Rosemount Hygienic Process Connection Adapters (FB-1045) Quick Start Guide

Page 1
Quick Start Guide
00825-0100-4105, Rev 01
January 2019
Rosemount™ Hygienic Process Connection Adapter
Universal process adapter (RD52) for transmitters with a G1 process connection
FB-1045
Page 2
Contents
Overview........................................................................................ 3
1
2 Install the adapter.......................................................................... 4
3 Mount the transmitter....................................................................9
4 Product certifications................................................................... 10
4.1 Other industry certifications......................................................10
2
Page 3

1 Overview

Use the process connection to install Rosemount 326 and 327 transmitters with G1 process connectors.
Safety instructions
CAUTION
Read this document before using the product and keep it during
the entire service life.
The product must be suitable for the corresponding applications
and environmental conditions without any restrictions.
Only use the product for its intended purpose.
If the operating instructions or the technical data are not adhered
to, personal injury and/or damage to property might occur.
The manufacturer assumes no liability or warranty for any
consequences caused by tampering with the product or incorrect use by the operator.
Installation, electrical connection, set-up, operation and
maintenance of the product must be carried out by qualified personnel.
3
Page 4

2 Install the adapter

Follow these steps to install the universal process adapter to a transmitter.
Procedure
Grease thread and seal (B) of the coupling nut (C) with
1. lubricating paste (A).
Note
The paste must be approved for the application and compatible with the elastomers.
2. Slip the coupling nut onto the transmitter (D) from the bottom.
4
Page 5
3. Grease the transmitter thread with lubricating paste (A) (see the note above).
Place the transmitter ring (E) in the groove (F) of the
4. transmitter.
5
Page 6
The adapter comes with an EPDM O-ring. More sealing rings are available. For more information see the transmitter datasheet or visit Emerson.com/Rosemount.
FKM O-ring
PEEK sealing ring
Note
Use a new adapter when replacing a PEEK sealing ring or changing from a PEEK seal to O-ring sealing.
5. Screw the adapter (G) onto the transmitter until it is hand­tight.
Note
Avoid mechanical effects on sealing areas, process wetted surfaces, and the pressure measuring cell if mounting a Rosemount 326P Pressure Transmitter.
6. Ensure the O-ring (H) is correctly positioned.
6
Page 7
7. Secure the transmitter and adapter assembly into a vice (I).
Note
Do not over-tighten. Over-tightening the vice may cause the transmitter and adapter assembly to warp.
7
Page 8
8. Tighten the transmitter to a torque of 25.81 ft/lbs (35 Nm).
CAUTION
Further tightening may affect the sealing effect.
8
Page 9

3 Mount the transmitter

Follow these steps to install the transmitter after installing the hygienic process connection adapter.
Procedure
Insert the transmitter and adapter assembly in a universal
1. process connection RD52.
2. Tighten the coupling nut.
9
Page 10

4 Product certifications

Other industry certifications

4.1
All connector surfaces and materials which come into contact with process medium comply with the following regulations:
(EC) No. 1935/2004
(EC) No. 2023/2006
CFR Title 21 (FDA) § 177.2600
CFR Title 21 (FDA) § 177. 2415
10
Page 11
11
Page 12
*00825-0100-4105*
Quick Start Guide
00825-0100-4105, Rev. 01
January 2019
Global Headquarters
Emerson Automation Solutions 6021 Innovation Blvd. Shakopee, MN 55379, USA
+1 800 999 9307 or +1 952 906 8888
+1 952 949 7001
RFQ.RMD-RCC@Emerson.com
Linkedin.com/company/Emerson-Automation-Solutions
Twitter.com/Rosemount_News
Facebook.com/Rosemount
Youtube.com/user/RosemountMeasurement
©
2019 Emerson. All rights reserved.
Emerson Terms and Conditions of Sale are available upon request. The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount is mark of one of the Emerson family of companies. All other marks are the property of their respective owners.
North America Regional Office
Emerson Automation Solutions 8200 Market Blvd. Chanhassen, MN 55317, USA
+1 800 999 9307 or +1 952 906 8888
+1 952 949 7001
RMT-NA.RCCRF@Emerson.com
Loading...