1.1About the Rosemount™ 8732EM EtherNet/IP™
Module
The Rosemount 8732EM EtherNet/IP™ Module is a customization of the Anybus®
Communicator
of industrial devices into the Ethernet network with no loss of functionality, control, or
reliability. The Ethernet module can be used for new or retrofit installations.
This manual contains only the information required to install, configure, and use the
Ethernet module. Other OEM features are still enabled on the device, but are not
documented here. For information on other features of the device, see the Anybus
Communicator User Manual manual, available on the HMS web site.
1.1.1Functional overview
™
from HMS Industrial Networks. The Ethernet module enables integration
The Rosemount 8732EM EtherNet/IP Module acts as a gateway between the serial output of
a Rosemount 8732EM Modbus
The Ethernet module is a Modbus master and an Ethernet slave. On the Modbus side, it polls
the transmitter for a standard set of process variables and stores the data locally. See
Section B.3 for a list of available data. On the Ethernet side, it receives requests for data and
responds with the current values. Figure 1-1 illustrates the Ethernet module in operation.
The Ethernet module is installed with a Rosemount 8732EM Modbus Transmitter.
The web browser is used for transmitter configuration and administration, via a
connection to the Rosemount web pages on the Ethernet module.
Figure 1-1 EtherNet/IP Module with Rosemount 8732EM Modbus Transmitter
®
Magnetic Flowmeter Transmitter and an Ethernet network.
A. PLCF. Configuration loop (with configuration cable)
B. Web browserG. Modbus/RS-485
C. EthernetH. PC with Ethernet config tool
D. Other devices (SCADA, PC, Inverter)I. Rosemount 8732EM Transmitter
E. EtherNet/IP ModuleJ. To sensor
Introduction
1
Introduction
A
B
C
D
E
F
G
April 2016
1.1.2Communications
The following communications methods and protocols are supported:
Ethernet module to Rosemount transmitter: Modbus RTU on RS-485
Ethernet module to Ethernet network:
-EtherNet/IP group 2 and 3 servers
-Web server
-10/100 Mbit/sec, twisted pair
1.1.3External view of device
Figure 1-2. External View of Device
Reference Manual
00809-0100-4765, Rev. AB
A. Ethernet connectorE. Modbus serial connector (transmitter)
B. Configuration switchesF. Power connector
C. Status LEDsG. DIN rail connector
D. PC connector (configuration)
1.1.4Default web pages
2
The Ethernet module is preloaded with the Rosemount 8732EM web pages. These pages
allow the user to view process data and alerts, configure the most commonly used
parameters on the transmitter, perform maintenance procedures, and download support
files from the device.
11.Wait for the auto-configuration process to complete.
Installation
5
Installation
April 2016
Important
For initial startup, the auto-configuration process is required to ensure device memory is
completely set up.
12.Add the Ethernet module to the Ethernet network control system. The EDS file is
available on the Resource CD, the Ethernet module (download from Administration
page), and the Rosemount web site.
For more information on transmitter installation and wiring, see the transmitter installation
manual. For information on configuring the RS-485 terminals and making an RS-485
connection, see the transmitter configuration manual.
2.3Final steps
1.From a browser, access the login screen and enter admin. Ignore the
auto-configuration popup window.
2.Use the Device Configuration page to configure the Ethernet module.
To participate on the Ethernet network, the Rosemount™ 8732EM EtherNet/IP™ Module
needs a valid TCP/IP configuration.
The Ethernet module can retrieve the TCP/IP settings from a DHCP or BootP server. If no
such server is found, the Ethernet module uses the settings from the system file \ethcfg.cfg.
If this file is not found, or the settings are invalid, the Ethernet module will halt and report an
error on the status LED. However, the network configuration may still be accessed via the
Ethenet Config Tool.
You can define the TCP/IP settings for the Ethernet module in four ways:
Rosemount Network Configuration web page (recommended)
Configuration switches on the device
Ethernet Config Tool
System file \ethcfg.cfg on the device
Rosemount web page
The Network Configuration page, in the Rosemount web pages, allows setting of the IP
address, gateway address, and subnet address. Connecting to the Ethernet module using a
crossover cable and the default IP address allows setting all three parameters. The changes
take effect at the next connection.
Configuration switches
If the configuration switches on the Ethernet module are set to any non-zero value, the
device is locked to the following network settings:
Table 3-1 Network settings, locked
ParameterValu e
IP address192.168.0.x
Basic Network Configuration
where x is determined by the switches
7
Basic Network Configuration
April 2016
Table 3-1 Network settings, locked
ParameterValu e
Gateway192.168.0.255
Subnet255.255.255.0
DHCPOFF
To set the IP address, see the following table.
Table 3-2 Network settings using switches
Switch
12345678
OFFOFFOFFOFFOFFOFFOFFON192.168.0.1
OFFOFFOFFOFFOFFOFFONOFF192.168.0.2
OFFOFFOFFOFFOFFOFFONON192.168.0.3
ONONONONONONONOFF192.168.0.254
ONONONONONONONONInvalid
Reference Manual
00809-0100-4765, Rev. AB
IP address
Ethernet Config Tool
See the Anybus® Communicator™ manual for instructions.
Important
If you change the network settings using the Ethernet Config Tool, you will not be able to
use the Rosemount web pages to change network settings in the future. All future changes
to network settings must be performed using the Ethernet Config Tool.
ethcfg.cfg file
To set the network settings using the \ethcfg.cfg file:
1.Set all configuration switches on the device to OFF.
2.Make a connection to the device from the Ethernet Config Tool and disable TCP/IP Settings (Fieldbus parameter section). Alternatively, you can access the TCP/IP
parameters using the TCP/IP Interface Object.
3.From the FTP server, access and edit \ethcfg.cfg as desired.
In this scenario, if no \ethcfg.cfg file is found, the Ethernet module will attempt to retrieve
the settings via DHCP for 30 seconds. If the attempt fails, the Ethernet module will halt and
indicate an error via the LEDs.
See the Anybus Communicator manual for more information.
8
Basic Network Configuration
Reference Manual
00809-0100-4765, Rev. AB
3.1.1IP access control
You can limit the set of IP addresses that are allowed to connect to the Ethernet module.
This information is stored in the system file \ip_accs.cfg.
Sample file:
[Web]
xxx.xxx.xxx.xxx(All nodes listed can access the EtherNet/IP Module
web server)
...
[FTP]
xxx.xxx.xxx.xxx(All nodes listed can access the EtherNet/IP Module
FTP server)
...
[EtherNet/IP]
xxx.xxx.xxx.xxx(All nodes listed can access the EtherNet/IP Module
via EtherNet/IP)
...
[All]
xxx.xxx.xxx.xxx(Fallback setting; used when one or more of the
above keys is omitted)
...
Basic Network Configuration
April 2016
Basic Network Configuration
9
Basic Network Configuration
April 2016
3.2Modbus® serial network settings
The required parameters for the Modbus serial network for use with the Ethernet module
are listed in the following table.
Reference Manual
00809-0100-4765, Rev. AB
Note
The Rosemount 8732EM Modbus
®
Transmitter default parameters for Modbus serial
network communication are different than those listed below. Transmitter configuration
may be required to match the parameters in Table 3 - 3.
Table 3-3 Required parameters for Modbus serial network
ParameterRequired setting
Baud38400
Float byte sequence order0-1-2-3
Data bits8 (Modbus RTU)
ParityNone
Physical layerRS485
Start bits1
Stop bits
1. For baud rates of 38400 and above, 2 stop bits are required.
(1)
2
These must match the RS-485 parameters configured in the transmitter. To change them in
the Ethernet module, you must use the Ethernet Config Tool. See the Anybus
Communicator manual for more information.
The configuration and administration functions of the Rosemount 8732EM EtherNet/IP™
Module are implemented as web pages on the device. Users use their web browsers to
connect to the web server. They are automatically directed to the Rosemount web pages.
4.2General access information
April 2016
4.2.1Ports
The web server communicates through port 80.
4.2.2Users
Two users are predefined for the Rosemount web pages. You can change the passwords, but
you cannot add or delete users.
Username
adminadmin
operatoroperator
Default
password
Description
Complete access to all functions on the
Read-only access to the
4.3Rosemount web pages
When the user connects to the Ethernet module, he is prompted for a user name and
password, then taken to the Ethernet module home page.
Rosemount web pages
Rosemount web pages
Rosemount™ Web Ser ver
11
Rosemount™ Web Server
April 2016
4.3.1Home page
Figure 4-2. EtherNet/IP Module Home Page
Reference Manual
00809-0100-4765, Rev. AB
12
On this page, current data for the most commonly used process variables is displayed. Tabs
provide access to other web pages:
Administration page: Allows the admin user to change passwords and perform
downloads from the Ethernet module (the EDS file).
Network Configuration page: Allows the user to view or configure Ethernet module
network settings
All other pages: Various transmitter tasks, including viewing process data,
configuration, calibration, stopping and starting totalizers, and Smart Meter
Verification. For more information about any of these tasks, see your transmitter’s
configuration manual.
Note
If the Ethernet module loses communication with the Rosemount device, all process variables
are shown as 0.0f. Also, an explicit read to 0xB0-0x01-0x1D returns a value of 0.
N/A4ActivityFlashing greenPacket is received or transmitted.
Status
StatusMeaning
OffNo power applied to the module.
Solid greenThe module is operating correctly.
Flashing greenStandby; the module has not been initialized.
Flashing redMinor fault. The module may or may not be able to recover.
Solid redMajor fault. No recovery is possible. The module must be returned to
Rosemount
Flashing green/redSelf-test
OffThe module has no power or no IP address has been assigned.
Solid greenThe module has at least one established Ethernet connection.
Flashing greenThere are no Ethernet connections established to the module.
Flashing redOne or more of the connections to this module has timed out.
Solid redThe module has detected that its IP address is already in use.
Flashing green/redSelf-test
Solid GreenThe module is connected to an Ethernet network.
™
for repair. See the manual for the return policy.
Troubleshooting
13
Troubleshooting
April 2016
Reference Manual
00809-0100-4765, Rev. AB
LED display
number/name
5Subnet
Status
6Device StatusOffPower off.
Modbus Serial
StatusMeaning
OffPower off.
Flashing greenRunning correctly, but one or more transaction errors has occurred.
Solid GreenRunning.
Solid RedTransaction error/timeout or network stopped. Check the Modbus
serial network wiring and configuration, especially the baud.
Flashing redMissed transactions.
Flashing red/greenConfiguration missing or invalid.
Solid RedContact Rosemount customer service.
Flashing redContact Rosemount customer service.
Solid GreenInitializing
Flashing greenConfiguration OK.
5.2Common problems
SymptomResolution
Problem during configuration
upload/download.
The Config Line LED turns red in
the Ethernet Config Tool.
The serial port seems to be available, but it is not possible to
connect to the
module
Poor performance• In the Ethernet Config Tool, right-click
No Modbus serial network functionality
Process variables displayed or
reported as 0
Ethernet
.
Serial communication failed. Try again.
Serial communication failed. Try again.
• The serial port may be in use by another application. Exit the Ethernet module
Configuration Tool and close all other applications, including the ones in the system
tray. Try again.
• Select another serial port. Try again.
Sub-Network Status to see status / diagnostic information about the Moldbus
select
serial network. If the
check your cabling and/or try a lower baud rate setting for the Modbus serial
network (if possible).
• Is the Sub-Net Monitor in the Ethernet Config Tool active? The sub-network
monitor has a negative influence on the overall performance of the gateway, and
should be used only when necessary.
• Is the Node Monitor in the Ethernet Config Tool active? The node monitor has a
negative influence on the overall performance of the gateway, and should be used
only when necessary.
• Use the Data logger functionality of the Ethernet Config Tool to record the serial
data communication on the sub-network.
• If no data is being transmitted, use the Ethernet Config Tool to check the configuration.
• If no data is being received, check the cables and connections. Also verify that the
transmitted data is correct.
• Verify the Modbus connection between the
Ethernet module reports a large number of re-transmissions,
Sub-Network in the Navigation window and
Ethernet module and the device.
14
Troubleshooting
Reference Manual
00809-0100-4765, Rev. AB
5.3Customer Service
LocationTelephone number
U.S.A.800-522-6277 (toll free)
Canada and Latin America+1 303-527-5200 (U.S.A.)
AsiaJapan3 5769-6803
All other locations+65 6777-8211 (Singapore)
EuropeU.K.0870 240 1978 (toll-free)
All other locations+31 (0) 318 495 555 (The Netherlands)
Email: flow.support@emerson.com
5.4Return policy
5.4.1Requirements
Troubleshooting
April 2016
Emerson Process Management procedures must be followed when returning equipment.
These procedures ensure legal compliance with government transportation agencies and
help provide a safe working environment for Emerson employees. Failure to follow Emerson
Process Management procedures will result in your equipment being refused delivery.
Information on return procedures and forms is available from the Rosemount Customer
Service department.
5.4.2New and unused equipment
Only equipment that has not been removed from the original shipping package will be
considered new and unused. New and unused equipment requires a completed Return
Materials Authorization form.
5.4.3Used equipment
To expedite the return process outside the United States, contact the nearest Rosemount
representative. Within the United States and Canada, call the North American Response
Center using the 800-654-RSMT (7768) toll-free number. The Response Center, available 24
hours a day, will assist you with any needed information or materials.
The center will ask for product, model, and serial numbers and will provide a Return Material
Authorization (RMA) number. The center will also ask for the name of the process material
to which the product was last exposed.
Troubleshooting
Mishandling products exposed to a hazardous substance may result in death or serious
injury. If the product being returned was exposed to a hazardous substance as defined by
OSHA, a copy of the required Material Safety Data Sheet (MSDS) for each hazardous
substance identified must be included with the returned goods. The North American
Response Center will detail the additional information and procedures necessary to return
goods exposed to hazardous substances.
The terminal tightening torque must be between 5 and 7 lbs-in (0.5 to 0.8 Nm).
17
Reference Manual
1
2
3
4
5
6
7
8
9
1
2
3
4
DP9F (PC)RJ-11 (EIP)
Ground
Ground
Rx
Tx
RS232 Tx
RS232 Rx
Ground
1
2
3
4
PinDescription
1Ground
2Ground
3RS-232 Rx (Input)
4RS-232 Tx (Output)
PinDescription
1Unused
2RS-232 Rx (Input)
3RS-232 Tx (Output)
4Unused
5Signal ground
6–9Unused
96
15 (female)
Connector Pin Assignments
00809-0100-4765, Rev. AB
A.3Ethernet Config Tool connection
A.3.1Configuration cable
April 2016
A.3.2RJ-11 (EtherNet/IP
A.3.3DBF9 (PC)
™
Module)
18
Connector Pin Assignments
Connector Pin Assignments
PinDescription
1Unused
2Unused
3Unused
4Unused
5Ground
6Unused
7Unused
8RS-485/A (Tx+)
9RS-485/B (Tx–)
(housing)Cable shield
96
15 (female)
April 2016
A.4Modbus® serial network interface
The Modbus serial network is based on an RS-485 physical layer.
A.4.1Bias resistors
When idle, RS-485 enters an indeterminate state, which may cause the serial receivers to
pick up noise from the serial lines and interpret this as data. To prevent this, the serial lines
should be forced into a known state using pull-up and pull-down resistors, commonly
known as bias resistors.
The bias resistors forms a voltage divider, forcing the voltage between the differential pair
to be higher than the threshold for the serial receivers, typically >200 mV. Note that bias
resistors shall only be installed on one node. Installing bias resistors on several nodes may
compromise the signal quality on the network and cause transmission problems.
A.4.2Termination
To avoid reflections on the serial lines, it is important to properly terminate the sub-network
by placing termination resistors between the serial receivers near the end nodes.
Reference Manual
00809-0100-4765, Rev. AB
Additionally, if the distance from the Ethernet module to the transmitter is greater than
100 feet, Rosemount
The resistor value should ideally match the characteristic impedance of the cable, typically
100 to 120 ohms.
Ta bl e B -1 lists and describes all object classes supported by the Ethernet module.
Table B-1. Object Classes and Descriptions
Reference Manual
00809-0100-4765, Rev. AB
ObjectClass ID
Identity0x01RequiredContains information that uniquely describes the device
Message Router 0x02RequiredTracks the accessibility of the object classes and instances
Assembly 0x04RequiredContains a list of attributes that data can be written to (sink) or read
Port0xF4Required
TCP/IP Interface0xF5RequiredGroups settings related to TCP/IP.
Ethernet Link0xF6RequiredGroups diagnostic information for the Ethernet interface
Diagnostic0xAAOptionalGroups diagnostic information for the fieldbus interface
Parameter Data
Input Mapping
Parameter Data
Output Mapping
0xBOOptionalUsed for acyclic access to input data
0xB1OptionalUsed for acyclic acces to output data
Optional/
required
Description
from (source)
B.2Object details
B.2.1Identity Object, Class 01h
This object provides identification of and general information about the device. It contains
informational attributes that uniquely describe the device.
Device Profile
Example: The use of attributes Vendor ID, Device Type, Product Code, and Serial Number
together uniquely identify this device.
21
Reference Manual
00809-0100-4765, Rev. AB
Supported services
Class services:
Get Attribute All
Get Attribute Single
Instance services:
Get Attribute All
Get Attribute Single
Reset
Class attributes
#AccessNameTyp eValueDescription
1GetRevisionUINT0001hRevision 1
Device Profile
April 2016
Instance attributes
#Access NameTypeValueDescription
1GetVendor IDUINTDefault: 0392hRosemount Inc
2GetDevice Type UINTDefault: 000ChCommunication Adapter
3GetProduct
Code
4GetRevision Struct of:
5GetStatusWORDDevice status; see
6GetSerial
Number
7GetProduct
Name
UINTDefault: 0002h
USINTMajor fieldbus version
USINTMinor fieldbus version
UDINTSerial number(set at production)
SHORT_STRING “8732EM EtherNet/IP
Module”
2 = 8732EM EtherNet/IP™
Module
following table
Name of product
22
Device Profile
Device Profile
April 2016
Reference Manual
00809-0100-4765, Rev. AB
Device status
Bit(s)Name
0Module Owned
1(reserved)
2Configured
3(reserved)
4... 7Extended Device Status:
Value:Meaning:
0000bUnknown
0010bFaulted I/O Connection
0011bNo I/O connection established
0100bNon-volatile configuration bad
0110bConnection in Run mode
0111bConnection in Idle mode
(other)(reserved)
8Set for minor recoverable faults
9Set for minor unrecoverable faults
10Set for major recoverable faults
11Set for major unrecoverable faults
12... 15(reserved)
Reset service
When the Identity Object receives a Reset request, it:
Determines if it can provide the type of reset requested
Responds to the request
Attempts to perform the type of reset requested
B.2.2Message Router, Class 02h
The Message Router Object provides a messaging connection point through which a Client
may address a service to any object class or instance residing in the physical device.
B.2.3Assembly Object, Class 04h
The Assembly Object binds attributes of multiple objects, which allows data to or from each
object to be sent or received over a single connection. Assembly objects can be used to bind
input data or output data. The terms “input” and “output” are defined from the network's
point of view. An input produces data on the network and an output consumes data from
the network.
This object provides access to the I/O Data in the Input and Output Data areas in the
Ethernet module.
Instance attributes - Instance/Connection Point 64h
Device Profile
April 2016
number
This instance corresponds to I/O Data (Input) in the Rosemount™ 8732EM EtherNet/IP
Module. The Ethernet module supports two different configurations. Specific input
assembly attributes depend on the configuration in use.
ConfigurationInput assembly attributes
BasicSee Section B.3.1
Note
The default input data size is non-zero. The actual size depends on the configuration in use.
If the I/O input data size is set to 0, this instance will NOT be initialized.
#AccessNameTy peValueDescription
3GetDataArray of BYTE-Data produced by the Ethernet
module
Instance attributes - Instance/Connection Point 96h
This instance corresponds to I/O Data (Output) in the Ethernet module. The Ethernet
module supports two different configurations. Specific input assembly attributes depend
on the configuration in use.
24
ConfigurationOutput assembly attributes
BasicSee Section B.3.2
Device Profile
Device Profile
April 2016
Note
The default output data size is non-zero. The actual size depends on the configuration in
use. If the I/O output data size is set to 0, this instance will NOT be initialized.
#AccessNameTyp eValueDescription
3SetDataArray of BYTE-Data consumed by the Ethernet
Note
Rockwell Automation PLCs have the first four bytes consumed by a device defined as status
information. This behavior is specific to devices from Rockwell Automation and is not
defined in the Ethernet specification. However, since all known PLCs are implemented this
way, the Ethernet module adopts this behavior and strips off the corresponding four bytes
from the consumed data.
B.2.4Port Object, Class F4h
Reference Manual
00809-0100-4765, Rev. AB
module
Supported services
Class services:
Get Attribute Single
Get Attribute All
Instance services:
Get Attribute Single
Get Attribute All
Class attributes
#Access NameTy peValueDescription
1GetRevisionUINT0001hRevision 1
2GetMax InstanceUINT0002h2 is the highest instance number
3GetNo. of instances UINT0001h1 instance is implemented
8GetEntry PortUINT0002hReturns the instance of the Port object
that describes the port.
9GetAll PortsArray of
STRUCT
{UINT; UINT;} 0000h
0000h
0000h
0000h
0004h
0002h
Array of structure containing attributes
1 and 2 from each instance. Instance 1 is
at byte offset 4. Instance 2 is at byte
offset 8, etc. The 4 bytes at offset 0 shall
be 0. (Default)
2GetConfiguration Capability DWORD00000016hAttribute #5 is settable. Capable
of obtaining network configuration via DHCP.
3Get/SetConfiguration ControlDWORD0: Configuration from
non-volatile memory
2: Configuration from DHCP
26
Device Profile
Device Profile
April 2016
Reference Manual
00809-0100-4765, Rev. AB
#AccessNameTyp eValueComments
4GetPort ObjectStruct of:
Path SizeUINT0002h2 words
PathPadded EPATH20 F6 24 01hPath to Ethernet Class, Instance 1
5Get/SetInterface ConfigurationStruct of:
IP AddressUDINTIP address
Subnet MaskUDINTSubnet mask
Gateway AddressUDINTGateway Address
Name Server 1UDINTPrimary DNS
Name Server 2UDINTSecondary DNS
Domain NameSTRINGDefault domain name
6Get/SetHost NameSTRINGHost name
B.2.6Ethernet Link Object, Class F6h
This object groups diagnostic information for the Ethernet interface.
Supported services
Class services:
Get Attribute All
Get Attribute Single
Instance services:
Get Attribute All
Get Attribute Single
Class attributes
#Access NameTyp eValueDescription
1GetRevisionUINT0001hRevision 1
2GetMax InstanceUINT0001h1 is the highest instance number
3GetNo. of instances UINT0001h1 instance is implemented
Instance attributes
Device Profile
#AccessNameTy peValu eComments
1GetInterface SpeedUDINT10 or 100Actual Ethernet interface
speed
2GetInterface FlagsDWORD
3GetPhysical Address Array of 6 USINTS (MAC ID)Physical network address
27
Reference Manual
00809-0100-4765, Rev. AB
B.2.7Diagnostic Object, Class AAh
This object groups diagnostic information for the fieldbus interface.
Supported services
Class services:
Get Attribute All
Instance services:
Get Attribute Single
Class attributes
# Access NameTy peValueDescription
1GetRevisionUINT0001hRevision 1
Instance attributes
Device Profile
April 2016
#AccessNameTyp eDescription
01h GetModule serial numberUDINT Serial number
02h GetVendor IDUINTManufacturer Vendor ID
03h GetFieldbus TypeUINTFieldbus Type
04h GetModule Software version UINTModule software version
0Ah GetModule TypeUINTModule Type
0FhGetIN cyclic I/O lengthUINTSize of I/O Input area (in bytes)
11h GetIN total lengthUINTTotal number of IN bytes supported
12h GetOUT cyclic I/O lengthUINTSize of I/O Output area (in bytes)
14h GetOUT total lengthUINTTotal number of OUT bytes supported
B.2.8Parameter Data Input Mapping Object, Class B0h
This object can be used to access Input Data acyclically, and is set up dynamically based on
the Parameter Data Mailbox initialization (see Section B.3.3).
Supported services
Class services:
Get Attribute All
28
Instance services:
Get Attribute Single
Device Profile
Device Profile
April 2016
Reference Manual
00809-0100-4765, Rev. AB
Class attributes
#AccessNameTyp eValueDescription
1GetRevision UINT0001hRevision 1
Instance attributes, Instance 01h
Each attribute corresponds to a block of Input Data.
#Access NameTy peDescription
01h GetDataArray of USINTMapped block of Input Data
02h GetDataArray of USINTMapped block of Input Data
...
32h GetDataArray of USINTMapped block of Input Data
The specific parameters in the block depend on the configuration in use.
ConfigurationInput parameters (explicit data)
BasicSee Section B.3.3
B.2.9Parameter Data Output Mapping Object, Class B1h
This object can be used to access Output Data acyclically, and is set up dynamically (see
Section B.3.4).
Supported services
Class services:
Get Attribute All
Instance services:
Get Attribute Single
Set Attribute Single
Class attributes
#Access NameTyp eVa lueDescription
1GetRevisionUINT0001hRevision 1
Device Profile
29
Reference Manual
00809-0100-4765, Rev. AB
Instance attributes, Instance 01h
#AccessNameTy peDescription
01h Get/SetDataArray of USINTMapped block of Output Data
02h Get/SetDataArray of USINTMapped block of Output Data
...
32h Get/SetDataArray of USINTMapped block of Output Data
The specific parameters in the block depend on the configuration in use.
ConfigurationOutput parameters (explicit data)
BasicSee Section B.3.4
Device Profile
April 2016
30
Device Profile
Device Profile
April 2016
B.3I/O data
B.3.1Input assembly
Bytes Access NameTyp eNotes
0-3GetFlow RateFloat
4–7GetTotal AFloat
8–11GetTotal BFloat
12–15 GetTotal CFloat
16-19GetElectronics TemperatureFloat
20-23GetLine NoiseFloat
24-27Get5 Hz SNRFloat
28-31Get37 Hz SNRFloat
32-35GetSignal PowerFloat
36-39GetEmpty Pipe ValueFloat
40-43GetElectrode Coating ValueFloat
44-47GetInternal Flow Simulator Test Deviation (Continuous)Float
48-51GetElectrode Resistance Value (Continuous)Float
Internal Flow Simulator Value (SMART
tion) (Do not use)
™
Meter Verifica-
Reference Manual
00809-0100-4765, Rev. AB
35
0–2
35
0–2
35
0–2
Float
B.3.2Output assembly
Bytes AccessNameTyp eNotes
0Get/SetStart/Stop All TotalsByte0: Stop
1Get/SetReset All TotalsByte0: No Action
2Get/SetReset Total AByte0: No Action
3Get/SetReset Total BByte0: No Action
4Get/SetReset Total CByte0: No Action
Device Profile
1: Start
1: Reset
1: Reset
1: Reset
1: Reset
31
Reference Manual
00809-0100-4765, Rev. AB
B.3.3Input parameters—explicit data
To update any of these attribute values, the associated trigger byte must be toggled before
reading the attribute value (executing the Get service). See Section B.3.4 for more
information on trigger bytes.
For all input parameters in Ta bl e B - 2, the class is B0h and the instance is 01h.
Table B-2. Input Parameters—Explicit Data
Trigger
Attribute Access NameTy pe
01hGetSoftware RevisionU16110h
02hGetInternal Flow Simulator Test Deviation (Contin-