Rosemount CAT 7 Thermal Conductivity Transmitter-Rev B Manuals & Guides

Page 1
Instruction Manual
748451-B March 2002
Model CAT7
Thermal Conductivity Analyzer
http://www.processanalytic.com
Page 2

ESSENTIAL INSTRUCTIONS

READ THIS PAGE BEFORE PROCEEDING!
Rosemount Analytical designs, manufactures and tests its products to meet many national and international standards. Because these instruments are sophisticated technical products, you MUST properly install, use, and maintain them to ensure they continue to operate within their normal specifications. The following instructions MUST be adhered to and integrated into your safety program when installing, using, and maintaining Rosemount Analytical products. Failure to follow the proper instructions may cause any one of the following situations to occur: Loss of life; personal injury; property damage; damage to this instrument; and warranty invalidation.
Read all instructions prior to installing, operating, and servicing the product.
If you do not understand any of the instructions, contact your Rosemount Analytical repre-
sentative for clarification.
Follow all warnings, cautions, and instructions marked on and supplied with the product.
Inform and educate your personnel in the proper installation, operation, and mainte-
nance of the product.
Install your equipment as specified in the Installation Instructions of the appropriate In- struction Manual and per applicable local and national codes. Connect all products to the
proper electrical and pressure sources.
To ensure proper performance, use qualified personnel to install, operate, update, program, and maintain the product.
When replacement parts are required, ensure that qualified people use replacement parts specified by Rosemount. Unauthorized parts and procedures can affect the product’s per­formance, place the safe operation of your process at risk, and VOID YOUR WARRANTY. Look-alike substitutions may result in fire, electrical hazards, or improper operation.
Ensure that all equipment doors are closed and protective covers are in place, except when maintenance is being performed by qualified persons, to prevent electrical shock and personal injury.
The information contained in this document is subject to change without notice.
Teflon® is a registered trademark of E.I. duPont de Nemours and Co., Inc. SNOOP® is a registered trademark of NUPRO Co.
Emerson Process Management
Rosemount Analytical Inc. Process Analytic Division
1201 N. Main St. Orrville, OH 44667-0901 T (330) 682-9010 F (330) 684-4434 e-mail: gas.csc@EmersonProcess.com
http://www.processanalytic.com
Page 3
Model CAT7
PREFACE...........................................................................................................................................1
Definitions ...........................................................................................................................................1
safety Summary..................................................................................................................................2
General Precautions For Handling And Storing High Pressure Gas Cylinders .................................4
Documentation....................................................................................................................................5
Compliances .......................................................................................................................................5
1.0 DESCRIPTION AND SPECIFICATIONS..............................................................................1-1
1-1 Analyzer Module....................................................................................................................1-1
1-2 Thermal Conductivity Cell......................................................................................................1-1
1-3 Electronic Circuitry.................................................................................................................1-4
1-4 Gas Selector Panel................................................................................................................1-4
1-5 Specifications ........................................................................................................................1-5
Instruction Manual
748451-B
March 2002

TABLE OF CONTENTS

2.0 INSTALLATION ....................................................................................................................2-1
2-1 Site Preparation.....................................................................................................................2-1
2-2 Customer Electrical Connections ..........................................................................................2-1
2-3 Flow Diagrams.......................................................................................................................2-1
2-4 Location and Mounting ..........................................................................................................2-1
a. Location...........................................................................................................................2-1
b. Mounting .........................................................................................................................2-1
2-5 Unpacking..............................................................................................................................2-3
2-6 Gas Requirements.................................................................................................................2-3
2-7 Calibration Gas Requirements ..............................................................................................2-3
a. Sample Gas Composition ...............................................................................................2-3
2-8 Suppressed-Zero Ranges .....................................................................................................2-3
2-9 Leak Check............................................................................................................................2-3
2-10 Gas Connections ...................................................................................................................2-4
2-11 Recorder Output Selection and Cable Connections .............................................................2-8
a. Standard (Non-linearized) Voltage Output......................................................................2-8
b. Linearized Voltage Output (Optional)..............................................................................2-8
c. Isolated 4 to 20 mA Current Output (Optional) ...............................................................2-8
2-12 Alarms (Optional)...................................................................................................................2-10
2-13 Linearized Voltage, Two Ranges (Optional)..........................................................................2-12
2-14 Linearized Voltage and Isolated 4 to 20 mA Current Output (Optional)................................2-12
2-15 Electrical Power Connections................................................................................................2-13
3.0 OPERATION .........................................................................................................................3-1
3-1 Analyzer Controls and Adjustments ......................................................................................3-1
3-2 Gas Selector Panel Controls .................................................................................................3-1
3-3 Startup Procedure .................................................................................................................3-1
3-4 Calibration..............................................................................................................................3-2
Rosemount Analytical Inc. A Division of Emerson Process Management Contents i
Page 4
Instruction Manual
748451-B March 2002
4.0 THEORY................................................................................................................................4-1
4-1 Thermal Conductivity Cell and Associated Bridge Adjustments ...........................................4-1
4-2 Master Board .........................................................................................................................4-1
a. Functions Associated with AR1 ......................................................................................4-1
b. Coarse zero and zero-suppression.................................................................................4-2
c. Functions Associated with AR2 ......................................................................................4-2
d. Meter ...............................................................................................................................4-2
e. Output Selection Switch S1 ............................................................................................4-2
4-3 Voltage Output Linearizer Board Option ...............................................................................4-2
4-4 Isolated 4 to 20 mA Current Output Board Option ................................................................4-4
4-5 Bridge Power Supply .............................................................................................................4-4
4-6 ±15 Volt Power Supply ..........................................................................................................4-4
4-7 Detector Blocks .....................................................................................................................4-4
4-8 Case Temperature Controller Assembly ...............................................................................4-4
4-9 Dual Alarms Option ...............................................................................................................4-5
5.0 SERVICE AND MAINTENANCE ..........................................................................................5-1
5-1 Thermal Conductivity Cell......................................................................................................5-1
5-2 Electronic Circuitry.................................................................................................................5-4
a. Amplifier Zero Adjustments.............................................................................................5-4
b. Bridge Balance and Range Sensitivity Adjustments.......................................................5-4
c. Case Temperature Controller .........................................................................................5-5
d. Dual Alarm Module (Optional).........................................................................................5-5
5-3 Suppressed Zero Adjustment................................................................................................5-5
Model CAT7
6.0 REPLACEMENT PARTS ......................................................................................................6-1
6-1 Matrix .....................................................................................................................................6-1
6-2 Circuit Board Replacement Policy .........................................................................................6-3
6-3 Replacement Parts ................................................................................................................6-4
7.0 RETURN OF MATERIAL ......................................................................................................7-1
7-1 Return Of Material .................................................................................................................7-1
7-2 Customer Service ..................................................................................................................7-1
7-3 Training..................................................................................................................................7-1
ii Contents Rosemount Analytical Inc. A Division of Emerson Process Management
Page 5
Model CAT7
Figure 1-1. CAT7 Controls, Adjustments, Ports .......................................................................... 1-2
Figure 1-2. Fuse Location............................................................................................................ 1-2
Figure 1-3. CAT7 – Exploded View ............................................................................................. 1-3
Figure 1-4. Typical Gas Selector Panel....................................................................................... 1-4
Figure 2-1. Gas Selector Panel for Thermal Conductivity Cell with Sealed-In Reference Gas .. 2-1 Figure 2-2. Gas Selector Panel for Thermal Conductivity Cell Using Flowing Reference Gas .. 2-2
Figure 2-3. Gas Connections – Bottom View of Analyzer ........................................................... 2-4
Figure 2-4. Connection of Analyzer Using Sealed-In Reference Gas to Associated Gas .......... 2-5
Figure 2-5. Connection of Analyzer Using Flowing Reference Gas to Associated Gas Selector
Figure 2-6. Intrinsic Safety Box ................................................................................................... 2-7
Figure 2-7. Intrinsic Safety Box Interconnect .............................................................................. 2-7
Figure 2-8. Master Board............................................................................................................. 2-9
Figure 2-9. Alarm Adjustments ..................................................................................................2-10
Figure 2-10. Typical Alarm Settings .......................................................................................... 2-11
Figure 2-11. Case Heater Temperature Control Board............................................................. 2-13
Figure 4-1. Thermal Conductivity Cell ......................................................................................... 4-3
Instruction Manual
748451-B
March 2002

LIST OF ILLUSTRATIONS

Panel...................................................................................................................... 2-6

LIST OF TABLES

Table 1-1. Available Gas Selector Panels................................................................................... 1-5
Table 4-1. Range Switch Connections ........................................................................................ 4-2
DRAWINGS
613561 Schematic Diagram, Bridge Power Supply - Regulated 5 to 15V 619710 Schematic Diagram, 15V Power Supply 624003 Schematic Diagram, Temperature Controller 652813 Schematic Diagram, Isolated Current Output 652863 Schematic Diagram, Linearizer Board 654616 Schematic Diagram, Master Board 661200 Assembly Instructions, CAT7 661203 Assembly, Chassis 661318 Installation Drawing, CAT7 661540 Assembly, Temperature Control 661541 Assembly, Meter 661562 Wiring Diagram, CAT7
(LOCATED IN REAR OF MANUAL)
Rosemount Analytical Inc. A Division of Emerson Process Management Contents iii
Page 6
Instruction Manual
748451-B March 2002
Model CAT7
iv Contents Rosemount Analytical Inc. A Division of Emerson Process Management
Page 7
Instruction Manual
Model CAT7

PREFACE

The purpose of this manual is to provide information concerning the components, functions, installation and maintenance of the CAT7 Thermal Conductivity Analyzer.
Some sections may describe equipment not used in your configuration. The user should become thoroughly familiar with the operation of this module before operating it. Read this instruction manual completely.

DEFINITIONS

The following definitions apply to DANGERS, WARNINGS, CAUTIONS and NOTES found throughout this publication.
DANGER .
748451-B
March 2002
Highlights the presence of a hazard which will cause severe personal injury, death, or substantial property damage if the warning is ignored.
WARNING .
Highlights an operation or maintenance procedure, practice, condition, statement, etc. If not strictly observed, could result in injury, death, or long-term health hazards of personnel.
CAUTION.
Highlights an operation or maintenance procedure, practice, condition, statement, etc. If not strictly observed, could result in damage to or destruction of equipment, or loss of effectiveness.
NOTE
Highlights an essential operating procedure, condition or statement.
Rosemount Analytical Inc. A Division of Emerson Process Management Preface P-1
Page 8
Instruction Manual
748451-B March 2002
Model CAT7

SAFETY SUMMARY

To avoid explosion, loss of life, personal injury and damage to this equipment and on-site property, all per­sonnel authorized to install, operate and service the Model CAT7 Thermal Conductivity Analyzer should be thoroughly familiar with and strictly follow the instructions in this manual. Save these instructions.
If this equipment is used in a manner not specified in these instructions, protective systems may be impaired.
AUTHORIZED PERSONNEL
To avoid explosion, loss of life, personal injury and damage to this equipment and on-site property, all personnel authorized to install, operate and service the this equipment should be thoroughly familiar with and strictly follow the instructions in this manual. SAVE THESE IN­STRUCTIONS.
DANGER.
ELECTRICAL SHOCK HAZARD
Do not operate without doors and covers secure. Servicing requires access to live parts which can cause death or serious injury. Refer servicing to qualified personnel.
For safety and proper performance this instrument must be connected to a properly grounded three-wire source of power.
NOTE
Before supplying electrical power to the analyzer, remove power to the bridge by disconnecting the red lead from the bridge to TB1-1 or TB1-2 (depending on the bridge polarity). See drawing 661562. To safeguard against filament damage, this lead should remain disconnected until proper gas flow has been established.
DANGER
EXPLOSION HAZARD
Do not operate the Model CAT7 Explosion-Proof Analyzer without the lens cover in place and com­pletely secured, unless location have been determined to be non-hazardous.
P-2 Preface Rosemount Analytical Inc. A Division of Emerson Process Management
Page 9
Instruction Manual
Model CAT7
DANGER
EXPLOSION HAZARD
This analyzer is of a type capable of analysis of sample gases which may be flammable. If used for analysis of such gases, the instruments explosion-proof enclosure must be suitable for the gas.
If explosive gases are introduced into this analyzer, the sample containment system must be care­fully leak-checked upon installation and before initial startup, during routine maintenance and any time the integrity of the sample containment system is broken, to ensure the system is in leak-proof condition. Leak-check instructions are provided in Section 2-9.
Internal leaks resulting from failure to observe these precautions could result in an explosion causing death, personal injury or property damage.
WARNING .
PARTS INTEGRITY
Tampering or unauthorized substitution of components may adversely affect safety of this product. Use only factory documented components for repair.
748451-B
March 2002
WARNING.
HIGH PRESSURE GAS CYLINDERS
This instrument requires periodic calibration with a known standard gas. See also General Precau­tions for Handling and Storing High Pressure Gas Cylinders, page P-4.
Rosemount Analytical Inc. A Division of Emerson Process Management Preface P-3
Page 10
Instruction Manual
748451-B March 2002
Model CAT7
GENERAL PRECAUTIONS FOR HANDLING AND STORING HIGH
PRESSURE GAS CYLINDERS
Edited from selected paragraphs of the Compressed Gas Association's "Handbook of Compressed Gases" published in 1981
Compressed Gas Association 1235 Jefferson Davis Highway Arlington, Virginia 22202
Used by Permission
1. Never drop cylinders or permit them to strike each other violently.
2. Cylinders may be stored in the open, but in such cases, should be protected against extremes of weather and, to prevent rusting, from the dampness of the ground. Cylinders should be stored in the shade when lo­cated in areas where extreme temperatures are prevalent.
3. The valve protection cap should be left on each cylinder until it has been secured against a wall or bench, or placed in a cylinder stand, and is ready to be used.
4. Avoid dragging, rolling, or sliding cylinders, even for a short distance; they should be moved by using a suit­able hand-truck.
5. Never tamper with safety devices in valves or cylinders.
6. Do not store full and empty cylinders together. Serious suckback can occur when an empty cylinder is at­tached to a pressurized system.
7. No part of cylinder should be subjected to a temperature higher than 125 permitted to come in contact with any part of a compressed gas cylinder.
8. Do not place cylinders where they may become part of an electric circuit. When electric arc welding, precau­tions must be taken to prevent striking an arc against the cylinder.
°
F (52°C). A flame should never be
P-4 Preface Rosemount Analytical Inc. A Division of Emerson Process Management
Page 11
Instruction Manual
Model CAT7

DOCUMENTATION

The following CAT7 Thermal Conductivity Analyzer instruction materials are available. Contact Customer Service or the local representative to order.
748451 Instruction Manual (this document)

COMPLIANCES

This product may carry approvals from several certifying agencies. The certification marks appear on the product name-rating plate.
Area Classifications:
USA
Class I Zone 1 AEx d e m IIB + H
2
T4
748451-B
March 2002
Canada
Ex d e m IIB + H
European Union
ATEX, Category 2, Zone 1, IIB + H
USA/Canada
Certified by Canadian Standards Association, an OSHA Nationally Recog­nized Testing Laboratory (NRTL) for USA and Canada.
European Union
Conforms with the provisions of the EMC Directive 89/336/EEC, Low Volt­age Directive 73/23/EEC, Potentially Explosive Atmospheres Directive 94/9/EC, including amendments by the CE marking Directive 93/68/EEC.
EC type Examination Certificate, LCIE 00 ATEX 6009 X.
Rosemount Analytical has satisfied all obligations from the European Leg­islation to harmonize the product requirements in Europe.
Australia/New Zealand
T4
2
T4
2
®
0081
EEx d e m II B (+H2) T4
LCIE 00 ATEX 6009 X
II 2 G
Conforms with Electromagnetic Compatibility – Generic Emission standard and AS/NZS 4251.1 – 1994 Part 1 – Residential, commercial, and light in­dustrial.
Complies with the NAMUR RECOMMENDATION, Electromagnetic Com­patibility (EMC) issue 1998.
Rosemount Analytical Inc. A Division of Emerson Process Management Preface P-5
NAMUR
N96
Page 12
Instruction Manual
748451-B March 2002
Model CAT7
P-6 Preface Rosemount Analytical Inc. A Division of Emerson Process Management
Page 13
Model CAT7
Instruction Manual
748451-B
March 2002
SECTION 1

DESCRIPTION AND SPECIFICATIONS

The Model CAT7 Thermal Conductivity Analyzer is designed to continuously measure the concentration of a single component of interest in a flowing gas mix­ture. The measurement is based on the different thermal conductivity's of the individual components of the sample stream. The method is especially well suited to analysis of two-component sample streams. However, analysis of multi-component streams is pos­sible if the various components of the background gas occur in relatively constant ratio, or have similar ther­mal conductivity's.
Each Model CAT7 Analyzer is factory-assembled, as ordered, for determination of a specified component, with specified range of concentration, contained in a background component or background mixture of known composition. Typical examples include: 0 to 100 % hydrogen in nitrogen; 20 to 50 % helium in methane; and 0% to 3% carbon dioxide in air. If so ordered, the instrument is provided with two or three ranges; selectable via a side-panel switch. Informa­tion specific to the individual instrument is provided in the data sheet inserted in the back of this instruction manual.
A Model CAT7 Analyzer consists of an analyzer mod­ule, Section 1-1, and, if ordered, an accessory gas selector panel, Section 1-4.

1-2 THERMAL CONDUCTIVITY CELL

The thermal conductivity cell is a metal block with separate passages for the sam­ple and reference gases. In all applications, the sample passage receives a continuous flow of sample gas. Depending on the ap­plication, the reference passage may re­ceive a continuous flow of reference gas, or may have the reference gas sealed within.
The sample passage contains a pair of temperature-sensitive resistive filaments. The reference passage contains a similar pair. Electrically, the filaments are con­nected as legs of a Wheatstone bridge. An internal voltage-regulated power supply is connected via a 20-ohm dropping resistor, to the bridge.
With the power supply output adjusted to provide an appropriate voltage across the bridge, an electric current flows through the filaments, heating them and thus increasing their electrical resistance. The heat-dissipation rate for each filament de­pends on the thermal conductivity of the surrounding gas.

1-1 ANALYZER MODULE

The analyzer module is supplied in an explo­sion-proof enclosure suitable for installation in hazardous locations classified as Zone 1, Groups II B (+H Group II B (+H
Rosemount Analytical Inc. A Division of Emerson Process Management Description and Specifications 1-1
), T4, Category 2, Zone 1,
2
), T4.
2
Initially, with suitable downscale calibration gas flowing through the sample passage (and also through the reference passage if of the flow-through configuration), the bridge is balanced. Thereafter, any change in the relative proportions of the compo­nents passing through the sample passage changes the thermal conductivity of the gas mixture, causing a temperature differential between sample and reference filaments. The resultant change in filament resistance unbalances the bridge, applying a signal to the electronic circuitry (Section 1-3).
Page 14
Instruction Manual
Adj
748451-B March 2002
AC Power Port
Model CAT7
Signal Output, Alarm Ports
Alarm
Alarm
Figure 1-1. CAT7 Controls, Adjustments, Ports
Range Select
Zero
ust
Span
Fuse
Figure 1-2. Fuse Location
1-2 Description and Specifications Rosemount Analytical Inc. A Division of Emerson Process Management
Page 15
Model CAT7
Instruction Manual
748451-B
March 2002
Chassis Assembly
Meter Assembly
Alarm Module
Figure 1-3. CAT7 – Exploded View
Rosemount Analytical Inc. A Division of Emerson Process Management Description and Specifications 1-3
Page 16
Instruction Manual
1
1
748451-B March 2002
Model CAT7

1-3 ELECTRONIC CIRCUITRY

The analyzer module contains solid-state cir­cuitry that conditions the bridge-imbalance signal as required to provide readout on the meter. In addition, a field-selectable output for a voltage-type recorder is provided as standard. A field-selectable output of 4 to 20 mA for a current-actuated recorder or other device is obtainable through use of an op­tional plug-in circuit board. A calibration curve can be used to convert meter or re­corder readings into concentration values. Typical calibration curves are supplied for standard ranges. Calibration curves for spe­cial ranges are available as options.
To avoid use of a calibration curve in an ap­plication where it would otherwise be required, the analyzer may be equipped with an op­tional linearizer board. If so, the linearizer is factory set for a given range only, and is not usable on another range. Note that a line­arizer is usable only if non-linearity at mid-
scale does not exceed approximately 20% of fullscale.

1-4 GAS SELECTOR PANEL

If so ordered, the analyzer module is provided with an appropriate gas selector panel, Figure 1-4. The gas selector panel permits selection, flow adjustment, and flow measurement for the various gases: sample; flowing reference gas, if used; and downscale and upscale cali­bration gases. Proper choice of a gas selec­tor panel depends on:
1. Configuration of the thermal conductivity cell, i.e., flowing or sealed-in reference gas.
2. Composition of the sample stream. For non-corrosive streams, the gas selector panel is assembled with brass compo­nents. For corrosive streams, stainless steel is used.
Reference Gas
Flow Meter
Downscale Calibration Gas Needle Valve
DOWNSCALE
CAL GAS
UPSCA LE
CAL GAS
Upscale Calibration Gas Needle Valve
1 Provided only if thermal conductivity cell uses flowing reference gas.
REF
SAMPLE
Figure 1-4. Typical Gas Selector Panel
Sample/Calibration Gas Flow Meter
SAMPLE
REFERENCE
Sample Gas Needle Valve
Reference Gas
Needle Valve
1-4 Description and Specifications Rosemount Analytical Inc. A Division of Emerson Process Management
Page 17
Model CAT7
Brass and Copper construction for use with sealed reference 113357 Stainless steel construction for use with sealed reference 113920 Brass and Copper construction for use with flowing reference 117195 Stainless steel construction for use with flowing reference 118210

1-5 SPECIFICATIONS

Reproducibility............................... ±0.5% of fullscale
Zero Drift
Span Drift
Noise ............................................. Less than ±0.5% of fullscale
Cell Response Time
Sample Flow.................................. Nominal, 50 to 350 cc/min; recommended, 250 cc/min.
Calibration Gas Flow ..................... Nominal, 50 to 350 cc/min; recommended, 250 cc/min.
Reference Gas Flow (If Req’d)...... 5 to 50 cc/min.
Supply Pressure ............................ 10 to 50 psig (69 to 345 kPa)
Meter ............................................. Indicating analog meter is standard.
Operating Ranges ......................... Various zero-based and zero-suppressed ranges, from 0% to
Ambient Temperature Range........ 32°F to 100°F (0°C to 38°C). Case Temperature controlled at
Output Voltage
1
...................................... ±1% of fullscale per 24 hours
1
Non-Linearized (Standard) .... Switch selectable: 0 to 10 mV, 0 to 100 mV, 0 to 1V or 0 to 5V DC
Linearized (Option) ................ Switch selectable: 0 to 10 mV, 0 to 100 mV, 0 to 1V or 0 to 5V DC
DESCRIPTION PART NUMBER
Table 1-1. Available Gas Selector Panels
..................................... ±1% of fullscale per 24 hours
2
..................... 30 seconds for 95% response, with sample flow of 250 cc/min.
100%, are available. Single range is standard; switch-selectable dual or triple range is optional.
117°F (47°C).
Instruction Manual
748451-B
March 2002
Isolated Current Output (Option)... 4 to 20 mA, maximum load 1500 ohms
Dual Alarms (Option)..................... Relay contact rating: 1.0 A, 120V AC; 5.0 A, 120V DC, resistive
loads
Cell Materials (Standard Cell) ....... 316 stainless steel block with tungsten or Hitempco filaments. Cor-
rosion-resistant filaments available on order
Power Requirements..................... 115/230 VAC ±10%, 50/60 Hz, 250 Watts
Enclosure....................................... Zone 1, Groups II B (+H
(+H
), T4
2
1
Zero and Span drift specifications based on ambient temperature shifts of less than 18 Fahrenheit degrees (10 Celsius de-
grees) at a maximum rate of 18 Fahrenheit degrees (11 Celsius degrees) per hour.
2
Cell response time is less than 45 seconds for 95% response, with sample flow rate of 250 cc/min, for the following gas
combinations: Argon and air, nitrogen, or oxygen; carbon dioxide and argon, nitrogen, or oxygen; helium and methane; hy­drogen and methane.
Rosemount Analytical Inc. A Division of Emerson Process Management Description and Specifications 1-5
), T4, Category 2, Zone 1, Group II B
2
Page 18
Instruction Manual
748451-B March 2002
Model CAT7
1-6 Description and Specifications Rosemount Analytical Inc. A Division of Emerson Process Management
Page 19
Model CAT7
Instruction Manual
748451-B
March 2002
SECTION 2

INSTALLATION

2-1 SITE PREPARATION

This section provides information that may be required prior to installation.
For outline and mounting dimensions of the analyzer drawing 661318. For outline and mounting dimensions of the gas selector panel, see Figure 2-1, and Figure 2-2.

2-2 CUSTOMER ELECTRICAL CONNECTIONS

Customer electrical connections are shown in Figure 2-7 and drawing 661562.

2-3 FLOW DIAGRAMS

For gas connections, refer to appropriate flow diagram:
Analyzer using sealed reference gas, Figure 2-4.
Analyzer using flowing reference gas, Figure 2-5.

2-4 LOCATION AND MOUNTING

a. Location

Proper location for the analyzer depends on two basic considerations:
Accessibility to the sampling point
Protection of the instrument
Ideally, the analyzer should be located as close to the sampling point as possible. Short sample lines reduce time lag in readings. In practice, however, protection of the instrument sometimes calls for more remote placement.
The analyzer should be mounted in a clean, dry atmosphere. Ambient tem­perature should be within the range of
o
32
F to 100 F (0oC to 38oC).

b. Mounting

The analyzer is designed for wall mount­ing. Refer to drawing 661318.
10.25 [260]
SAMPLE
Span Gas In
To Analyzer
Sample In
Zero Gas In
8.25 [210]
Mounting Holes (4) NO. 8 Flat Head Screw
ZERO SPAN
Figure 2-1. Gas Selector Panel for Thermal Conductivity Cell with Sealed-In Reference Gas
Rosemount Analytical Inc. A Division of Emerson Process Management Installation 2-1
Page 20
Instruction Manual
748451-B March 2002
Model CAT7
Sample Gas
To Analyzer Sample Inlet
To Analyzer Ref Gas Inlet
Downscale Cali­bration Gas
1.25 [32]
DOWNSCALE
CALIBRATION GAS
10.25 [260]
8.25 [210]
REF SAMPLE
UPSCALE
CALIBRATION GAS
3.25 [83]
.12
[3]
Mounting Holes (4) NO. 8 Flat Head Screw
Ref Gas
Upscale Cali­bration Gas
Figure 2-2. Gas Selector Panel for Thermal Conductivity Cell Using Flowing Reference Gas
SAMPLE
REF
2-2 Installation Rosemount Analytical Inc. A Division of Emerson Process Management
Page 21
Model CAT7
Instruction Manual
748451-B
March 2002

2-5 UNPACKING

The Model CAT7 Thermal Conductivity Ana­lyzer is a precision instrument and should be handled carefully. Carefully examine the shipping carton and contents for signs of damage. Immediately notify the carrier if the carton or its contents are damaged. Retain the carton and packing material until the in­strument is operational.

2-6 GAS REQUIREMENTS

The Model CAT7 requires cylinder gases ap­propriate to the particular application (refer to the Data Sheet in the rear of this manual). Suitable gases are available from various suppliers.

2-7 CALIBRATION GAS REQUIREMENTS

For calibration, the analyzer requires a down­scale and an upscale calibration gas, both normally specified in the Data Sheet. Proper choice of calibration gases for a particular ap­plication depends on the composition of the sample stream and the operating range used.

a. Sample Gas Composition

WARNING
POSSIBLE EXPLOSION HAZARD
This analyzer is of a type capable of analy­sis of sample gases which may be flam­mable. If used for analysis of such gases, the instruments explosion-proof enclosure must be suitable for the gas.
If explosive gases are introduced into this analyzer, the sample containment system must be carefully leak-checked upon in­stallation and before initial startup, during routine maintenance and any time the in­tegrity of the sample containment system is broken, to ensure the system is in leak­proof condition.
Internal leaks resulting from failure to ob­serve these precautions could result in an explosion causing death, personal injury or property damage.

2-9 LEAK CHECK

Pressurize the system with air or inert gas such as nitrogen, making sure not to exceed specified pressure limitation.
In a typical application, the sample gas consists of two components, for example: hydrogen in nitrogen. In this example, hydrogen is designated the “measured component” and nitrogen constitutes the “background gas.”

2-8 SUPPRESSED-ZERO RANGES

With any zero-suppressed range, the zero-concentration point for the measured component lies off-scale, below the lower range-limit. A typical example is 80% to 100% hydrogen in nitrogen. Here the appro­priate upscale calibration gas would be pure hydrogen. The downscale gas would have a composition appropriate to establishing a cali­bration point slightly above the lower range-limit e.g., 81% hydrogen in nitrogen.
Liberally cover all fittings, seals and other possible sources of leakage with leak test liq­uid such as SNOOP (PN 837801).
Bubbling or foaming indicates leakage, which MUST be corrected before introduction of flammable-sample and/or application of elec­trical power.
Rosemount Analytical Inc. A Division of Emerson Process Management Installation 2-3
Page 22
Instruction Manual
748451-B March 2002
Model CAT7

2-10 GAS CONNECTIONS

The analyzer and gas selector panel modules must be interconnected according to the flow diagram specified in the Data Sheet at the front of this manual. Gas fittings on both modules are tagged as to use. Fittings are 1/4-inch NPT for 1/4-inch (6.3 mm) tubing. For interconnection, use 1/4-inch (6.3 mm)
copper or stainless steel tubing, depending on whether the sample stream is corrosive.
Connect sample/calibration gas lines to fit­tings tagged “INLET” on bottom of analyzer. Connect appropriate vent line to fitting labeled “OUTLET.”
Follow similar procedure for reference gas, if any.
GAS INLET
(CH1)
OUTLET
ZERO GAS
INLET1
GAS
OUTLET
(CH1)
SAMPLE
GAS INLET
SPAN GAS
1 INLET
GAS INLET
(CH2)
SPARE SPARE
SPAN GAS
2 INLET
GAS
OUTLET
(CH2)
Figure 2-3. Gas Connections – Bottom View of Analyzer
2-4 Installation Rosemount Analytical Inc. A Division of Emerson Process Management
Page 23
Model CAT7
Instruction Manual
748451-B
March 2002
Sample In
Zero Standard Gas
Span Standard Gas
Needle Valves
113357 or 113920
Gas Selector Panel
Flowmeter
Model CAT7
Thermal Conductivity Analyzer
Reference Gas Sealed-In
Thermal Conductivity Cell
To Vent
Figure 2-4. Connection of Analyzer Using Sealed-In Reference Gas to Associated Gas
Rosemount Analytical Inc. A Division of Emerson Process Management Installation 2-5
Page 24
Instruction Manual
748451-B March 2002
A. DIFFERENT REFERENCE GAS AND CALIBRATION GAS
Model CAT7
Reference Gas
Sample Gas
Downscale Calibration Gas
Upscale Calibration Gas
Needle Valves
117195 or 118210
Gas Selector Panel
Reference
Gas
Flowmeter
Sample
Gas
Flowmeter
B. REFERENCE GAS ALSO USED AS CALIBRATION GAS
Downscale Cali­bration Gas Used as Reference
Needle Valves
117195 or 118210
Gas Selector Panel
Model CAT7
Thermal Conductivity Ana-
Thermal Conductivity Cell
Thermal Conductivity Ana-
lyzer
Model CAT7
lyzer
To
Sample
Vent
To
Reference
Vent
Sample Gas
Downscale Calibration Gas
Upscale Calibration Gas
Reference
Gas
Flowmeter
Sample
Gas
Flowmeter
Thermal Conductivity Cell
To
Sample
Vent
To
Reference
Vent
Figure 2-5. Connection of Analyzer Using Flowing Reference Gas to Associated Gas Selector Panel
2-6 Installation Rosemount Analytical Inc. A Division of Emerson Process Management
Page 25
Model CAT7
Instruction Manual
748451-B
March 2002
LINE
NEUT
GND
1234
Figure 2-6. Intrinsic Safety Box
ALARM #1 NO
ALARM #1 COM
ALARM #1 NC
ALARM #2 NO
ALARM #2 COM
+VOLT OUT
-VOLT OUT
+CUR OUT
-CUR OUT
1234 121234
ALARM #2 NC
Figure 2-7. Intrinsic Safety Box Interconnect
Rosemount Analytical Inc. A Division of Emerson Process Management Installation 2-7
Page 26
Instruction Manual
748451-B March 2002
CAUTION
Do not plug or restrict vents.
2-11 RECORDER OUTPUT SELECTION AND CA-
BLE CONNECTIONS
If a recorder, controller, or other output device is used, connect it to the analyzer (refer to Figure 2-6 and Figure 2-7) via a number 22 or number 24 AWG two-conductor shielded ca­ble. Route the cable through conduit to the analyzer, and into the case through the ap­propriate opening shown in Figure 1-1.
NOTE
Route recorder cable through a separate conduit, not with power cable.
Model CAT7
b. Linearized Voltage Output (Optional)
1. Verify that Voltage-Output Linearizer Board is properly inserted in J102 on the Master Board.
2. On the Master Board (Figure 2-8):
a. Verify that TB2-1 is jumpered to
TB2-4, and TB2-2 is jumped to TB2-5.
b. Set S1 for desired voltage: 5V,
1V, .1 V, or .01 V.
3. In the Intrinsic Safety Box, connect the recorder cable to the terminals labeled +VOLT OUT and –VOLT OUT (Figure 2-7).
NOTE
Output selection and cable connections for voltage-actuated and current-actuated de­vices are explained in Sections 2-11a through 2-12b.
a. Standard (Non-linearized) Voltage Out-
put
1. On the Master Board (Figure 2-8):
a. Verify that TB2-1 is jumpered to
TB2-2.
b. Set S1 for desired voltage: 5V,
1V, .1V, or .01V.
2. In the Intrinsic Safety Box, connect the recorder cable to the terminals la­beled +VOLT OUT and –VOLT OUT (Figure 2-7).
NOTE
Take the usual precautions to avoid AC pickup. DO NOT GROUND EITHER LEAD.
3. Connect the cable to input terminals of the recorder; ensure that polarity is correct.
Take the usual precautions to avoid AC pickup. DO NOT GROUND EITHER LEAD.
4. Connect the cable to the recorder input terminals; ensure that polarity is correct.

c. Isolated 4 to 20 mA Current Output

(Optional)
5. Verify that the Isolated 4 to 20 mA Cur­rent Output Board is properly in­serted in J103 on the Master Board.
6. On the Master Board (Figure 2-8):
c. Verify that TB2-1 is jumpered to
TB2-2 and TB2-2 is jumpered to TB2-6.
7. In the Intrinsic Safety Box, connect the
recorder cable to the terminals la­beled +CUR OUT and -CUR OUT (Figure 2-7).
8. Connect the cable to the recorder input
terminals; ensure that polarity is cor­rect. Total resistance of the output device and associated cable must not exceed 1500 ohms.
4. Ground shield on one end only.
2-8 Installation Rosemount Analytical Inc. A Division of Emerson Process Management
Page 27
Model CAT7
11
230
A
A
A
Instruction Manual
748451-B
March 2002
C
POWER
HEATER POWER
FAN
- + - +
CUR
VOLT
OUT
OUT
J4
1
1
5V
R4 R9 R7 R22 R26 R6 R8
TB4
R15
C2
F13
1
R12
R10
C4
R14
R19R21 R18
J2
J7
J6
1
V
S2
R2
AR1
R11
R17R20
S1
R24
R16
6 5 4 3 2 1
BOARD
OPTIONS
RESISTOR SELECT
R27
RANGE
R1 R5 C3
C1
SPAN R3 R2
METER
C5
C6
R23
R3
C7
U1
TB2
TP1 TP2
1 2 3 4
TB5
1 2 3 4 5 6 7 8
TB3
11
J101 J100
TP3 TP4 TP5
1
J103 J102
1
TB1
6 5 4 3 2 1
DETECTOR
R100
S1
Used to select voltage output range: 5V, 1V, 0.1V, or .01V AR1 gain adjust. Permits adjustment of AR1 gain from
R4
X1 to X100, to establish the sensitivity desired for Range 1. This is the highest sensitivity range. AR1 zero adjust. Used to eliminate voltage offset within AR1 and Bridge, and provide zero suppression. Setting determines attenuation factor applicable to AR2 output, Range 3. Setting determines attenuation factor applicable to AR2 output Range 2. Permits adjusting meter fullscale to agree with re­corder fullscale Used to eliminate voltage offset within AR2.
Sets the stable ±10 V source.
.01V .1V 1V 5V
DETAIL OF S1
R6, R8, R26
R9
R7
R22
R15 R16
ADJUSTMENTS
Figure 2-8. Master Board
Rosemount Analytical Inc. A Division of Emerson Process Management Installation 2-9
Page 28
Instruction Manual
748451-B March 2002
2-12 ALARMS (OPTIONAL)
The analyzer is factory configured per cus­tomer order and requires no user adjust­ments.
Pins for AC power (1, 2, and 3), alarm setpoint control (8, 10, 18, and 19), and signal from ana­lyzer circuitry (7 and 9) are wired at the factory. Connections of the remaining pins depend on indi­vidual application requirements.
Deadband Potentiometer ALARM 1
LED Indicator ALARM 1
Deadband Potentiometer ALARM 2
Model CAT7
deadband
SET
POINT
1
deadband
If the instrument has this option, the analyzer will have setpoint adjustment potentiometers: Alarm 1 (the Low Alarm) and Alarm 2 (the High Alarm) (Figure 1-1) and Deadband on the alarm module (see Figure 2-9).
NOTE
Do not adjust the setpoints on the alarm module (Figure 2-9). Use the adjustments from the exterior of the analyzer (Figure 1-1).
The power and input wiring (18 or 20 AWG) is routed into the intrinsic safety box. (see Figure 2-6).
The alarm relay is in energized mode when power is applied. Wire output to the appropri­ate contact (see Figure 2-7). The Form C re­lay contacts are rated at 5 A, 120 VDC and 1 A, 120 VAC, resistive loads.
A lit LED next to the Deadband pots indicates the alarm is activated.
LED Indicator ALARM 2
SET
POINT
2
Front View Of Alarm Module
span
Figure 2-9. Alarm Adjustments
The following is recommended:
1. A fuse should be inserted into the line between the customer-supplied power supply and the alarm module termi­nals in the intrinsic safety box..
2. If the alarm contacts are connected to any device that produces radio fre­quency interference (RFI), the device should be arc-suppressed (P/N 858728 Arc Suppressor is recom­mended).
NOTE
The Zero and Span for setting the input voltage from the analyzer has been set at
3. The analyzer and any RFI-producing device should operate on different AC power sources to avoid RFI.
the factory. To check it, see Section 5-2d.
2-10 Installation Rosemount Analytical Inc. A Division of Emerson Process Management
Page 29
Model CAT7
Instruction Manual
748451-B
March 2002
Removal of AC power from the analyzer, as in a power failure, de-energizes both alarm module relays, setting an alarm condition. Switching characteristics of the ALARM 1 and ALARM 2 relays are as follows:

Alarm 1 Relay

The ALARM 1 relay coil is de-energized when the meter needle moves downscale through the value that corresponds to setpoint minus deadband. This relay coil is energized when the needle moves up­scale through the value that corresponds to setpoint plus deadband (see Figure 2-10).

Alarm 2 Relay

The ALARM 2 relay coil is de-energized when the meter needle moves upscale
through the value that corresponds to the setpoint plus deadband. This relay coil is energized when the needle moves down­scale through the value that corresponds to setpoint minus deadband (see Figure 2-10).

Fail-safe Applications

By making the appropriate connections to the double-throw relay contacts, the op­erator can obtain either 1) a contact clo­sure or contact opening for an energized relay, or 2) a contact closure or contact opening for a de-energized relay. For fail-safe applications, the operator must understand which circuit conditions are required to achieve relay de-energization in the event of power failure
A. Typical ALARM 1 Setting (LOW)
DEADBAND SET FOR
20% OF FULLSCALE
B. Typical ALARM 2 Setting (HIGH)
DEADBAND SET FOR
10% OF FULLSCALE
INPUT SIGNAL
Percent of Fullscale
INPUT SIGNAL
Percent of Fullscale
When input signal moves upscale through this point, the
40
30
20
55
50
45
coil of ALARM 1 relay (K1) is energized, providing continuity between the common and normally-closed contacts of the relay.
ALARM 1 Setpoint
When input signal moves downscale through this point, the coil of ALARM 1 relay (K1) is de-energized, providing continuity between the common and normally-open contacts of the relay.
When input signal moves upscale through this point, the coil of ALARM 2 relay (K2) is de-energized, providing continuity between the common and normally-open contacts of the relay.
ALARM 2 Setpoint
When input signal moves upscale through this point, the coil of ALARM 2 relay (K2) is energized, providing continuity between the common and normally-closed contacts of the relay.
Figure 2-10. Typical Alarm Settings
Rosemount Analytical Inc. A Division of Emerson Process Management Installation 2-11
Page 30
Instruction Manual
748451-B March 2002
Model CAT7
2-13 LINEARIZED VOLTAGE, TWO RANGES (OP-
TIONAL)
1. Verify that the Voltage Output Linearizer Board is properly inserted in both J102 and J103.
2. On the Master Board (Figure 2-8):
a. Verify that TB2-1 is jumpered to
TB2-4, and TB2-4 is jumped to TB2-6.
b. Select desired range on S1.
3. In the intrinsic safety box (Figure 2-7) con­nect recorder cable to the terminals la­beled +VOLT OUT and –VOLT OUT.
NOTE
Take the usual precautions to avoid AC pickup. DO NOT GROUND EITHER LEAD.
4. Connect the cable to the recorder input terminals; ensure that polarity is correct.
2-14 LINEARIZED VOLTAGE AND ISOLATED 4
TO 20 MA CURRENT OUTPUT (OPTIONAL)
1. Verify that the Voltage Output Linearizer Board is properly inserted in J102 on the Master Board (Figure 2-8).
2. Verify that the Isolated 4 to 20 mA Current Output Board is properly inserted in J103 on the Master Board (Figure 2-8).
3. On the Master Board (Figure 2-8):
a. Verify that TB2-1 is jumped to TB2-4,
TB2-2 is jumped to TB2-5, and TB2-5 is jumped to TB2-6.
b. Set S1 for the desired voltage: 5 V, 1
V, .1 V, or .01 V.
4. In the Intrinsic Safety Box (Figure 2-7) connect the recorder cable to the termi­nals labeled +VOLT OUT and –VOLT OUT.
NOTE
Take the usual precautions to avoid AC pickup. DO NOT GROUND EITHER LEAD.
5. In the Intrinsic Safety Box (Figure 2-7) connect the recorder cable to the termi­nals labeled +CUR OUT and –CUR OUT.
6. Connect the cable to the recorder CUR­RENT input terminals; ensure that polarity is correct.
2-12 Installation Rosemount Analytical Inc. A Division of Emerson Process Management
Page 31
Model CAT7
Instruction Manual
748451-B
March 2002

2-15 ELECTRICAL POWER CONNECTIONS

DANGER
ELECTRICAL SHOCK HAZARD
For safety and proper performance, this instrument must be connected to a prop­erly grounded three-wire source of power.
NOTE
Before supplying electrical power to ana­lyzer, disconnect the red lead from the bridge to TB1-1 or TB1-2 (depending on bridge polarity). This action disconnects power to the bridge (see drawing 661562). To safeguard against filament damage, this lead should remain disconnected until proper gas flow has been established.
SENSOR J18
400A 880 951E
R10 R11 R7 R8
C2
CR1
C
B
Q2
R17 R16 R12 CR
R4
R3
C1
E
+
Q1
K
A
TEMP CONTROL BD
The analyzer is supplied, as ordered, for op­eration on 107 to 127 or 214 to 254 VAC, 50/60 Hz, 250 watts. Verify that the power source conforms to the requirements of the individual instrument as noted on the name rating plate. Ensure that switches S2 on the Master Board (see Figure 2-8) and S3 on the case heater temperature control board (see Figure 2-11) are set to required voltage.
Electrical power is supplied to the analyzer via a customer-supplied three-conductor cable, type SJT, minimum wire size 18 AWG. Route the power cable through conduit and into the appropriate opening in the instrument case (see drawing 661318 and Figure 1-1). In the Intrinsic Safety Box, connect power cable leads to terminals 4 (LINE), 3 (NEUT), and 2 (GND). See Figure 2-7.
Set switch window for voltage required
S3
POWER SUPPLY
1
R2R1
G
R6
C3
AR1
R13
R9 R5
CR
1
E
B
Q3
C
TEST
J19
J11
R15
POWER LINE J5
C4
3 2 1
R14
1
U1
1 2 1 2 3
T.I.F. HEATER
U2
J17
2
3
1
S3
230
115
115
Figure 2-11. Case Heater Temperature Control Board
Rosemount Analytical Inc. A Division of Emerson Process Management Installation 2-13
Page 32
Instruction Manual
748451-B March 2002
Model CAT7
2-14 Installation Rosemount Analytical Inc. A Division of Emerson Process Management
Page 33
Model CAT7
Instruction Manual
748451-B
March 2002
SECTION 3

OPERATION

3-1 ANALYZER CONTROLS AND ADJUST-
MENTS
Normal operation of the analyzer involves adjustments of only the ZERO, SPAN, and RANGE Switch, if provided. See Figure 1-1.
The various internal adjustments are factory set and normally do not require readjustment except after replacement of a circuit board or major component. Refer to Section 1.

3-2 GAS SELECTOR PANEL CONTROLS

The controls provided on the optional gas se­lector panel will depend on the application. For use of sealed-in reference gas, refer to Figure 2-1 and Figure 2-4. For flowing refer­ence gas, refer to Figure 2-2 and Figure 2-5.

3-3 STARTUP PROCEDURE

If explosive gases are introduced into this analyzer, the sample containment system must be carefully leak-checked upon in­stallation and before initial startup, during routine maintenance and any time the in­tegrity of the sample containment system is broken, to ensure the system is in leak­proof condition. Leak-check instructions are provided in Section 2-9.
Internal leaks resulting from failure to ob­serve these precautions could result in an explosion causing death, personal injury or property damage.
NOTE:
Never apply power to analyzer without gas flowing. The filaments in the cell tend to deteriorate faster than normal.
Board (depending on detector bridge po­larity). This action disconnects power to the bridge. To safeguard against filament damage, this lead should remain discon­nected until proper gas flow has been es­tablished. Refer to drawing 661562.
After performing a leak check, start up the analyzer as follows:
1. Set regulators on the gas cylinders for a supply pressure of 10 to 50 psig f(69 to 345 kPa).
2. Provide a sample flow of 50 to 350 cc/minute through the analyzer. A rate of 250 cc/minute is recommended unless faster flow is desired to reduce sample transport time.
3. If the thermal conductivity cell uses flow­ing reference gas, provide a reference flow of 5 to 50 cc/minute.
4. Apply power to the analyzer. The fila­ments will now begin to heat. Verify proper flow of sample gas and flowing reference gas, if used.
5. Allow the analyzer to warm-up for a mini­mum of six hours to ensure temperature equilibrium.
NOTE:
If ambient temperature is below 60°F (15.6°C), or if the temperature will go below 60°F (15.6°C) within the next six hours, al­low a minimum of 12 hours for the instru­ment to stabilize.
Startup is now complete; the analyzer is ready for calibration per Section 3-4.
NOTE:
Before supplying electrical power to the analyzer, disconnect the red lead from the bridge to TB1-1 or TB1-2 on the Master
Rosemount Analytical Inc. A Division of Emerson Process Management Operation 3-1
Page 34
Instruction Manual
748451-B March 2002
Model CAT7

3-4 CALIBRATION

1. Set downscale calibration point as follows:
a. On the analyzer, set SPAN control to
mid-scale (five turns). If the analyzer has a RANGE Switch, set it at Range 1, the highest sensitivity range.
b. Admit downscale calibration gas to the
analyzer at the same flow rate as is used for sample gas. Wait for the reading on the meter or recorder to stabilize.
c. On the analyzer, adjust the ZERO
control so that the reading on the me­ter or recorder is appropriate to the downscale calibration gas.
d. If a proper reading is unobtainable by
adjustment of the ZERO control, refer to Section 5-2b.
2. Set upscale calibration point as follows:
a. If the analyzer has a RANGE switch,
set it for the desired range.
b. Admit upscale calibration gas to the
analyzer at the same flow rate as is used for sample gas. Wait for the reading on the meter or recorder to stabilize.
c. Adjust the SPAN control so that the
reading on the meter or recorder is appropriate to the upscale calibration gas.
If a proper reading is unobtainable by adjust­ment of the SPAN control, refer to Section 1, Service and Maintenance.
After the downscale and upscale calibration points have been established, the analyzer is ready for routine operation.
If the analyzer has Suppressed-Zero Ranges and does not calibrate properly, refer to Sec­tion 5-3 for Suppressed Zero Adjustment.
3-2 Operation Rosemount Analytical Inc. A Division of Emerson Process Management
Page 35
Model CAT7
Instruction Manual
748451-B
March 2002
SECTION 4

THEORY

4-1 THERMAL CONDUCTIVITY CELL AND AS-
SOCIATED BRIDGE ADJUSTMENTS
Within the thermal conductivity cell are four resistive filaments suspended in individual cavities of a metal block (Figure 4-1A) and connected electrically as legs of a Wheat­stone bridge (Figure 4-1B). Although physi­cally the cell block is one piece, functionally it may be considered to have two sides as shown:

Sample Side

Two filaments that constitute opposite legs of the bridge are positioned in a passage that receives a continuous flow of the sample gas.

Reference Side

The remaining two filaments are positioned in a passage filled with the reference gas. De­pending on the application, the reference gas may flow continuously through the passage, or it may be sealed within the cell.
The Bridge Voltage Power Supply is con­nected, via a 20-ohm dropping resistor, to the bridge (See Section 4-5). The power supply output is adjusted to provide an appropriate voltage across bridge terminals 1(+) and 2(-). An electric current flows through the filaments, heating them and thus increasing their electri­cal resistance. The heat-dissipation rate for each filament depends on the thermal con­ductivity of the surrounding gas. Initially, with downscale calibration gas flowing through the sample and reference sides of the flow-through configuration, R26 is set for zero bridge-output signal. During subsequent analysis of the sample stream, any change in the relative proportions of the components passing through the sample side changes the thermal conductivity of the gas mixture, caus-
ing a temperature differential between sample and reference filaments. The resultant change in filament resistance unbalances the bridge.
The bridge-imbalance signal is routed to the Master Board, where it is processed to drive the meter and recording device, if used (see Section 4-2).
Periodically, downscale calibration gas is passed through the cell, and the ZERO Pot is adjusted for an appropriate reading on the meter or recorder.

4-2 MASTER BOARD

The Master Board, Figure 2-8, provides two stages of amplification utilizing inte­grated-circuit amplifiers AR1 and AR2.

a. Functions Associated with AR1

AR1: Gain Adjust Potentiometer R4.
This screwdriver-adjustable, factory-set trimming potentiometer determines feed­back resistance for AR1 and thus permits adjustment of AR1 gain from X1 to X100. This adjustment sets the sensitivity for Range 1, i.e., the highest-sensitivity range.
Range Provisions: In the basic sin­gle-range Model CAT7, a jumper is con­nected from TB3-1 to TB3-4, thus routing the unattenuated output from AR1 directly to the non-inverting input of AR2. During factory assembly of a dual-range or tri­ple-range instrument, the jumper is omit­ted and a RANGE Switch is connected as shown below. The output from AR1 is then routed to AR2 through a network that provides adjustable attenuation for ranges 2 and 3.
Rosemount Analytical Inc. A Division of Emerson Process Management Theory 4-1
Page 36
Instruction Manual
748451-B March 2002
RANGE AR1 OUTPUT ATTENUATION RANGE SWITCH POSITION TB3 POSITION
1 X1, fixed 1 1 2 adjustable by R7 2 2 3 adjustable by R9 3 3
Model CAT7
Table 4-1. Range Switch Connections

b. Coarse zero and zero-suppression

Pots R26, R6 or R8, depending upon range number, provide the zero correction at the non-inverting input of AR1.

c. Functions Associated with AR2

AR2 Zero Adjustment Potentiometer R1: This screwdriver-adjustable, factory-set trimming potentiometer is used to elimi­nate voltage offset within AR2. When the input signal is zero, R15 is adjusted so that the output signal also is zero.
SPAN Control: This potentiometer pro­vides continuously variable adjustment of closed-loop gain for AR2, to permit estab­lishing an upscale calibration point on the meter scale or recorder chart. With up­scale calibration gas flowing through the analyzer, the SPAN Control is adjusted for the appropriate reading.

d. Meter

The meter is connected from TB3-7 to TB3-8. Potentiometer R22 permits ad­justing meter sensitivity so that meter full­scale agrees with recorder fullscale.

e. Output Selection Switch S1

4-3 VOLTAGE OUTPUT LINEARIZER BOARD

OPTION
The output signal from the Master Board is a function of the degree of imbalance in the bridge circuit, but is not linear with respect to the concentration of the measured compo­nent. Providing that the non-linearity of the calibration curve does not exceed 20% at midscale (for 50 % H put Linearizer Board may be used to equip a given operating range for linear readout of concentration on the meter and on a potenti­ometric recorder.
Straightening of the concentration-vs.-output curve is accomplished by sequential adjust­ment of eight odd-numbered trimming potenti­ometers designated R19 through R33. Each pot controls the gain of an associated opera­tional amplifier.
During factory checkout of a linearizer circuit board, potentiometers R19 through R33 are initially set at midrange. With zero input sig­nal applied to the linearizer circuit, ZERO po­tentiometer R35 is adjusted for zero output. Then an appropriate low-level signal is ap­plied to the input, and R19 is adjusted for full­scale output. The procedure is repeated as many times as required to obtain properly linearized output.
max.), the Voltage Out-
2
The desired output is obtained by appro­priate selection of switch contacts: 5V, 1V, .1V, or .01V.
4-2 Theory Rosemount Analytical Inc. A Division of Emerson Process Management
Page 37
Model CAT7
     
      
A. Sectional View of Thermal Conductivity Cell
Instruction Manual
748451-B
March 2002
Thermal Conductivity Cell Block
Sample Gas Out
Reference Filaments
Reference * Gas In
Sample Gas In
* Reference Ports Capped if Cell Uses Sealed-In, Non-Flowing Reference Gas.
B. Functional Diagram of Bridge Circuit
3
0.5
Front Panel Zero Potentiometer
4
O-Ring Seals
Sample Filaments
NOTE: Cell Block Sectioned Through Sample Side. Section Through Reference side is Similar.
6
0.5
7
Reference Flow
1
Rosemount Analytical Inc. A Division of Emerson Process Management Theory 4-3
0.5 20
5
Resistor values are in ohms.
Bridge Power
Supply (+)
Figure 4-1. Thermal Conductivity Cell
Sample Flow
2
Bridge Power
Supply (-)
0.5
8
Page 38
Instruction Manual
748451-B March 2002
Model CAT7
4-4 ISOLATED 4 TO 20 MA CURRENT OUTPUT
BOARD OPTION
This option provides isolated current output for applications which require 4 to 20 mA into a maximum load of 1500 ohms. This output is NOT linearized. A description of the board and the functions of its main components fol­lows.
The purpose of the Isolated Current-Output Board is to convert an input signal of 0 to -5 V to an isolated output signal of 4 to 20 mA. With a zero voltage at the input, R6 is ad­justed so that the output at AR1 is 1 V. The gain of AR1 is .8 so that an input of 0 to -5 V is converted to 1 to 5 V. This voltage is fed to a variable output level-inverter consisting of AR2, Q1, Q2, and T1. T1 has two identical output windings, each with a rectified DC out­put. One is used to provide feedback to the inverter input of AR2. The other is used as an isolated output to drive AR3 and Q3 with a 1 to 5 V signal across R16. Trim-pot R17 is adjusted to provide a span of 4 to 20 mA. This current is presented to the collector of Q3 and is capable of driving loads of up to 1500 ohms.

4-5 BRIDGE POWER SUPPLY

The regulated, adjustable voltage required for the thermal conductivity bridge (Section 4-1) is provided by the Bridge Power Supply. It consists of a power transformer, fullwave rec­tifiers CR1 and CR2, voltage regulator Q1, and an RC filter network. Bridge voltage, as measured between bridge terminals 1(+) and 2(-), is adjustable from 5 to 13 VDC via R2. Proper setting depends primarily on filament material: 3 to 4 VDC for tungsten; 5 to 12 VDC for Hitempco. Bridge voltage is fac­tory-set as required for the application (see Data Sheet) and normally does not require readjustment unless the power supply is re­placed.
619710, power transformer T1 has three sec­ondary that are used as follows:
38 VAC center-tapped secondary
Powers both 15 volt supplies through diode bridge CR1 and filter capacitors C1 and C4.
The adjustable positive regulator, VR1, is set by voltage divider R1, R2 and R3 and its out­put is applied to pin A of the circuit board and to test point TP1. Potentiometer R2 should be adjusted to +15.5 VDC ±50 mVDC.
The negative DC, regulated by VR2 is applied to pin D of the circuit board.
The center tap is the common reference for both the +15 and -15 volt supplies and is ap­plied to pin R of the circuit board and to test point TP2.
Both outputs are used for individual amplifiers on the various circuit boards.
90-volt center-tapped secondary
Drives a rectifier circuit on the optional Cur­rent Output Board. The transformer winding and the associated circuit constitute a floating power supply for the emitter-follower stage.
9.5 VAC secondary
Drives a +5 VDC supply not used in this in­strument.

4-7 DETECTOR BLOCKS

There are two types of detector configura­tions; flowing reference and sealed nitrogen reference. The sealed reference with nitrogen can be recharged by flowing nitrogen through the reference and closing the plugs. Three filament types are available: tungsten, Hitempco, and gold-sheathed tungsten.
4-6 ±15 VOLT POWER SUPPLY
The ±15 Volt Power Supply plugged into J101 of the Master Board, provides power for the various circuits. As shown in schematic
4-4 Theory Rosemount Analytical Inc. A Division of Emerson Process Management
4-8 CASE TEMPERATURE CONTROLLER AS-
SEMBLY
The case Temperature Controller Assembly maintains an approximate 117°F (47°C) tem­perature within the instrument.
Page 39
Model CAT7
Instruction Manual
748451-B
March 2002
Changes in case temperature affect the re­sistance of the sensor connected to J18. This in turn changes the bias of amplifier AR1, which controls the input to the case heater via switch U2. The heater receives power through pins 3, 4 and/or 5, depending on the voltage selected at switch S3. A thermal fuse at J5 prevents the case from overheating.
4-9 DUAL ALARMS OPTION
Instruments with optional Dual Alarms have two pots on the front door which are used to select setpoints. The scales on the name­plate designate setpoints from 0 to 100%.
The module plugs into a socket, which is part of a terminal block mounted onto the chassis of the instrument. A marker on the alarm module indicates the function of each socket pin.
This unit is factory configured and requires no user adjustment. Pins for AC power (1, 2, and
3), alarm setpoint control (8, 10, 18, and 19),
and signal from analyzer circuitry (7 and 9) are wired at the factory.
Connections of the remaining pins depend upon the application. The relays are rated at
1.0 A, 120 VAC and 5.0 A, 120 VDC, form C,
resistive loads.
Rosemount Analytical Inc. A Division of Emerson Process Management Theory 4-5
Page 40
Instruction Manual
748451-B March 2002
Model CAT7
4-6 Theory Rosemount Analytical Inc. A Division of Emerson Process Management
Page 41
Model CAT7
Instruction Manual
748451-B
March 2002
SECTION 5

SERVICE AND MAINTENANCE

DANGER
POSSIBLE EXPLOSION HAZARD
If explosive gases are introduced into this analyzer, the sample containment system must be carefully leak-checked upon in­stallation and before initial startup, during routine maintenance and any time the in­tegrity of the sample containment system is broken, to ensure the system is in leak­proof condition. Leak-check instructions are provided in Section 2-9.
Internal leaks resulting from failure to ob­serve these precautions could result in an explosion causing death, personal injury or property damage.
In troubleshooting, the basic approach is to isolate the analyzer from the sample and the sample-handling system.
First admit downscale and upscale standard gases to analyzer and note response:
1. If performance is normal with standard gases, although not with sample gas, the sample and the sample-handling system are suspect. Check these areas.
2. If analyzer gives off-scale or erratic read­ings with standard gases, as well as with sample gas, the problem might be the filaments or the electronic circuitry. To isolate the malfunction, substitute fixed precision resistors of appropriate value for the filaments. Hitempco filaments have a cold resistance of 72 ohms. Tungsten filaments have a cold resistance of 18 ohms. Filament connections are shown in
schematic 654616. With appropriate re­sistors substituted for the filaments, at­tempt to balance the bridge as follows:
a. If bridge balance is obtained with the
fixed resistors, the filaments are probably defective and should be re­placed.
b. If bridge balance is unobtainable with
the fixed resistors, the problem might be the electronic circuitry. Substitute each circuit board, in turn, until proper operation is obtained.

5-1 THERMAL CONDUCTIVITY CELL

The thermal conductivity cell and associated elements of the bridge are mounted inside the analyzer case, within a thermally-insulated compartment.
Depending on the bridge current level, the filaments gradually become mismatched, and eventually burn out. Normal progression of symptoms is baseline drift. Sealed reference cells must be serviced by the factory.
If the cell uses flowing reference gas, the fila­ments may be replaced by the user. Refer to Figure 4-1 and the parts list in Section 1.
Filaments are sold as matched sets. If one must be replaced, its mate also must be re­placed. Electrically, the filaments are mated across the diagonals of the cell. Refer to Figure 4-1B. The filament across points 3 and 1 corresponds to the filament across 8 and 1, and the filament across points 6 and 2 corre­sponds to the filament across 5 and 2.
Rosemount Analytical Inc. A Division of Emerson Process Management Service and Maintenance 5-1
Page 42
Instruction Manual
748451-B March 2002
Model CAT7

5-2 ELECTRONIC CIRCUITRY

a. Amplifier Zero Adjustments

The zero adjustments on the Master Board are factory set and normally do not require readjustment except after re­placement of a major component. If re­adjustment becomes necessary, use following procedure:
AR2 Zero Adjustment (Refer to Figure 2-8):
1. Open the input to AR2. In a sin­gle-range instrument, this is done by disconnecting the jumper from TB3-1 to TB3-4.
2. Ground the input of AR2 by connect­ing a jumper from TB3-4 to TP1 (GND).
3. Adjust R15 for 0 VDC output signal at TB4-2.
4. Restore connections to normal.
b. Bridge Balance and Range Sensitivity
Adjustments
Perform start-up procedure in Section 3-3, then proceed as follows:
Sensitivity Adjustment(s) are:
1. Admit upscale calibration gas to the analyzer at the same flow rate as is used for the sample gas. Wait for reading on meter or recorder to stabi­lize.
2. On the Master Board, set AR2 Gain Adjustment R4 so that reading on the recorder, if used, or on the meter is appropriate to the upscale calibration gas. Refer to data sheet or calibra­tion curve. Range 1 sensitivity is now properly adjusted.
3. If analyzer has more than one range, set the RANGE Switch for Range 2. This is the reduced sensitivity range. Then, on the Master Board, set Range 2 Attenuation Adjustment R7 so that the reading on the recorder, if used, or on the meter is appropriate to the upscale calibration gas.
4. If the analyzer has three ranges, set the RANGE Switch for Range 3. This is the least sensitive range. Then, on the Master Board, set Range 3 At­tenuation Adjustment R9 so that the reading on the recorder, if used, or on the meter is appropriate to the up­scale calibration gas.
1. On the analyzer, set the ZERO and SPAN controls to their midpoints (five turns). If the analyzer has a RANGE Switch, set it to Range 1, the high­est-sensitivity range.
2. Admit downscale calibration gas to the analyzer at the same flow rate as is used for the sample gas. Wait for the reading on the meter or recorder to stabilize.
3. Refer to Figure 2-8 and set the Bal­ance Adjustment on the Master Board, (range 1 or single range R8, range 2 R6, range 3 R26) so that the reading on the meter or recorder is zero or an offset value. Refer to Data Sheet.
5-2 Service and Maintenance Rosemount Analytical Inc. A Division of Emerson Process Management
5. If previous readings were obtained on a recorder, set the Meter 100% Ad­justment R22 so that the meter full­scale matches the recorder fullscale. If the analyzer has more than one range, this adjustment should be made on Range 1.
Bridge Voltage Adjustment
Bridge voltage is factory set as required for the application (see Data Sheet) and normally does not require readjustment unless the bridge power supply is re­placed. Bridge voltage is measured be­tween terminals 1(-) and 2(+), and is adjustable via R2. See schematic
613561.
Page 43
Model CAT7
Instruction Manual
748451-B
March 2002

c. Case Temperature Controller

Refer to drawing 661540. Malfunction in this option can occur in three areas:
Heater
Check continuity with ohmmeter. Verify that resistance is approximately 113 ohms at 25°C.
Temperature Sensor
This is an RTD and should have approxi­mately 550 ohms at 25°C. Check for continuity with ohmmeter.
Thermal Fuse
The fuse opens at temperatures above 72°C. Check continuity with ohmmeter.
d. Dual Alarm Module (Optional)
This module is not user-serviceable. If problems occur, contact Rosemount Analytical service.
The module has Zero and Span potenti­ometers that set the 0 to 5 V input. To check these, adjust the analyzer for zero gas, set the Low Alarm set point to 0 %, and turn the Deadband counterclockwise. Adjust the Zero pot to trigger the alarm. Do the same for High Alarm (ALARM 2 on the front panel). The alarm span should agree with the analyzer meter span. Re­adjust the deadbands to the desired level. (See Figure 2-9 and Figure 2-10)
NOTE
For instruments with more than one range, RANGE 1 is the most sensitive range; it must be set for the highest gain. This range should be used for the smallest span. Always start procedure with RANGE 1 (i.e., RANGE 1 ... 95 to 100%, RANGE 2 ... 90 to 100%, RANGE 3 ... 60 to 80%).
1. Set the ZERO and SPAN controls to their midpoints (five turns).
2. If the instrument has a Range Switch, set it to RANGE 1.
3. On the Master Board, connect a digital voltmeter between TB3-1 and TP1 (polar­ity does not matter).
4. Flow downscale calibration gas through the sample inlet of the analyzer. Adjust R8 until the reading on the voltmeter is zero. The analyzer meter should also read zero.
5. Flow upscale calibration gas through the sample inlet of the instrument. Adjust R4 until the meter reads 100 % (fullscale).
6. Repeat steps 4 and 5 above until no ad­justment is required.
If the analyzer has more than one range, re­peat steps 2 through 6 with the following al­terations:
Range 2

5-3 SUPPRESSED ZERO ADJUSTMENT

If the instrument has suppressed-zero ranges and does not calibrate properly, adjust the potentiometers located on the Master Board (see Figure 2-8). Follow the startup proce­dure in Section 3-3. After the analyzer has stabilized, use appropriate calibration gases to make the following adjustments. Refer to Section 2-7 for information on selecting ap­propriate gases.
Rosemount Analytical Inc. A Division of Emerson Process Management Service and Maintenance 5-3
Set the Range Switch to RANGE 2. In step 4, adjust R6, and in step 5, adjust R7.
Range 3
Set the Range Switch to RANGE 3. In step 4, adjust R26, and in step 5, adjust R9.
Page 44
Instruction Manual
748451-B March 2002
Model CAT7
5-4 Service and Maintenance Rosemount Analytical Inc. A Division of Emerson Process Management
Page 45
Instruction Manual
748451-B
Model CAT7
March 2002
SECTION 6

REPLACEMENT PARTS

WARNING
PARTS INTEGRITY
Tampering with or unauthorized substitution of components may adversely affect safety of this product. Use only factory-approved components for repair.

6-1 MATRIX

Each analyzer is configured per the customer sales order. Below is the CAT7 sales matrix which lists the various configurations available.
To identify the configuration of an analyzer, locate the analyzer name-rating plate. The sales matrix identi­fier number appears on the analyzer name-rating plate.
CAT7 CAT7 THERMAL CONDUCTIVITY ANALYZER
Code Parameter And Background Gas
10 Hydrogen in Air 11 Hydrogen in Nitrogen 12 Hydrogen in Methane 13 Hydrogen in Argon 14 Hydrogen in Carbon Dioxide 20 Helium in Air 21 Helium in Nitrogen 22 Helium in Oxygen 23 Helium in Methane 24 Helium in Argon 25 Helium in Carbon Dioxide 26 Helium in Argon & Oxygen 90 Argon in Air 91 Argon in Nitrogen 92 Argon in Oxygen 93 Carbon Dioxide in Air 94 Carbon Dioxide in Nitrogen 95 Carbon Dioxide in Oxygen 96 Nitrogen in Argon 50 Nitrogen in Hydrogen (0-5000 ppm Range Only. Range Code 31 60 Refinery (15% Hydrocarbon – 85% N2; 100% N2; 1% Hydrogen in 99% N2). Range Code 60 61 Utilities (BD Special) (80-100% H2 in Air, 0-100% H2 in CO2 and 0-100% Air in CO2). Range Code 61 97 Corrosive Gas Mixture Application (Zero Based Ranges Only). Range Code 97 98 Corrosive Gas Mixture Application (Suppressed Range Only). Range Code 98 99 Special
Rosemount Analytical Inc. A Division of Emerson Process Management Replacement Parts 6-1
Page 46
Instruction Manual
748451-B March 2002
Model CAT7
Code Range
14 85-100% 15 95-100% 16 99-100% 17 99.5-100% 19 Special Suppressed Range 30 0-500 ppm 31 0-5000 ppm 01 0-1% 02 0-5% 03 0-10% 04 0-15% 05 0-25% 06 0-50% 07 0-75% 08 0-100% 09 Special Zero Based Range 10 20-50% 11 45-55% 12 60-80% 13 50-100% 60 Refinery 61 Utilities 97 Corrosive Gas Mixture Application – Zero Based Range 98 Corrosive Gas Mixture Application – Suppressed Range
Code Single and Dual Range Analyzer
01 One Range, Voltage Output 02 One Range, Linearized Voltage Output 03 One Range with 4-20 mA Isolated Current Output 04 One Range, Linearized with 4-20 mA Isolated Current Output 05 Two Ranges, Voltage Output 06 Two Ranges, Range One Linearized Voltage Output 07 Two Ranges, Both Linearized Voltage Output 08 Two Ranges with 4-20 mA Isolated Current Output 09 Two Ranges, Range One Linearized Output; Both Ranges 4-20 mA Output 99 Triple Range
6-2 Replacement Parts Rosemount Analytical Inc. A Division of Emerson Process Management
Page 47
Model CAT7
Instruction Manual
748451-B
March 2002
Code Dual Range Analyzer; Second Range
14 85-100% 15 95-100% 16 99-100% 17 99.5-100% 19 Special Suppressed Range 30 0-500 ppm 31 0-5000 ppm 01 0-1% 02 0-5% 03 0-10% 04 0-15% 05 0-25% 06 0-50% 07 0-75% 08 0-100% 09 Special Zero Based Range 10 20-50% 11 45-55% 12 60-80% 13 50-100% 60 Refinery 61 Utilities 97 Corrosive Gas Mixture Application – Zero Based Range 98 Corrosive Gas Mixture Application – Suppressed Range 00 No Second Range
Code Power, Alarm, Tropicalization
01 115V, 50/60 Hz 02 115V, 50/60 Hz with Dual Alarm 03 115V, 50/60 Hz with Tropicalization 04 115V, 50/60 Hz with Dual Alarm and Tropicalization 05 230V, 50/60 Hz 06 230V, 50/60 Hz with Dual Alarm 07 230V, 50/60 Hz with Tropicalization 08 230V, 50/60 Hz with Dual Alarm and Tropicalization
CAT7 11 03 02 17 04 Example
6-2 CIRCUIT BOARD REPLACEMENT POLICY
In most situations involving a malfunction of a circuit board, it is more practical to replace the board than to attempt isolation and replacement of the individual component. The cost of test and replacement will ex­ceed the cost of a rebuilt assembly from the factory.
The following list does not include individual electronic components. If circumstances necessitate replace­ment of an individual component which can be identified by inspection or from the schematic diagrams, obtain the replacement component from a local source of supply.
Rosemount Analytical Inc. A Division of Emerson Process Management Replacement Parts 6-3
Page 48
Instruction Manual
748451-B March 2002

6-3 REPLACEMENT PARTS

The following parts are recommended for routine maintenance and troubleshooting of the Model CAT7 Analyzer. If the troubleshooting procedures do not resolve the problem, contact Rosemount Analytical Customer Service Center (Section 7).
661540 Temperature Control Assembly 624006 Temperature Control Board 901913 Alarm Module 613560 Bridge Power Supply 619714
654632
654630
654628
654627
654631
654629
902444 902443 902442
1
3
3
3
3
3
3
1
1
±15V Power Supply Detector Assembly w/Filaments ­Flowing Ref (Gold Sheathed Tungsten) Detector Assembly w/Filaments ­Flowing Ref (Hytempco) Detector Assembly w/Filaments ­Flowing Ref (Tungsten) Detector Assembly w/Filaments ­Sealed Ref (Tungsten) Detector Assembly w/Filaments ­Sealed Ref Nitrogen (Gold Sheathed Tungsten) Detector Assembly w/Filaments ­Sealed Ref Nitrogen (Hytempco) Filaments (Gold Sheathed Tungsten) Filaments (Hytempco)
Filaments (Tungsten) 801566 Fuse 1.5A (230VAC) 000516 Fuse 3A (115VAC) 652816 Isolated Current Output Board 616443 Linearizer Kit (Factory Installed option. Consult factory.) 654620 Master Board 633875 Meter
Model CAT7
1
Sealed reference cells must be serviced at factory.
6-4 Replacement Parts Rosemount Analytical Inc. A Division of Emerson Process Management
Page 49
Model CAT7
Instruction Manual
748451-B
March 2002
SECTION 7

RETURN OF MATERIAL

7-1 RETURN OF MATERIAL

If factory repair of defective equipment is re­quired, proceed as follows:
1. Secure a return authorization from a Rosemount Analytical Inc. Sales Office or Representative before returning the equipment. Equipment must be returned with complete identification in accordance with Rosemount instructions or it will not be accepted.
Rosemount CSC (Customer Service Center) will provide the shipping address for your instrument.
In no event will Rosemount be responsi­ble for equipment returned without proper authorization and identification.
2. Carefully pack the defective unit in a sturdy box with sufficient shock absorbing material to ensure no additional damage occurs during shipping.
3. In a cover letter, describe completely:
The symptoms that determined the
equipment is faulty.
The environment in which the equip-
ment was operating (housing, weather, vibration, dust, etc.).
Site from where the equipment was
removed.
Whether warranty or non-warranty
service is expected.
Complete shipping instructions for the
return of the equipment.
4. Enclose a cover letter and purchase order and ship the defective equipment ac­cording to instructions provided in the Rosemount Return Authorization, prepaid, to the address provided by Rosemount CSC.
Rosemount Analytical Inc.
Process Analytical Division
Customer Service Center
1-800-433-6076
If warranty service is expected, the defective unit will be carefully inspected and tested at the factory. If the failure was due to the condi­tions listed in the standard Rosemount war­ranty, the defective unit will be repaired or replaced at Rosemount’s option, and an oper­ating unit will be returned to the customer in accordance with the shipping instructions fur­nished in the cover letter.
For equipment no longer under warranty, the equipment will be repaired at the factory and returned as directed by the purchase order and shipping instructions.

7-2 CUSTOMER SERVICE

For order administration, replacement Parts, application assistance, on-site or factory re­pair, service or maintenance contract informa­tion, contact:
Rosemount Analytical Inc.
Process Analytical Division
Customer Service Center
1-800-433-6076

7-3 TRAINING

A comprehensive Factory Training Program of operator and service classes is available. For a copy of the Current Operator and Service Training Schedule contact the Technical Services Department at:
Rosemount Analytical Inc.
Phone: 1-714-986-7600
FAX: 1-714-577-8006
Rosemount Analytical Inc. A Division of Emerson Process Management Return of Material 7-1
Page 50
Instruction Manual
748451-B March 2002
Model CAT7
7-2 Return of Material Rosemount Analytical Inc. A Division of Emerson Process Management
Page 51

WARRANTY

Goods and part(s) (excluding consumables) manufactured by Seller are warranted to be free from defects in workmanship and material under normal use and service for a period of twelve (12) months from the date of shipment by Seller. Consumables, glass electrodes, membranes, liquid junctions, electrolyte, o-rings, etc., are warranted to be free from defects in workmanship and material under normal use and service for a period of ninety (90) days from date of shipment by Seller. Goods, part(s) and consumables proven by Seller to be defective in workmanship and/or material shall be replaced or repaired, free of charge, F.O.B. Seller's factory provided that the goods, part(s) or consumables are returned to Seller's designated factory, transportation charges prepaid, within the twelve (12) month period of warranty in the case of goods and part(s), and in the case of consumables, within the ninety (90) day period of warranty. This warranty shall be in effect for replacement or repaired goods, part(s) and the remaining portion of the ninety (90) day warranty in the case of consumables. A defect in goods, part(s) and consumables of the com­mercial unit shall not operate to condemn such commercial unit when such goods, part(s) and consumables are capable of being renewed, repaired or replaced.
The Seller shall not be liable to the Buyer, or to any other person, for the loss or damage directly or indirectly, arising from the use of the equipment or goods, from breach of any warranty, or from any other cause. All other warranties, expressed or implied are hereby excluded.
IN CONSIDERATION OF THE HEREIN STATED PURCHASE PRICE OF THE GOODS, SELLER GRANTS ONLY THE ABOVE STATED EXPRESS WARRANTY. NO OTHER WAR­RANTIES ARE GRANTED INCLUDING, BUT NOT LIMITED TO, EXPRESS AND IMPLIED WARRANTIES OR MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
Limitations of Remedy. SELLER SHALL NOT BE LIABLE FOR DAMAGES CAUSED BY DE­LAY IN PERFORMANCE. THE SOLE AND EXCLUSIVE REMEDY FOR BREACH OF WAR­RANTY SHALL BE LIMITED TO REPAIR OR REPLACEMENT UNDER THE STANDARD WARRANTY CLAUSE. IN NO CASE, REGARDLESS OF THE FORM OF THE CAUSE OF AC­TION, SHALL SELLER'S LIABILITY EXCEED THE PRICE TO BUYER OF THE SPECIFIC GOODS MANUFACTURED BY SELLER GIVING RISE TO THE CAUSE OF ACTION. BUYER AGREES THAT IN NO EVENT SHALL SELLER'S LIABILITY EXTEND TO INCLUDE INCIDEN­TAL OR CONSEQUENTIAL DAMAGES. CONSEQUENTIAL DAMAGES SHALL INCLUDE, BUT ARE NOT LIMITED TO, LOSS OF ANTICIPATED PROFITS, LOSS OF USE, LOSS OF REVE­NUE, COST OF CAPITAL AND DAMAGE OR LOSS OF OTHER PROPERTY OR EQUIPMENT. IN NO EVENT SHALL SELLER BE OBLIGATED TO INDEMNIFY BUYER IN ANY MANNER NOR SHALL SELLER BE LIABLE FOR PROPERTY DAMAGE AND/OR THIRD PARTY CLAIMS COVERED BY UMBRELLA INSURANCE AND/OR INDEMNITY COVERAGE PROVIDED TO BUYER, ITS ASSIGNS, AND EACH SUCCESSOR INTEREST TO THE GOODS PROVIDED HEREUNDER.
Force Majeure. Seller shall not be liable for failure to perform due to labor strikes or acts beyond Seller's direct control.
Page 52
Instruction Manual
748451-B March 2002
Model CAT7
Emerson Process Management
Rosemount Analytical Inc. Process Analytic Division
1201 N. Main St. Orrville, OH 44667-0901 T (330) 682-9010 F (330) 684-4434 E gas.csc@emersonprocess.com
ASIA - PACIFIC Fisher-Rosemount Singapore Private Ltd.
1 Pandan Crescent Singapore 128461 Republic of Singapore T 65-777-8211 F 65-777-0947
http://www.processanalytic.com
© Rosemount Analytical Inc. 2001
Fisher-Rosemount GmbH & Co.
Industriestrasse 1 63594 Hasselroth Germany T 49-6055-884 0 F 49-6055-884209
EUROPE, MIDDLE EAST, AFRICA Fisher-Rosemount Ltd.
Heath Place Bognor Regis West Sussex PO22 9SH England T 44-1243-863121 F 44-1243-845354
LATIN AMERICA Fisher - Rosemount
Av. das Americas 3333 sala 1004 Rio de Janeiro, RJ Brazil 22631-003 T 55-21-2431-1882
Page 53
Page 54
Page 55
Page 56
Page 57
Page 58
Page 59
Page 60
Page 61
Page 62
Page 63
Page 64
Loading...