Emerson designs, manufactures, and tests products to function within specific conditions. Because these products are
sophisticated technical instruments, it is important that the owner and operation personnel strictly adhere both to the
information printed on the product nameplate and to all instructions provided in this manual prior to installation, operation, and
maintenance.
WARNING
Installing, operating, or maintaining an Emerson product improperly could lead to serious injury or death from explosion or
exposure to dangerous substances.
Comply with all information on the product, in this manual, and in any local and national codes that apply to the product.
Do not allow untrained personnel to work with this product.
Use Emerson parts and work procedures specified in this manual.
Authorized personnel for installing, operating, servicing, and maintaining the GDU-Incus are instructed and trained qualified
personnel of the operating company and the manufacturer.
It is the operating company's responsibility to:
• Train staff.
• Observe safety regulations.
• Follow the Reference Manual.
Operators must:
• Have been trained.
• Have read and understood all relevant sections of the Reference Manual before commencing work.
• Know the safety mechanisms and regulations.
To avoid personal injury and loss of property, do not install, operate, maintain, or service this instrument before reading and
understanding this reference manual and receiving appropriate training.
WARNING
Heavy instrument
The GDU-Incus weighs approximately 40 lb. (18 kg).
Take care when lifting and carrying the unit.
Ensure that all bolts and fixings selected for mounting are suitable for the weight and that the wall, pole, or mounting surface
is solid and stable.
WARNING
Physical access
Unauthorized personnel may potentially cause significant damage to and/or misconfiguration of end users’ equipment. This could
be intentional or unintentional and needs to be protected against.
Physical security is an important part of any security program and fundamental to protecting your system. Restrict physical access
by unauthorized personnel to protect end users’ assets. This is true for all systems used within the facility.
2
NOTICE
The contents of this publication are presented for informational purposes only and while every effort has been made to ensure
their accuracy, they are not to be construed as warranties or guarantees, expressed or implied, regarding the products or services
described herein or their use or applicability. All sales are governed by Emerson's terms and conditions, which are available upon
request. We reserve the right to modify or improve the designs or specifications of such products at any time.
Emerson does not assume responsibility for the selection, use, or maintenance of any product. Responsibility for proper selection,
use, and maintenance of any Emerson product(s) remains solely with the purchaser and end user.
To the best of Emerson's knowledge, the information herein is complete and accurate. Emerson makes no warranties, expressed
or implied, including implied warranties of merchantability and fitness for a particular purpose with respect to this manual and, in
no event, shall Emerson be liable for any incidental, punitive, special, or consequential damages including, but not limited to, loss
of production, loss of profits, loss or revenue, or use and costs incurred including without limitation for capital, fuel and power,
and claims of third parties.
Product names used herein are for manufacturer or supplier identification only and may be trademarks or registered trademarks
of these companies.
All rights reserved. No part of this work may be reproduced or copied in any form or by any means graphic, electronic, or
mechanical without first receiving written permission of Emerson, Shakopee, Minnesota, United States.
Appendix ATheory of operation................................................................................................. 43
GDU-Incus5
ContentsReference Manual
August 202100809-0100-3003
6Emerson.com
Reference ManualIntroduction
00809-0100-3003August 2021
1Introduction
1.1Product overview
The GDU-Incus is an ultrasonic gas leak detector used for detecting airborne ultrasound
generated from pressurized gas leaks. Airborne ultrasound is generated when gas moves
from a high pressure area to a low pressure area with a ratio in excess of 1.8 to 1 upstream
to downstream. However, Emerson only recommends this detector for pressures above 2
bar (30 psi) gauge. The intensity of airborne ultrasound generated is dependent on a
number of factors including gas pressure, gas leak size, and gas temperature.
The detector uses four individual Piezo ceramic sensing heads designed using a patentpending floating crystal design. The sensor design makes the sensing heads virtually
indestructible and totally immune to temperature, moisture, and other contaminants
found in hazardous areas. The detector uses a continuous electronic monitoring test
feature to ensure complete functionality.
The detector has a large dynamic range, which allows use in a wide range of applications,
from offshore platforms to gas transportation systems. The multi-stage amplifier ensures
a linear output across the entire detector range without drop-off at each end of the range.
The detector is not designed to detect specific gas types, LEL, or ppm. It responds
instantaneously to the ultrasound produced by a wide range of gas leak sizes and remains
unaffected by even the most extreme weather conditions. The detector is rated to IP66/
IP67 and NEMA® Type 4X to withstand harsh environments.
The detector is supplied with a 4-20 mA analog output, a HART® interface, and two
configured relays.
1.2Service support
For technical support, contact your Emerson representative or email
safety.csc@emerson.com.
The Response Center will ask for product model and serial numbers and will provide a
Return Material Authorization (RMA) number.
The Response Center will also ask for the installation and application details.
WARNING
Hazardous substances
Individuals who handle products exposed to a hazardous substance can avoid injury if they
are informed of and understand the hazard. If the product being returned was exposed to
a hazardous substance as defined by the Occupational Safety and Health Administration
(OSHA), a copy of the required Safety Data Sheet (SDS) for each hazardous substance
identified must be included with the returned goods.
GDU-Incus7
IntroductionReference Manual
August 202100809-0100-3003
1.3Product recycling/disposal
Consider recycling equipment and packaging. Dispose of the product and packaging in
accordance with local and national legislations and regulations.
8Emerson.com
Reference Manual
00809-0100-3003August 2021
Installation
2Installation
2.1Safety messages
Instructions in this section may require special precautions to ensure the safety of
personnel performing the operations.
WARNING
Failure to follow these installation guidelines could result in death or serious injury.
Ensure that only qualified personnel perform the installation.
The area in which the detector is mounted must be in accordance with the certification
of the apparatus and in accordance with local or national standards.
Do not modify the enclosure or component parts; this will compromise the Hazardous
Area Certification.
Ensure that all wiring and power supply to the detector is within specified operating
parameters.
Except for the terminal cover, the GDU-Incus is a sealed unit. The main enclosure may
be opened only by Emerson or Emerson-authorized personnel. All warranties and
certifications are nullified if the seals are tampered with or broken.
The GDU-Incus is supplied without cable glands. Ensure that all cable entry threads are
sealed with an appropriate plug to eliminate water ingress and thread damage. At
installation, remove all shipping cable entry plugs and replace them with approved Ex d
cable glands or blanking plugs to meet hazardous locations requirements. If the
detector is to be installed in a Zone 1 Hazardous Area, an Ex d barrier seal must be used.
WARNING
Electrical hazard
Electrical shock could cause death or serious injury.
Use extreme caution when making contact with leads and terminals.
CAUTION
Equipment damage
Identification tags must be firmly secured to the GDU-Incus bracket to prevent unwanted,
locally-generated, ultrasonic noise. Refer to Figure 2-1.
2.2Unpack and inspect
Procedure
1. Carefully remove all components from the packaging.
GDU-Incus9
Installation
August 202100809-0100-3003
2. Verify the components against the enclosed packing list.
3. Inspect all components for obvious damage, such as broken or loose parts.
4. If any components are missing or damaged, contact your local Emerson
representative or the factory immediately.
Reference Manual
2.3Dimensions
Refer to Figure 2-1 for the dimensions of the GDU-Incus.
Note
Dimensions are in millimeters (top number) and inches (bottom number).
Figure 2-1: Dimensions
A. Suitable for M10 or equivalent
B. Main body enclosure (housing)
C. Standard mounting bracket shown. U-bolt kits (for pole mounting) and a "DNV" certified
bracket are available.
D. Display
E. Sensor head (four positions)
F. Customer cable entry position available for dual entry/relay output (ATEX/IECEx units
only)
G. Terminal compartment housing
H. Customer cable entry M20 standard. M250.5 in (13 mm) NPT or 0.75 in (19.0 mm) NPT
alternative
I. Identification tag (sold separately) can be mounted on either side of bracket using holes
provided.
J. Top body enclosure (housing)
10Emerson.com
Reference ManualInstallation
00809-0100-3003August 2021
2.4Installation procedure
Emerson recommends mounting the GDU-Incus between 10 and 16 ft. (3 and 5 m) above
the floor level to eliminate ground reflections and absorption. You may mount the
detector lower than 10 ft. (3 m), but that may reduce the coverage; contact an Emerson
representative for more details.
Check the area of installation for equipment capable of generating high levels of spurious
airborne noise that would not be classified as "normal background noise", such as pressure
release valves, etc. If any are present in the detector range of coverage, contact Emerson
or monitor the detector when activated to ensure immunity.
2.4.1Mechanical installation
The detector incorporates a dedicated flameproof terminal compartment certified to Ex d
and a flameproof main electronics compartment certified to Ex d, both sealed to IP66/
IP67.
CAUTION
Take care when removing the terminal cover during installation to ensure that the
flamepath surfaces are not scratched or damaged. See Wire the detector for more
information.
The detector has a large detection radius capability; take care when positioning it to use
the maximum coverage while eliminating blind spots and spurious alarms.
The detector has a variety of mounting options to incorporate installation into most
situations in industrial environments, such as wall/flat surface mounting (Mount to wall or
flat surface), vertical pole mounting (Mount to a pole), and mounting in an environment
where DNV certification is required (Mount DNV certified detector).
The detector should be mounted so that the four sensor heads are pointing vertically
downwards towards the floor or ground. See Figure 2-2.
GDU-Incus11
InstallationReference Manual
August 202100809-0100-3003
Figure 2-2: Three-Dimensional View of Detector Coverage.
The detector uses four independent sensor heads for full coverage. Figure 2-2 shows a
three-dimensional view of the coverage (detector not to scale) at a 10-ft. (3 m) height
above floor level with the detector pointing vertically downwards. The detector coverage
is specified as meters radius at the floor level, as this is the minimum sensing distance. As
shown, the entire area below the detector is covered, as well as some of the area above
and around the detector. Each sensor overlaps the next, so multiple sensors cover areas
underneath the detector.
12Emerson.com
Reference ManualInstallation
00809-0100-3003August 2021
2.5Mounting
2.5.1Mount to wall or flat surface
When mounting on a vertical flat surface, such as a wall with no significant vibration, use
the standard mounting bracket supplied with the detector. If you suspect vibration at the
fixing point, contact an Emerson representative for additional options.
Figure 2-3: Wall/Flat Surface Mounting Diagram
Dimensions in mm.
A. Wall mounting bracket
B. Standard bracket
C. Floor
D. Vertical mounting locking fastener, typical both sides
E. Roof
F. See Step 3.
G. See Step 2.
H. See Step 1.
Note
GDU-Incus assembly weight: approximately 40 lb. (18 kg). Ensure fixings are capable of
supporting assembly weight and local standards for shock loading.
GDU-Incus13
Installation
Reference Manual
August 202100809-0100-3003
Figure 2-4: Wall Mounting Drilling Template
Figure 2-4 shows the position of the mounting slots on the wall mounting bracket supplied
with the standard GDU-Incus. Drill pairs of Ø 0.4-in. (10 mm) holes on the mounting
surface between 1.2 in. (30 mm) and 2.8 in. (70 mm) apart, with a vertical distance of 7.48
in. (190 mm) between the two pairs of holes.
Procedure
1. Attach wall mounting bracket to wall of flat horizontal support using four M10
bolts.
14Emerson.com
Reference ManualInstallation
00809-0100-3003August 2021
2. Position the detector so that the standard bracket is on the studs of the wall
bracket. Secure the brackets together using the two M10 nuts supplied.
3. Permanently fix the brackets together using the socket head bolts and nuts
supplied.
Make sure to use spring washers.
2.5.2Mount to a pole
In large open areas, Emerson recommends mounting the detector on a pole to take
advantage of the large omni-directional detection coverage.
Mount the detector 10 to 16 ft. (3 to 5 m) high to eliminate reflections and ground
absorption. You may mount the detector lower than 10 ft. (3 m), but coverage may be
reduced; contact an Emerson representative for details.
Make sure the pole complies with local standards and is capable of supporting the
detector weight at the installation height, taking environmental factors into
consideration.
Attach the detector to the pole using two U-bolts fixed to the pole mounting adapter (you
can use the wall bracket for pole mounting if the pole is 1.5 to 2-in. (38.1 to 50.8 mm)
diameter. Emerson suggests torquing to 45 Nm, but use local standards in the first
instance.
GDU-Incus15
Installation
Reference Manual
August 202100809-0100-3003
Figure 2-5: Pole Mounting Diagram
A. See Step 1.
B. See Step 2.
C. See Step 3.
D. Floor
E. Vertical mounting locking fastener
F. Roof
G. Pole mounting adapter
Note
Specify U-bolt and pole mounting adapter size at time of order. Standard parts are
available for tube sizes from Ø 1.5 in. (38.1 mm) to 4 in. (101.6 mm).
Weight of detector is 40 lb. (18 kg) approximately. Specify free-standing pole size to
support the detector to local standards. Ensure calculations employ suitable civic factor of
safety to support extended weight at detection height. Ensure nyloc fixing nuts are
tightened to 45 Nm or to applicable local standards.
Procedure
1. Attach pole mounting adapter to pole using two M10 U-bolts. Secure using nyloc
nuts and/or spring washers.
2. Position the detector so that the standard bracket is on the studs of the pole
adapter. Secure the brackets together using the two M10 nuts provided.
3. Permanently fix the brackets together using the socket head bolts and nuts
supplied.
Use spring washers.
16Emerson.com
Reference ManualInstallation
00809-0100-3003August 2021
2.5.3Mount DNV certified detector
When an installation requires equipment to be DNV certified, you must mount the
detector using a DNV mounting bracket.
Figure 2-6: DNV Mounting Diagram
A. Roof
B. Detector permanently locked in vertical position by 4X M10 bolts (one either side and
two on underside of bracket)
C. Floor
D. See Step 3.
E. See Step 2.
F. See Step 1.
G. DNV mounting bracket: GDU-02-412
Figure 2-6 shows the mounting arrangement for DNV installation. Torque all bolts to
45 Nm and use spring washers in all cases.
GDU-Incus17
InstallationReference Manual
August 202100809-0100-3003
Figure 2-7: DNV Mounting Drilling Template
Figure 2-7 shows the position of the mounting slots on the DNV mounting bracket
supplied with the DNV detector. Drill pairs of Ø 0.4-in. (10 mm) holes between 2.8 in.
(70 mm) and 3.5 in. (90 mm) apart, with a vertical distance of 3 in. (75 mm) between the
two pairs of holes.
Procedure
1. Attach DNV mounting bracket directly to wall or flat horizontal support using 4 M10
bolts as shown.
Use spring washers.
2. Rest the detector on the flat base plate of the DNV bracket and secure using M10
bolts either side, making sure to use spring washers.
3. Secure the detector to the base plate using two M10 bolts, making sure to use
spring washers.
2.6Terminal compartment wiring
WARNING
Failure to follow these installation guidelines could result in death or serious injury.
Ensure that only qualified personnel install the detector.
18Emerson.com
Reference ManualInstallation
00809-0100-3003August 2021
WARNING
Electrical shock could cause death or serious injury.
Use extreme caution when making contact with the leads and terminals.
Do not open the detector's enclosure in a classified area or where an explosive
atmosphere may be present unless the power to the detector has been removed.
The detector's terminal cover is certified to flameproof standards; do not open it while
energized.
NOTICE
Connect the detector housing to local ground via the external earth point as shown in
Figure 2-12. Make sure the ground wire is a minimum of 4 mm2 (8 AWG) and as short as
possible. Make sure termination at the detector is suitable for M6 (0.25-in.) fastener.
Ensure earth wire is attached using the supplied spring washer.
The standard GDU-Incus is temperature rated between -40 and +185 °F (-40 and +85 °C),
and the heated variant is temperature rated between -67 and +185 °F (-55 and +85 °C).
Ensure that all cable is rated to the appropriate temperature of installation.
GDU-Incus19
Installation
August 202100809-0100-3003
Reference Manual
2.6.1Wire the detector
NOTICE
Wiring codes and regulations may vary. Wiring must comply with all applicable regulations
relating to the installation of electrical equipment in a hazardous area and is the installer's
responsibility. If in doubt, consult a qualified official before wiring the system.
In applications where wiring is installed in a conduit, do not use the conduit for wiring to
other equipment.
For full EMC requirements, ensure incoming cables are threaded through the ferrite beads
(provided with the detector). See Figure 2-8.
Figure 2-8: Ferrite Bead Locations
A. Thread cable through ferrite
B. Ferrite
20Emerson.com
Reference Manual
Installation
00809-0100-3003August 2021
Procedure
1. To gain access to the terminal compartment, undo the six terminal cover fixing
screws and raise the terminal cover vertically until clear of the main enclosure.
The terminal cover is held in place with a stainless steel wire. You can lower the
terminal cover to the side of the detector during installation, but take care to
ensure the flame path is not damaged. Refer to Figure 2-9 for the flamepath details.
Figure 2-9: Flame Path Details
A. Terminal cover
B. Flame path
C. O-ring
2. Seal the terminal compartment with two O-rings to prevent water ingress.
Before closing, Emerson recommends visually inspecting the detector to ensure the
O-rings are in place and undamaged. Also check the flame paths of the terminal
GDU-Incus21
Installation
Reference Manual
August 202100809-0100-3003
cover and main enclosure for signs of damage. See Figure 2-9 for O-ring and flame
path positions.
3. Connect cable shield to instrument earth in the control room only unless extra radio
frequency interference (RFI) protection is required and all local and site grounding
regulations are met, in which case, terminate the shield to local ground via one of
A. Customer cable entry position 1
B. M4 internal earth point for use with multiple cable entry
C. Ferrite supplied in box
D. Terminal row 1
E. Terminal board
F. Terminal row 2
G. M4 internal earth point for use with multiple cable entry
H. Customer cable entry position 2 (not available for FM certified detectors)
22Emerson.com
Reference ManualInstallation
00809-0100-3003August 2021
Figure 2-10 shows a view of the GDU-Incus with the terminal cover removed. For
single entry enclosures, enter customer cable via position 1; use positions 1 and 2
for dual entry enclosures.
The terminals are separated into power and communications for terminal row 1 and
relay outputs for terminal row 2.
4. Tighten the six terminal cover fixing screws to a torque of 9 Nm.
WARNING
Ensure cable entry is via suitable hazardous area approved and ingress
protection certified cable glands (customer supplied) or conduit.
The ATEX/IECEx approved GDU-Incus has two positions for M20 cable glands,
while the FM approved detector has one position for ¾-in. national pipe thread
(NPT) conduit.
Fit cable glands and conduit in accordance with manufacturers' instructions for
assembly to a certified flame-proof enclosure.
Seal all unused cable entries with a flame-proof certified plugging device.
Ensure all cable gland and plugging devices are ingress protected to the same
standard as the enclosure to maintain certification and are suitable for the size
of the cable used.
If the detector is to be installed in an ATEX Zone 1 Hazardous Area, use an Exd
barrier seal.
Seal all FM approved detectors (US and Canada) within 18 in. (457.2 mm) of
enclosure entry using a suitably rated conduit seal.
NOTICE
The terminal cover label specifies thread size for cable entry.
GDU-Incus23
InstallationReference Manual
August 202100809-0100-3003
2.6.2Wiring configurations
Figure 2-11: Electrical Connection Drawing
A. Terminal row 1
B. Terminal row 2
Table 2-1: Terminal Row 1
SymbolDescription
Single cable entry internal earth
0V24 V return - (0 V)
+24v+24 Vdc (15 to 30 Vdc)
mA4-20 mA output
24Emerson.com
Reference ManualInstallation
00809-0100-3003August 2021
Table 2-2: Terminal Row 2
AbbreviationDescription
F NOFault relay normally open
F NCFault relay normally closed
F CFault relay circuit contact
A1 NOAlarm 1 normally open
A1 NCAlarm 1 normally closed
A1 CAlarm 1 circuit contact
485+Factory use only
485-Factory use only
F1Factory use only
F2Factory use only
Refer to Table 2-1 and Table 2-2 for descriptions of the cable entries for terminal rows 1
and 2.
According to standard, connect three-wire connection cables to Terminal Row 1 in
positions +24 v, 0 V, and current loop output connected to the mA terminal. The
maximum loop resistance is 500 Ω.
Current source is the standard default operation; current sink is an option you should
specify when you order.
Relay data: 1.4 A, 30 Vdc switch voltage.
Related information
Relay options
2.7External cables
WARNING
Choose customer cable in accordance with hazardous area certification and applicable
local regulations.
The GDU-Incus has a temperature rating of 185 °F (85 °C). When used in areas with an
ambient temperature above 140 °F (60 °C), ensure cable has a rating that is equal to or
exceeds the proposed maximum working temperature.
The following data indicates maximum cable length restriction due to voltage drop based
on a nominal input voltage of 24 Vdc.
Conductor cross sectional
area/gauge
0.5 mm2, 20 AWG1770 ft. (540 m)240 ft. (75 m)
GDU-Incus25
Maximum cable length for
standard, non-heated GDUIncus
Maximum cable length for
heated GDU-Incus
InstallationReference Manual
August 202100809-0100-3003
Conductor cross sectional
area/gauge
1.0 mm2, 18 AWG2800 ft. (855 m)380 ft. (115 m)
1.5 mm2, 16 AWG4470 ft. (1360 m)620 ft. (185 m)
2.5 mm2, 14 AWG7120 ft. (2170 m)990 ft. (300 m)
2.8External ground
Connect the detector housing to local ground via the external earth point as shown in
Figure 2-12.
Figure 2-12: External Grounding Point
Maximum cable length for
standard, non-heated GDUIncus
Maximum cable length for
heated GDU-Incus
A. Terminal cover in open position
B. Terminal cover restraint
C. M6 external earth point
26Emerson.com
Reference Manual
00809-0100-3003August 2021
Installation
2.9Commissioning
2.9.1Visual inspection
Before powering the detector, inspect the following:
Refer to Figure 2-13 for key locations on the GDU-Incus when completing this inspection.
Figure 2-13: Components of the GDU-Incus
A. Display
B. Sensor (four positions)
C. Sensor pod (four positions)
D. Mounting bracket
E. Enclosure mounting point
F. Terminal cover bolts (six positions). Tighten to 9 Nm.
G. Terminal cover
H. External earth point
I. Main enclosure bolts (six positions). Do not remove or adjust.
• Ensure detector is correctly situated for area of detection.
• Ensure mounting bracket is secured to mounting points on the detector and mounting
surface/pole.
• Check pole mount (if present) for suitability to withstand detector weight and
measurement
• Ensure external earth is correctly attached using spring washer.
• Ensure correct cable gland installation and appropriate certification or local regulations
have been observed. Check correct cable installation in the terminal compartment;
ensure terminal compartment flame paths and seals are intact.
• Ensure incoming cable is threaded through ferrite beads (Figure 2-8).
GDU-Incus27
InstallationReference Manual
August 202100809-0100-3003
• Tighten terminal cover bolts to the 9 Nm recommended torque.
• Verify main enclosure bolts are in place. Emerson torques these bolts at the factory; do
not adjust or tamper with them.
• Check display glass for damage or contaminants that may display.
• Ensure correct operating supply voltage.
2.9.2Power up
Upon power up, a brief functionality check runs to ensure detector functionality; this lasts
no more than five seconds. Once completed, the detector goes into normal operation
using the factory/customer defaults specified at time of order or signals any faults that
may be present.
In addition, the display shows the real-time ultrasonic sound level, the detector becomes
responsive to commands for function setup via hand-held TREX or AMS, and all relays are
energized or de-energized as per defaults.
Note
If Emerson has set the detector at the factory for specific site requirements, Emerson
recommends carrying out the steps in Check sensor functionality before you finish
commissioning.
Related information
Fault outputs
28Emerson.com
Reference ManualOperation
00809-0100-3003August 2021
3Operation
3.1Normal operation
On power-up, the detector initializes a diagnostic check and then enters normal operation
mode as per factory default settings.
Factory operation mode 71 settings
• 4-20 mA = 4-120 dB (linear scale factor).
• Relays are energized open; loss of power causes alarm (fail-safe).
• Relays are set to non-latching.
• Reset alarms enabled; allows latched relays to be reset and restarts alarm delay.
• Alarm level set to 70 dB for relay output.
• Delay time set to 15 seconds for relay output.
3.1.1
• All communication ports are active and ready to receive commands.
Alarm level
The alarm level is the ultrasonic sound level at which an alarm state is triggered. During
the alarm state, the display flashes, the relays switch states, and the current loop becomes
active if one or more sensors were in fault mode (if no sensors are in fault, the current loop
will already be outputting dB level).
To avoid false alarms, Emerson recommends setting the alarm level above the background
level established by mapping when all processes are operational. If you don't know the
background level, Emerson recommends using the detector to analyze the background.
Take care to observe all processes that may cause intermittent ultrasonic noise, such as
pressure relief valves.
Contact an Emerson representative for advice on alarm levels.
Note
The higher the alarm level, the smaller the detector coverage radius; it is therefore
important to establish a safe alarm level at the lowest permissible rate.
GDU-Incus29
Operation
Reference Manual
August 202100809-0100-3003
Figure 3-1: Suggested Alarm Levels
A. Alarm level (dB), 6 dB above background sound level
B. Background sound level (dB)
Figure 3-1 shows the suggested alarm level settings (6 dB above background sound level)
for known background sound levels. The values shown have been found to provide
sufficient immunity against most spurious alarms; however, take care to survey the area of
installation for potential spurious noise.
If you don't know background levels, use typical historical process background levels along
with a safety factor. Contact an Emerson representative for historical values and guidance.
You can set alarm levels in the detector (via HART®/TREX/AMS) or at the control panel.
Most installations set the alarm levels in the control system. However, please note that the
best practice is to have the control panel and the GDU-Incus's internal alarm level to
always mirror each other. The reason for this is when the detector is in a sensor fault
condition, the detector's mA output will be a constant 2 mA and will not change to the real
30Emerson.com
Reference Manual
00809-0100-3003August 2021
time mA output (which can be converted to real-time dB) until the device's internally set
alarm level is reached or exceeded.
For example, assume a sensor fault is present and the detector's internal alarm level is set
at 70 dB. The detector's mA output will be 2 mA until the real time dB level meets or
exceeds 70 dB, at which point the detector's mA output will change to the mA value that
coincides with the real-time 70 db level the detector is sensing.
Lastly, the display on the detector will read the real time dB values at all times, regardless
of the mA loop output.
Operation
3.1.2Delay time
To avoid spurious alarms, Emerson recommends using a delay time for non-toxic gas
applications or when instantaneous detection is not required. The delay timer is activated
from the point at which the alarm threshold is first exceeded.
If ultrasonic noise drops below the alarm level threshold, the delay time is reset as shown
in Figure 3-3. If the ultrasonic noise level remains above the alarm level threshold for the
duration of the delay time, the alarm is activated as shown in Figure 3-2.
Figure 3-2: Graph Showing Alarm Activation with Leak
A. Ultrasonic sound level
B. Time duration (seconds)
C. Delay time (30 seconds)
D. Delay reached - alarm
E. Delay start point
F. Ultrasonic noise level
G. Background noise level
H. Alarm level
GDU-Incus31
OperationReference Manual
August 202100809-0100-3003
Figure 3-3: Graph Showing No Alarm Activation with Spurious Noise
A. Ulstrasonic sound level
B. Delay start point
C. Noise 1
D. Alarm dB exceeded
E. Delay reset
F. Delay start point
G. Delay reset
H. Noise 2
I. Delay time (30 seconds)
J. Noise 3
K. Delay start point
L. Delay reset
M. Alarm level
N. Background noise level
In Figure 3-3, noises 1 and 2 are spurious noise spikes of approximately 1.5 seconds,
typical of man-made ultrasonic noise produced through normal maintenance procedures.
Noise 3 is a longer spurious noise of approximately 13 seconds, typical of a pressure relief
valve. Delay time is introduced to ignore spurious noise spikes, as the detector will reset
when noise level drops below alarm level before the delay time is reached.
32Emerson.com
Reference Manual
Operation
00809-0100-3003August 2021
Figure 3-4: Graph Showing Alarm Activation with Spurious Noise and Leak
A. Ultrasonic sound level
B. Time duration (seconds)
C. Delay time (30 seconds)
D. Delay reached - alarm
E. Noise 1
F. Noise 2
G. Delay start point
H. Alarm level
I. Background noise level
Figure 3-4 shows detector response when a leak is encountered during a spurious noise
spike, such as a pressure relief valve. Noise 1 represents a pressure relief valve actuating
for approximately 13 seconds before a leak (noise 2) occurs. The detector starts the delay
time when the pressure relief valve opens and continues to monitor for leaks. If a leak
occurs during a spurious noise spike, the delay time is reduced by the duration of the
spurious noise spike.
It is important to identify all spurious noise spikes of significant duration within the
detector coverage. Emerson recommends setting the alarm delay to a value greater than
the maximum spurious noise spike operating duration. If two or more spurious noise
sources are situated within the detector coverage area, Emerson recommends assessing
whether activation of these sources can overlap in time, in which case you should extend
the delay time accordingly.
GDU-Incus33
OperationReference Manual
August 202100809-0100-3003
The factory alarm delay value is set at 15 seconds. To modify this value, connect to the
GDU-Incus with a hand-held TREX device or AMS. Please note when changing the alarm
delay that setting values 0 to 99 are in 10 second increments and 100 to 127 are in 1
second increments. 0 and 100 represent instantaneous alarms. For example, 1 represents
a 10 second alarm delay, and 99 represents a 990 second alarm delay; whereas 101
represents a 1 second alarm delay, and 127 represents a 27 second alarm delay. Therefore,
the factory alarm delay value for 15 seconds would be 115. See Table 3-1 for more
information.
Table 3-1: Alarm Delays
Desired alarm delay valueActual input value in TREX/AMS
15 seconds (factory default)115
101 or 110
303
606
00 or 100
3.1.3Automatic self-test
The automatic self-test checks the complete detector every 320 milliseconds by sending
an electrical signal of known amplitude through the sensing circuitry and analyzing the
result, without interrupting the normal functionality of the sensor.
If drift, component failure, or damage occurs, the automatic self-test signals a fault.
Related information
Fault outputs
3.2Check sensor functionality
Emerson calibrates the sensors on the GDU-Incus at the factory; they do not need to be
adjusted. Before operation, Emerson recommends functionality checks to ensure correct
installation. On power-up, the detector performs a diagnostic check to ensure all main
functions are operational and continuously monitors the sensors via the built-in self-test.
The sensor's functionality can be verified using the GDU-01-TT Ultrasonic Test Transmitter
and the following procedure:
1. Ensure that the background ultrasonic level is suitable for the distance of the
proposed transmitter test.
2. Aim the transmitter at the sensor face from a known distance. The detector's
display dB level will rise according to the hand-held device used and the distance.
3. Check all four sensors, if possible, by moving around the detector and repeating.
34Emerson.com
Reference ManualOperation
00809-0100-3003August 2021
3.3Output options
The GDU-Incus comes with the following industry-standard forms of communication:
• Analog (4-20 mA)
• HART® communication protocol
• Two configured relays
This enables the detector to be operated as part of a system, as a standalone unit, or hard
wire linked to form a sub network.
3.3.1Relay options
The GDU-Incus has two relays configured as follows for the standard factory default:
Table 3-2: Relay Defaults
RelayTypeFactory default setting
1FaultEnergized in normal operating condition, de-
energized in fault condition, non-latching
2AlarmEnergized in normal operating condition, de-
Table 3-3: Relay Data
Maximum switching current1.4 A
Maximum switching voltage30 Vdc
You can change relay configuration to suit installation requirements with the user
changeable functions; options include normally open/normally closed condition and
latching/non-latching.
3.4Display
The GDU-Incus incorporates a five-digit segment, 0.31-in. high x 0.16-in. wide (8 mm high
x 4 mm wide) character light-emitting diode (LED) display with red numerals as standard.
During operation, the real-time dB level is continuously shown while below the
programmed alarm level and flashing when above the programmed alarm level.
energized in fault condition, non-latching
GDU-Incus35
OperationReference Manual
August 202100809-0100-3003
Figure 3-5: Example of Real-Time dB Level Display: 53 db
B. Detector fault detected
C. 100 percent of range
D. Linear scale
E. 0 percent of range
F. 2.0 mA sensor head test fault
G. 1.0 mA internal process fault
H. 0.5 mA all sensor heads failed
I. 0 mA major fault
Figure 3-6 shows the 4-20 mA output values for the detector during normal operation and
under various fault conditions. The value on the left side shows the mA output tolerance
band; internal fault is set for a 1.0 mA output with a tolerance of 0.8 to 1.2 mA, for
example.
All mA outputs are grouped in descending order to signify importance and to allow for
instant status recognition.
The GDU-Incus is providing coverage when the 2.0 mA sensor test fault is active.
(1)
GDU-Incus37
(1)
OperationReference Manual
August 202100809-0100-3003
Normal operation between 4 to 20 mA (±0.2 mA): detector working, no fault conditions.
Related information
2.0 mA sensor test fault
Fault outputs
38Emerson.com
Reference ManualHART® functionality
00809-0100-3003August 2021
4HART® functionality
The GDU-Incus has HART communication enabled by default. The HART communication
mode is standard current output FSK, to HART protocol revision number 7.
The device reports the primary variable (PV) measurement of sound pressure level in units
of dB. The secondary variable (SV) reports the internal case temperature (degrees Celsius)
of the detector. The tertiary variable (TV) reports the temperature of the heated section of
the detector if the heater option is fitted; otherwise, it will report the same data as the
secondary variable.
A device driver (DD) file for Emerson AMS and the hand-held TREX field terminals is
available from Emerson. In addition, you can use the detector with FDT frame applications
using a generic DTM with limited functionality.
The Incus HART Field Device Specification provides full technical details of the HART
interface.
Note
1. The detector does not support the delayed-response mechanism, burst-mode, or
write protection.
2. The HART device parameters Tag and Long Tag are set to INCUS and GDU-02-INCUS
by default. If unique identification is required, set up the parameters on site.
GDU-Incus39
HART® functionalityReference Manual
August 202100809-0100-3003
40Emerson.com
Reference Manual
00809-0100-3003August 2021
Maintenance
5Maintenance
5.1Hand-held test
You can use the GDU-01-TT test transmitter to emit an ultrasonic tone of 40 kHz with a
sound pressure level of approximately 106 dB at 3 ft. (1 m). Using the GDU-01-TT handheld device makes testing the GDU-Incus and other types of ultrasonic detectors quick and
cost-effective, as you can test at floor level at distances of up to 26 ft. (8 m) (dependent on
background noise) if you can achieve line of sight with the sensor.
Emerson recommends disabling all alarms and monitoring the 4-20 mA output from the
control room or observing it on the display. Test to ensure that the sensors are functioning
correctly in addition to any internal test function contained within the detector. Emerson
recommends doing a hand-held test in line with existing site maintenance procedures.
Note
Ensure that any internal test functions are disabled or deactivated when doing a handheld
test to avoid spurious results.
WARNING
This device will need a Hot Work Permit.
5.2Troubleshooting
The GDU-Incus cannot be repaired in the field.
If a problem develops, carefully check installation and wiring. If you determine that the
problem is caused by an electronic or other defect, contact your Emerson representative.
Related information
Service support
5.2.1
Fault outputs
2.0 mA sensor test fault
One or more sensor heads fail to respond with the correct value during the automatic selftest.
Output is continuous at 2.0 mA unless the test is subsequently passed successfully or an
alarm condition occurs, in which case the normal sound level is transmitted on the current
loop.
Related information
Alarm level
GDU-Incus41
MaintenanceReference Manual
August 202100809-0100-3003
1.0 mA internal process fault
Continuous 1.0 mA (±0.2 mA) output for any known internal or external faults that include
over-voltage, high/low external voltage, blown fuse, or high/low internal voltage.
0.5 mA all sensors dead fault
Continuous 0.5 mA (±0.2 mA) output, indicating that all four sensors have failed self-test.
Firmware version 3.4 onwards.
Recommended action
Contact your Emerson representative.
Zero mA major fault
Zero (0) mA output is either caused by a total loss of power to the detector or a serious
microprocessor fault.
Potential cause
Loss of power.
Recommended action
Apply power to the detector.
Potential cause
Serious microprocessor fault.
Recommended action
Contact your Emerson representative.
5.3Storage
Store the detector in a location free from dust and moisture.
Make sure the storage temperature is well within the limits of the certified temperatures
of the equipment.
42Emerson.com
Reference ManualTheory of operation
00809-0100-3003August 2021
ATheory of operation
The GDU-Incus is omni-directional. Emerson recommends mounting it between 10 and
16 ft. (3 and 5 m) above the area of interest to eliminate ground absorption and
reflections.
Emerson recommends ultrasonically mapping the area where the detector is to be
situated prior to installation or at commissioning while all processes are running to
establish a background noise level for alarm purposes. Set the alarm level above the
background noise level. Contact your Emerson representative for more information
regarding mapping.
The detector responds instantaneously to pressurized gas leaks or other sources of
ultrasonic noise between 25 kHz and 100 kHz. Therefore, Emerson recommends building
in a delay time to the control system or programming it in the detector when using it in
stand-alone mode to prevent spurious alarms. Emerson recommends setting the delay
time at a minimum of 15 seconds, but increase this time in response to the process
located near the detector as shown in Figure 3-2.
Several factors affect the maximum area which can be monitored by a single detector.
These factors include:
• Background (ambient) ultrasound level
• Gas pressure
• Leak size
• Gas temperature
• Environmental conditions
Emerson has formulated a series of calculations that take all of these external factors into
account in order to determine accurate coverage information for most installations.
Contact an Emerson representative to advice on appropriate coverage for each
installation.
Emerson recommends completing a verification test of the GDU-Incus after installation
and in line with existing site maintenance procedures. You can verify the detection
coverage at installation or as part of a maintenance schedule using the GDU-01-TT
Ultrasonic Test Transmitter, which electrically replicates the airborne ultrasound
generated from a pressurized gas leak using a piezoelectric disc and can activate alarm
conditions with any ultrasonic gas leak detector.
Compared to other ultrasonic and traditional forms of detection, the GDU-Incus has the
following advantages:
• Gas does not need to reach the sensor to be detected.
• Unaffected by weather conditions.
• Sensors are unaffected by temperature, pressure, moisture, and contamination build-
up.
• Multiple sensor redundancy in each unit.
• Continuous self-test function.
GDU-Incus43
Theory of operationReference Manual
August 202100809-0100-3003
• No calibration required, which results in cost savings over the detector lifecycle.
• Can be remotely tested from up to 26.2 ft. (8 m) distance, saving on maintenance
scaffold costs.
• 4-20 mA current loop with HART® communication as standard, plus relay outputs for
Fault and Alarm conditions.
• Can operate standalone or as part of an interfaced control system.
Emerson Terms and Conditions of Sale are available upon
request. The Emerson logo is a trademark and service mark of
Emerson Electric Co. Rosemount is a mark of one of the
Emerson family of companies. All other marks are the property
of their respective owners.