Rosemount Legacy Quick Start Guide: Rosemount™ 4600 Oil & Gas Panel Pressure Transmitter Manuals & Guides

00825-0200-4022, Rev HB
Rosemount™ 4600 Oil & Gas Panel Pressure Transmitter
Quick Start Guide
January 2022
Quick Start Guide
February 2019
NOTICE
This guide provides basic guidelines for the Rosemount 4600 Oil & Gas Panel Pressure Transmitter. It does not provide instructions for diagnostics, maintenance, service, troubleshooting, explosion-proof, flameproof, or intrinsically safe (I.S.) installations. Refer to the Rosemount 4600 Reference Manual This manual is also available electronically on Emerson.com/Rosemount
Explosions can result in death or serious injury.
Transmitters located in hazardous areas should be installed in accordance with local codes and
requirements fo r that area.
Connection to transmitter housing uses a
Rosemount 4600 shall be connected using a suitable junction box, e.g. in the type of protection flameproof enclosure “d” or increased safety “e”. Use appropriately rated Ex adapters, blanking elements, and glands during installation.
Keep process insulation at least 1-in. (25 mm) from transmitter connection.
Electrical shock can result in death or serious injury.
Avoid contact with the leads and the terminals. High voltage that may be present on leads can cause electrical shock.
Apply torque only to the hex flat located at the process end of the transmitter. Do not apply torque to the transmitter body or electrical connection - severe damage could result. Do not exceed 100 ft-lb.
1
/2–14 NPT thread form. For hazardous location installations, the
.
for more instruction.
Contents
Mount the transmitter . . . . . . . . . . . . . . . . . . . . 3
Connect the wiring and power . . . . . . . . . . . . . 3
Configure the transmitter . . . . . . . . . . . . . . . . . 4
Trim the transmitter . . . . . . . . . . . . . . . . . . . . . . 5
2
Safety Instrumented Systems (SIS) . . . . . . . . . . . . . 6
Operation and maintenance . . . . . . . . . . . . . . . . . . 8
Product Certifications . . . . . . . . . . . . . . . . . . . . . . . . 9
February 2019
A
F
B
C
D
E

1.0 Mount the transmitter

1.1 Electrical connection
1. Pull the leads through the threaded mounting hole in the panel wall.
2. Hand tighten the electrical connection into the mounting hole.
3. Using a wrench on the hex flat at the process connection, apply sufficient torque to prevent transmitter vibration. Do not exceed 100 ft-lb.
1.2 Process connection
1. Hand tighten the appropriate sized impulse piping connector into the process connection.
2. Using a wrench on the hex flat at the impulse piping connection, apply enough torque to prevent process fluid leakage. Do not exceed 100 ft-lb.

2.0 Connect the wiring and power

Use the following steps to wire the transmitter:
1. Connect the red lead to the “+” terminal of the power supply.
2. Connect the black lead to the “-” terminal of the I/O card on the PLC.
3. Connect the green lead to panel ground.
The figure below shows the wiring connections necessary to power a Rosemount 4600 and enable communications with a hand-held Field Communicator.
Quick Start Guide
Figure 1. Rosemount 4600 Field Wiring
A. Rosemount 4600
L > 250 ohm
B. R C. Power supply
D. I/A card E. PLC F. Field Communicator
3
Quick Start Guide
1387
11.25
20
30
42.4
0
500
1000
Volt age (Vdc)
Load (Ohms)
Operating
region
2.1 Power supply
The dc power supply should provide power with less than two percent ripple. The total resistance load is the sum of the resistance of the signal leads and the load resistance of the controller, indicator, and related pieces. Note that the resistance of intrinsic safety barriers, if used, must be included.
Figure 2. Load Limitation
Maximum loop resistance = 43.5 (power supply voltage – 11.25)
The Field Communicator requires a minimum loop resistance of 250Ω for communication.

3.0 Configure the transmitter

February 2019
Note
A check ( ) indicates the basic configuration parameters. At a minimum, these parameters should be verified as part of the configuration and startup procedure.
Table 1. Field Communicator Fast Key Sequence
Function Fast Key sequence
Alarm Level Config. 1, 4, 2, 7, 7
Alarm and Saturation Levels 1, 4, 2, 7
Analog Output Alarm Direction 1, 4, 2, 7, 6
Analog Output Trim 1, 2, 3, 2
Burst Mode On/Off 1, 4, 3, 3, 3
Burst Options 1, 4, 3, 3, 4
Damping 1, 3, 6
4
Date 1, 3, 4, 1
Descriptor 1, 3, 4, 2
Digital To Analog Trim (4–20 mA Output) 1, 2, 3, 2, 1
Field Device Information 1, 4, 4, 1
Loop Test 1, 2, 2
February 2019
Table 1. Field Communicator Fast Key Sequence
Tag 1, 3, 1
Units (Process Variable) 1, 3, 2
Quick Start Guide
Function Fast Key sequence
Lower Sensor Trim 1, 2, 3, 3, 2
Message 1, 3, 4, 3
Number of Requested Preambles 1, 4, 3, 3, 2
Pressure Alert Config. 1, 4, 3, 5, 3
Poll Address 1, 4, 3, 3, 1
Poll a Multidropped Transmitter Left Arrow, 4, 1, 1
Re-mapping 1, 4, 3, 6, 4
Rerange- Keypad Input 1, 2, 3, 1, 1
Saturation Level Config. 1, 4, 2, 7, 8
Scaled D/A Trim (4–20 mA Output) 1, 2, 3, 2, 2
Scaled Variable Config. 1, 4, 3, 4, 7
Self Test (Transmitter) 1, 2, 1, 1
Sensor Information 1, 4, 4, 2
Sensor Temperature 1, 1, 4
Sensor Trim 1, 2, 3, 3
Sensor Trim Points 1, 2, 3, 3, 5
Status 1, 2, 1, 2
Temperature Alert Config. 1, 4, 3, 5, 4
Transmitter Securit y (Write Protect) 1, 3, 4, 5
Upper Sensor Trim 1, 2, 3, 3, 3
Zero Trim 1, 2, 3, 3, 1

4.0 Trim the transmitter

4.1 Zero trim
Note
Transmitters are shipped from Emerson™ fully configured per request or by the factory default of full scale (span = upper range limit).
A zero trim is a single-point adjustment to compensate mounting position and sealed gauge pressure effects. When performing a zero trim, ensure the transmitter is vented to atmosphere.
5
Quick Start Guide
A
B
4.2 Using the Field Communicator
February 2019
Fast Keys
1. Vent the transmitter to atmosphere and connect Field Communicator.
2. At the main menu, input the Fast Key sequence.
3. Follow the commands to perform a zero trim.
1, 3, 3, 2
4.3 Using the transmitter zero adjustment target
1. Vent the transmitter.
2. Set the 4 mA point by touching the magnetic end of a small magnetic tool to the zero target (Z) on the transmitter. You must maintain contact for at least two seconds, but no longer than 10 seconds for the zero function to activate.
3. Verify the output is 4 mA.
Figure 3. Local Zero and Span Target Locations
A. Magnetic span target B. Magnetic zero target

5.0 Safety Instrumented Systems (SIS)

The following section applies to Rosemount 4600 Transmitters used in SIS applications.
Note
6
Transmitter output is not safety-rated during the following: configuration changes, multidrop, loop test. Alternative means should be used to ensure process safety during transmitter configuration and maintenance activities.
Installation
No special installation is required in addition to the standard installation practices outlined in this document.
The loop must be designed so the terminal voltage does not drop below
11.25 Vdc when the transmitter output is 22.5 mA.
Loading...
+ 12 hidden pages