Rosemount Magnetic Flow Meter System for Utility, Water, and Wastewater Applications - Model 8750WB Quick Start Guide

Quick Start Guide
00825-0200-4750, Rev AA
February 2014
Rosemount 8750WB Magnetic Flowmeter System
for Utility, Water, and Wastewater Applications
Quick Start Guide
February 2014
This document provides basic installation guidelines for the Rosemount® 8750W Magnetic Flowmeter System. For comprehensive instructions, for detailed configuration, diagnostics, maintenance, service, installation or troubleshooting, refer to the Rosemount 8750W reference manual (document number 00809-0100-4750 Rev. BA). The manual and this QSG are also available electronically on www.rosemount.com.
Failure to follow these installation guidelines could result in death or serious injury:
Installation and servicing instructions are for use by qualified personnel only. Do not perform
any servicing other than that contained in the operating instructions, unless qualified.
Verify that the operating environment of the sensor and transmitter is consistent with the
operating environment.
Do not connect a Rosemount transmitter to a non-Rosemount sensor that is located in an
explosive atmosphere.
The sensor liner is vulnerable to handling damage. Never place anything through the sensor
for the purpose of lifting or gaining leverage. Liner damage may render the sensor inoperable.
Metallic or spiral-wound gaskets should not be used as they will damage the liner face of the
sensor.
If frequent removal is anticipated, take precautions to protect the liner ends. Short spool
pieces attached to the sensor ends are often used for protection.
Rosemount Magnetic Flowmeters ordered with non-standard paint options may be subject to
electrostatic discharge. To avoid electrostatic charge build-up, do not rub the flowmeter with a dry cloth or clean with solvents.
Correct flange bolt tightening is crucial for proper sensor operation and life. All bolts must be
tightened in the proper sequence to the specified torque specifications. Failure to observe these instructions could result in severe damage to the sensor lining and possible sensor replacement.
Contents
Pre-installation . . . . . . . . . . . . . . page 3
Handling . . . . . . . . . . . . . . . . . . . page 7
Mounting . . . . . . . . . . . . . . . . . .page 8
Installation . . . . . . . . . . . . . . . . page 10
Grounding . . . . . . . . . . . . . . . .page 15
Wiring . . . . . . . . . . . . . . . . . . . . page 17
Basic configuration . . . . . . . . .page 28
2
February 2014
Quick Start Guide

Step 1: Pre-installation

Before installing the Rosemount 8750W Flowmeter, there are several pre-installation steps that should be completed to make the installation process easier:
Identify the options and configurations that apply to your application Set the hardware switches if necessary Consider mechanical, electrical, and environmental requirements

Mechanical considerations

The mounting site for the Rosemount 8750W transmitter should provide enough room for secure mounting, easy access to conduit ports, full opening of the transmitter covers, and easy readability of the LOI screen (see
Figure 2).
If the Rosemount 8750W transmitter is mounted separately from the sensor, it may not be subject to the same limitations that apply to the sensor.

Figure 1. Field mount transmitter dimensional drawing

7.49 (190)
6.48 (165)
LOI Cover
Figure 1 and
1
/2”-14 NPT (3 places)*
1
/2”-14 NPT (2 places)*
5.82
(148)
8.81
(224)
4.97
(126)
3.00 (76)
3.07 (78)
4.97
(126)
*Non- standard conduit entry thread. M20 connections are available with the use of threaded
conduit adapters.
3
Quick Start Guide

Figure 2. Wall mount transmitter dimensional drawing

WITH STANDARD COVER
February 2014
4.31
(109)
2.96 (75)
9.01
(229)
2.81 (71)
WITH LOI COVER
3.11 (79)
11.15 (283)
0.44 (11)
12.02 (305)
4
Ground Lug
NOTE
Dimensions are in inches (millimeters)
1
/2–14 NPT
Conduit
Connection
(4 Places)
LOI Keypad
Cover
February 2014
Quick Start Guide

Environmental considerations

To ensure maximum transmitter life, avoid extreme temperature and excessive vibration. Typical problem areas:
high-vibration lines with integrally mounted transmitters warm-climate installations in direct sunlight outdoor installations in cold climates.
Remote-mounted transmitters may be installed in the control room to protect the electronics from the harsh environment and provide easy access for configuration or service.
Both remotely and integrally mounted Rosemount 8750W transmitters require external power so there must be access to a suitable power source.
Installation procedures
Rosemount 8750W installation includes both detailed mechanical and electrical installation procedures.

Mount the transmitter

At a remote site the transmitter may be mounted on a pipe up to two inches in diameter or against a flat surface.

Pipe mounting

To mount the transmitter on a pipe:
1. Attach the mounting bracket to the pipe using the mounting hardware.
2. Attach the Rosemount 8750W transmitter to the mounting bracket using the mounting screws.

Identify options and configurations

The standard application of the 8750W includes a 4–20 mA output and control of the sensor coils and electrodes. Other applications may require one or more of the following configurations or options:
HART Multidrop Configuration Discrete Output Discrete Input Pulse Output
Be sure to identify any additional options and configurations that apply to the installation. Keep a list of these options nearby for consideration during the installation and configuration procedures.
5
Quick Start Guide

Hardware jumpers/switches

The 8750W electronics board is equipped with user-selectable hardware switches depending on the transmitter model ordered. These switches set the Failure Alarm Mode, Internal/External Analog Power, Internal/External Pulse Power and Transmitter Security. The standard configuration for these switches when shipped from the factory is as follows:
Failure Alarm Mode: HIGH
Internal/External Analog Power: INTERNAL
Internal/External Pulse Power: EXTERNAL (Field Mount only)
Transmitter Security: OFF

Changing hardware switch settings

In most cases, it will not be necessary to change the setting of the hardware switches. If the switch settings need to be changed, follow the steps outlined in the manual.
Use a non-metallic tool to move switch positions.

Electrical considerations

Before making any electrical connections to the Rosemount 8750W, consider national, local and plant electrical installation requirements. Be sure to have the proper power supply, conduit, and other accessories necessary to comply with these standards.
February 2014

Rotate transmitter housing

The Field Mount transmitter housing can be rotated on the sensor in 90° increments by removing the four mounting bolts on the bottom of the housing. Do not rotate the housing more than 180 ° in any one direction. Prior to tightening, be sure the mating surfaces are clean, the O-ring is seated in the groove, and there is no gap between the housing and the sensor.
6
February 2014
Quick Start Guide

Step 2: Handling

Handle all parts carefully to prevent damage. Whenever possible, transport the system to the installation site in the original shipping containers. Rosemount flow sensors are shipped with end covers that protect it from mechanical damage. For PTFE lined sensors the cover also prevents normal liner relaxation. Remove the end covers just before installation.

Figure 3. Rosemount 8750W flanged sensor support for handling

½- through 4-Inch Sensors
5-Inch and Larger Sensors
7
Quick Start Guide

Step 3: Mounting

Upstream/downstream piping

To ensure specification accuracy over widely varying process conditions, install the sensor a minimum of five straight pipe diameters upstream and two pipe diameters downstream from the electrode plane (see

Figure 4. Upstream and downstream straight pipe diameters

5 Pipe Diameters
Flow
Installations with reduced upstream and downstream straight runs are possible. In reduced straight run installations, absolute performance may shift. Reported flow rates will still be highly repeatable.
The sensor should be mounted so the FORWARD end of the flow arrow points in the direction of flow through the sensor (see
Figure 5).
Figure 4).
2 Pipe Diameters
February 2014

Figure 5. Flow direction

8
February 2014
The sensor should be installed in a location that ensures it remains full during operation. Vertical installation with upward process fluid flow keeps the cross-sectional area full, regardless of flow rate. Horizontal installation should be restricted to low piping sections that are normally full.

Figure 6. Sensor orientation

FLOW
FLOW
Quick Start Guide
Mounting position
The electrodes in the sensor are properly orientated when the two measurement electrodes are in the 3 and 9 o’clock position or within 45 ° from the vertical, as shown on the right of measurement electrodes are in the 6 and 12 o’clock position as shown on the left of
Figure 7.
Figure 7. Avoid any mounting orientation where the two

Figure 7. Sensor mounting position

Incorrect Correct
9
Quick Start Guide
February 2014

Step 4: Installation

Flanged sensors

Gaskets

The sensor requires a gasket at each of its connections to adjacent devices or piping. The gasket material selected must be compatible with the process fluid and operating conditions. Gaskets are required on each side of a grounding ring. All other applications (including sensors with lining protectors or a grounding electrode) require only one gasket on each end connection.
Metallic or spiral-wound gaskets should not be used as they will damage the liner face of the sensor. If spiral wound or metallic gaskets are required for the application, lining protectors must be used.

Figure 8. Flanged gasket placement

10
February 2014
Quick Start Guide

Flange bolts

Do not bolt one side at a time. Tighten each side simultaneously. Example:
1. Snug upstream
2. Snug downstream
3. Tighten upstream
4. Tighten downstream
Do not snug and tighten the upstream side and then snug and tighten the downstream side.
Failure to alternate between the upstream and downstream flanges when tightening bolts may result in liner damage. Suggested torque values by sensor line size and liner type are listed in
page 12. Consult the factory if the flange rating of the sensor is not listed.
Tighten flange bolts on the upstream side of the sensor in the incremental sequence shown in Repeat the process on the downstream side of the sensor. For sensors with more or less flange bolts, tighten the bolts in a similar crosswise sequence. Repeat this entire tightening sequence at 40%, 60%, 80%, and 100% of the suggested torque values or until the leak between the process and sensor flanges stop.
If leakage has not stopped at the suggested torque values, the bolts can be tightened in additional 10% increments until the joint stops leaking, or until the measured torque value reaches the maximum torque value of the bolts. Practical consideration for the integrity of the liner often leads the user to distinct torque values to stop leakage due to the unique combinations of flanges, bolts, gaskets, and sensor liner material.
Check for leaks at the flanges after tightening the bolts. Failure to use the correct tightening methods can result in severe damage. Sensors require a second tightening 24 hours after the initial installation. Over time, sensor liner materials may deform under pressure.
Figure 9 on page 11 to 20% of the suggested torque values.
Table 1 on

Figure 9. Flange bolt torquing sequence

For torque values not listed in Table 1, Table 2, or Table 3, contact technical support.
11
Quick Start Guide
Table 1. Suggested flange bolt torque values for ASME
PTFE liner Neoprene liner
Size code Line size
005 0.5 inch (15 mm) 8 8 - -
010 1 inch (25 mm) 8 12 - -
015 1.5 inch (40 mm) 13 25 7 18
020 2 inch (50 mm) 19 17 14 11
025 2.5 inch (65 mm) 22 24 17 16
030 3 inch (80 mm) 34 35 23 23
040 4 inch (100 mm) 26 50 17 32
050 5 inch (125 mm) 36 60 25 35
060 6 inch (150 mm) 45 50 30 37
080 8 inch (200 mm) 60 82 42 55
100 10 inch (250 mm) 55 80 40 70
120 12 inch (300 mm) 65 125 55 105
140 14 inch (350 mm) 85 110 70 95
160 16 inch (400 mm) 85 160 65 140
180 18 inch (450 mm) 120 170 95 150
200 20 inch (500 mm) 110 175 90 150
240 24 inch (600 mm) 165 280 140 250
300 30 inch (750 mm) 195 415 165 375
360 36 inch (900 mm) 280 575 245 525
Class 150
(pound-feet)
Class 300
(pound-feet)
Class 150
(pound-feet)
February 2014
Class 300
(pound-feet)
12
February 2014
Table 2. Suggested flange bolt torque values for EN1092-1
PTFE liner
Size
code
005
010
015
020
025
030
040
050
060
080
100
120
140
160
180
200
240
Line size
0.5-inch
(15 mm)
1 inch
(25 mm)
1.5 inch
(40 mm)
2 inch
(50 mm)
2.5 inch
(65 mm)
3 inch
(80 mm)
4 inch
(100 mm)
5.0 inch
(125 mm)
6 inch
(150mm)
8 inch
(200 mm)
10 inch
(250 mm)
12 inch
(300 mm)
14 inch
(350 mm)
16 inch
(400 mm)
18 inch
(450 mm)
20 inch
(500 mm)
24 inch
(600 mm)
PN10 PN 16 PN 25 PN 40
(Newton-meter) (Newton-meter) (Newton-meter) (Newton-meter)
50 70
70 100
90 130
130 90 130 170
100 130 190 250
120 170 190 270
160 220 320 410
220 280 410 610
190 340 330 420
230 380 440 520
290 570 590 850
Quick Start Guide
10
20
50
60
50
50
13
Quick Start Guide
February 2014
Table 2. (cont) Suggested flange bolt torque values for EN1092-1
Neoprene liner
Size
code
010
015
020
025
030
040
050
060
080
100
120
140
160
180
200
240
Line size
1 inch
(25 mm)
1.5 inch
(40 mm)
2 inch
(50 mm)
2.5 inch
(65 mm)
3 inch
(80 mm)
4 inch
(100 mm)
5.0 inch
(125 mm)
6 inch
(150 mm)
8 inch
(200 mm)
10 inch
(250 mm)
12 inch
(300 mm)
14 inch
(350 mm)
16 inch
(400 mm)
18 inch
(450 mm)
20 inch
(500 mm)
24 inch
(600 mm)
PN 10 PN 16 PN 25 PN 40
(Newton-meter) (Newton-meter) (Newton-meter) (Newton-meter)
40 50
50 70
60 90
90 60 90 110
70 80 130 170
80 110 130 180
110 150 210 280
150 190 280 410
130 230 220 280
150 260 300 350
200 380 390 560
20
30
40
35
30
Table 3. Flange bolt torque and load specifications for large line sizes
AWWA C207 (Ft-Lbs) EN1092-1 (N-m)
40-in. (1000 mm)
42-in. (1050 mm)
48-in. (1200 mm)
AS2129 (N-m) AS4087 (N-m)
40-in. (1000 mm)
48-in. (1200 mm)
Class D
Class E
Class D
Class E
Class D
Class E
Table D
Table E
Table D
Table E
757
757 PN10 413
839 PN16 478
839
872 PN10 622
872
614
652 PN21 515
786
839 PN21 840
40-in. (1000 mm)
48-in. (1200 mm)
40-in. (1000 mm)
48-in. (1200 mm)
14
PN6 208
PN6 375
PN16 612
PN16 785
February 2014
Quick Start Guide

Step 5: Grounding

Use Table 4 to determine which process grounding option to follow for proper installation. The sensor case should be grounded in accordance with national and local electrical codes. Failure to do so may impair the protection provided by the equipment.
Table 4. Process grounding installation
Process grounding options
Grounding
Type of pipe Grounding straps
Conductive Unlined Pipe
Conductive Lined Pipe
Non-Conductive Pipe
See Figure 10 See Figure 11 See Figure 13 See Figure 11
Insufficient Grounding
Insufficient Grounding
rings
See Figure 11 See Figure 10 See Figure 11
See Figure 12
Figure 10. Grounding straps in conductive lined pipe or reference electrode in
lined pipe
Reference
electrode
Not Recommended
Lining
protectors
See Figure 12

Figure 11. Grounding with grounding rings or lining protectors in conductive pipe

Grounding
Rings or
Lining
Protectors
15
Quick Start Guide
February 2014
Figure 12. Grounding with grounding rings or lining protectors in non-conductive
pipe
Grounding
Rings or
Lining
Protectors

Figure 13. Grounding with reference electrode in conductive unlined pipe

16
February 2014
Quick Start Guide

Step 6: Wiring

This wiring section covers the connection between the transmitter and sensor, the 4-20 mA loop, and supplying power to the transmitter. Follow the conduit information, cable requirements, and disconnect requirements in the sections below.

Conduit ports and connections

Both the sensor and transmitter junction boxes have ports for 1/2-inch NPT conduit connections or optional M20 connection is available. These connections should be made in accordance with national, local, and plant electrical codes. Unused ports should be sealed with metal plugs. Proper electrical installation is necessary to prevent errors due to electrical noise and interference. Separate conduits are not necessary for the coil drive and electrode cables, but a dedicated conduit line between each transmitter and sensor is required. Shielded cable must be used for best results in electrically noisy environments. When preparing all wire connections, remove only the insulation required to fit the wire completely under the terminal connection. Removal of excessive insulation may result in an unwanted electrical short to the transmitter housing or other wire connections. For flanged sensors installed into an application requiring IP68 protection, sealed cable glands, conduit, and conduit plugs that meet IP68 ratings are required. Option Codes R05, R10, R15, R20, R25, and R30 provide a pre-wired potted and sealed junction box as additional protection to prevent the ingress of water. These options still require the use of sealed conduits to meet IP68 protection requirements.

Conduit requirements

A single dedicated conduit run for the coil drive and electrode cable is needed between the sensor and the remote transmitter. See in a single conduit are likely to create interference and noise problems in the system.
Electrode cables should not be run together and should not be in the same cable ray with power cables.
Output cables should not be run together with power cables.
Select conduit size appropriate to feed cables through to the flowmeter.

Figure 14. Conduit preparation

Wrong
Coil Drive and
Power
Outputs
Power
Electrode Cables
Power
Outputs
Figure 14. Bundled cables
Correct
Power
Outputs
Coil Drive and Electrode Cables
17
Quick Start Guide
Run the appropriate size cable through the conduit connections in your magnetic flowmeter system. Run the power cable from the power source to the transmitter. Run the coil drive and electrode cables between the flowmeter sensor and transmitter.
Installed signal wiring should not be run together and should not be in the
same cable tray as AC or DC power wiring.
Device must be properly grounded according to national and local electric
codes.
Rosemount combination cable part number 08732-0753-1003 (ft) or
08732-0753-2004 (m) is required to be used to meet EMC requirements.

Transmitter to sensor wiring

The transmitter can be integral to the sensor or remotely mounted following the wiring instructions.

Remote mount cable requirements and preparation

For installations using the individual coil drive and electrode cable, lengths should be limited to less than 1,000 feet (300 meters). Equal length cable is required for each. See
For installations using the combination coil drive and electrode cable, lengths should be limited to less than 330 feet (100 meters). See
Prepare the ends of the coil drive and electrode cables as shown in Limit the unshielded wire length to 1-inch on both the coil drive and electrode cables. Any unsheathed wire should be wrapped with proper insulation. Excessive lead length or failure to connect cable shields can create electrical noise resulting in unstable meter readings.
Table 5 on page 19.
Table 5 on page 19.
Figure 15.
February 2014

Figure 15. Cable preparation detail

Cable Shield
18
NOTE Dimensions are in inches (mm).
1.00 (26)
February 2014
Quick Start Guide
To order cable specify length as quantity desired. 25 feet = Qty (25) 08732-0753-1003
Table 5. Cable requirements
Description Length Part number
Coil Drive Cable (14 AWG) Belden 8720, Alpha 2442 or equivalent
Electrode Cable (20 AWG) Belden 8762, Alpha 2411 or equivalent
Combination Cable Coil Drive Cable (18 AWG) and Electrode Cable (20 AWG)
ft
m
ft
m
ft
m
08712-0060-0001 08712-0060-2013
08712-0061-0001 08712-0061-2003
08732-0753-1003 08732-0753-2004
Potential Shock Hazard Across Terminals 1 & 2 (40 VAC).

Wiring the transmitter to the sensor

When using individual cables for coil drive and electrode refer to Table 6. If using the combination coil drive and electrode cable, refer to
on page 20 for transmitter specific wiring diagrams.
1. Connect the coil drive cable using terminals 1, 2, and 3.
2. Connect the electrode cable using terminals 17, 18, and 19
Table 7. See Figure 16
Table 6. Individual coil and electrode cables
Transmitter terminal Sensor terminal Wire gauge Wire color
1 1 14 Clear
2 2 14 Black
3 3 14 Shield
17 17 20 Shield
18 18 20 Black
19 19 20 Clear
19
Quick Start Guide
Table 7. Combination coil and electrode cable
Transmitter terminal Sensor terminal Wire gauge Wire color
1 1 18 Red
2 2 18 Green
3 3 18 Shield
17 17 20 Shield
18 18 20 Black
19 19 20 White

Figure 16. Remote mount wiring diagrams

February 2014
20
February 2014
Quick Start Guide
Note
When using the Rosemount supplied combination cable, the electrode wires for terminals 18 and 19 contain an addition shield wire. These two shield wires should be tied with the main shield wire at terminal 17. See Figure 17.

Figure 17. Combination coil and electrode cable wiring diagram

Coil Drive Cable Electrode Cable
1 Red 2 Green 3 Shield
17 Shield 18 Black 19 White

Integral mount transmitters

The interconnecting wire harness for an integral mount transmitter is installed at the factory. See Process Management, Rosemount, Inc.
Figure 18. 8750W integral mount wiring Diagram
Figure 18. Do not use cable other than that supplied by Emerson
21
Quick Start Guide

Connecting the 4–20 mA analog signal

Cabling considerations

If possible, use individually shielded twisted pair cable, either in single pair or multi-pair varieties. Unshielded cables may be used for short distances, provided ambient noise and cross-talk will not adversely impact communication. The minimum conductor size is 0.51mm diameter (#24 AWG) for cable runs less than 1,500 meters (@ 5,000 ft.) and 0.81mm diameter (#20 AWG) for longer distances. Resistance in the loop must be 1000 ohms or less.
The 4–20 mA analog output loop signal may be powered internally or externally. The default position of the internal/external analog power switch is in the internal position. The user-selectable power supply switch is located on the electronics board.
Figure 19. Field mount analog signal wiring diagram
February 2014
+4–20 mA –4–20 mA
Analog output - connect negative (-)DC to Terminal 1 and positive (+)DC to Terminal 2. See
22
Figure 19.
February 2014
Figure 20. Wall mount analog signal wiring diagram
Quick Start Guide
+4–20 mA
–4–20 mA
Analog output - connect negative (-)DC to Terminal 8 and positive (+)DC to Terminal 7. See
Figure 20.

Internal power source

The 4–20 mA analog signal loop is powered from the transmitter itself.

External power source

The 4–20 mA analog signal loop is powered from an external power source. HART multidrop installations require a 10–30 VDC external analog power source.
Note:
If a HART Field Communicator or control system will be used, it must be connected across a minimum of 250 ohms resistance in the loop.
To connect any of the other output options (pulse output and/or discrete input/output), consult the comprehensive product manual.
23
Quick Start Guide
2

Powering the transmitter

The 8750W transmitter is designed to be powered by 90-250 VAC, 50–60 Hz, or 12–42 VDC. Before connecting power to the Rosemount 8750W, consider the following standards and be sure to have the proper power supply, conduit, and other accessories. Wire the transmitter according to national, local, and plant electrical requirements for the supply voltage. See

Figure 21. DC power supply current requirements

1
0.75
0.5
0.25
Supply Current (Amps)
0
12 18 24 30 36 4
Power Supply (Volts)
Figure 21 and Figure 22.
February 2014
24
February 2014

Figure 22. AC power supply requirements

0.320
0.300
0.280
0.260
0.240
0.220
0.200
0.180
0.160
0.140
Supply Current (Amps)
0.120
0.100
80 100 120
140
160 180
Power Supply Voltage (AC RMS)

Figure 23. Apparent power

38
36
34
32
30
28
26
24
Apparent Power (VA)
22
20
80 100 120 140 160 180 200 220 240
Quick Start Guide
200
220 240
250
Power Supply Voltage (AC RMS)

Supply wire requirements

Use 10 - 18 AWG wire rated for the proper temperature of the application. For wire 10 - 14 AWG use lugs or other appropriate connectors. For connections in ambient temperatures above 140 °F (60 °C), use a wire rated for 176 °F (80 °C). For ambient temperatures greater than 176 °F (80 °C), use a wire rated for 230 °F (110 °C). For DC powered transmitters with extended cable lengths, verify that there is a minimum of 12 VDC at the terminals of the transmitter. Disconnects
Connect the device through an external disconnect or circuit breaker.

Installation category

The installation category for the 8750W is (Overvoltage) Category II.

Overcurrent protection

The Rosemount 8750W flowmeter transmitter requires overcurrent protection of the supply lines. Maximum ratings of overcurrent devices are shown in
Table 8.
25
Quick Start Guide
Table 8. Overcurrent limits
Power system Fuse rating Manufacturer
95-250 VAC 2 Amp, Quick Acting Bussman AGC2 or Equivalent
12-42 VDC 3 Amp, Quick Acting Bussman AGC3 or Equivalent

Field mount power supply

For AC power applications (90-250 VAC, 50-60 Hz), connect AC Neutral to terminal 9 (AC N/L2) and connect AC Line to terminal 10 (AC/L1). For DC power applications, connect negative to terminal 9 (DC -) and positive to terminal 10 (DC +). Units powered by 12-42 VDC power supply may draw up to 1 amp of current. See
Figure 24. Field mount transmitter power connections
Figure 24 for terminal block connections.
February 2014

Wall mount power supply

For AC power applications (90-250 VAC, 50-60 Hz), connect AC Neutral to terminal N and connect AC Line to terminal L1. For DC power applications, connect negative to terminal N (DC -) and positive to terminal L1 (DC +). Ground the transmitter cage via the grounding stud located on the bottom of the transmitter housing. Units powered by 12-42 VDC power supply may draw up to 1 amp of current. See
26
Figure 25 for terminal block connections.
February 2014
Figure 25. Wall mount transmitter power connections
Fuse
AC Line or DC+
Quick Start Guide
AC Ground or DC Ground
AC Neutral or DC–
Transmitter
Power Cable
Field mount cover jam screw
For transmitter housings shipped with a cover jam screw, the screw should be properly installed once the transmitter has been wired and powered up. Follow these steps to install the cover jam screw:
1. Verify that the cover jam screw is completely threaded into the housing.
2. Install the transmitter housing cover and verify that the cover is tight against the housing.
3. Using a 2.5 mm hex wrench, loosen the jam screw until it contacts the transmitter cover.
1
4. Turn the jam screw an additional (Note: Application of excessive torque may strip the threads.)
5. Verify that the cover cannot be removed.
/2 turn counterclockwise to secure the cover.
27
Quick Start Guide

Step 7: Basic configuration

Once the magnetic flowmeter is installed and power has been supplied, the transmitter must be configured through the basic setup. These parameters can be configured through either a local operator interface or a HART communication device. A table of all the parameters begins on advanced functions are included in the comprehensive product manual.
page 29. Descriptions of the more
Basic setup
Tag
Tag is the quickest and shortest way of identifying and distinguishing between transmitters. Transmitters can be tagged according to the requirements of your application. The tag may be up to eight characters long.

Flow units (PV)

The flow rate units variable specifies the format in which the flow rate will be displayed. Units should be selected to meet your particular metering needs.

URV (Upper Range Value)

The upper range value (URV) sets the 20 mA point for the analog output. This value is typically set to full-scale flow. The units that appear will be the same as those selected under the units parameter. The URV may be set between –39.3 ft/s to 39.3 ft/s (–12 m/s to 12 m/s). There must be at least 1 ft/s (0.3 m/s) span between the URV and LRV.
February 2014

LRV (Lower Range Value)

Reset the lower range value (LRV) sets the 4 mA point for the analog output. This value is typically set to zero flow. The units that appear will be the same as those selected under the units parameter. The LRV may be set between –39.3 ft/s to 39.3 ft/s (–12 m/s to 12 m/s). There must be at least 1 ft/s (0.3 m/s) span between the URV and LRV.

Line size

The line size (sensor size) must be set to match the actual sensor connected to the transmitter. The size must be specified in inches.

Calibration number

The sensor calibration number is a 16-digit number generated at the Rosemount factory during flow calibration and is unique to each sensor.
Local operator interface
To activate the optional Local Operator Interface (LOI), press the DOWN arrow two times. Use the UP, DOWN, LEFT, and RIGHT arrows to navigate the menu structure. The display can be locked to prevent unintentional configuration changed. The display lock can be activated through a HART communication device, or by holding the UP arrow for 10 seconds. When the display lock is activated, DL will appear in the lower right hand corner of the display. To deactivate the display lock (DL), hold the UP arrow for 10 seconds. Once deactivated, the DL will no longer appear in the lower right hand corner of the display.
28
February 2014
Table 9. HART field communicator fast keys for Field mount
Function HART Fast Keys
Process Variables 1, 1
Primary Variable (PV) 1, 1, 1
PV Percent of Range 1, 1, 2
PV Analog Output (AO) 1, 1, 3
Totalizer Set-Up 1, 1, 4
Totalizer Units 1, 1, 4, 1
Gross Total 1,1,4,2
Net Total 1,1,4,3
Reverse Total 1,1,4,4
Start Totalizer 1,1,4,5
Stop Totalizer 1,1,4,6
Reset Totalizer 1,1,4,7
Pulse Output 1,1,5
Diagnostics 1,2
Diagnostic Controls 1,2,1
Basic Diagnostics 1,2,2
Self Test 1,2,2,1
AO Loop Test 1,2,2,2
Pulse Output Loop Test 1,2,2,3
Empty Pipe Limits 1,2,2,4
Empty Pipe (EP) Value 1,2,2,4,1
EP Trigger Level 1,2,2,4,2
EP Counts 1,2,2,4,3
Electronics Temp 1,2,2,5
Advanced Diagnostics 1,2,3
8714i Calibration Verification 1,2,3,1
Run 8714i Verification 1,2,3,1,1
8714i Results 1,2,3,1,2
Test Condition 1,2,3,1,2,1
Test Criteria 1,2,3,1,2,2
8714i Test Result 1,2,3,1,2,3
Quick Start Guide
29
Quick Start Guide
Function HART Fast Keys
Simulated Velocity 1,2,3,1,2,4
Actual Velocity 1,2,3,1,2,5
Velocity Deviation 1,2,3,1,2,6
Transmitter Calibration Test Result 1,2,3,1,2,7
Sensor Calibration Deviation 1,2,3,1,2,8
Sensor Calibration Test Result 1,2,3,1,2,9
Coil Circuit Test Result
Electrode Circuit Test Result
1
1
Sensor Signature 1,2,3,1,3
Signature Values 1,2,3,1,3,1
Re-Signature Meter 1,2,3,1,3,2
Recall Last Saved Values 1,2,3,1,3,3
Set Pass/Fail Criteria 1,2,3,1,4
No Flow Limit 1,2,3,1,4,1
Flowing Limit 1,2,3,1,4,2
Empty Pipe Limit 1,2,3,1,4,3
Measurements 1,2,3,1,5
4-20 mA Verify 1,2,3,2
4-20 mA Verification 1,2,3,2,1
4-20 mA Verify Result 1,2,3,2,2
Licensing 1,2,3,3
License Status 1,2,3,3,1
License Key 1,2,3,3,2
Device ID 1,2,3,3,2,1
License Key 1,2,3,3,2,2
Diagnostic Variables 1,2,4
EP Value 1,2,4,1
Electronics Temp 1,2,4,2
Line Noise 1,2,4,3
5 Hz Signal to Noise Ratio (SNR) 1,2,4,4
37 Hz SNR 1,2,4,5
February 2014
1,2,3,1,2,10
1,2,3,1,2,11
30
February 2014
Function HART Fast Keys
Signal Power 1,2,4,6
8714i results 1,2,4,7
Test Condition 1,2,4,7,1
Test Criteria 1,2,4,7,2
8714i Test Result 1,2,4,7,3
Simulated Velocity 1,2,4,7,4
Actual Velocity 1,2,4,7,5
Velocity Deviation 1,2,4,7,6
Transmitter Calibration Test Result 1,2,4,7,7
Tube Calibration Deviation 1,2,4,7,8
Tube Calibration Test Result 1,2,4,7,9
Coil Circuit Test Result
Electrode Circuit Test Result
1
1
Trims 1,2,5
D/A Trim 1,2,5,1
Scaled D/A Trim 1,2,5,2
Digital Trim 1,2,5,3
Auto Zero 1,2,5,4
Universal Trim 1,2,5,5
View Status 1,2,6
Basic Setup 1,3
Tag 1,3,1
Flow Units 1,3,2
PV Units 1,3,2,1
Special Units 1,3,2,2
Volume Unit 1,3,2,2,1
Base Volume Unit 1,3,2,2,2
Conversion Number 1,3,2,2,3
Base Time Unit 1,3,2,2,4
Flow Rate Unit 1,3,2,2,5
Line Size 1,3,3
Quick Start Guide
1,2,4,7,10
1,2,4,7,11
31
Quick Start Guide
Function HART Fast Keys
PV Upper Range Value (URV) 1,3,4
PV Lower Range Value (LRV) 1,3,5
Calibration Number 1,3,6
PV Damping 1,3,7
Detailed Setup 1,4
Additional Parameters 1,4,1
Coil Drive Frequency 1,4,1,1
Density Value 1,4,1,2
PV Upper Sensor Limit (USL) 1,4,1,3
PV Lower Sensor Limit (LSL) 1,4,1,4
PV Minimum Span 1,4,1,5
Configure Output 1,4,2
Analog Output 1,4,2,1
PV URV 1,4,2,1,1
PV LRV 1,4,2,1,2
PV AO 1,4,2,1,3
AO Alarm Type 1,4,2,1,4
AO Loop Test 1,4,2,1,5
D/A Trim 1,4,2,1,6
Scaled D/A Trim 1,4,2,1,7
Alarm Level 1,4,2,1,8
Pulse Output 1,4,2,2
Pulse Scaling 1,4,2,2,1
Pulse Width 1,4,2,2,2
Pulse Mode 1,4,2,2,3
Pulse Output Loop Test 1,4,2,2,4
DI/DO Output 1,4,2,3
Digital Input 1 1,4,2,3,1
Digital Output 2 1,4,2,3,2
Reverse Flow 1,4,2,4
Totalizer Set-Up 1,4,2,5
Totalizer Units 1,4,2,5,1
February 2014
32
February 2014
Function HART Fast Keys
Gross Total 1,4,2,5,2
Net Total 1,4,2,5,3
Reverse Total 1,4,2,5,4
Start Totalizer 1,4,2,5,5
Stop Totalizer 1,4,2,5,6
Reset Totalizer 1,4,2,5,7
Alarm Level 1,4,2,6
HART Output 1,4,2,7
Variable Mapping 1,4,2,7,1
TV is 1,4,2,7,1,1
4V is 1,4,2,7,1,2
Poll Address 1,4,2,7,2
# of Req Preams 1,4,2,7,3
# of Resp Preams 1,4,2,7,4
Burst Mode 1,4,2,7,5
Burst Option 1,4,2,7,6
LOI Config 1,4,3
Language 1,4,3,1
Flowrate Display 1,4,3,2
Totalizer Display 1,4,3,3
Display Lock 1,4,3,4
Signal Processing 1,4,4
Operating Mode 1,4,4,1
Manual Configure DSP 1,4,4,2
Status 1,4,4,2,1
Samples 1,4,4,2,2
% Limit 1,4,4,2,3
Time Limit 1,4,4,2,4
Coil Drive Frequency 1,4,4,3
Low Flow Cutoff 1,4,4,4
PV Damping 1,4,4,5
Quick Start Guide
33
Quick Start Guide
Function HART Fast Keys
Universal Trim 1,4,5
Device Info 1,4,6
Manufacturer 1,4,6,1
Tag 1,4,6,2
Descriptor 1,4,6,3
Message 1,4,6,4
Date 1,4,6,5
Device ID 1,4,6,6
PV Sensor Serial Number 1,4,6,7
Sensor Tag 1,4,6,8
Write Protect 1,4,6,9
Revision No.
Universal Rev
Transmitter Rev
Software Rev
Final Assembly #
Construction Materials
Flange Type
Flange Material
Electrode Type
Electrode Material
Liner Material
1
1
1
1
1
1
1
1
1
1
1
Review 1,5
1. Scroll through the menu on the Field Communicator to access this item.
1.
February 2014
1,4,6,10
1,4,6,10,1
1,4,6,10,2
1,4,6,10,3
1,4,6,10,4
1,4,6,11
1,4,6,11,1
1,4,6,11,2
1,4,6,11,3
1,4,6,11,4
1,4,6,11,5
34
February 2014
Table 10. HART field communicator fast keys for wall mount
Function HART Fast Keys
Process Variables (PV) 1,1
Primary Variable Value 1,1,1
Primary Variable% 1,1,2
PV Loop Current 1,1,3
Totalizer Set-Up 1,1,4
Totalizer Units 1,1,4,1
Gross Total 1,1,4,2
Net Total 1,1,4,3
Reverse Total 1,1,4,4
Start Totalizer 1,1,4,5
Stop Totalizer 1,1,4,6
Reset Totalizer 1,1,4,7
Pulse Output 1,1,5
Diagnostics 1,2
Diagnostic Controls 1,2,1
Basic Diagnostics 1,2,2
Self Test 1,2,2,1
AO Loop Test 1,2,2,2
Pulse Output Loop Test 1,2,2,3
Tune Empty Pipe 1,2,2,4
EP Value 1,2,2,4,1
EP Trigger Level 1,2,2,4,2
EP Counts 1,2,2,4,3
Electronics Temp 1,2,2,5
Flow Limit 1 1, 2,2,6
Control 1 1,2,2,6,1
Mode 1 1,2,2,6,2
High Limit 1 1,2,2,6,3
Low Limit 1 1,2,2,6,4
Quick Start Guide
35
Quick Start Guide
Function HART Fast Keys
Flow Limit Hysteresis 1,2,2,6,5
Flow Limit 2 1,2,2,7
Control 2 1,2,2,7,1
Mode 2 1,2,2,7,2
High Limit 2 1,2,2,7,3
Low Limit 2 1,2,2,7,4
Flow Limit Hysteresis 1,2,2,7,5
Total Limit 1,2,2,8
Total Control 1,2,2,8,1
Total Mode 1,2,2,8,2
Total High Limit 1,2,2,8,3
Total Low Limit 1,2,2,8,4
Total Limit Hysteresis 1,2,2,8,5
Advanced Diagnostics 1,2,3
8714i Meter Verification 1,2,3,1
Run 8714i 1,2,3,1,1
8714i Results 1,2,3,1,2
Test Condition 1,2,3,1,2,1
Test Criteria 1,2,3,1,2,2
8714i Test Result 1,2,3,1,2,3
Simulated Velocity 1,2,3,1,2,4
Actual Velocity 1,2,3,1,2,5
Velocity Deviation 1,2,3,1,2,6
Xmtr Cal Test Result 1,2,3,1,2,7
Sensor Cal Deviation 1,2,3,1,2,8
Sensor Cal Test Result 1,2,3,1,2,9
Coil Circuit Test Result
Electrode Circuit Test Result
1
1
Sensor Signature 1,2,3,1,3
Signature Values 1,2,3,1,3,1
February 2014
1,2,3,1,2,10
1,2,3,1,2,11
36
February 2014
Function HART Fast Keys
Coil Resistance 1,2,3,1,3,1,1
Coil Signature 1,2,3,1,3,1,2
Electrode Resistance 1,2,3,1,3,1,3
Re-Signature Meter 1,2,3,1,3,2
Recall Last Saved Values 1,2,3,1,3,3
Set Pass/Fail Criteria 1,2,3,1,4
No Flow Limit 1,2,3,1,4,1
Flowing Limit 1,2,3,1,4,2
Empty Pipe Limit 1,2,3,1,4,3
Measurements 1,2,3,1,5
Coil Resistance 1,2,3,1,5,1
Coil Signature 1,2,3,1,5,2
Electrode Resistance 1,2,3,1,5,3
Licensing 1,2,3,2
License Status 1,2,3,2,1
License Key 1,2,3,2,2
Device ID 1,2,3,2,2,1
License Key 1,2,3,2,2,2
Diagnostic Variables 1,2,4
EP Value 1,2,4,1
Electronics Temp 1,2,4,2
Line Noise 1,2,4,3
5 Hz Signal to Noise Ratio (SNR) 1,2,4,4
37 Hz SNR 1,2,4,5
Signal Power 1,2,4,6
8714i results 1,2,4,7
Test Condition 1,2,4,7,1
Test Criteria 1,2,4,7,2
8714i Test Result 1,2,4,7,3
Simulated Velocity 1,2,4,7,4
Actual Velocity 1,2,4,7,5
Quick Start Guide
37
Quick Start Guide
Function HART Fast Keys
Velocity Deviation 1,2,4,7,6
Xmtr Cal Test Result 1,2,4,7,7
Sensor Cal Deviation 1,2,4,7,8
Sensor Cal Test Result 1,2,4,7,9
Coil Circuit Test Result 1,2,4,7,10
Electrode Circuit Test Result 1,2,4,7,11
Trims 1,2,5
D/A Trim 1,2,5,1
Scaled D/A Trim 1,2,5,2
Digital Trim 1,2,5,3
Auto Zero 1,2,5,4
Universal Trim 1,2,5,5
View Status 1,2,6
Basic Setup 1,3
Tag 1,3,1
Flow Units 1,3,2
PV Units 1,3,2,1
Special Units 1,3,2,2
Volume Unit 1,3,2,2,1
Base Volume Unit 1,3,2,2,2
Conversion Number 1,3,2,2,3
Base Time Unit 1,3,2,2,4
Flow Rate Unit 1,3,2,2,5
Line Size 1,3,3
PV URV 1,3,4
PV LRV 1,3,5
Calibration Number 1,3,6
PV Damping 1,3,7
Detailed Setup 1,4
Additional Params 1,4,1
February 2014
38
February 2014
Function HART Fast Keys
Coil Drive Freq 1,4,1,1
Density Value 1,4,1,2
PV USL 1,4,1,3
PV LSL 1,4,1,4
PV Min Span 1,4,1,5
Configure Output 1,4,2
Analog Output 1,4,2,1
PV URV 1,4,2,1,1
PV LRV 1,4,2,1,2
PV Loop Current 1,4,2,1,3
PV Alarm Type 1,4,2,1,4
AO Loop Test 1,4,2,1,5
D/A Trim 1,4,2,1,6
Scaled D/A Trim 1,4,2,1,7
Alarm Level 1,4,2,1,8
Pulse Output 1,4,2,2
Pulse Scaling 1,4,2,2,1
Pulse Width 1,4,2,2,2
Pulse Output Loop Test 1,4,2,2,3
DI/DO Output 1,4,2,3
DI/DO 1 1,4,2,3,1
Configure I/O 1 1,4,2,3,1,1
DIO 1 Control 1,4,2,3,1,2
Digital Input 1 1,4,2,3,1,3
Digital Output 1 1,4,2,3,1,4
DO 2 1,4,2,3,2
Flow Limit 1 1,4,2,3,3
Control 1 1,4,2,3,3,1
Mode 1 1,4,2,3,3,2
High Limit 1 1,4,2,3,3,3
Quick Start Guide
39
Quick Start Guide
Function HART Fast Keys
Low Limit 1 1,4,2,3,3,4
Flow Limit Hysteresis 1,4,2,3,3,5
Flow Limit 2 1,4,2,3,4
Control 2 1,4,2,3,4,1
Mode 2 1,4,2,3,4,2
High Limit 2 1,4,2,3,4,3
Low Limit 2 1,4,2,3,4,4
Flow Limit Hysteresis 1,4,2,3,4,5
Total Limit 1,4,2,3,5
Total Control 1,4,2,3,5,1
Total Mode 1,4,2,3,5,2
Total High Limit 1,4,2,3,5,3
Total Low Limit 1,4,2,3,5,4
Total Limit Hysteresis 1,4,2,3,5,5
Diagnostic Status Alert 1,4,2,3,6
Reverse Flow 1,4,2,4
Totalizer Setup 1,4,2,5
Totalizer Units 1,4,2,5,1
Gross Total 1,4,2,5,2
Net Total 1,4,2,5,5
Reverse Total 1,4,2,5,4
Start Totalizer 1,4,2,5,5
Stop Totalizer 1,4,2,5,6
Reset Totalizer 1,4,2,5,7
Alarm Level 1,4,2,6
HART Output 1,4,2,7
Variable Mapping 1,4,2,7,1
TV is 1,4,2,7,1,1
QV is 1,4,2,7,1,2
Poll Address 1,4,2,7,2
# of Req Preams 1,4,2,7,3
# Resp Preams 1,4,2,7,4
February 2014
40
February 2014
Function HART Fast Keys
Burst Mode 1,4,2,7,5
Burst Option 1,4,2,7,6
LOI Config 1,4,3
Language 1,4,3,1
Flow Rate Display 1,4,3,2
Totalizer Display 1,4,3,3
Display Lock 1,4,3,4
Signal Processing 1,4,4
Operating Mode 1,4,4,1
Man Config DSP 1,4,4,2
Status 1,4,4,2,1
Samples 1,4,4,2,2
% Limit 1,4,4,2,3
Time Limit 1,4,4,2,4
Coil Drive Freq 1,4,4,3
Low Flow Cutoff 1,4,4,4
PV Damping 1,4,4,5
Universal Trim 1,4,5
Device Info 1,4,6
Manufacturer 1,4,6,1
Tag 1,4,6,2
Descriptor 1,4,6,3
Message 1,4,6,4
Date 1,4,6,5
Device ID 1,4,6,6
PV Sensor S/N 1,4,6,7
PV Sensor Tag 1,4,6,8
Write Protect 1,4,6,9
Quick Start Guide
41
Quick Start Guide
Function HART Fast Keys
Revision No.
Universal Rev
Transmitter Rev
Software Rev
Final Assembly #
Construction Materials
Flange Type
Flange Material
Electrode Type
Electrode Material
Liner Material
1
1
1
1
1
1
1
1
1
1
1
Review 1,5
1. Scroll through the menu on the Field Communicator to access this item.
Table 11. Electrical data
Rosemount 8750W with 8732 Flow Transmitter
Power supply: 250 V ac, 1 A or 50 Vdc, 2,5 A, 20 W maximum
Pulsed output circuit: 30 V dc (pulsed), 0,25 A, 7,5 W maximum
4-20 mA output circuit:
Sensors
Coil excitation circuit:
Electrode circuit:
30 V dc, 30 mA, 900 mW maximum
40 V dc (pulsed), 0,5 A, 20 W maximum
in type of explosion protection intrinsic safety EEx ia IIC, Ui = 5 V, li = 0.2 mA, Pi = 1 mW, Um = 250 V
February 2014
1,4,6,10
1,4,6,10,1
1,4,6,10,2
1,4,6,10,3
1,4,6,10,4
1,4,6,11
1,4,6,11,1
1,4,6,11,2
1,4,6,11,3
1,4,6,11,4
1,4,6,11,5
42
00825-0200-4750
Quick Start Guide
00825-0200-4750, Rev AA
February 2014
Emerson Process Management
Rosemount Inc. 8200 Market Boulevard Chanhassen, MN USA 55317 www.rosemount.com T (US) (800) 406-5252 T (Intnl) (303) 527-5200
Emerson Process Management Asia Pacific Private Limited
1 Pandan Crescent Singapore 128461 T (65) 6777 8211 F (65) 6777 0947 Enquiries@AP.EmersonProcess.com
Service Support Hotline: +65 6770 8711
Emerson Process Management Flow B.V.
Neonstraat 1 6718 WX Ede The Netherlands T +31 (0) 318 495555 F +31 (0) 318 495556
Emerson FZE
P.O. Box 17033 Jebel Ali Free Zone Dubai UAE T +971 4 811 8100 F +971 4 886 5465 FlowCustomerCare.MEA@Emerson.com
© 2014 Rosemount Inc. All rights reserved. All marks property of owner.
The Emerson logo is a trade mark and service mark of Emerson Electric Co Rosemount and the Rosemount logotype are registered trademarks of Rosemount Inc.
Emerson Process Management Latin America
Multipark Office Center Turrubares Building, 3rd & 4th floor Guachipelin de Escazu, Costa Rica T+(506) 2505-6962 international.mmicam@emersonprocess.com
Loading...