Rosemount CH88 In-Situ Combustion Oxygen Analyzer System Manuals & Guides

Installation/Start-up Manual

CMB_MAN_ABR_CH88
September 2017
CH88 In-Situ Combustion O2 Analyzer System
Section 1:
General Information
Essential Instructions..........................................................................................
2
Symbols used......................................................................................................
3 Overview………………………………………………………………………….................................
4
System Configurations........................................................ ...............................
5
Technical Support Hotline.................................................. .................................
5
Section 2:
Typical System Package
CH88 In-Situ Combustion O2 Analyzer System Ordering Information................
6
Section 3:
Specifications
System Specifications..........................................................................................
7
CH88 Flue Gas O2 Probe Specifications...............................................................
7
1056 Combustion Electronics Specifications....................................................
7
Section 4:
Installation
Mechanical installation.......................................................................................
9
Installation of1056 Combustion Electronics………...................................
9
Installation Specifications - Cable Connecting Probe to
9
Probe Installation.................................................. .................................
9
Electrical Installation...........................................................................................
15
Cable Connections.................................................................................
15
Probe Connections.................................................................................
16
Power Up Procedure...........................................................................................
16
Calibration.......................................................................... .................................
19
Manual/Semi-automatic Calibration…………………...................................
19
Calibration Record.................................................................................
20
Section 5:
Menu Trees
System Menu Tree (English and Chinese)……………………….. .................................
21 Probe Menu Tree (English and Chinese) ………………………...................................
22
Probe Menu Tree (English and Chinese) ………………………...................................
23
Section 6:
Parameters
System Parameters............................................................................................
24
Probe Parameters..............................................................................................
25
CH88 In-Situ Combustion O Analyzer System Alarms........................................
26
System Alarms.............................................................................................
29
Probe Alarms........................................................ ......................................
30
Contents
Electronics…………………………………………………………....................................
Table of Contents
Essential Instructions
September 2017
Installation/Start-up Manual
CMB_MAN_ABR_CH88
Section 1: General Infor m ati on
Essential Instructions
Read this page before proceedi ng
Emerson Process Management designs, manufactures and tests its Rosemount Analytical to meet many national and international standards. Because these instruments are sophisticated technical products, you MUST properly install, use, and maintain them to ensure they continue to operate with-in their normal specifications. The following instructions MUST be adhered to and integrated into your safety program when installing, using, and maintaining Rosemount Analytical products. Failure to follow the proper instructions may cause any one of the following situations to occur: Loss of life; personal injury; property damage; damage to this instrument; and warranty invalidation.
Read all instructions prior to installing, operating, and servicing the product.
If you do not understand any of the instructions, contact your Emerson Process Management representative for clarification.
Follow all warnings, cautions, and instructions marked on and supplied with the product, including this manual
Install your equipment as specified in the Installation Instructions and per applicable local and national codes. Connect all products to the proper electrical and pressure sources.
To ensure proper performance; inform, educate and only use qualified personnel to install, operate, update, program, and maintain the product.
Use only factory documented components for repair. Tampering or unauthorized substitution of parts and procedures can affect the performance and cause unsafe operation of your process.
All equipment doors must be closed and protective covers must be in place unless qualified personnel are performing maintenance.

WARNING: RISK OF ELECTRICAL SHOCK

1)
Main power wired to separate power source must be disconnected before servicing.
2)
Do not operate or energize instrument with case open!
3)
Wiring connected in this box must be at least rated 240 VAC and 14 gauge.
4)
Non-metallic cable strain reliefs do not provide grounding between conduit connections! Use grounding type bushings and jumper wires.
5)
Unused cable conduit entries must be securely sealed by non-flammable closures to provide transmitter's enclosure integrity in compliance with personal safety and environmental protection requirements.
6)
Operate only with front panel fastened and in place.
7)
Safety and performance require that this system be connected and properly grounded through a three wire power source.
8)
Proper use and configuration is the responsibility of the user.
9)
Before installing this equipment read the "Safety instructions for the wiring and installation of this apparatus". Failure to follow safety instructions could result in serious injury or death.
10)
Install all protective equipment covers and safety ground leads after installation. Failure to install covers and ground leads could result in serious injury or death.
11)
Local Ground connection shall be provided to CH88 Flue gas O Probe in order to avoid electric shock. The ground conductor should be equal or greater than 16 AWG for a copper conductor in free air or 12 AWG for an enclosed copper conductor.
12)
Disconnect and lock out power before connecting the power supply.
13)
Install all protective covers and safety ground leads after installation. Failure to install covers and ground leads could result in serious injury or death.
14)
Disconnect and lock out power before working on any electrical components. There is voltage up to 240 VAC. Verify the reliability and continuity of the grounding of the probe connection before powering the equipment.
15)
To meet the Safety Requirements of IEC 61010-1 (EC requirement), and ensure safe operation of this equipment, connection to the main electrical power supply must be made through a circuit breaker (max 10A) which will disconnect all current-carrying conductors during a fault situation. This circuit breaker should also include a mechanically operated isolating switch. If not, then another external means of disconnecting the supply from the equipment should be located close by. Circuit breakers or switches must comply with a recognized standard such as IEC 60947.

CAUTION

If the ducts will be washed down during outage MAKE SURE to power down the probes and remove them from the wash area. This manual concentrates on the installation, start-up, calibration, and operation of this product. There is also a more comprehensive manual that also covers troubleshooting, maintenance, repair, and spare parts identification.
3 Essential Instructions
Essential Instructions
September 2017
Installation/Start-up Manual
CMB_MAN_ABR_CH88
4
Essential Instructions
:
:
:
:
:
:
EQUIPMENT PROTECTED THROUGHOUT BY DOUBLE INSULATION(APPLIES TO 1056 COMBUSTION ELECTRONICS HOUSING ONLY)
When replacement parts are required, ensure that qualified people use replacement parts specified by Emerson Process Management. Unaut hori ze d parts a nd pr oc ed ures c an af f ec t the pr od uc t's performance; place the s af e operation of your process at risk, and VO ID YOU R WARRANTY. Look -alike s ubs tit uti ons may r esult in fire, electric al hazards, or improper operation.
Ensure that all equipment doors are closed and protective covers are in place, except when maintenance is being performed by qualified persons, to prevent electrical shock and personal injury.
The information contained in this document is subject to change without notice
Do not allow the temperature of the CH88 Flue Gas O2 Probe electronics to exceed 85°C (185°F) or damage to the unit may result.

Symbols Used on equipment and i n instr uc ti on m a nual

EARTH (GROUND) TERMINAL
PROTECTIVE CONDUCTOR TERMINAL
WARNING, RISK OF ELECTRIC SHOCK REFER TO INSTRUCTION MANUAL WARNING, HOT SURFACE
Note: If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.

Definitions

The following definitions apply to WARNINGS, CAUTIONS, and NOTES found throughout this publication.
WARNING
Highlights an operation or maintenance procedure, practice, condition, statement, etc. If not strictly observed, could result in injury, death, or long-term health hazards of personnel.

CAUTION

Highlights an operation or maintenance procedure, practice, condition, statement, etc. If not strictly observed, could result in damage to or destruction of equipment, or loss of effectiveness.
Highlights an essential operating procedure, condition, or statement.
Essential Instructions
September 2017
Installation/Start-up Manual
CMB_MAN_ABR_CH88
5
General Information
General Information Overview
The CH88 In-Situ Combustion O2 Analyzer System is Rosemount Analytical’s latest combustion flue gas oxygen analyzer consisting of 1056 Combustion Electronics and CH88 Flue Gas O2 Probe. This product is intended for measuring the flue gases resulting from any combustion process. It utilizes the same heated sensing technology as the O2 sensors found in most automobiles. Contact Rosemount Analytical’s technical support group at 800-433-6076 for any applications other than measuring combustion flue (exhaust) gases.
This product utilizes an “in situ” sensor, i.e. the sensor is placed at the end of a probe, and the probe extends directly into the flue gas duct or stack at a given length. The sensor is like a thermocouple, generating it’s own millivolt signal based on the difference between a reference gas (ambient or instrument air – always 20.95% O ), and the flue gases being measured.
2

System Configuration

CH88 Flue Gas O2 Probe with 1056 Combustion Electronics
There are no electronics inside the probe head, so the raw sensor signals for the heater thermocouple and zirconium oxide O sensor are sent to a remote 1056 Combustion electronics. The 1056 Combustion electronics will also directly apply power to the probe heater
in order to maintain the correct sensor temperature. This arrangement calls for a 9- conductor cable to carry this power and the sensor signals. Maximum length for this cable is 500 feet. This probe will also operate on previous Westinghouse/Rosemount electronics (World Class and Oxymitter), as well as many competitive electronics.
CH88 Flue Gas O2 Probe does not communicate via HART or FOUNDATION Fieldbus communications.
2

Technical Support Hotline

For assistance with technical problems, please call the Customer Support Center (CSC).
Rosemount Analytical Shangha i Serv ic e (086-21-28929294)
• 1-RAI-AND-U (1-855-724-2638)
• 1-800-433-6076
In addition to the CSC, you may also contact Field Watch. Field Watch coordinates Emerson Process Management’s field service throughout the U.S. and abroad.
• 1-800-654-RSMT (1-800-654-7768)
Emerson Process Management, Rosemount Analytical Inc. may also be reached via the Internet through e-mail and the World Wide Web
e-mail: GAS.CSC@emerson.com
World Wide Web: www.rosemountanalytical.com
Typical System Packag e and Ordering Information
Installation/Start-up Manual
6
Typical System Package and Ordering Information
CH88 Flue Gas O2 Probe
Length in Meters inches)
0.5 m (19.68 in)
8.6 Kgs (19 lbs)
6.1 Kgs(13.5 lbs)
6A00507G01
1056 Combustion in Millimeter(inches)
155 x 155 x 131mm (6.10 x 6.10 x 5.15 in.)
Cal gas adaptor kit to mate to existing tubing arrangement
September 2017
CMB_MAN_ABR_CH88

Section 2: Typical System Package

Figure 1
CH88 In-Situ Combustion O2 Anal yzer System Ordering Information
Shipping Weight Actual Weight Part Number
1 m (39.37 in) 10.43 Kgs (23 lbs) 7.6 Kgs(16.8 lbs) 6A00507G02 2m (78.74 in) 13.8 Kgs (30.5 lbs) 10.43 Kgs(23 lbs) 6A00507G03
Electronics dimensions
Accessory Part Number
Calibration Flowmeter 771B635H01
Replacement sensor board 6A00493G01 Replacement power supply board 24248-03
Shipping Weight
1.8 Kgs(4 lbs) 1.4 Kgs(3 lbs) 24490-00
1A98771H07
Actual Weight
Part Number
Replacement display board 24361-00
Specifications
Installation/Start-up Manual
7
Specifications
System Specifications
±1% of full scale for 0-10% ranges and above
Initial response in less than 3 seconds T90 in less than 8 seconds. velocity and particulate loading of the diffuser
Presentation of calibration gases matches the bottle value to within ±0.1% O2
Reference Air
Reference air is ambient air that will passively diffuse into the probe.
2
CH88 Flue Gas O2 Probe Specifications
Process-wetted materials are 304 Stainless
-40°to 705°C (40°to 1300°F) (1922°F)
Vertical or horizontal–2" 150# (4.75" (121mm) bolt circle) and DIN 145
Many adapter flanges are available to mate to existing flanges.
Manual/Semi-automatic Calibration electronics.
0.4% O2 and 8% O2, balance N2 recommended. Instrument air may be be used as the low cal gas.
Temperature: -40°to 90°C (-40°to 194°F) Humidity: 5 to 95% RH (non-condensing)
Temperature: 0-50°C (32-122°F) Humidity: 5 to 95% RH (non-condensing)
1056 Combustion Electronics
Overall 155 x 155 x 131mm (6.10 x 6.10 x 5.15 in.). Cutout: 1/2 DIN
Temperature: 20°C to 50°C (-4°F to 122°F) Humidity: 5 to 95% RH (non-condensing)
Temperature: -20°C to 60°C (-4°F to 140°F Humidity: 5 to 95% RH (non-condensing)
September 2017
Net O
2
Range Accuracy Lowest Detectable Limit Process Temperature Effect
System Speed of Response to Calibration Gas
Calibration Validity Power
Enclosure
Process Temperature Limits
CMB_MAN_ABR_CH88

Section 3: Specificat ions

Variable 0-10% to 0-50%
0.05% O2 Less than 0.05% O2 from 100°to 700°C (212°to 1292°F)
Response to process gas changes will vary depending on process gas
240V ±10%,50/60 Hz, 150 Watts max (during initial warm up)
The ambient air at the installation location must be fresh (20.95% O ).
optional bypass and jacket accessories permit operation to 1050°C
Output/s Probe Length
Mounting
Calibration
Calibration Gases
Calibration Gas Flow Ambient Conditions
Storage Conditions
Enclosure
One 4-20 mA
0.5, 1, 2 m
Note: Flanges are flat-faced and for mounting only. Flanges are not pressure-rated. A 2.5" diameter hole in the process is required. Spool piece P/N 3D39761G02 is available to offset probe housing from hot ductwork.
New calibration values are calc ula ted in the 10 56 Com bus tio n
used as a high cal gas but is not recommended. 100% nitrogen cannot
2.5-5 l/min. (5-10 scfh)
139mm x 139mm (5.45 x 5.45 in.),Polycarbonate Material Note: To ensure a water- tight seal, tighten all four front panel screws to 6 in -lbs of torque.
Mounting Conduit Openings
Pipe, wall, or panel (Refer to drawings) Accepts 1/2” or PG13.5 conduit fittings
Ambient Conditions
Storage Conditions
Specifications
Installation/Start-up Manual
8
Specifications
4-20 mA, max. load 550 ohms
Two (2) SPDT Form C, epoxy sealed contacts rated 5A, 30VDC, 120 VAC, or 230VAC; User configurable to alarm
The high-contrast LCD provides live measurement readouts in large
meet user requirements.
September 2017
Analog Output Alarm Relays
Display
CMB_MAN_ABR_CH88
digits and shows up to four additional process variables or diagnostic parameters. The display is back-lit and the format can be customized to
Installation
Installation/Start-up Manual
9
Installation
September 2017
CMB_MAN_ABR_CH88

Section 4: Installation

Mechanical Installa t ion
Installation of1056 Combustion Electronics
The 1056 Combustion Electronics is available in a panel mounting, or wall/pipe mounting configuration. Refer to Figure 5 or Figure 6 for the panel, wall, or pipe mounting details.
1.
Ensure all components are available to install the 1056 Combustion Electronics.
2.
Select a mounting location near or removed from the O2 Probe. Consider the temperature limitations of the 1056 Combustion Electronics (see "Specifications") when selecting the mounting location.
3.
Mount at a height convenient for viewing and operating the interface. Approximately 1.5 m (5 ft) is recommended.
4.
The keypad window on the 1056 Combustion Electronics may have an exterior protective membrane. Remove the protective membrane prior to use of the 1056 Combustion Electronics enclosure. Failure to remove the protective membrane may cause the display to appear distorted. The membrane may be difficult or impossible to remove after extended use at elevated temperatures.

Installation Specifications - Cable Connecting Probe to Electronics

Customer supplied, total of 9 conductors, rated for 105°C or greater, insulation rated for 250V or greater:

Heater Power

2 conductors, 12 – 18 ga. (<200ft.); use 12 ga. for lengths between 200 and 500 ft.

Probe sensing

7 conductors (3 twisted pairs plus shield) 16 to 25 ga. (<200 ft.); Use 16ga. for lengths between 200 and 500ft. Shield connected to ground at 1056 Combustion Electronics. All wiring must be rated for 250VAC. Minimum 105°C temperature.

CH88 Flue Gas O2 Probe Installation

A “weld plate” for welding to the flue gas duct can be supplied for new installations.
1.
Ensure all components are available to install the CH88 Flue Gas O2 probe. Refer to Figure 1.
2.
If using the standard square weld plate (Figure 1) or an optional flange mounting plate weld or bolt the plate onto the duct. The through hole diameter in the stack or duct wall and refractory material must be at least 63.5 mm (2-1/2 in).
3.
Insert probe through the opening in the mounting flange and bolt through the probe gasket and flange.

Grounding screws

A Grounding Screw is located on the outside of the CH88 Flue Gas O local ground. A second Grounding Screw is located inside the probe housing. It is intended to connect the grounding conductor to the control electronics.
WARNING: RISK OF ELECTRICAL SHOCK
Local Ground connection shall be provided to CH88 Flue Gas O2 Probe in order to avoid electric shock. The ground conductor should be equal or greater than 16 AWG for a copper conductor in free air or 12 AWG for an enclosed copper conductor.

WARNING

Before installing this equipment read the "Safety instructions for the wiring and installation of this apparatus" at the front of this Instruction Manual. Failure to follow safety instructions could result in serious injury or death. Install all protective equipment covers and safety ground leads after installation. Failure to install covers and ground leads could result in serious injury or death.

Probe enclosure. It is intended to provide a
2
Installation
Installation/Start-up Manual
10
Installation
September 2017
CMB_MAN_ABR_CH88
CAUTION
Do not allow the temperature of the CH88 Flue Gas O2 Probe electronics to exceed 85°C (185°F) or damage to the unit may result.
CAUTION
If the ducts will be washed down during outage MAKE SURE to power down the probes and remove them from the wash area.
Figure 2: CH88 Flue Gas O2 Probe Installation
NOTE: ALL DIMENSIONS ARE IN MILLIMETERS WITH INCHES IN PARENTHESES
Installation
Installation/Start-up Manual
11
Installation
September 2017

Figure 3: CH88 Flue Gas O2 Probe Installation

NOTE: ALL DIMENSIONS ARE IN MILLIMETERS WITH INCHES IN PARENTHESES
CMB_MAN_ABR_CH88
Installation
Installation/Start-up Manual
September 2017

Figure 4: Drip Loop and Insulation Removal

CMB_MAN_ABR_CH88
Note: Probe installation may be vertical or hori zontal.
12 Installation
Installation
Installation/Start-up Manual
September 2017

Figure 5: Wall/Surface and Pipe Mount

CMB_MAN_ABR_CH88
13 Installation
Installation
Installation/Start-up Manual
14
Installation
September 2017

Figure 6: Panel Mount

CMB_MAN_ABR_CH88
Installation
Installation/Start-up Manual
15
Installation
September 2017
CMB_MAN_ABR_CH88

Electrical Installation

All wiring must conform to local and national codes. Multiple wiring diagrams are shown in this section. Always refer to the diagrams that apply to your transmitter configuration and disregard all other wiring diagrams.

WARNING

Disconnect and lock out power before conne cting the power supply. Install all protective covers and safety ground leads after installation. Failure to install covers and ground leads could

result in serious injury or death. To meet the Safety Requirements of IEC 61010-1 (EC requirement), and ensure safe operation of this equipment,
connection to the main electrical power supply must be made through a circuit breaker (max 10A) which will disconnect all current-carrying conductors during a fault situation. This circuit breaker should also include a mechanically operated isolating switch. If not, then another external means of disconnecting the supply from the equipment should be located close by. Circuit breakers or switches must comply with a recognized standard such as IEC 60947.

WARNING

Before installing this equipment read the "Safety instructions for the wiring and installation of this apparatus" at the front of this Instruction Manual. Failure to follow safety instructions could result in serious injury or death.
Note: To maintain proper earth grounding ensure a positive connection exists between the probe terminations housing and earth. The connecting ground wire must be 14 AWG minimum.
Note: Line voltage, signal, and relay wiring must be rated for at least 105°C (221°F). Note: If metal conduit is used with the 1056 Combustion the conduit should be reliably bonded to protective earth. The
grounding plate inside the 1056 Combustion is not bonded to PE and does not provide adequate grounding.
WARNING

Disconnect and lock out power before working on any electrical components. There is volta g e up to 240 VAC. Verify the reliability and continuity of the grounding of the probe connection before powering the equipment.

Cable Connections
All electronics are housed inside the 1056 Combustion Electronics. A customer supplied multi-conductor power/signal cable connects between the probe and the 1056 Combustion Electronics. Use the following procedure to connect the probe to the 1056 Combustion Electronics.
NOTE: To maintain EMC/EMI noise protection customer supplied 9 conductor cable and cable glands must be properly connected to ground.
1.
Run the signal and power cables cable between the probe and the installation site for 1056 Combustion Electronics. Use
new cable conduit or trough as needed.
2.
Install the cable and lead wires to the probe per manufacturer’s instructions.
3.
Install the cable at the probe housing and at the 1056 Combustion Electronics enclosure according to the following
procedure:
a.
Unscrew locking nut from gland assembly and slide locking nut back along cable.
b.
Pull the gland body away from the plastic insert. Use care not to damage the cable shield braid.
c.
Insert the cable wires into the proper entry ports in the probe and the 1056 Combustion Electronics enclosures.
d.
At the probe housing, apply Teflon tape or similar sealing compound to the tapered pipe threads. Thread the gland
body into the probe housing until properly seated.
e.
At the 1056 Combustion Electronics enclosure, insert the gland body into the left front cable port from the inside of
the enclosure. Use the rubber O-ring provided to seal the cable port.
16
Installation
Installation Installation/Start-up Manual
September 2017 CMB_MAN_ABR_CH88
f.
Ensure the cable shield braid is evenly formed over the gray insert. When properly formed, the braid should be
evenly spaced around the circumference of the insert and not extend beyond the narrow diameter portion.
g.
Carefully press the gray insert into the gland body. The grooves on the insert should align with similar grooves
inside the gland body. Press the insert in until it bottoms out in the gland body.
h.
Slide the locking nut up and thread it onto the gland body. Tighten the locking nut so the rubber grommet inside the
plastic insert compresses against the cable wall to provide an environmental seal.
4.
At the 1056 Combustion Electronics, connect the cable leads to the connectors on the sensor I/O board as indicated in Figure 7.

Probe Connections

There are no electronics inside the probe head, so the raw sensor signals for the heater thermocouple and zirconium oxide O sensor are sent to a rem ote 1056 C ombustion Electronics . The 1056 Combustion Electro nic s will als o d irec tly apply power to
the probe heater in order to maintain the correct sensor temperature. This arrangement calls for a 9- conductor cable to carry this power and the sensor signals. Maximum length for this cable is 500 feet (see specifications).
2
1.
Remove cover from probe.
2.
Feed all probe wiring through the conduit port of probe.
3.
Refer to figure 7. Connect probe heater power leads to probe connector.
4.
Connect O signal, thermocouple, and cold Junction (CJC) wires from probe to 1056 Combustion Electronics
2

Power-Up Procedure

1.
Apply AC line power to 1056 Combustion Electronics.
2.
The probe will take approximately 45 minutes to warm up to the 736°C heater setpoint. The 4-20 mA signal will remain
at a default value of 3.5 mA and the O2 reading will remain at 0% through this warm-up period. After warm up, the probe will begin reading oxygen and the 4-20 mA output will be based on the default range of 0-10% O2.
3.
If there is an error condition at startup, an alarm message will be displayed on the 1056 Combustion Electronics. Refer to full instruction manual for troubleshooting alarms.
Installation
Installation/Start-up Manual
Figure 7: Wiring Diagram
17
Installation
September 2017
CMB_MAN_ABR_CH88
Installation
Installation/Start-up Manual
Figure 8: Wiring Diagram
18
Installation
September 2017
CMB_MAN_ABR_CH88

Calibration

Installation/Start-up Manual
19
Calibration
September 2017
CMB_MAN_ABR_CH88
Calibration
The CH88 In-Situ Combustion O2 Analyzer System can be calibrated in the installed condition without removing the instrument from the process duct and also while the combustion process is on-line. A stainless steel tube runs the length of the probe, and delivers the calibration gasses into the cell area. Factory calibration will usually be satisfactory for initial start-up and operation, but most accurate measurement is gained by executing a calibration under normal operating conditions.
Recommended calibration gases are 0.4% O and 8% O , with the balance of nitrogen in the gas bottles, but other values can be used as long as the electronics are configured identically. Instrument air or pure nitrogen are not recommended as
calibration gas values. A two-stage pressure regulator should be used to establish a pressure of 20 PSI, from the bottles, and the flowmeter should be set to 5 SCFH flow rate.
2 2

Manual/Semi-automatic Calibration

The CH88 Flue Gas O2 Probe with the standard housing can be calibrated in a semi-automatic fashion, with a technician following prompts via the display of the 1056 Combustion Electronics. The technician will need to manually switch the gases based upon these prompts. Recommended calibration gases are 0.4% O2 and 8% O2, balance nitrogen. A two-stage pressure regulator should always be used, set to 20 PSI. The calibration gas flowmeter should be set for 5 SCFH, with the cal gas fitting removed from the probe. A diffuser/filter that is plugged over time may cause the flowmeter to deliver less flow to the sensing cell, but the flow rate should never be readjusted until a new diffuser is installed. Readjusting the flowmeter back up to the 5 SCFH level could pressurize the cell during calibration, and cause the O2 reading to shift downwards.
The electronics will determine if the calibration was successful, and calculate new calibration values. New calibration values are automatically loaded into the electronics after a successful calibration. Record the calibration data on the log provided (cell slope, constant, and impedance, as well as the speed of response data).
Calibration Records
Installation/Start-up Manual
20
Calibration Records
September 2017
Probe Serial Number: Probe Tag Number: Probe Location: Date Placed Into Service:
CMB_MAN_ABR_CH88
Calibration Record
For
Rosemount Analytical In-Situ O2 Probe
Notes: Response
Response final When the second calibration gas is turned off, note the number of seconds
initial When the second calibration gas is turned off, note the number of seconds
required for the O value to begin migrating back to the process value.
required for the O value to settle out at the process value.
2
2
CAUTION
Make sure that the calibration gas cap is replaced tightly after calibration is complete. Many combustion processes operate at a slight negative pressure (draft pressure), and can draw ambient air down the cal gas lines and into the sensing cell, causing a false elevated O reading. This same phenomenon is possible if the calibration gas hoses are permitted to become degraded or
2
loose.
CH88 In-Situ Combustion O2 Analyzer System Menu Trees
Installation/Start-up Manual
21
CH88 Menu Trees
September 2017
CMB_MAN_ABR_CH88
Section 5: Menu Trees
CH88 In-Situ Combustion O2 Analyzer System Menu Trees

System Menu Tree (English) System Menu Tree (Chinese)

CH88 In-Situ Combustion O2 Analyzer System Menu Trees
Installation/Start-up Manual
22
CH88 Menu Trees
September 2017
CMB_MAN_ABR_CH88

Probe Menu Tree (English) Probe Menu Tree (Chinese)

CH88 In-Situ Combustion O2 Analyzer System Menu Trees
Installation/Start-up Manual
23
CH88 Menu Trees
September 2017 CMB_MAN_ABR_CH88

CH88 In-Situ Combustion O2 Analyzer System Menu Trees Menu Trees

Probe Menu Tree (English) Probe Menu Tree (Chinese)

Parameters
Installation/Start-up Manual
24
Parameters
September 2017
CH88 In-Situ Combustion O2 Analyzer System Parameters
System Parameters
CMB_MAN_ABR_CH88
Section 6: Parameters
Parameters
Installation/Start-up Manual
25
Parameters
September 2017
Probe Parameters
CMB_MAN_ABR_CH88
Parameters
Installation/Start-up Manual
26
Parameters
September 2017

Probe Parameters (cont inued)

CMB_MAN_ABR_CH88
Parameters
Installation/Start-up Manual
27
Parameters
September 2017
Probe Parameters (cont inued)
CMB_MAN_ABR_CH88
Parameters
Installation/Start-up Manual
28
Parameters
September 2017

Probe Parameters (cont inued)

CMB_MAN_ABR_CH88
Parameters
Installation/Start-up Manual
29
CH88 Alarms
September 2017

CH88 In-Situ Combustion O2 Anal yzer S ystem Alarms

System Alarms

CMB_MAN_ABR_CH88
Parameters
Installation/Start-up Manual
September 2017
Probe Alarms
CMB_MAN_ABR_CH88
30 CH88 Alarms
Parameters
Installation/Start-up Manual
September 2017

Probe Alarms

CMB_MAN_ABR_CH88
31 CH88 Alarms

CH88 Manual

CMB_MAN_ABR_CH88 September 2017
Global Headquarters
Emerson Automation Solutions
6021 Innovation Blvd. Shakopee, MN 55379, USA
+1 800 999 9307 or +1 952 906 8888 +1 952 949 7001
Gas.CSC@Emerson.com
North America Regional Office
Emerson Automation Solutions
8200 Market Blvd. Chanhassen, MN 55317, USA
+1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RFQ-NA.RCCRFQ@Emerson.com
Latin America Regional Office
Emerson Automation Solutions
1300 Concord Terrace, Suite 400 Sunrise, FL 33323, USA
+1 954 846 5030 +1 952846 5121 RFQ.RMD-RCC@Emerson.com

Europe Regional Office

Emerson Automation Solutions Europe GmbH

Neuhofstrasse 19a P.O. Box 1046 CH 6340 Baar Switzerland
+1 954 846 5030 +1 952846 5121 RFQ.RMD-RCC@Emerson.com

Asia Pacific Regional Office

Emerson Automation Solutions Asia Pacific Pte LTD

1 Pandan Crescent Singapore 128461
+65 6777 8211 +65 6777 0947
Enquiries@AP.Emerson.com

Middle East and Africa Regional Office

Emerson Automation Solutions
Emerson FZE P.O. Box 17033 Jebel Ali Free Zone South 2
+971 4 8118100 +971 4 88665465
RMTMEA@Emerson.com
RFQ.
Analyticexpert.com
Linkedin.com/company/Emerson-Automation-Solutions
Twitter.com/Rosemount_News
Facebook.com/Rosemount
Youtube.com/user/RosemountMeasurement
Google.com/+RosemountMeasurement
The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount and Rosemount logotype are trademarks of Emerson. All other marks are the property of their respective owners. © 2017 Emerson. All rights reserved.
Loading...