1, Groups C, D with IS output
for Class I, Division 1, Groups A, B, C, D. Temp Code – T6 at 60°C
Dust-Ignition proof Class II/III, Division 1, Groups E, F, G
Temp Code – T6 at 60°C
Class I, Division 2, Groups A, B, C, D
Temp Codes – T4 60°C
Enclosure Type 4X
Rosemount 8742C/8700 Series
FINAL
Quick Installation Guide
00825-0100-4793, Rev BA
July 2003
Canadian Standards Association (CSA)
N0 Suitable for Class I, Division 2, Groups A, B, C, D
Temp Code T4 at 60°C
Dust-Ignition proof Class II/III, Division 1, Groups E, F, G
Enclosure Type 4X
K0 Reference Rosemount Control Drawing 08742-1052
Suitable for Class I, Division 2, Groups A, B, C, D with IS output for
Class I, Division 1, Groups A, B, C, D. Temp Code – T4 at 40°C
Dust-Ignition proof Class II/III, Division 1, Groups E, F, G
Enclosure Type 4X
European Certifications
EDCENELEC Flame-Proof
Certificate No: KEMA03ATEX2159X II 2G
EEx de IIB T6 (Ta = -20°C to +65°C)
= 250 V AC or 50 V DC
V
max
0575
KD CENELEC Flame-Proof with
Intrinsically Safe Output
Certificate No: KEMA03ATEX2159X II 2G
EEx de [ia] IIB T6 (Ta = -20°C to +65°C)
V
= 250 V AC or 50 V DC
max
0575
Rosemount 8742C/8700 Series
FINAL
Quick Installation Guide
00825-0100-4793, Rev BA
July 2003
Rosemount 8742C/8700 Series
SPECIAL CONDITIONS FOR SAFE USE (X):
The relation between ambient temperature, process temperature and
temperature class is to be taken from the table under (15 - description)
above. (See Table 10).
INSTALLATION INSTRUCTIONS:
The cable and conduit entry devices and the closing elements shall be
of a certified increased safety type, suitable for the conditions of use
and correctly installed.
At ambient temperatures above 50°C, the flow meter shall be used
with heat resistant cables with a temperature rating of at least 90°C.
(1) CE Marking is standard on Rosemount 8705 and 8711. No hazardous
(2) Refer to Table 10 on page 36 for relation between ambient temperature,
For
Non-flammable
Fluids
(2)
(2)
location certifications are available on the Rosemount 570TM.
process temperature, and temperature class.
Flammable
Fluids
••
(1)
For
For
Non-flammable
Fluids
••
••••
For
Flammable
Fluids
Non-flammable
Fluids
For
FINAL
Flammable
Fluids
••
••
For
Quick Installation Guide
00825-0100-4793, Rev BA
July 2003
North American Certifications
Factory Mutual (FM)
N0Division 2 Approval for
Non-Flammable Fluids (All Flowtubes)
Class I, Division 2, Groups A, B, C, D
Temp Code – T5 (8705/8711 at 60°C)
Temp Code – T3C (8707 at 60°C)
Dust-Ignition proof Class II/III, Division 1, Groups E, F, G
Temp Code – T6 (8705/8711 at 60°C)
Temp Code – T5 (8707 at 60°C)
Enclosure Type 4X
N5Division 2 Approval for Flammable Fluids
(All Flowtubes)
Class I, Division 2, Groups A, B, C, D
Temp Code – T5 (8705/8711 at 60°C)
Temp Code – T3C (8707 at 60°C)
Dust-Ignition proof Class II/III, Division 1, Groups E, F, G
Temp Code – T6 (8705/8711 at 60°C)
Temp Code – T5 (8707 at 60°C)
Enclosure Type 4X
E5Explosion-Proof (8711 Only)
Explosion-Proof for Class I, Division 1, Groups C, D
Temp Code – T6 at 60°C
Dust-Ignition proof Class II/III, Division 1, Groups E, F, G
Temp Code – T6 at 60°C
Class I, Division 2, Groups A, B, C, D
Temp Code – T5 at 60°C
Enclosure Type 4X
Rosemount 8742C/8700 Series
FINAL
Quick Installation Guide
00825-0100-4793, Rev BA
July 2003
Canadian Standards Association (CSA)
Suitable for Class I, Division 2, Groups A, B, C, D
Temp Code – T5 (8705/8711 at 60°C)
Temp Code – T3C (8707 at 60°C)
Dust-Ignition proof Class II/III, Division 1, Groups E, F, G
Enclosure Type 4X
European Certifications
N1Pending - CENELEC Non-Sparking/Non-incendive
(8705/8711 Only)
Certificate No: KEMA02ATEX1302X II 3G
EEx nA [L] IIC T3... T6
SPECIAL CONDITIONS FOR SAFE USE (X):
To Be Determined
CD CENELEC Increased Safety (Zone 1)
with IS Electrodes (8711 only)
Certificate No: KEMA03ATEX2052X II 1/2G
EEx e ia IIC T3... T6 (Ta = -20 to +65°) (See Table 10)
0575
INSTALLATION INSTRUCTIONS:
At ambient temperature above 50°C, the flowmeter shall be used with
heat resistant cables with a temperature rating of at least 90°C.
A fuse with a rating of maximum 0,7 A according to IEC 127 shall be
included in the coil excitation circuit if the flowtubes are used with other
flow transmitters (e.g. Model 8712).
Rosemount 8742C/8700 Series
FINAL
Quick Installation Guide
00825-0100-4793, Rev BA
July 2003
KD CENELEC Increased Safety (Zone 1)
with IS Electrodes (8705 only)
Certificate No. KEMA 03ATEX2052X II 1/2G
EEx e ia IIC T3... T6 (Ta = -20 to 65°C) (See Table 10)
0575
INSTALLATION INSTRUCTIONS:
At ambient temperature above 50°C, the flowmeter shall be used with
heat resistant cables with a temperature rating of at least 90°C.
A fuse with a rating of maximum 0,7 A according to IEC 127 shall be
included in the coil excitation circuit if the flowtubes are used with
other flow transmitters (e.g. Model 8712).
Rosemount 8742C/8700 Series
FINAL
Quick Installation Guide
00825-0100-4793, Rev BA
July 2003
Rosemount 8742C/8700 Series
Table 10. Relation between ambient temperature, process temperature,
and temperature class
Meter Size
(Inches)
(1) This table is applicable for CD and KD option codes only.
Maximum Ambient
1
/2149°F (65°C)239°F (115°C)
1149°F (65°C)248°F (120°C)
195°F (35°C)95°F (35°C)
11/2149°F (65°C)257°F (125°C)
11/2140°F (60°C)140°F (60°C)
2149°F (65°C)257°F (125°C)
2149°F (65°C)167°F (75°C)
2104°F (40°C)104°F (40°C)
3 - 4149°F (65°C)266°F (130°C)
3 - 4149°F (65°C)194°F (90°C)
3 - 4131°F (55°C)131°F (55°C)
3 - 4104°F (40°C)104°F (40°C)
6149°F (65°C)275°F (135°C)
6149°F (65°C)230°F (110°C)
6149°F (65°C)167°F (75°C)
6140°F (60°C)140°F (60°C)
8 - 36149°F (65°C)284°F (140°C)
8 - 36149°F (65°C)239°F (115°C)
8 - 36149°F (65°C)176°F (80°C)
8 - 36149°F (65°C)149°F (65°C)
(1)
Temperature
Maximum Process
Tem per atu re
FINAL
Temperature Class
T3
T3
T4
T3
T4
T3
T4
T5
T3
T4
T5
T6
T3
T4
T5
T6
T3
T4
T5
T6
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.