Emerson™ Wireless 1410D Gateway with 781
Field Link
Gateway connects the WirelessHART
Easy configuration and management of self-organizing networks
Easy integration into control systems and data applications through serial and EtherNet connections
Seamless integration into AMS Device Manager
Greater than 99 percent data reliability with industry proven security
Wireless capabilities extend the full benefits of Plantweb
®
self-organizing networks with any host system
™
architecture to previously inaccessible locations
Emerson Wireless 1410D Gateway and 781 Field Link
Emerson Wireless Solution
IEC 62591 (WirelessHART)... the industry standard
Self-organizing, adaptive mesh routing
No wireless expertise required, network automatically finds the best
communication paths
The self-organizing, self-healing network manages multiple communication paths
for any given device. If an obstruction is introduced into the network, data will
continue to flow because the device already has other established paths. The
network will then lay in more communication paths as needed for that device
Reliable wireless architecture
Standard IEEE 802.15.4 radios
2.4 GHz ISM band sliced into 15 radio-channels
Time Synchronized Channel Hopping to avoid interference from other radios,
®
, and EMC sources and increase reliability
Wi-Fi
Direct sequence spread spectrum (DSSS) technology delivers high reliability in
challenging radio environment
February 2018
Emerson Wireless
Seamless integration via LAN to all existing host systems
Native integration into Ovation
Gateways interface with existing host systems via LAN using industry standard
protocols including OPC, Modbus® TCP/IP, and Modbus RTU
Layered security keeps your network safe
All wireless data is encrypted so your data is kept safe
All wireless devices are authenticated so you know exactly what is on your network
Third party security certifications including Achilles and FIPS-197 certification
demonstrate Emerson's commitment to security
Complete control of your network using the Gateway secure web interface
SmartPower™ solutions
Optimized Emerson instrumentation, both hardware and software, to extend power module life
SmartPower technologies enable predictable power life
Contents
™
is transparent and seamless
Emerson Wireless 1410D Gateway and 781 Field Link . . .3
Dashboards to configure devices and view diagnostic data
Drag and drop device provisioning enables a secure method to add new wireless devices
to the wireless field network
Emerson.com/Rosemount
3
Emerson Wireless 1410D Gateway and 781 Field Link
February 2018
Emerson Wireless 1410D Gateway
Specification and selection of product materials, options, or components must be made by the purchaser of the equipment.
See page 8 for more information on material selection
Table 1. Emerson Wireless 1410D Gateway Ordering Information
The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject
to additional delivery lead time.
100 Device Network with Emerson 781 Field Link (10.5 to 30 Vdc)
EtherNet communications - physical connection
(2)(3)
1
(4)(5)(6)
2
Single EtherNet connection
Dual EtherNet connection
Serial communication
NNone
(7)
A
Modbus RTU via RS-485
EtherNet communication - data protocols
D1Modbus TCP/IP
D2OPC
D3EtherNet/IP
D4Modbus TCP/IP, OPC
D5EtherNet/IP, Modbus TCP/IP
D6EtherNet/IP, OPC
(8)
E1
E2
E3
(8)
(9)
DeltaV ready
Ovation ready
Webserver only
™
★
★
★
★
★
★
★
★
★
★
★
★
★
★
★
Antenna options
WNAFor use with the Emerson Wireless 781 Remote Field Link
Product certifications
NANo approvals
N1ATEX Type n
N5USA Division 2, Non-incendive
N6Canada Division 2, Non-incendive
N7IECEx Type n
4
★
★
★
★
Emerson.com/Rosemount
February 2018
Emerson Wireless 1410D Gateway and 781 Field Link
Table 1. Emerson Wireless 1410D Gateway Ordering Information
The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject
to additional delivery lead time.
Redundancy options
(10)(11)
RDGateway redundancy
1.Must order the Emerson Wireless 781Remote Field Link. Reference Emerson Wireless 781 Field Link on page 6 for detail s.
2.Single active 10/100 baseT EtherNet port with RJ45 connector.
3.Additional ports disabled.
4.Dual active 10/100 baseT EtherNet ports with RJ45 connectors.
5.Multiple active ports have separate IP addresses, firewall isolation, and no packet forwarding.
6.Selection of Dual EtherNet option code 2 is recommended.
7.Convertible to RS232 via adapter, not included with Gateway.
8. Includes Modbus TCP and OPC.
9.Requires (A) Modbus RTU via RS-485 Communication protocol.
10.Requires the selection of Dual EtherNet option code 2.
11.Not available with EtherNet/IP option codes D3, D5, and D6.
★
Emerson.com/Rosemount
5
Emerson Wireless 1410D Gateway and 781 Field Link
February 2018
Emerson Wireless 781 Field Link
Table 2. Emerson Wireless 781 Field Link Ordering Information
The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject
to additional delivery lead time.
ModelProduct description
781Wireless Field Link
Network capacity and physical connection
A1100 device capacity, RS485
(1)
C1
25 Device Capacity, RS485
Housing
DDual compartment housing - aluminum
EDual compartment housing - stainless steel
Conduit threads
1
1
/2–14 NPT
Product certifications
(2)
I3
I5
I6
I1
I7
KD
KL
IM
(2)
(2)
(2)
(2)
(2)
(2)
(2)
China Intrinsic Safety
USA Intrinsically Safe, Non-incendive
Canada Intrinsically Safe
ATEX Intrinsic Safety
IECEx Intrinsic Safety
USA and Canada Intrinsically Safe, ATEX and IECEx Intrinsic Safety
USA and Canada Intrinsically Safe, ATEX Intrinsic Safety
Technical Regulations Customs Union (EAC) Intrinsic Safety
★
★
★
★
★
★
★
★
★
★
★
★
★
★
NANo approvals
Wireless update rate, operating frequency, and protocol
WM3Extended range, external antenna, line power 10 to 30 Vdc
Display
M5LCD display
6
★
★
★
★
Emerson.com/Rosemount
February 2018
Table 2. Emerson Wireless 781 Field Link Ordering Information
The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject
to additional delivery lead time.
Emerson Wireless 1410D Gateway and 781 Field Link
Gland and connector options
G2Cable gland (7.5 to 11.9 mm)
G4Thin wire cable gland (3 to 8 mm)
Typical model number: 781 A1 D 1 KL WA3 WM3 M5
1.Only works with firmware version 4.7.53 or higher.
2.Use of the Emerson Wireless 781 Field Link with an 1410D Gateway requires the use of an appropriate intrinsic safety barrier.
Table 3. Accessories
Item descriptionPart number
Serial Port HART Modem and cables only03095-5105-0001
USB Port HART Modem and cables only03095-5105-0002
Emerson.com/Rosemount
7
Emerson Wireless 1410D Gateway and 781 Field Link
Specifications
February 2018
Emerson Wireless 1410D Gateway
Functional specifications
Input voltage
10.5 to 30 Vdc
Note
For best results, use a high quality industrial galvanically isolated
power supply.
Current draw
Operating current draw is based on 3.6 W power consumption.
At startup, the power supply must be capable of momentarily
sourcing at least twice the operating current indicated in the
figure below. The Gateway may draw significantly more current
momentarily at startup if not limited by the power supply.
Antenna options
See “Emerson Wireless 781 Field Link” on page -9.
Physical specifications
Material selection
™
Emerson provides a variety of Rosemount
product options and configurations including materials of
construction that can be expected to perform well in a wide
range of applications. The Rosemount product information
presented is intended as a guide for the purchaser to make an
appropriate selection for the application. It is the purchaser’s sole
responsibility to make a careful analysis of all process parameters
(such as all chemical components, temperature, pressure, flow
rate, abrasives, contaminants, etc.), when specifying product,
materials, options and components for the particular application.
Emerson is not in a position to evaluate or guarantee the
compatibility of the process fluid or other process parameters
with the product, options, configuration or materials of
construction selected.
Weight
0.70 lb (0.318 kg)
Material of construction
product with various
Note
For recommended intrinsic safety barrier installation:
Input voltage 20 to 30 Vdc is needed
Current draw is based on 6.6 W power consumption of
Gateway and barriers combined
Environmental
Operating temperature range:
–40 to 167 °F (–40 to 75 °C)
Operating humidity range:
0 to 100% relative humidity
Electromagnetic Compatibility (EMC) performance
Meets all industrial environment requirements of EN61326 and
NAMUR NE-21. Maximum deviation <1% span during EMC
disturbance
1.During surge event, device may exceed maximum EMC deviation limit or
(1)
.
reset; however, device will self-recover and return to normal operation
within specified start-up time.
Housing
Polycarbonate
Rail mount
Top hat rail EN 50022
(35 x 7.5 mm and 35 x 15 mm)
Communication specifications
Isolated RS-485
2-wire communication link for Modbus RTU multidrop
connections
Baud rate: 57600, 38400, 19200, or 9600
Protocol: Modbus RTU
Wiring: Single twisted shielded pair, 18 AWG
Wiring distance: approximately 4000 ft. (1,524 m)
EtherNet
Ethernet Ports 1 and 2 are independent interfaces with unique
MAC addresses, no routing or switching capabilities
(for Web Interface)
Wiring: Cat5E shielded cable
Wiring distance: 328 ft. (100 m)
8
Emerson.com/Rosemount
February 2018
Emerson Wireless 1410D Gateway and 781 Field Link
Modbus
Supports Modbus RTU and Modbus TCP with 32-bit floating point
values, integers, and scaled integers.
Modbus Registers are user-specified.
OPC
OPC server supports OPC DA v2, v3
EtherNet/IP
Supports EtherNet/IP protocol with 32-bit Floating Point values
and Integers
EtherNet/IP Assembly Input-Output instances are user
configurable.
EtherNet/IP specifications are managed and distributed by
ODVA.
For details on capabilities, see the Emerson Wireless Manual
Supplement.
Self-organizing network specifications
Protocol
IEC 62591(WirelessHART), 2.4 to 2.5 GHz DSSS
Maximum network size
100 wireless devices at 8 seconds or more
50 wireless devices at 4 seconds
25 wireless devices at 2 seconds
12 wireless devices at 1 second
For information on network size and update rate, see the capacity
estimator tool on the Emerson Wireless homepage
Supported device update rates
1, 2, 4, 8, 16, 32 seconds or 1 to 60 minutes
Network size/latency
100 Devices: less than 10 seconds
50 Devices: less than 5 seconds
Data reliability
> 99 percent
.
System security specifications
EtherNet
Self-organizing network
AES-128 Encrypted WirelessHART, including individual session
keys. Drag and drop device provisioning, including unique join
keys and white listing.
Internal firewall
User configurable TCP ports for communications protocols,
including Enable/Disable and user specified port numbers.
Inspects both incoming and outgoing packets.
Third party certification
Wurldtech: Achilles Level 1 certified for network resiliency
National Institute of Standards and Technology (NIST): Advanced
Encryption Standard (AES) Algorithm conforming to Federal
Information Processing Standard Publication 197 (FIPS-197).
Emerson Wireless 781 Field Link
Functional specifications
Wireless output
IEC 62591 (WirelessHART), 2.4 GHBz DSSS
Local display
The optional five-digit integral LCD display can display wireless
information.
Environmental
0 to 99 percent non-condensing relative humidity
Radio frequency power output from antenna
External antenna (WK1 option):
Maximum of 10 mW (10 dBm) EIRP
Field link wiring distance
Wiring distance between Field Link and Gateway:
up to 200 m using single twisted shielded pair, 18 AWG
Barrier Recommendations
For use in a hazardous area the recommended intrinsic safety
barriers are
Role-Based Access Control (RBAC) including Administrator,
Maintenance, Operator, and Executive. Administrator has
complete control of the Gateway and connections to host
systems and the self-organizing network.
Emerson.com/Rosemount
9
Emerson Wireless 1410D Gateway and 781 Field Link
February 2018
Physical specifications
Material selection
Emerson provides a variety of Rosemount product with various
product options and configurations including materials of
construction that can be expected to perform well in a wide
range of applications. The Rosemount product information
presented is intended as a guide for the purchaser to make an
appropriate selection for the application. It is the purchaser’s sole
responsibility to make a careful analysis of all process parameters
(such as all chemical components, temperature, pressure, flow
rate, abrasives, contaminants, etc.), when specifying product,
materials, options and components for the particular application.
Emerson is not in a position to evaluate or guarantee the
compatibility of the process fluid or other process parameters
with the product, options, configuration or materials of
construction selected.
Mounting brackets also permit remote mounting.
See Figure 3 on page 16.
Weight
Low-copper aluminum
Emerson Wireless 781 without LCD display - 4.1 lb (1.9 kg)
Emerson Wireless 781 with M5 LCD display - 4.2 lb (2.0 kg)
Stainless steel
Emerson Wireless 781 without LCD display - 8.0 lb (3.5 kg)
Emerson Wireless 781 with M5 LCD display - 8.1 lb (3.6 kg)
Enclosure ratings (781)
Housing style option codes D and E are Type 4X and IP66/67
rated dual-compartment housings
Performance specifications
EMC performance
Meet all industrial environment requirements of EN61326 and
NAMUR NE-21. Maximum deviation <1% span during EMC
disturbance.
(1)
10
1.During surge event, device may exceed maximum EMC deviation limit or
reset; however, device will self-recover and return to normal operation
within specified start-up time.
Emerson.com/Rosemount
February 2018
Product certifications
Emerson Wireless 1410D Gateway and 781 Field Link
Emerson Wireless 1410 Gateway
Rev 2.0
European Directive Information
A copy of the EU Declaration of Conformity can be found at the
end of the Quick Start Guide. The most recent revision of the
EEUC Declaration of Conformity can be found at
Emerson.com/Rosemount
Telecommunication Compliance
All wireless devices require certification to ensure that they
adhere to regulations regarding the use of the RF spectrum.
Nearly every country requires this type of product certification.
Emerson is working with governmental agencies around the
world to supply fully compliant products and remove the risk of
violating country directives or laws governing wireless device
usage.
FCC and IC
This device complies with Part 15 of the FCC Rules. Operation is
subject to the following conditions: This device may not cause
harmful interference. This device must accept any interference
received, including interference that may cause undesired
operation. This device must be installed to ensure a minimum
antenna separation distance of 20 cm from all persons.
Ordinary Location Certification
.
Special Condition for Safe Use:
1. When installed as Division 2 equipment, the Emerson
Wireless 1410 Gateway shall be mounted within a
tool-secured enclosure which meets the requirements of
ANSI/ISA 61010-1 and be capable of accepting the
applicable wiring methods per the NEC.
Markings: Suitable for CL I, DIV 2, GP A, B, C, D.
≤ T
Temperature code: T4 (–40 °C
Note
Shall be powered by a Class 2 power supply.
Suitable for dry indoor locations only.
Equipment must be installed in a suitable tool accessible
enclosure subject to the end use application.
Using the Emerson Wireless 1410D and the Wireless Field Link
781 in a hazardous location requires barriers between the two
units in some cases.
≤ 70 °C)
a
As standard, the transmitter has been examined and tested to
determine that the design meets the basic electrical, mechanical,
and fire protection requirements by a nationally recognized test
laboratory (NRTL) as accredited by the Federal Occupational
Safety and Health Administration (OSHA).
Installing Equipment in North America
The US National Electrical Code® (NEC) and the Canadian
Electrical Code (CEC) permit the use of Division marked
equipment in Zones and Zone marked equipment in Divisions.
The markings must be suitable for the area classification, gas,
and temperature class. This information is clearly defined in the
respective codes.
USA
N5 USA Division 2
Certificate: 30349590 (FM)
Standards: FM Class 3600 –2011,
FM Class 3611 – 2004,
FM Class 3616 – 2011,
FM Class 3810 – 2005
Markings: NI CL 1, DIV 2, GP A, B, C, D T4;
Suitable for use in CL II, III, DIV 2, GP F, G T4;
≤ T
T4(–40 °C
≤ 60 °C)
a
Europe
N1 ATE X Type n
Certificate: Baseefa14ATEX0125X
Standards: EN 60079-0: 2012, EN 60079-15: 2010
Markings: II 3 G Ex nA IIC T4 Gc, T4 (–40 °C
= 30 Vdc
,V
max
Special Conditions for Safe Use:
1. The equipment must be installed in an area of not more
than Pollution Degree 2 as defined in IEC 60664-1, and in an
enclosure that provides a degree of protection of at least
IP54 and meets the relevant requirements of EN 60079-0
and EN 60079-15.
2. External connections to the equipment must not be
inserted or removed unless either the area in which the
equipment is installed is known to be non-hazardous, or the
circuits connected have been de-energised.
≤ T
≤ 75 °C)
a
Emerson.com/Rosemount
11
Emerson Wireless 1410D Gateway and 781 Field Link
3. The equipment is not capable of withstanding the 500 V
electrical strength test as defined in clause 6.5.1 of EN
60079-15: 2010. This must be taken into account during
installation.
4. When fitted, the surface resistivity of the remote antenna is
greater than 1 GΩ. To avoid electrostatic charge build up, it
must not be rubbed with a dry cloth or cleaned with
solvents.
1. The equipment must be installed in an area of not more
than Pollution Degree 2 as defined in IEC 60664-1, and in an
enclosure that provides a degree of protection of at least
IP54 and meets the relevant requirements of EN 60079-0
and EN 60079-15.
2. External connections to the equipment must not be
inserted or removed unless either the area in which the
equipment is installed is known to be nonhazardous, or the
circuits connected have been de-energised.
3. The equipment is not capable of withstanding the 500 V
electrical strength test as defined in clause 6.5.1 of EN
60059-15: 2010. This must be taken into account during
installation.
4. When fitted, the surface resistivity of the remote antenna is
greater than 1 GΩ. To avoid electrostatic charge build-up, it
must not be rubbed with a dry cloth or cleaned with
solvents.
≤ 75 °C),
a
February 2018
12
Emerson.com/Rosemount
February 2018
Emerson Wireless 1410D Gateway and 781 Field Link
Emerson Wireless 781 Field Link
Rev 2.0
European Directive Information
A copy of the EU Declaration of Conformity can be found at the
end of the Quick Start Guide. The most recent revision of the EU
Declaration of Conformity can be found at
Emerson.com/Rosemount
Ordinary Location Certification
As standard, the transmitter has been examined and tested to
determine that the design meets the basic electrical, mechanical,
and fire protection requirements by a nationally recognized test
laboratory (NRTL) as accredited by the Federal Occupational
Safety and Health Administration (OSHA).
Installing in North America
The US National Electrical Code (NEC) and the Canadian Electrical
Code (CEC) permit the use of Division marked equipment in
Zones and Zone marked equipment in Divisions. The markings
must be suitable for the area classification, gas, and temperature
class. This information is clearly defined in the respective codes.
USA
I5USA Intrinsically Safe (IS), Nonincendive (NI) and
Dust-ignitionproof
Certificate: FM17US0235X
Standards: FM Class 3600 – 2011,
FM Class 3610 – 2010,
FM Class 3611 – 2004,
FM Class 3810 – 2005,
ANSI/ISA 60079-0:2009,
ANSI/UL 60079-11:2009,
ANSI/ISA 61010-1:2004,
ANSI/NEMA 250 – 2003,
ANSI/IEC 60529 – 2004
Markings: IS CL I, DIV 1, GP A, B, C, D; CL II, DIV 1, GP E, F,
G; Class III T4; Class 1, Zone 0 AEx ia IIC T4;
NI CL I, DIV 2, GP A, B, C, D T4;DIP CL II, DIV 1,
GP E, F, G; CL III T4; when installed per drawing
00781-1010 T4(–40 °C
Input parameters
(power terminals)
V
/Ui = 30 VV
MAX
I
/Ii = 200 mAI
MAX
P
/Pi = 1 WP
MAX
C
= 10 nFCi = 5 nFCa/CO = 13.49 μF
i
L
= 3.3 μHLi = 2.2 μHLa/LO = 2 mH
i
.
≤ T
≤ +70 °C)
a
Input parameters Output parameters
Sensor terminals
/Ui = 11 VVOC/UO = 7.14 V
MAX
/Ii = 300 mAISC/IO = 112 mA
MAX
/Pi = 1 WP
MAX
MAX/PO
= 640 mW
Special Conditions for Safe Use (X):
1. The Emerson Wireless 781 transmitter housing contains
aluminum and is considered a potential risk of ignition by
impact or friction. Care must be taken into account during
installation and use to prevent impact and friction.
2. The surface resistivity of the unit is greater than 1 gigaohm.
To avoid electrostatic charge buildup, it must not be rubbed
or cleaned with solvents or a dry cloth.
3. The Emerson Wireless 781 transmitter will not pass the 500
Vrms electric strength test and this must be taken into
account during installation.
Markings: Intrinsically Safe Class I, Division 1, Groups A, B,
C, and D T3C (T
≤ +60 °C) Type 4X;
a
IP 66/67;when installed per 00781-1011
Europe
I1ATEX Intrinsic Safety
Certificate: Baseefa11ATEX0059X
Standards: EN 60079-0: 2012 + A11: 2013,
EN 60079-11: 2012
Markings: II 1 G Ex ia IIC T4 Ga,
≤ T
T4(–40 °C
Input parameters
Input parameters Output parameters
(power terminals)
Ui = 30 VUi = 11 VUO = 7.14 V
I
= 200 mAIi = 300 mAIO = 112 mA
i
P
= 1 WPi = 1 WPO = 1 W
i
C
= 0 μFCi = 5.1nFCO = 13.9 μF
i
L
= 0 mHLi = 0 mHLO = 1000 μH
i
Special Conditions for Safe Use (X):
1. The plastic antenna may present a potential electrostatic
ignition hazard and must not be rubbed or cleaned with a
dry cloth.
2. The Emerson Wireless 781 enclosure is made of aluminum
alloy and given a protective paint finish; however, care
should be taken to protect it from impact or abrasion if
located in a zone 0 environment.
3. The apparatus is not capable of withstanding the 500 V
isolation test required by EN 60079-11. This must be taken
into account when installing the apparatus.
≤ +70 °C)
a
RS485
Emerson.com/Rosemount
13
Emerson Wireless 1410D Gateway and 781 Field Link
February 2018
International
I7IECEx Intrinsic Safety
Certificate: IECEx BAS 11.0028X
Standards: IEC 60079-0: 2011,
IEC 60079-11: 2011
≤ T
RS485
≤ +70 °C)
a
Markings: Ex ia IIC T4 Ga, T4(–40 °C
Input parameters
Input parameters Output parameters
(power terminals)
Ui = 30 VUi = 11 VUO = 7.14 V
I
= 200 mAIi = 300 mAIO = 112 mA
i
P
= 1 WPi = 1 WPO = 1 W
i
C
= 0 μFCi = 5.1 nFCO = 13.9 μF
i
L
= 0 mHLi = 0 mHLO = 1000 μH
i
Special Conditions for Safe Use (X):
1. The plastic antenna may present a potential electrostatic
ignition hazard and must not be rubbed or cleaned with a
dry cloth.
2. The Emerson Wireless 781 enclosure is made of aluminum
alloy and given a protective paint finish; however, care
should be taken to protect it from impact or abrasion if
located in a zone 0 environment.
3. The apparatus is not capable of withstanding the 500 V
isolation test required by EN 60079-11. This must be taken
into account when installing the apparatus.
Emerson Terms and Conditions of Sale are available upon request.
The Emerson logo is a trademark and service mark of Emerson Electric Co.
Rosemount is a mark of one of the Emerson family of companies. All other
marks are the property of their respective owners.