This document provides basic installation guidelines for the Rosemount® 8750W Magnetic
Flowmeter System. For comprehensive instructions, for detailed configuration, diagnostics,
maintenance, service, installation or troubleshooting, refer to the Rosemount 8750W
reference manual (document number 00809-0100-4750 Rev. BA). The manual and this QSG
are also available electronically on www.rosemount.com.
Failure to follow these installation guidelines could result in death or serious injury:
Installation and servicing instructions are for use by qualified personnel only. Do not perform
any servicing other than that contained in the operating instructions, unless qualified.
Verify that the operating environment of the sensor and transmitter is consistent with the
operating environment.
Do not connect a Rosemount transmitter to a non-Rosemount sensor that is located in an
explosive atmosphere.
The sensor liner is vulnerable to handling damage. Never place anything through the sensor
for the purpose of lifting or gaining leverage. Liner damage may render the sensor inoperable.
Metallic or spiral-wound gaskets should not be used as they will damage the liner face of the
sensor.
If frequent removal is anticipated, take precautions to protect the liner ends. Short spool
pieces attached to the sensor ends are often used for protection.
Rosemount Magnetic Flowmeters ordered with non-standard paint options may be subject to
electrostatic discharge. To avoid electrostatic charge build-up, do not rub the flowmeter with
a dry cloth or clean with solvents.
Correct flange bolt tightening is crucial for proper sensor operation and life. All bolts must be
tightened in the proper sequence to the specified torque specifications. Failure to observe
these instructions could result in severe damage to the sensor lining and possible sensor
replacement.
Before installing the Rosemount 8750W Flowmeter, there are several
pre-installation steps that should be completed to make the installation process
easier:
Identify the options and configurations that apply to your application
Set the hardware switches if necessary
Consider mechanical, electrical, and environmental requirements
Mechanical considerations
The mounting site for the Rosemount 8750W transmitter should provide enough
room for secure mounting, easy access to conduit ports, full opening of the
transmitter covers, and easy readability of the LOI screen (see
Figure 2).
If the Rosemount 8750W transmitter is mounted separately from the sensor, it
may not be subject to the same limitations that apply to the sensor.
Figure 1. Field mount transmitter dimensional drawing
7.49 (190)
6.48 (165)
LOI Cover
Figure 1 and
1
/2”-14 NPT (3 places)*
1
/2”-14 NPT (2 places)*
5.82
(148)
8.81
(224)
4.97
(126)
3.00
(76)
3.07
(78)
4.97
(126)
NOTICE
*Non- standard conduit entry thread. M20 connections are available with the use of threaded
conduit adapters.
3
Quick Start Guide
Figure 2. Wall mount transmitter dimensional drawing
WITH STANDARD COVER
February 2014
4.31
(109)
2.96
(75)
9.01
(229)
2.81
(71)
WITH LOI COVER
3.11
(79)
11.15
(283)
0.44
(11)
12.02
(305)
4
Ground Lug
NOTE
Dimensions are in inches (millimeters)
1
/2–14 NPT
Conduit
Connection
(4 Places)
LOI Keypad
Cover
February 2014
Quick Start Guide
Environmental considerations
To ensure maximum transmitter life, avoid extreme temperature and excessive
vibration. Typical problem areas:
high-vibration lines with integrally mounted transmitters
warm-climate installations in direct sunlight
outdoor installations in cold climates.
Remote-mounted transmitters may be installed in the control room to protect
the electronics from the harsh environment and provide easy access for
configuration or service.
Both remotely and integrally mounted Rosemount 8750W transmitters require
external power so there must be access to a suitable power source.
Installation procedures
Rosemount 8750W installation includes both detailed mechanical and electrical
installation procedures.
Mount the transmitter
At a remote site the transmitter may be mounted on a pipe up to two inches in
diameter or against a flat surface.
Pipe mounting
To mount the transmitter on a pipe:
1. Attach the mounting bracket to the pipe using the mounting hardware.
2. Attach the Rosemount 8750W transmitter to the mounting bracket using the
mounting screws.
Identify options and configurations
The standard application of the 8750W includes a 4–20 mA output and control of
the sensor coils and electrodes. Other applications may require one or more of
the following configurations or options:
Be sure to identify any additional options and configurations that apply to the
installation. Keep a list of these options nearby for consideration during the
installation and configuration procedures.
5
Quick Start Guide
Hardware jumpers/switches
The 8750W electronics board is equipped with user-selectable hardware switches
depending on the transmitter model ordered. These switches set the Failure
Alarm Mode, Internal/External Analog Power, Internal/External Pulse Power and
Transmitter Security. The standard configuration for these switches when
shipped from the factory is as follows:
Failure Alarm Mode: HIGH
Internal/External Analog Power:INTERNAL
Internal/External Pulse Power:EXTERNAL (Field Mount only)
Transmitter Security:OFF
Changing hardware switch settings
In most cases, it will not be necessary to change the setting of the hardware
switches. If the switch settings need to be changed, follow the steps outlined in
the manual.
Use a non-metallic tool to move switch positions.
Electrical considerations
Before making any electrical connections to the Rosemount 8750W, consider
national, local and plant electrical installation requirements. Be sure to have the
proper power supply, conduit, and other accessories necessary to comply with
these standards.
February 2014
Rotate transmitter housing
The Field Mount transmitter housing can be rotated on the sensor in 90°
increments by removing the four mounting bolts on the bottom of the housing.
Do not rotate the housing more than 180 ° in any one direction. Prior to
tightening, be sure the mating surfaces are clean, the O-ring is seated in the
groove, and there is no gap between the housing and the sensor.
6
February 2014
Quick Start Guide
Step 2: Handling
Handle all parts carefully to prevent damage. Whenever possible, transport the
system to the installation site in the original shipping containers. Rosemount flow
sensors are shipped with end covers that protect it from mechanical damage. For
PTFE lined sensors the cover also prevents normal liner relaxation. Remove the
end covers just before installation.
Figure 3. Rosemount 8750W flanged sensor support for handling
½- through 4-Inch Sensors
5-Inch and Larger Sensors
7
Quick Start Guide
Step 3: Mounting
Upstream/downstream piping
To ensure specification accuracy over widely varying process conditions, install
the sensor a minimum of five straight pipe diameters upstream and two pipe
diameters downstream from the electrode plane (see
Figure 4. Upstream and downstream straight pipe diameters
5 Pipe Diameters
Flow
Installations with reduced upstream and downstream straight runs are possible.
In reduced straight run installations, absolute performance may shift. Reported
flow rates will still be highly repeatable.
The sensor should be mounted so the FORWARD end of the flow arrow points in
the direction of flow through the sensor (see
Figure 5).
Figure 4).
2 Pipe Diameters
February 2014
Figure 5. Flow direction
8
February 2014
The sensor should be installed in a location that ensures it remains full during
operation. Vertical installation with upward process fluid flow keeps the
cross-sectional area full, regardless of flow rate. Horizontal installation should be
restricted to low piping sections that are normally full.
Figure 6. Sensor orientation
FLOW
FLOW
Quick Start Guide
Mounting position
The electrodes in the sensor are properly orientated when the two measurement
electrodes are in the 3 and 9 o’clock position or within 45 ° from the vertical, as
shown on the right of
measurement electrodes are in the 6 and 12 o’clock position as shown on the left
of
Figure 7.
Figure 7. Avoid any mounting orientation where the two
Figure 7. Sensor mounting position
Incorrect Correct
9
Quick Start Guide
February 2014
Step 4: Installation
Flanged sensors
Gaskets
The sensor requires a gasket at each of its connections to adjacent devices or piping.
The gasket material selected must be compatible with the process fluid and operating
conditions. Gaskets are required on each side of a grounding ring. All other
applications (including sensors with lining protectors or a grounding electrode)
require only one gasket on each end connection.
Metallic or spiral-wound gaskets should not be used as they will damage the liner face of the
sensor. If spiral wound or metallic gaskets are required for the application, lining protectors
must be used.
Figure 8. Flanged gasket placement
10
February 2014
Quick Start Guide
Flange bolts
Do not bolt one side at a time. Tighten each side simultaneously. Example:
1. Snug upstream
2. Snug downstream
3. Tighten upstream
4. Tighten downstream
Do not snug and tighten the upstream side and then snug and tighten the
downstream side.
Failure to alternate between the upstream and downstream flanges when
tightening bolts may result in liner damage.
Suggested torque values by sensor line size and liner type are listed in
page 12. Consult the factory if the flange rating of the sensor is not listed.
Tighten flange bolts on the upstream side of the sensor in the incremental
sequence shown in
Repeat the process on the downstream side of the sensor. For sensors with more
or less flange bolts, tighten the bolts in a similar crosswise sequence. Repeat this
entire tightening sequence at 40%, 60%, 80%, and 100% of the suggested torque
values or until the leak between the process and sensor flanges stop.
If leakage has not stopped at the suggested torque values, the bolts can be
tightened in additional 10% increments until the joint stops leaking, or until the
measured torque value reaches the maximum torque value of the bolts. Practical
consideration for the integrity of the liner often leads the user to distinct torque
values to stop leakage due to the unique combinations of flanges, bolts, gaskets,
and sensor liner material.
Check for leaks at the flanges after tightening the bolts. Failure to use the correct
tightening methods can result in severe damage. Sensors require a second
tightening 24 hours after the initial installation. Over time, sensor liner materials
may deform under pressure.
Figure 9 on page 11 to 20% of the suggested torque values.
Table 1 on
Figure 9. Flange bolt torquing sequence
For torque values not listed in Table 1, Table 2, or Table 3, contact technical
support.
11
Quick Start Guide
Table 1. Suggested flange bolt torque values for ASME
PTFE linerNeoprene liner
Size codeLine size
0050.5 inch (15 mm)88--
0101 inch (25 mm)812--
0151.5 inch (40 mm)1325718
0202 inch (50 mm)19171411
0252.5 inch (65 mm)22241716
0303 inch (80 mm)34352323
0404 inch (100 mm)26501732
0505 inch (125 mm)36602535
0606 inch (150 mm)45503037
0808 inch (200 mm)60824255
10010 inch (250 mm)55804070
12012 inch (300 mm)6512555105
14014 inch (350 mm)851107095
16016 inch (400 mm)8516065140
18018 inch (450 mm)12017095150
20020 inch (500 mm)11017590150
24024 inch (600 mm)165280140250
30030 inch (750 mm)195415165375
36036 inch (900 mm)280575245525
Class 150
(pound-feet)
Class 300
(pound-feet)
Class 150
(pound-feet)
February 2014
Class 300
(pound-feet)
12
February 2014
Table 2. Suggested flange bolt torque values for EN1092-1
Table 3. Flange bolt torque and load specifications for large line sizes
AWWA C207(Ft-Lbs)EN1092-1(N-m)
40-in. (1000 mm)
42-in. (1050 mm)
48-in. (1200 mm)
AS2129(N-m)AS4087(N-m)
40-in. (1000 mm)
48-in. (1200 mm)
Class D
Class E
Class D
Class E
Class D
Class E
Table D
Table E
Table D
Table E
757
757PN10413
839PN16478
839
872PN10622
872
614
652PN21515
786
839PN21840
40-in. (1000 mm)
48-in. (1200 mm)
40-in. (1000 mm)
48-in. (1200 mm)
14
PN6208
PN6375
PN16612
PN16785
February 2014
Quick Start Guide
Step 5: Grounding
Use Table 4 to determine which process grounding option to follow for proper
installation. The sensor case should be grounded in accordance with national and
local electrical codes. Failure to do so may impair the protection provided by the
equipment.
Table 4. Process grounding installation
Process grounding options
Grounding
Type of pipeGrounding straps
Conductive
Unlined Pipe
Conductive
Lined Pipe
Non-Conductive
Pipe
See Figure 10See Figure 11See Figure 13See Figure 11
Insufficient
Grounding
Insufficient
Grounding
rings
See Figure 11See Figure 10See Figure 11
See Figure 12
Figure 10. Grounding straps in conductive lined pipe or reference electrode in
lined pipe
Reference
electrode
Not
Recommended
Lining
protectors
See Figure 12
Figure 11. Grounding with grounding rings or lining protectors in conductive pipe
Grounding
Rings or
Lining
Protectors
15
Quick Start Guide
February 2014
Figure 12. Grounding with grounding rings or lining protectors in non-conductive
pipe
Grounding
Rings or
Lining
Protectors
Figure 13. Grounding with reference electrode in conductive unlined pipe
16
February 2014
Quick Start Guide
Step 6: Wiring
This wiring section covers the connection between the transmitter and sensor,
the 4-20 mA loop, and supplying power to the transmitter. Follow the conduit
information, cable requirements, and disconnect requirements in the sections
below.
Conduit ports and connections
Both the sensor and transmitter junction boxes have ports for 1/2-inch NPT
conduit connections or optional M20 connection is available. These connections
should be made in accordance with national, local, and plant electrical codes.
Unused ports should be sealed with metal plugs. Proper electrical installation is
necessary to prevent errors due to electrical noise and interference. Separate
conduits are not necessary for the coil drive and electrode cables, but a dedicated
conduit line between each transmitter and sensor is required. Shielded cable
must be used for best results in electrically noisy environments. When preparing
all wire connections, remove only the insulation required to fit the wire
completely under the terminal connection. Removal of excessive insulation may
result in an unwanted electrical short to the transmitter housing or other wire
connections. For flanged sensors installed into an application requiring IP68
protection, sealed cable glands, conduit, and conduit plugs that meet IP68
ratings are required. Option Codes R05, R10, R15, R20, R25, and R30 provide a
pre-wired potted and sealed junction box as additional protection to prevent the
ingress of water. These options still require the use of sealed conduits to meet
IP68 protection requirements.
Conduit requirements
A single dedicated conduit run for the coil drive and electrode cable is needed
between the sensor and the remote transmitter. See
in a single conduit are likely to create interference and noise problems in the
system.
Electrode cables should not be run together and should not be in the same cable
ray with power cables.
Output cables should not be run together with power cables.
Select conduit size appropriate to feed cables through to the flowmeter.
Figure 14. Conduit preparation
Wrong
Coil Drive and
Power
Outputs
Power
Electrode Cables
Power
Outputs
Figure 14. Bundled cables
Correct
Power
Outputs
Coil Drive and
Electrode Cables
17
Quick Start Guide
Run the appropriate size cable through the conduit connections in your magnetic
flowmeter system. Run the power cable from the power source to the
transmitter. Run the coil drive and electrode cables between the flowmeter
sensor and transmitter.
Installed signal wiring should not be run together and should not be in the
same cable tray as AC or DC power wiring.
Device must be properly grounded according to national and local electric
codes.
Rosemount combination cable part number 08732-0753-1003 (ft) or
08732-0753-2004 (m) is required to be used to meet EMC requirements.
Transmitter to sensor wiring
The transmitter can be integral to the sensor or remotely mounted following the
wiring instructions.
Remote mount cable requirements and preparation
For installations using the individual coil drive and electrode cable, lengths should
be limited to less than 1,000 feet (300 meters). Equal length cable is required for
each. See
For installations using the combination coil drive and electrode cable, lengths
should be limited to less than 330 feet (100 meters). See
Prepare the ends of the coil drive and electrode cables as shown in
Limit the unshielded wire length to 1-inch on both the coil drive and electrode
cables. Any unsheathed wire should be wrapped with proper insulation. Excessive
lead length or failure to connect cable shields can create electrical noise resulting
in unstable meter readings.
Table 5 on page 19.
Table 5 on page 19.
Figure 15.
February 2014
Figure 15. Cable preparation detail
Cable Shield
18
NOTE
Dimensions are in inches (mm).
1.00
(26)
February 2014
Quick Start Guide
To order cable specify length as quantity desired.
25 feet = Qty (25) 08732-0753-1003
Potential Shock Hazard Across Terminals 1 & 2 (40 VAC).
Wiring the transmitter to the sensor
When using individual cables for coil drive and electrode refer to Table 6. If using
the combination coil drive and electrode cable, refer to
on page 20 for transmitter specific wiring diagrams.
1. Connect the coil drive cable using terminals 1, 2, and 3.
2. Connect the electrode cable using terminals 17, 18, and 19
Table 7. See Figure 16
Table 6. Individual coil and electrode cables
Transmitter terminalSensor terminal Wire gaugeWire color
1114Clear
2214Black
33 14Shield
171720Shield
181820Black
191920Clear
19
Quick Start Guide
Table 7. Combination coil and electrode cable
Transmitter terminalSensor terminal Wire gaugeWire color
1118Red
2218Green
3 3 18Shield
171720Shield
181820Black
191920White
Figure 16. Remote mount wiring diagrams
February 2014
20
February 2014
Quick Start Guide
Note
When using the Rosemount supplied combination cable, the electrode wires for terminals 18 and
19 contain an addition shield wire. These two shield wires should be tied with the main shield wire
at terminal 17. See Figure 17.
Figure 17. Combination coil and electrode cable wiring diagram
Coil Drive CableElectrode Cable
1 Red 2 Green 3 Shield
17 Shield 18 Black 19 White
Integral mount transmitters
The interconnecting wire harness for an integral mount transmitter is installed at
the factory. See
Process Management, Rosemount, Inc.
Figure 18. 8750W integral mount wiring Diagram
Figure 18. Do not use cable other than that supplied by Emerson
21
Quick Start Guide
Connecting the 4–20 mA analog signal
Cabling considerations
If possible, use individually shielded twisted pair cable, either in single pair or
multi-pair varieties. Unshielded cables may be used for short distances, provided
ambient noise and cross-talk will not adversely impact communication. The
minimum conductor size is 0.51mm diameter (#24 AWG) for cable runs less than
1,500 meters (@ 5,000 ft.) and 0.81mm diameter (#20 AWG) for longer
distances. Resistance in the loop must be 1000 ohms or less.
The 4–20 mA analog output loop signal may be powered internally or externally.
The default position of the internal/external analog power switch is in the internal
position. The user-selectable power supply switch is located on the electronics
board.
Figure 19. Field mount analog signal wiring diagram
February 2014
+4–20 mA
–4–20 mA
Analog output - connect negative (-)DC to Terminal 1 and positive (+)DC to
Terminal 2. See
22
Figure 19.
February 2014
Figure 20. Wall mount analog signal wiring diagram
Quick Start Guide
+4–20 mA
–4–20 mA
Analog output - connect negative (-)DC to Terminal 8 and positive (+)DC to
Terminal 7. See
Figure 20.
Internal power source
The 4–20 mA analog signal loop is powered from the transmitter itself.
External power source
The 4–20 mA analog signal loop is powered from an external power source. HART
multidrop installations require a 10–30 VDC external analog power source.
Note:
If a HART Field Communicator or control system will be used, it must be connected across a
minimum of 250 ohms resistance in the loop.
To connect any of the other output options (pulse output and/or discrete
input/output), consult the comprehensive product manual.
23
Quick Start Guide
2
Powering the transmitter
The 8750W transmitter is designed to be powered by 90-250 VAC, 50–60 Hz, or
12–42 VDC. Before connecting power to the Rosemount 8750W, consider the
following standards and be sure to have the proper power supply, conduit, and
other accessories. Wire the transmitter according to national, local, and plant
electrical requirements for the supply voltage. See
Figure 21. DC power supply current requirements
1
0.75
0.5
0.25
Supply Current (Amps)
0
12182430364
Power Supply (Volts)
Figure 21 and Figure 22.
February 2014
24
February 2014
Figure 22. AC power supply requirements
0.320
0.300
0.280
0.260
0.240
0.220
0.200
0.180
0.160
0.140
Supply Current (Amps)
0.120
0.100
80100120
140
160180
Power Supply Voltage (AC RMS)
Figure 23. Apparent power
38
36
34
32
30
28
26
24
Apparent Power (VA)
22
20
80100120140160180200220240
Quick Start Guide
200
220240
250
Power Supply Voltage (AC RMS)
Supply wire requirements
Use 10 - 18 AWG wire rated for the proper temperature of the application. For
wire 10 - 14 AWG use lugs or other appropriate connectors. For connections in
ambient temperatures above 140 °F (60 °C), use a wire rated for 176 °F (80 °C). For
ambient temperatures greater than 176 °F (80 °C), use a wire rated for 230 °F (110
°C). For DC powered transmitters with extended cable lengths, verify that there is
a minimum of 12 VDC at the terminals of the transmitter. Disconnects
Connect the device through an external disconnect or circuit breaker.
Installation category
The installation category for the 8750W is (Overvoltage) Category II.
Overcurrent protection
The Rosemount 8750W flowmeter transmitter requires overcurrent protection of
the supply lines. Maximum ratings of overcurrent devices are shown in
Table 8.
25
Quick Start Guide
Table 8. Overcurrent limits
Power systemFuse ratingManufacturer
95-250 VAC2 Amp, Quick ActingBussman AGC2 or Equivalent
12-42 VDC3 Amp, Quick ActingBussman AGC3 or Equivalent
Field mount power supply
For AC power applications (90-250 VAC, 50-60 Hz), connect AC Neutral to
terminal 9 (AC N/L2) and connect AC Line to terminal 10 (AC/L1). For DC power
applications, connect negative to terminal 9 (DC -) and positive to terminal 10
(DC +). Units powered by 12-42 VDC power supply may draw up to 1 amp of
current. See
Figure 24. Field mount transmitter power connections
Figure 24 for terminal block connections.
February 2014
Wall mount power supply
For AC power applications (90-250 VAC, 50-60 Hz), connect AC Neutral to
terminal N and connect AC Line to terminal L1. For DC power applications,
connect negative to terminal N (DC -) and positive to terminal L1 (DC +). Ground
the transmitter cage via the grounding stud located on the bottom of the
transmitter housing. Units powered by 12-42 VDC power supply may draw up to
1 amp of current. See
26
Figure 25 for terminal block connections.
February 2014
Figure 25. Wall mount transmitter power connections
Fuse
AC Line or DC+
Quick Start Guide
AC Ground or
DC Ground
AC Neutral or DC–
Transmitter
Power Cable
Field mount cover jam screw
For transmitter housings shipped with a cover jam screw, the screw should be
properly installed once the transmitter has been wired and powered up. Follow
these steps to install the cover jam screw:
1. Verify that the cover jam screw is completely threaded into the housing.
2. Install the transmitter housing cover and verify that the cover is tight against
the housing.
3. Using a 2.5 mm hex wrench, loosen the jam screw until it contacts the
transmitter cover.
1
4. Turn the jam screw an additional
(Note: Application of excessive torque may strip the threads.)
5. Verify that the cover cannot be removed.
/2 turn counterclockwise to secure the cover.
27
Quick Start Guide
Step 7: Basic configuration
Once the magnetic flowmeter is installed and power has been supplied, the
transmitter must be configured through the basic setup. These parameters can
be configured through either a local operator interface or a HART communication
device. A table of all the parameters begins on
advanced functions are included in the comprehensive product manual.
page 29. Descriptions of the more
Basic setup
Tag
Tag is the quickest and shortest way of identifying and distinguishing between
transmitters. Transmitters can be tagged according to the requirements of your
application. The tag may be up to eight characters long.
Flow units (PV)
The flow rate units variable specifies the format in which the flow rate will be
displayed. Units should be selected to meet your particular metering needs.
URV (Upper Range Value)
The upper range value (URV) sets the 20 mA point for the analog output. This
value is typically set to full-scale flow. The units that appear will be the same as
those selected under the units parameter. The URV may be set between
–39.3 ft/s to 39.3 ft/s (–12 m/s to 12 m/s). There must be at least 1 ft/s (0.3 m/s)
span between the URV and LRV.
February 2014
LRV (Lower Range Value)
Reset the lower range value (LRV) sets the 4 mA point for the analog output. This
value is typically set to zero flow. The units that appear will be the same as those
selected under the units parameter. The LRV may be set between
–39.3 ft/s to 39.3 ft/s (–12 m/s to 12 m/s). There must be at least 1 ft/s (0.3 m/s)
span between the URV and LRV.
Line size
The line size (sensor size) must be set to match the actual sensor connected to the
transmitter. The size must be specified in inches.
Calibration number
The sensor calibration number is a 16-digit number generated at the Rosemount
factory during flow calibration and is unique to each sensor.
Local operator interface
To activate the optional Local Operator Interface (LOI), press the DOWN arrow
two times. Use the UP, DOWN, LEFT, and RIGHT arrows to navigate the menu
structure. The display can be locked to prevent unintentional configuration
changed. The display lock can be activated through a HART communication
device, or by holding the UP arrow for 10 seconds. When the display lock is
activated, DL will appear in the lower right hand corner of the display. To
deactivate the display lock (DL), hold the UP arrow for 10 seconds. Once
deactivated, the DL will no longer appear in the lower right hand corner of the
display.
28
February 2014
Table 9. HART field communicator fast keys for Field mount
FunctionHART Fast Keys
Process Variables1, 1
Primary Variable (PV)1, 1, 1
PV Percent of Range1, 1, 2
PV Analog Output (AO)1, 1, 3
Totalizer Set-Up1, 1, 4
Totalizer Units1, 1, 4, 1
Gross Total1,1,4,2
Net Total1,1,4,3
Reverse Total1,1,4,4
Start Totalizer1,1,4,5
Stop Totalizer1,1,4,6
Reset Totalizer1,1,4,7
Pulse Output1,1,5
Diagnostics1,2
Diagnostic Controls1,2,1
Basic Diagnostics1,2,2
Self Test1,2,2,1
AO Loop Test1,2,2,2
Pulse Output Loop Test1,2,2,3
Empty Pipe Limits1,2,2,4
Empty Pipe (EP) Value1,2,2,4,1
EP Trigger Level1,2,2,4,2
EP Counts1,2,2,4,3
Electronics Temp1,2,2,5
Advanced Diagnostics1,2,3
8714i Calibration Verification1,2,3,1
Run 8714i Verification1,2,3,1,1
8714i Results1,2,3,1,2
Test Condition1,2,3,1,2,1
Test Criteria1,2,3,1,2,2
8714i Test Result1,2,3,1,2,3
Quick Start Guide
29
Quick Start Guide
FunctionHART Fast Keys
Simulated Velocity1,2,3,1,2,4
Actual Velocity1,2,3,1,2,5
Velocity Deviation1,2,3,1,2,6
Transmitter Calibration Test Result1,2,3,1,2,7
Sensor Calibration Deviation1,2,3,1,2,8
Sensor Calibration Test Result1,2,3,1,2,9
Coil Circuit Test Result
Electrode Circuit Test Result
1
1
Sensor Signature1,2,3,1,3
Signature Values1,2,3,1,3,1
Re-Signature Meter1,2,3,1,3,2
Recall Last Saved Values1,2,3,1,3,3
Set Pass/Fail Criteria1,2,3,1,4
No Flow Limit1,2,3,1,4,1
Flowing Limit1,2,3,1,4,2
Empty Pipe Limit1,2,3,1,4,3
Measurements1,2,3,1,5
4-20 mA Verify1,2,3,2
4-20 mA Verification1,2,3,2,1
4-20 mA Verify Result1,2,3,2,2
Licensing1,2,3,3
License Status1,2,3,3,1
License Key1,2,3,3,2
Device ID1,2,3,3,2,1
License Key1,2,3,3,2,2
Diagnostic Variables1,2,4
EP Value1,2,4,1
Electronics Temp1,2,4,2
Line Noise1,2,4,3
5 Hz Signal to Noise Ratio (SNR)1,2,4,4
37 Hz SNR1,2,4,5
February 2014
1,2,3,1,2,10
1,2,3,1,2,11
30
February 2014
FunctionHART Fast Keys
Signal Power1,2,4,6
8714i results1,2,4,7
Test Condition1,2,4,7,1
Test Criteria1,2,4,7,2
8714i Test Result1,2,4,7,3
Simulated Velocity1,2,4,7,4
Actual Velocity1,2,4,7,5
Velocity Deviation1,2,4,7,6
Transmitter Calibration Test Result1,2,4,7,7
Tube Calibration Deviation1,2,4,7,8
Tube Calibration Test Result1,2,4,7,9
Coil Circuit Test Result
Electrode Circuit Test Result
1
1
Trims1,2,5
D/A Trim1,2,5,1
Scaled D/A Trim1,2,5,2
Digital Trim1,2,5,3
Auto Zero1,2,5,4
Universal Trim1,2,5,5
View Status1,2,6
Basic Setup1,3
Tag1,3,1
Flow Units1,3,2
PV Units1,3,2,1
Special Units1,3,2,2
Volume Unit1,3,2,2,1
Base Volume Unit1,3,2,2,2
Conversion Number1,3,2,2,3
Base Time Unit1,3,2,2,4
Flow Rate Unit1,3,2,2,5
Line Size1,3,3
Quick Start Guide
1,2,4,7,10
1,2,4,7,11
31
Quick Start Guide
FunctionHART Fast Keys
PV Upper Range Value (URV)1,3,4
PV Lower Range Value (LRV)1,3,5
Calibration Number1,3,6
PV Damping1,3,7
Detailed Setup1,4
Additional Parameters1,4,1
Coil Drive Frequency1,4,1,1
Density Value1,4,1,2
PV Upper Sensor Limit (USL)1,4,1,3
PV Lower Sensor Limit (LSL)1,4,1,4
PV Minimum Span1,4,1,5
Configure Output1,4,2
Analog Output1,4,2,1
PV URV1,4,2,1,1
PV LRV1,4,2,1,2
PV AO1,4,2,1,3
AO Alarm Type1,4,2,1,4
AO Loop Test1,4,2,1,5
D/A Trim1,4,2,1,6
Scaled D/A Trim1,4,2,1,7
Alarm Level1,4,2,1,8
Pulse Output1,4,2,2
Pulse Scaling1,4,2,2,1
Pulse Width1,4,2,2,2
Pulse Mode1,4,2,2,3
Pulse Output Loop Test1,4,2,2,4
DI/DO Output1,4,2,3
Digital Input 11,4,2,3,1
Digital Output 21,4,2,3,2
Reverse Flow1,4,2,4
Totalizer Set-Up1,4,2,5
Totalizer Units1,4,2,5,1
February 2014
32
February 2014
FunctionHART Fast Keys
Gross Total1,4,2,5,2
Net Total1,4,2,5,3
Reverse Total1,4,2,5,4
Start Totalizer1,4,2,5,5
Stop Totalizer1,4,2,5,6
Reset Totalizer1,4,2,5,7
Alarm Level1,4,2,6
HART Output1,4,2,7
Variable Mapping1,4,2,7,1
TV is1,4,2,7,1,1
4V is1,4,2,7,1,2
Poll Address1,4,2,7,2
# of Req Preams1,4,2,7,3
# of Resp Preams1,4,2,7,4
Burst Mode1,4,2,7,5
Burst Option1,4,2,7,6
LOI Config1,4,3
Language1,4,3,1
Flowrate Display1,4,3,2
Totalizer Display1,4,3,3
Display Lock1,4,3,4
Signal Processing1,4,4
Operating Mode1,4,4,1
Manual Configure DSP1,4,4,2
Status1,4,4,2,1
Samples1,4,4,2,2
% Limit1,4,4,2,3
Time Limit1,4,4,2,4
Coil Drive Frequency1,4,4,3
Low Flow Cutoff1,4,4,4
PV Damping1,4,4,5
Quick Start Guide
33
Quick Start Guide
FunctionHART Fast Keys
Universal Trim1,4,5
Device Info1,4,6
Manufacturer1,4,6,1
Tag1,4,6,2
Descriptor1,4,6,3
Message1,4,6,4
Date1,4,6,5
Device ID1,4,6,6
PV Sensor Serial Number1,4,6,7
Sensor Tag1,4,6,8
Write Protect1,4,6,9
Revision No.
Universal Rev
Transmitter Rev
Software Rev
Final Assembly #
Construction Materials
Flange Type
Flange Material
Electrode Type
Electrode Material
Liner Material
1
1
1
1
1
1
1
1
1
1
1
Review1,5
1. Scroll through the menu on the Field Communicator to access this item.
1.
February 2014
1,4,6,10
1,4,6,10,1
1,4,6,10,2
1,4,6,10,3
1,4,6,10,4
1,4,6,11
1,4,6,11,1
1,4,6,11,2
1,4,6,11,3
1,4,6,11,4
1,4,6,11,5
34
February 2014
Table 10. HART field communicator fast keys for wall mount
FunctionHART Fast Keys
Process Variables (PV)1,1
Primary Variable Value1,1,1
Primary Variable%1,1,2
PV Loop Current1,1,3
Totalizer Set-Up1,1,4
Totalizer Units1,1,4,1
Gross Total1,1,4,2
Net Total1,1,4,3
Reverse Total1,1,4,4
Start Totalizer1,1,4,5
Stop Totalizer1,1,4,6
Reset Totalizer1,1,4,7
Pulse Output1,1,5
Diagnostics1,2
Diagnostic Controls1,2,1
Basic Diagnostics1,2,2
Self Test1,2,2,1
AO Loop Test1,2,2,2
Pulse Output Loop Test1,2,2,3
Tune Empty Pipe1,2,2,4
EP Value1,2,2,4,1
EP Trigger Level1,2,2,4,2
EP Counts1,2,2,4,3
Electronics Temp1,2,2,5
Flow Limit 11, 2,2,6
Control 11,2,2,6,1
Mode 11,2,2,6,2
High Limit 11,2,2,6,3
Low Limit 11,2,2,6,4
Quick Start Guide
35
Quick Start Guide
FunctionHART Fast Keys
Flow Limit Hysteresis1,2,2,6,5
Flow Limit 21,2,2,7
Control 21,2,2,7,1
Mode 21,2,2,7,2
High Limit 21,2,2,7,3
Low Limit 21,2,2,7,4
Flow Limit Hysteresis1,2,2,7,5
Total Limit1,2,2,8
Total Control1,2,2,8,1
Total Mode1,2,2,8,2
Total High Limit1,2,2,8,3
Total Low Limit1,2,2,8,4
Total Limit Hysteresis1,2,2,8,5
Advanced Diagnostics1,2,3
8714i Meter Verification1,2,3,1
Run 8714i1,2,3,1,1
8714i Results1,2,3,1,2
Test Condition1,2,3,1,2,1
Test Criteria1,2,3,1,2,2
8714i Test Result1,2,3,1,2,3
Simulated Velocity1,2,3,1,2,4
Actual Velocity1,2,3,1,2,5
Velocity Deviation1,2,3,1,2,6
Xmtr Cal Test Result1,2,3,1,2,7
Sensor Cal Deviation1,2,3,1,2,8
Sensor Cal Test Result1,2,3,1,2,9
Coil Circuit Test Result
Electrode Circuit Test Result
1
1
Sensor Signature1,2,3,1,3
Signature Values1,2,3,1,3,1
February 2014
1,2,3,1,2,10
1,2,3,1,2,11
36
February 2014
FunctionHART Fast Keys
Coil Resistance1,2,3,1,3,1,1
Coil Signature1,2,3,1,3,1,2
Electrode Resistance1,2,3,1,3,1,3
Re-Signature Meter1,2,3,1,3,2
Recall Last Saved Values1,2,3,1,3,3
Set Pass/Fail Criteria1,2,3,1,4
No Flow Limit1,2,3,1,4,1
Flowing Limit1,2,3,1,4,2
Empty Pipe Limit1,2,3,1,4,3
Measurements1,2,3,1,5
Coil Resistance1,2,3,1,5,1
Coil Signature1,2,3,1,5,2
Electrode Resistance1,2,3,1,5,3
Licensing1,2,3,2
License Status1,2,3,2,1
License Key1,2,3,2,2
Device ID1,2,3,2,2,1
License Key1,2,3,2,2,2
Diagnostic Variables1,2,4
EP Value1,2,4,1
Electronics Temp1,2,4,2
Line Noise1,2,4,3
5 Hz Signal to Noise Ratio (SNR)1,2,4,4
37 Hz SNR1,2,4,5
Signal Power1,2,4,6
8714i results1,2,4,7
Test Condition1,2,4,7,1
Test Criteria1,2,4,7,2
8714i Test Result1,2,4,7,3
Simulated Velocity1,2,4,7,4
Actual Velocity1,2,4,7,5
Quick Start Guide
37
Quick Start Guide
FunctionHART Fast Keys
Velocity Deviation1,2,4,7,6
Xmtr Cal Test Result1,2,4,7,7
Sensor Cal Deviation1,2,4,7,8
Sensor Cal Test Result1,2,4,7,9
Coil Circuit Test Result1,2,4,7,10
Electrode Circuit Test Result1,2,4,7,11
Trims1,2,5
D/A Trim1,2,5,1
Scaled D/A Trim1,2,5,2
Digital Trim1,2,5,3
Auto Zero1,2,5,4
Universal Trim1,2,5,5
View Status1,2,6
Basic Setup1,3
Tag1,3,1
Flow Units1,3,2
PV Units1,3,2,1
Special Units1,3,2,2
Volume Unit1,3,2,2,1
Base Volume Unit1,3,2,2,2
Conversion Number1,3,2,2,3
Base Time Unit1,3,2,2,4
Flow Rate Unit1,3,2,2,5
Line Size1,3,3
PV URV1,3,4
PV LRV1,3,5
Calibration Number1,3,6
PV Damping1,3,7
Detailed Setup1,4
Additional Params1,4,1
February 2014
38
February 2014
FunctionHART Fast Keys
Coil Drive Freq1,4,1,1
Density Value1,4,1,2
PV USL1,4,1,3
PV LSL1,4,1,4
PV Min Span1,4,1,5
Configure Output1,4,2
Analog Output1,4,2,1
PV URV1,4,2,1,1
PV LRV1,4,2,1,2
PV Loop Current1,4,2,1,3
PV Alarm Type1,4,2,1,4
AO Loop Test1,4,2,1,5
D/A Trim1,4,2,1,6
Scaled D/A Trim1,4,2,1,7
Alarm Level1,4,2,1,8
Pulse Output1,4,2,2
Pulse Scaling1,4,2,2,1
Pulse Width1,4,2,2,2
Pulse Output Loop Test1,4,2,2,3
DI/DO Output1,4,2,3
DI/DO 11,4,2,3,1
Configure I/O 11,4,2,3,1,1
DIO 1 Control1,4,2,3,1,2
Digital Input 11,4,2,3,1,3
Digital Output 11,4,2,3,1,4
DO 21,4,2,3,2
Flow Limit 11,4,2,3,3
Control 11,4,2,3,3,1
Mode 11,4,2,3,3,2
High Limit 11,4,2,3,3,3
Quick Start Guide
39
Quick Start Guide
FunctionHART Fast Keys
Low Limit 11,4,2,3,3,4
Flow Limit Hysteresis1,4,2,3,3,5
Flow Limit 21,4,2,3,4
Control 21,4,2,3,4,1
Mode 21,4,2,3,4,2
High Limit 21,4,2,3,4,3
Low Limit 21,4,2,3,4,4
Flow Limit Hysteresis1,4,2,3,4,5
Total Limit1,4,2,3,5
Total Control1,4,2,3,5,1
Total Mode1,4,2,3,5,2
Total High Limit1,4,2,3,5,3
Total Low Limit1,4,2,3,5,4
Total Limit Hysteresis1,4,2,3,5,5
Diagnostic Status Alert1,4,2,3,6
Reverse Flow1,4,2,4
Totalizer Setup1,4,2,5
Totalizer Units1,4,2,5,1
Gross Total1,4,2,5,2
Net Total1,4,2,5,5
Reverse Total1,4,2,5,4
Start Totalizer1,4,2,5,5
Stop Totalizer1,4,2,5,6
Reset Totalizer1,4,2,5,7
Alarm Level1,4,2,6
HART Output1,4,2,7
Variable Mapping1,4,2,7,1
TV is1,4,2,7,1,1
QV is1,4,2,7,1,2
Poll Address1,4,2,7,2
# of Req Preams1,4,2,7,3
# Resp Preams1,4,2,7,4
February 2014
40
February 2014
FunctionHART Fast Keys
Burst Mode1,4,2,7,5
Burst Option1,4,2,7,6
LOI Config1,4,3
Language1,4,3,1
Flow Rate Display1,4,3,2
Totalizer Display1,4,3,3
Display Lock1,4,3,4
Signal Processing1,4,4
Operating Mode1,4,4,1
Man Config DSP1,4,4,2
Status1,4,4,2,1
Samples1,4,4,2,2
% Limit1,4,4,2,3
Time Limit1,4,4,2,4
Coil Drive Freq1,4,4,3
Low Flow Cutoff1,4,4,4
PV Damping1,4,4,5
Universal Trim1,4,5
Device Info1,4,6
Manufacturer1,4,6,1
Tag1,4,6,2
Descriptor1,4,6,3
Message1,4,6,4
Date1,4,6,5
Device ID1,4,6,6
PV Sensor S/N1,4,6,7
PV Sensor Tag1,4,6,8
Write Protect1,4,6,9
Quick Start Guide
41
Quick Start Guide
FunctionHART Fast Keys
Revision No.
Universal Rev
Transmitter Rev
Software Rev
Final Assembly #
Construction Materials
Flange Type
Flange Material
Electrode Type
Electrode Material
Liner Material
1
1
1
1
1
1
1
1
1
1
1
Review1,5
1. Scroll through the menu on the Field Communicator to access this item.
Table 11. Electrical data
Rosemount 8750W with 8732 Flow Transmitter
Power supply:250 V ac, 1 A or 50 Vdc, 2,5 A, 20 W maximum
Pulsed output circuit: 30 V dc (pulsed), 0,25 A, 7,5 W maximum
4-20 mA output
circuit:
Sensors
Coil excitation
circuit:
Electrode circuit:
30 V dc, 30 mA, 900 mW maximum
40 V dc (pulsed), 0,5 A, 20 W maximum
in type of explosion protection intrinsic safety EEx ia IIC, Ui = 5 V, li = 0.2 mA,
Pi = 1 mW, Um = 250 V
February 2014
1,4,6,10
1,4,6,10,1
1,4,6,10,2
1,4,6,10,3
1,4,6,10,4
1,4,6,11
1,4,6,11,1
1,4,6,11,2
1,4,6,11,3
1,4,6,11,4
1,4,6,11,5
42
00825-0200-4750
Quick Start Guide
00825-0200-4750, Rev AA
February 2014
Emerson Process Management
Rosemount Inc.
8200 Market Boulevard
Chanhassen, MN USA 55317
www.rosemount.com
T (US) (800) 406-5252
T (Intnl) (303) 527-5200
Emerson Process Management
Asia Pacific Private Limited
1 Pandan Crescent
Singapore 128461
T (65) 6777 8211
F (65) 6777 0947
Enquiries@AP.EmersonProcess.com
Service Support Hotline: +65 6770 8711
Emerson Process Management
Flow B.V.
Neonstraat 1
6718 WX Ede
The Netherlands
T +31 (0) 318 495555
F +31 (0) 318 495556
Emerson FZE
P.O. Box 17033
Jebel Ali Free Zone
Dubai UAE
T +971 4 811 8100
F +971 4 886 5465
FlowCustomerCare.MEA@Emerson.com
The Emerson logo is a trade mark and service mark of Emerson Electric Co
Rosemount and the Rosemount logotype are registered trademarks of Rosemount Inc.
Emerson Process Management Latin America
Multipark Office Center
Turrubares Building, 3rd & 4th floor
Guachipelin de Escazu, Costa Rica
T+(506) 2505-6962
international.mmicam@emersonprocess.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.