The device described in this document is the property of Emerson.
No part of the hardware, software, or documentation may be reproduced, transmitted, transcribed, stored in a retrieval system,
or translated into any language or computer language, in any form or by any means, without prior written permission from
Emerson.
While great efforts have been made to ensure the accuracy and clarity of this document, Emerson assumes no liability resulting
from any omissions in this document or from misuse of the information obtained herein. The information in this document has
been carefully checked and is believed to be entirely reliable with all of the necessary information included. Emerson reserves the
right to make changes to any products described herein to improve reliability, function, or design and reserves the right to revise
this document and make changes from time to time in content hereof with no obligation to notify any persons of revisions or
changes. Emerson does not assume any liability arising out of the application or any use of any product or circuit described herein;
neither does it convey license under its patent rights or the rights of others.
WARNING
All individuals who have or will have responsibility for using, maintaining, or servicing this product must read this document
carefully.
WARNING
Physical access
Unauthorized personnel may potentially cause significant damage to and/or misconfiguration of end users’ equipment. This could
be intentional or unintentional and needs to be protected against.
Physical security is an important part of any security program and fundamental to protecting your system. Restrict physical access
by unauthorized personnel to protect end users’ assets. This is true for all systems used within the facility.
CAUTION
Equipment damage
This device is not field repairable due to the meticulous alignment and calibration of the sensors and the respective circuits.
Modifying or repairing the internal circuits may impair the system's performance and void the Emerson product warranty.
Do not attempt to modify or repair the internal circuits or change their settings.
Warranty
1. Limited Warranty . Subject to the limitations contained in Section 2 (Limitation of Remedy and Liability) herein, Seller
warrants that (a) the licensed firmware embodied in the Goods will execute the programming instructions provided by
Seller; (b) that the Goods manufactured by Seller will be free from defects in materials or workmanship under normal use
and care; and (c) Services will be performed by trained personnel using proper equipment and instrumentation for the
particular Service provided. The foregoing warranties will apply until the expiration of the applicable warranty period.
Products purchased by Seller from a third party for resale to Buyer (Resale Products) shall carry only the warranty
extended by the original manufacturer. Buyer agrees that Seller has no liability for Resale Products beyond making a
reasonable commercial effort to arrange for procurement and shipping of the Resale Products. If Buyer discovers any
warranty defects and notifies Seller thereof in writing during the applicable warranty period, Seller shall, at its option, (i)
correct any errors that are found by Seller in the firmware or Services; (ii) repair or replace FOB point of manufacture that
portion of the Goods found by Seller to be defective; or (iii) refund the purchase price of the defective portion of the
Goods/Services. All replacements or repairs necessitated by inadequate maintenance; normal wear and usage; unsuitable
power sources or environmental conditions; accident; misuse; improper installation; modification; repair; use of
unauthorized replacement parts; storage or handling; or any other cause not the fault of Seller, are not covered by this
limited warranty and shall be replaced or repaired at Buyer's sole expense, and Seller shall not be obligated to pay any
costs or charges incurred by Buyer or any other party except as may be agreed upon in writing in advance by Seller. All
costs of dismantling, reinstallation, freight, and the time and expenses of Seller's personnel and representatives for site
travel and diagnosis under this limited warranty clause shall be borne by Buyer unless accepted in writing by Seller. Goods
repaired and parts replaced by Seller during the warranty period shall be in warranty for the remainder of the original
warranty period or 90 days, whichever is longer. This limited warranty is the only warranty made by Seller and can be
amended only in a writing signed by an authorized representative of Seller. The limited warranty herein ceases to be
effective if Buyer fails to operate and use the Goods sold hereunder in a safe and reasonable manner and in accordance
2
with any written instructions from the manufacturers. THE WARRANTIES AND REMEDIES SET FORTH ABOVE ARE
Legacy
EXCLUSIVE. THERE ARE NO REPRESENTATIONS OR WARRANTIES OF ANY KIND, EXPRESSED OR IMPLIED, AS TO
MERCHANTABILITY, FITNESS FOR PARTICULAR PURPOSE, OR ANY OTHER MATTER WITH RESPECT TO ANY OF THE GOODS
OR SERVICES.
2. Limitation of Remedy and Liability SELLER SHALL NOT BE LIABLE FOR DAMAGES CAUSED BY DELAY IN PERFORMANCE. THE
REMEDIES OF BUYER SET FORTH IN THE AGREEMENT ARE EXCLUSIVE. IN NO EVENT, REGARDLESS OF THE FORM OF THE
CLAIM OR CAUSE OF ACTION (WHETHER BASED IN CONTRACT INFRINGEMENT, NEGLIGENCE, STRICT LIABILITY, OTHER
TORT, OR OTHERWISE), SHALL SELLER'S LIABILITY TO BUYER AND/OR BUYER'S CUSTOMERS EXCEED THE PRICE TO BUYER
OF THE SPECIFIC GOODS MANUFACTURED OR SERVICES PROVIDED BY SELLER GIVING RISE TO THE CLAIM OR CAUSE OF
ACTION. BUYER AGREES THAT IN NO EVENT SHALL SELLER'S LIABILITY TO BUYER AND/OR BUYER'S CUSTOMERS EXTEND
TO INCLUDE INCIDENTAL, CONSEQUENTIAL, OR PUNITIVE DAMAGES. THE TERM "CONSEQUENTIAL DAMAGES" SHALL
INCLUDE, BUT NOT BE LIMITED TO, LOSS OF ANTICIPATED PROFITS, REVENUE OR USE AND COSTS INCURRED INCLUDING
WITHOUT LIMITATION FOR CAPITAL, FUEL AND POWER, AND CLAIMS OF BUYER'S CUSTOMERS.
Technical support
To get technical support for this product, contact your local Rosemount representative or the Rosemount Technical Support
department at +1 866 347 3427 or safety.csc@emerson.com
Return of material
To expedite the repair and return of this product, proper communication between the customer and the factory is important.
Before returning a product for repair, call +1 866 347 3427 or email safety.csc@emerson.com for a return material authorization
(RMA) number.
On the return of equipment, provide the following information:
1. RMA number provided to you by Emerson
2. Company name and contact information
3. Purchase order from your company authorizing repairs of request for quote
Ship all equipment prepaid to:
Emerson Automation Solutions
Measurement Solutions
6021 Innovation Blvd
Shakopee, MN 55379
Mark all packages with "Return for Repair" and include the RMA number.
Pack items to protect them from damage and use anti-static bags or aluminum-backed cardboard as protection from electrostatic
damage.
Ship all equipment prepaid. Emerson will not accept collect shipments.
E.2 Guidelines for configuring, installing, operating, and service..................................................... 75
Appendix FEnd of line resistor....................................................................................................79
6Emerson.com/Rosemount
Reference ManualIntroduction
Legacy
00809-0100-4976November 2021
1Introduction
1.1Overview
The Rosemount 975HR Multi-spectrum Infrared Hydrogen Flame Detector is specifically
designed for the detection of hydrocarbon and hydrogen flames. It detects hydrocarbonbased fuel and gas fires at long distances with the highest immunity to false alarms. The
detector can detect a gasoline pan fire at 215 ft. (65 m) or a hydrogen flame at 100 ft. (30
m) in less than five seconds.
All Rosemount 975 series detectors include a heated optical window for improved
performance in icing, snow, and condensation conditions.
The operator can easily adapt detection performance to all environments, applications,
and requirements by changing the detector's configuration parameters. Adjusting these
parameters, as well as performing other maintenance and monitoring tasks, is possible by
means of RS-485 based Modbus® communication or HART® communication (in models
with 0-20 mA output).
The detector enclosure is ATEX certified Exd flameproof with an integral, segregated, rear,
Exe terminal compartment (avoiding exposure of the sensors and electronics to
surrounding environment). Hence the combined approval:
Ex II 2G D
Ex db eb op is IIC T4 G
Ex tb op is IIIC T96 °C Db
(-55 °C ≤ Ta ≤ +75 °C)
or
Ex II 2G D
Ex db eb op is IIC T4 Gb
Ex tb op is IIIC T106 °C Db
(-55 °C ≤ Ta ≤ +85 °C)
The flame detector is designed to operate as a stand-alone unit directly connected to an
alarm system or an automatic fire extinguishing system. The detector can also be part of a
more complex system where many detectors and other devices are integrated through a
common control unit.
Rosemount 975HR7
IntroductionReference Manual
Legacy
November 202100809-0100-4976
1.2Ordering information
The Rosemount 975HR is provided in various configurations depending on:
• Output configurations
• Temperature ranges
• Type of cable entries
• Housing material type
• Required approval
The configuration detail is included in the product part
number on the product label and takes the form:
Rosemount 975HR-XXXXXXX, where XXXXXXX defines the
model according to the above requirements.
To modify the default or pre-ordered configuration and
perform maintenance tasks, please refer to the following
manuals: Rosemount 975 Flame Detector HART
Communication Manual (00809-0200-4975) or WinHost
Configuration and Diagnostic Software for Rosemount 975
Flame Detectors (00809-0300-4975).
CONFIGURE > VIEW PRODUCT >
Typical model number: 975HR1A6A1A1
The starred offerings (★) represent the most common
options and should be selected for best delivery. The nonstarred offerings are subject to additional delivery lead
time.
1.2.1Product description
CodeDescription
975975 flame detector★
1.2.2Technology
CodeDescription
MRMulti-spectrum infrared★
HRMulti-spectrum infrared hydrogen★
UFUltra fast ultraviolet infrared★
URUltraviolet infrared★
8Emerson.com/Rosemount
Reference ManualIntroduction
Legacy
00809-0100-4976November 2021
1.2.3Output configuration
CodeOutputsFault relayAlarm relayAuxiliary relayCurrent type
1AAnalog/HART®/
RS-485/relays
(fault, alarm)
2AAnalog/HART/
RS-485/relays
(fault, alarm)
3AAnalog/HART/
RS-485/relays
(fault, alarm)
1RRS-485/relays
(fault, alarm,
auxiliary)
2RRS-485/relays
(fault, alarm,
auxiliary)
Normally closedNormally openN/ASink★
Normally closedNormally open,
normally closed
Normally openNormally open,
normally closed
Normally closedNormally openNormally openN/A★
Normally openNormally openNormally openN/A★
N/ASource★
N/ASource★
1.2.4Housing style
CodeMaterialConduit entry
(1)
6A
8A
Aluminum¾-in. national pipe thread (NPT)★
(1)
AluminumM25★
6SStainless steel¾-in. NPT★
8SStainless steelM25★
(1) Aluminum housing is not available in FM/CSA product certification.
1.2.5Temperature
CodeDescription
1167 °F (75 °C)★
2185 °F (85 °C)★
1.2.6Product certifications
CodeDescription
A1ATEX and IECEx flameproof★
A2FM and CSA flameproof★
E2InMetro flameproof★
EMTechnical Regulations Customs Union (EAC) flameproof★
Rosemount 975HR9
IntroductionReference Manual
Legacy
November 202100809-0100-4976
1.2.7Spare parts and accessories
Part numberDescription
00975-9000-0001Tilt mount★
00975-9000-0002Duct mount★
00975-9000-0003Weather cover (plastic)★
00975-9000-0004Weather cover (stainless steel)★
00975-9000-0005Air shield★
00975-9000-00072-in. (50.8 mm) pipe mount★
00975-9000-00083-in. (76.2 mm) pipe mount★
00975-9000-0011USB RS-485 harness kit★
00975-9000-0012Spare battery pack for use with flame simulator★
00975-9000-0015Spare battery charger for use with flame simulator★
1.2.8Output configurations
Output
configuration
1APowerManual built-
2APowerManual built-
3APowerManual built-
1RPowerManual built-
2RPowerManual built-
Connections provided
in test
in test
in test
in test
in test
Fault relay
N.C.
Fault relay
N.C.
Fault relay
N.O.
Fault relay
N.C.
Fault relay
N.O.
Alarm relay
N.O.
Alarm relay,
N.O., N.C.
Alarm relay
N.O., N.C.
Alarm relay
N.O.
Alarm relay
N.O.
NOTICE
Output configuration 1A is default. You can change the mA sink output to source type,
with a link between terminals 1 and 8. You cannot change any other output configurations
on site.
0-20 mA sink RS-485HART
0-20 mA
source
0-20 mA
source
Auxiliary
N.O.
Auxiliary
N.O.
RS-485HART
RS-485HART
RS-485N/A
RS-485N/A
®
For example, product number Rosemount 975HR3A8S2A1 has the following options:
Check your specific part numbers against the information in Checking the product type.
1.3Features and benefits
The flame detector has the following features and benefits.
• Detects hydrocarbons and hydrogen flames.
• Detection range: Up to 215 ft. (65 m) for a 1 ft.2 (0.1 m2) n-heptane fire.
• Ultra high immunity to false alarms. See Table 1-3.
• Advanced digital processing of the dynamic characteristics of fire: flickering, threshold,
correlation, and ratio.
• Multi infrared channels: between two and five microns.
• Field programmable sensitivity: four ranges to avoid zone crossover.
• Built-in-test (BIT): manual and automatic (see Built-in test (BIT)).
• Heated window: prevents effects of icing, snow, and condensation.
• Electrical interface:
— Dry contact relays
— Communication network RS-485
— 0-20 mA output
• HART® protocol: communication protocol (see HART® protocol).
• Exde: integral junction box for easy wiring.
• SIL-2: TÜV approved.
• Hazardous area certification: ATEX, IECEx, FM, and CSA.
• Functionality approval:
— EN54-10 approved by VdS
— FM approved per FM3260
• Accessories are approved as part of ATEX and IECEx approval.
1.4Principles of operation
1.4.1Fire detection principle
Emerson designed this flame detector to detect hydrocarbon flames that produce CO2 in
their combusion process and non-hydrocarbon flames that produce mainly water vapor
Rosemount 975HR11
IntroductionReference Manual
Legacy
November 202100809-0100-4976
(H2O) from inorganic fuels, for example, hydrogen, ammonia, hydrofluoric acid,
hydrochloric acid, etc.
The detector's principle of operation is based on the patented spectral analysis technology
that identifies the infrared spectral signature of fire products, namely the hot CO2 spectral
emissions band at 4.2 to 4.7 microns and the hot water (H2O) spectral emission band at
2.7 to 3.0 microns. The detector also analyzes additional spectral bands (above and below
these bands) for background interferences.
The spectral analysis incorporates several detection algorithms, according to several types
of fire events, taking into account simultaneous detection of both CO2 and H2O peaks or
only one of them, as well as flickering analysis at frequencies typical to these flames. Only
when all the parameters of the spectral analysis and the flickering analysis meet the
predetermined values is a fire condition identified and the fire alarm activated.
When exposed to non-fire radiation sources, these parameters do not identify a fire
condition, and the detector does not react.
1.4.2Heated optics
The flame detector uses heated optics. The heater increases the temperature of the
optical surface by 5 to 8 °F (3 to 5 °C) above the ambient temperature to improve
performance in icing, condensation, and snow conditions.
The heated optics can be set to one of the following:
• Off, not operating.
• On continuously.
• Automatic, per temperature change (default): the operator can define the start
temperature below which the window is heated. The default is 41 °F (5 °C). The
operator can define this temperature between 32 °F (0 °C) and 122 °F (50 °C). The
heating stops when the temperature is 27 °F (15 °C) above the start temperature.
For more information, see Configure the detector.
1.4.3HART® protocol
The flame detector uses the HART protocol.
HART communication is a bi-directional industrial field communication protocol used to
communicate between intelligent field instruments and host systems. HART is the global
standard for smart process instrumentation, and the majority of smart field devices
installed in plants worldwide are HART-enabled. HART is available in output configurations
1A, 2A, and 3A (see Output configuration).
HART technology is easy to use and very reliable.
Through the HART connection, you can do the following:
• Detector setup
• Detector troubleshooting
• Detector health and status
12Emerson.com/Rosemount
Reference ManualIntroduction
Legacy
00809-0100-4976November 2021
For more details, refer to Rosemount 975 HART Communication Manual
(00809-0200-4975).
1.4.4RS-485 Modbus
For more advanced communications, the flame detector has an RS-485 Modbuscompatible output that provides data communication from a network (up to 247
detectors) to a host computer or universal controller for central monitoring. This feature
allows for reduced installation costs, easy maintenance, and local or remote diagnostic
tools.
®
1.4.5Product certifications
The flame detector has the following certifications:
• ATEX, IECEx
• FM, CSA
• SIL-2 (TÜV)
• EN54-10
• InMetro (UL)
• TR CU/EAC
ATEX, IECEx
The flame detector is certified to:
ATEX per SIRA 15ATEX1364X and IECEx per IECEx SIR 15.0138X.
Ex II 2G D
Ex db eb op is IIC T4 Gb
Ex tb op is IIIC T96 °C Db
(-55 °C ≤ Ta ≤ +75 °C)
or
Ex II 2G D
Ex db eb op is IIC T4 Gb
Ex tb op is IIIC T106 °C Db
(-55 °C ≤ Ta ≤ +85 °C)
The accessories: tilt mount (PN 00975-9000-0001), weather cover (PN 00975-9000-0003
[plastic] and PN 00975-9000-0004 [stainless steel]), duct mount (PN 00975-9000-0002),
and air shield (PN 00975-9000-0005), are included in the approval.
This product is available to use in hazardous zones 1 and 2 with IIC gas group vapors
present and zones 21 and 22 with IIIC dust type present.
Rosemount 975HR13
IntroductionReference Manual
Legacy
November 202100809-0100-4976
FM, CSA
The flame detector is certified to FM and CSA explosion proof and functionality per
FM3260.
• Class I, Division 1, Groups B, C, and D, T5 Ta = 85 °C.
• Dust ignition proof - Class II/III Division 1, Groups E, F, and G.
• Ingress protection - IP67, IP66, NEMA 250 Type 6P
• For more details, see FM Report Project ID3029553 and CSA Report No. 2451134.
SIL-2 (TÜV)
The flame detector is certified to SIL-2 requirement per IEC 61508A, Chapter 3.5.12.
The alert condition according to SIL-2 can be implemented by:
• Alert signal via 0-20 mA current loop
or
• Alert signal via alarm relay and fault relay
For more details and guidelines for configuring, installing, operating, and service, see SIL-2
features and TUV Report No. 968/FSP 1223.
EN54-10
The flame detector is approved per EN54-10 and CPD.
• The detector is listed as Class 1 for sensitivity settings 15, 30, 45, and 60 and Class 2 for
sensitivity settings 15, 30, 45, and 60.
• The detector has been tested and approved per EN54-10 Vds.
• This test includes functional test, environmental test, EMI/EMC test, and software
check.
• For more details, see Vds Reports Numbers BMA 12117 and BMA 12118.
InMetro (UL)
The flame detector is in compliance with the following standards as of May 18, 2010:
• ABNT NBR IEC 60079-0
• ABNT NBRIEC 60079-1
• ABNT NBR IEC 60079-7
• ABNT NBR IEC 60079-18
• ABNT NBR IEC 60079-31
• INMETRO decree No. 179
For further details, see the Certificate of Compliance No. UL-BR 16.065XX.
14Emerson.com/Rosemount
Reference ManualIntroduction
Legacy
00809-0100-4976November 2021
TR CU/EAC
The flame detector is in compliance with the standard TR CU 012/2011 per:
1Ex db eb op is IIC T4 Gb X
Ex tb op is IIIC T96 °C Db X
-55 °C ≤ Ta ≤ +75 °C
or
1Ex db eb op is IIC T4 Gb X
Ex tb op is IIIC T106 °C Db X
-55 °C ≤ Ta ≤ +85 °C
For more details, see TR CU certificate No. TC RU C-US MЮ 62.B05535.
1.5Performance considerations
1.5.1Detection sensitivity
Detection sensitivity is the maximum distance at which the detector reliably detects a
specific size of fire and typical type of fuel (standard fire).
Standard fire
Defined as 1 ft.2 (0.1 m2) n-heptane pan fire with maximum wind speed of 6.5 ft./sec
(2 m/sec).
Sensitivity ranges
The detector has four user-selectable sensitivity ranges. For each range, there are two
response levels:
• Warning (Pre-alarm)
• Alarm
The detection distance for the Warning level is approximately 10 percent higher than the
Alarm distance.
Alarm response times for a standard fire at a specified range are shown in Table 1-1.
Table 1-1: Sensitivity Range Levels
LevelResponse time (sec)Sensitivity range - ft. (m) (for
1 ft.2 (0.1 m2) n-heptane pan
fire)
1350 (15)
2 default5100 (30)
38150 (45)
Rosemount 975HR15
IntroductionReference Manual
Legacy
November 202100809-0100-4976
Table 1-1: Sensitivity Range Levels (continued)
LevelResponse time (sec)Sensitivity range - ft. (m) (for
1 ft.2 (0.1 m2) n-heptane pan
fire)
410215 (65)
For some typical ambient conditions, the Zeta parameter as defined in NFPA 72 for the
detector is 0.005 (1/meter).
Note
Zeta parameters may vary significantly with changes in temperature, air pressure,
humidity, visibility conditions, etc.
Other fuels
The detector reacts to other types of fire as follows:
• The baseline fire refers to n-heptane 1 ft.2 (0.1 m2) and is defined as 100 percent
sensitivity.
• For fuel fire: standard pan fire size: 1 ft.2 (0.1 m2)
• For gas flame: 30 in. (0.75 m) high, 10 in. (0.25 m) wide plume fire
• Maximum response time: 10 sec.
Table 1-2: Fuel Sensitivity Ranges
Type of fuelPercent of max. distance at each sensitivity rangeMax. distance
Gasoline100%215 / 65
n-Heptane100%215 / 65
JP570%150 / 45
Kerosene70%150 / 45
Diesel fuel70%150 / 45
Ethanol 95%60%135 / 40
IPA60%135 / 40
Methanol55%115 / 35
(1)
(1)
70%150 / 45
70%150 / 45
Methane
LPG
Paper38%82 / 25
(ft. / m)
Polypropylene55%115 / 35
(2)
(2)
(1)
50%125 / 38
3%7 / 2
27%60 / 18
Hydrogen
Silane
Ammonia
(1) 30 in. (0.75 m) high, 10 in. (0.25 m) wide plume fire
16Emerson.com/Rosemount
Reference ManualIntroduction
Legacy
00809-0100-4976November 2021
(2) 20 in. (0.5 m) high, 8 in. (0.2 m) wide plume fire
Rosemount 975HR17
IntroductionReference Manual
Legacy
November 202100809-0100-4976
1.5.2Field of view
Gasoline
For Rosemount 975HR.
• Horizontal: 80 °
• Vertical: 80 °
Figure 1-1: Vertical and Horizontal Field of View for Gasoline
Hydrogen
For Rosemount 975HR.
• Horizontal: 70 °
18Emerson.com/Rosemount
• Vertical: 80 °
Reference ManualIntroduction
Legacy
00809-0100-4976November 2021
Figure 1-2: Horizontal Field of View for Hydrogen
A. Relative range
Rosemount 975HR19
IntroductionReference Manual
Legacy
November 202100809-0100-4976
Figure 1-3: Vertical Field of View for Hydrogen
A. Relative range
1.5.3False alarms prevention
20Emerson.com/Rosemount
To prevent false alarms, the detector will not alarm or react to the radiation sources
specified in the table below.
Table 1-3: Immunity to False Alarm Sources
Radiation sourceImmunity distance ft. (m)
Indirect or reflected sunlightIAD
Vehicle headlights (low beam) conforming to
MS53023-1
Incandescent frosted glass light, 300 WIAD
Fluorescent light with white enamel reflector,
standard office or shop, 70 W (or two 35 W)
IAD
IAD
Reference ManualIntroduction
Legacy
00809-0100-4976November 2021
Table 1-3: Immunity to False Alarm Sources (continued)
Radiation sourceImmunity distance ft. (m)
Electric arc (15/32 in. [12 mm] gap at 4,000 Vac,
60 Hz)
One three-color LED indicator is located inside the detector window, as shown in Figure
1-4. The detector statuses are listed in Table 1-5.
Rosemount 975HR21
IntroductionReference Manual
Legacy
November 202100809-0100-4976
Table 1-5: LED Indications
Detector statusLED colorLED mode
Fault, BIT FaultYellow4 Hz - flashing
NormalGreen1 Hz - flashing
WarningRed2 Hz -flashing
AlarmRedSteady
Figure 1-4: Indication LED
A. Indicator LED
1.5.5Output signals
Outputs are available according to the default configuration or the wiring options selected
for the detector.
Determine the outputs of your model according to Table 1-6.
The detector incorporates several types of output suitable to different control systems.
• 0-20 mA (stepped) with HART
22Emerson.com/Rosemount
®
Reference ManualIntroduction
Legacy
00809-0100-4976November 2021
• Relays (alarm, fault, auxiliary)
• RS-485 Modbus
Table 1-6: Available Output Types
Output typeVersionDetector status
®
Alarm relay975HR- output configurations
Auxiliary relay975HR - output configurations
Fault relay975HR - output configurations
0-20 mA current output975HR - output configuration
RS-485All versionsModbus protocol
1.5.6Detector status
1AXXXXX, 1RXXXXX, and
2RXXXXX
975HR - output configurations
2AXXXXX and 3AXXXXX
1AXXXXX, 2AXXXXX, and
1RXXXXX
1AXXXXX, 2AXXXXX, and
1RXXXXX
975HR - output configurations
3AXXXXX and 2RXXXXX
1AXXXXX
975H - output configurations
2AXXXXX and 3AXXXXXR
The relay is N.O.
The relay is N.O. and N.C.
The relay is N.O.
The relay is N.C. energized.
The relay is N.O. energized.
Sink with the HART protocol
(can be changed to Source - see
Figure B-3, Figure B-4, and
Figure B-5).
Source with the HART protocol
The possible detector function statuses are listed in the table below. Use HART® or
Modbus® to see a more detailed fault analysis.
Table 1-7: Detector Statuses
StatusDescription
Rosemount 975HR23
NormalNormal operation.
BITBuilt-in test being performed.
WarningFire detected - changed to Warning (pre-alarm state).
AlarmFire detected - changed to Fire Alarm state.
Latched alarm (optional)The alarm outputs remain latched on following detection of a fire
that has already been extinguished.
BIT faultA fault is detected during built-in test sequence or other electric
failure. The detector will continue to detect for fire.
FaultA fault is detected when the power supply is too low or due to a
software fault or electrical failure. The detector will not detect fire
in this condition.
IntroductionReference Manual
Legacy
November 202100809-0100-4976
In each state, the detector activates different outputs, as specified in Table 1-8.
Table 1-8: Output Signals vs. Detector State
Detector state LED indicatorLED modeAlarm relayAuxiliary relay Fault relaymA output
NormalGreen1 HzOffOffOn4 mA
On
(1)
(1)
(1)
On16 mA
On20 mA
Off16 mA
WarningRed2 HzOffOn
(2)
Alarm
(3)
Latch
BIT Fault
Warning at BIT
Fault
(4)
RedConstantOnOnOn20 mA
RedConstantOnOffOn20 mA
Yellow4 HzOffOffOff2 mA
Red2 HzOffOn
Alarm at BIT
Fault
FaultYellow4 HzOffOffOff0 mA
(1) The auxiliary relay can be activated at the Warning level or Alarm level, depending on programmed function.
(2) The alarm outputs are activated while alarm conditions exist and will stop approximately five seconds after a fire is no
longer detected.
(3) The Alarm state can be optionally latched via programmed function. (Default is non-latching).
(4) The detector will remain in BIT Fault state until it has passed a successful built-in test.
RedConstantOnOnOff20 mA
Note
The outputs depend on the output configurations.
Optional latching
Alarms are set as non-latching by default. However, the detector includes a latched alarm
output capability, which operates according to the programmed function.
If selected, upon detection of a fire, the detection signal is latched until the operator
manually resets the detector (disconnecting the power supply or performing a manual
built-in test [see Manual built-in test]).
Latching affects the alarm relay, 0-20 mA output, and the alarm LED. The auxiliary relay is
latched only when the programmable function Auxiliary Relay is set to Yes.
NOTICE
The auxiliary relay is available only in models with output configurations - 1RXXXXX and
2RXXXXX.
The 0-20 mA is available only in models with output configurations - 1AXXXXX, 2AXXXXX,
and 3AXXXXX.
24Emerson.com/Rosemount
Loading...