Flexibility to meet your most demanding applications
Wireless output with >99 percent data reliability delivers rich HART data, protected by industry leading
®
devices
security
Gain access to additional HART information, such as diagnostics or multi-variable data
Add wireless to almost any measurement point
Wireless brings measurement capabilities to previously inaccessible locations
Page 2
THUM Adapter
September 2017
IEC 62591 (WirelessHART®)... the Industry Standard
Self-organizing, adaptive mesh
routing
No wireless expertise required. Devices automatically find the
best communication paths.
Network continuously monitors paths for degradation and
repairs itself.
Adaptive behavior provides reliable, hands-off operation and
simplifies network deployments, expansion, and
reconfiguration.
Supports both star and mesh topologies.
Industry standard radio with channel
hopping
Standard IEEE 802.15.4 radios
2.4 GHz ISM band sliced into 16 radio channels
Continually “hop” across channels to avoid interference and
increase reliability
Direct sequence spread spectrum (DSSS) technology delivers
high reliability in challenging radio environment
Self-healing network
The self-organizing, self-healing network manages multiple
communication paths for any given device. If an obstruction is
introduced into the network, data will continue to flow
because the device already has other established paths. The
network will then lay in more communication paths as needed
for that device.
Online, in-service valve testing through AMS ValveLink
™
SNAP-ON
Monitor alerts such as travel deviation with AMS Device
Manager, supply pressure, and electronics health.
Trend actual valve position.
Gain access to advanced instrument diagnostics
Rosemount
Micro Motion
Meter Verification SNAP-ON
Rosemount Radar Echo Curve
Rosemount Magnetic Flow Meter Verification with AMS
Device Manager
Efficiently gather data from multivariable devices
Rosemount 3051S MultiVariable
Rosemount 3095 Mass Flow Transmitters
Application.
™
3051S with Advanced Process Diagnostics
™
Coriolis Meter Verification with optional AMS
™
Transmitter and
Rosemount 3300 and 5300 Radar Level Transmitters
Micro Motion Coriolis Meters
Rosemount TankRadar
Rosemount Magnetic Flowmeter
Rosemount MultiVariable Vortex Flowmeter
™
Rex and TankRadar Pro
Make any HART device wireless access new
measurement information
Level
Flow
Valves
Liquid and Gas Analytical
Pressure
Tem pe ra tu re
Remotely manage devices and monitor health
with AMS Device Manager
Reduce troubleshooting time
As found, as left data
Emerson.com/Rosemount
Calibration tracking
3
Page 4
THUM Adapter
September 2017
Ordering Information
Specification and selection of product materials, options, or components must be made by the purchaser of the equipment.
See page 6 for more information on material selection.
Tabl e 1.
The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject
to additional delivery lead time.
ModelProduct description
775Wireless THUM Adapter
Output
XWireless
Housing
DAluminum★
ESST
Mounting connection
1
2M20 conduit adapter★
THUM Adapter Ordering Information
1
/2–14 NPT★
PlantWeb functionality
1HART data★
Certification
NANo approval★
I5FM Intrinsically Safe, Non-incendive★
I6CSA Intrinsically Safe★
I1ATEX Intrinsic Safety★
N1ATEX Type n★
I7IECEx Intrinsic Safety★
N7IECEx Type n★
I2INMETRO Intrinsic Safety★
N2INMETRO Type n★
I3China Intrinsic Safety★
IPKorea (KOSHA) Intrinsic Safety★
IWIndia (CCOE) Intrinsic Safety★
IMTechnical Regulation Customs Union (EAC) Intrinsic Safety
NMTechnical Regulation Customs Union (EAC) Type n
KMTechnical Regulation Customs Union (EAC) Intrinsic Safety and Type n
E5USA Explosionproof
E6Canada Explosionproof
4
Emerson.com/Rosemount
Page 5
September 2017
THUM Adapter
Tabl e 1.
The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject
to additional delivery lead time.
Wireless update rate, operating frequency, and protocol
Omni-directional, wireless antenna and SmartPower options
WK9Long range, integral antenna, power scavenging★
Typical model number: 775 X D 1 1 I5 WA3 WK9
Table 2. Accessories
THUM Adapter Ordering Information
Item descriptionPart number
Remote mount kit - aluminum00775-9000-0001
Remote mount kit - stainless steel00775-9000-0011
M20 conduit adapter00775-9001-0001
Emerson.com/Rosemount
5
Page 6
THUM Adapter
Specifications
September 2017
Functional specifications
Input
Any 2-, 3-, or 4-wire HART powered device
Output
IEC 62591 (WirelessHART)
Humidity limits
0–100% relative humidity
Update rate
User selectable, eight seconds to 60 minutes.
Physical specifications
Material selection
Emerson provides a variety of Rosemount product with various
product options and configurations including materials of
construction that can be expected to perform well in a wide
range of applications. The Rosemount product information
presented is intended as a guide for the purchaser to make an
appropriate selection for the application. It is the purchaser’s
sole responsibility to make a careful analysis of all process
parameters (such as all chemical components, temperature,
pressure, flow rate, abrasives, contaminants, etc.), when
specifying product, materials, options and components for the
particular application. Emerson is not in a position to evaluate or
guarantee the compatibility of the process fluid or other process
parameters with the product, options, configuration or
materials of construction selected.
Electrical connections
The THUM Adapter is connected into a powered 4–20 mA loop,
powering itself by scavenging power. The THUM Adapter causes
a voltage drop across the loop. The drop is linear from 2.25 V at
3.5 mA to 1.2 V at 25 mA, but does not effect the 4–20 mA
signal on the loop. Under fault conditions, the maximum voltage
drop is 2.5 V.
Power supply
Minimum load on loop 250 Ohms
To maintain normal operating functions of the sub-device, the
power in the loop must have at least a 2.5 V margin at a 250 Ω
load.
Limit power supply to 0.5 Amps maximum.
Limit power supply to 55 Vdc maximum.
Field Communicator connections
Utilize wired device HART connections
Materials of construction
Enclosure
Housing option D - Low-copper aluminum
Housing option E - 316 SST
Polybutadine terephthalate (PBT)/Polycarbonate (PC)
integrated omni directional antenna
Weight
THUM Adapter only AL - 0.65 lb (0.29 kg)
THUM Adapter only SST - 1.1 lb(0.5 kg)
AL THUM Adapter with AL remote kit - 3.2 lb (1.45 kg)
SST THUM Adapter with SST remote kit - 5.8 lb (2.65 kg)
AL THUM Adapter with M20 conduit adapter - 0.85 lb (.038 kg)
SST THUM Adapter with M20 conduit adapter - 1.3 lb (0.59 kg)
Enclosure ratings
Housing option code D and remote mount kits are enclosure
Type 4X and IP66.
Mounting
The THUM Adapter may be attached directly to the conduit of
any 2- or 4-wire HART device or mounted remotely by using
remote mount kit.
6
Emerson.com/Rosemount
Page 7
September 2017
Performance specifications
ElectroMagnetic Compatibility (EMC)
Meets all industrial environments of EN61326 and NAMUR
NE-21 when installed with shielded wiring. The sub-device must
also use shielded wiring for installation. Maximum deviation
span during EMC disturbance
(1)
.
Vibration effect
Output unaffected when tested per the requirements of
IEC60770-1 field with general application or pipeline with low
vibration level (10–60 Hz 0.15 mm displacement peak
amplitude/60-500 Hz 2 g).
When the THUM Adapter is used on wired devices that are
subject to vibration levels greater than 2g, it is recommended
that the THUM Adapter be remotely mounted using the remote
mount kit.
Temperature limits
Operating limitStorage limit
≤1%
THUM Adapter
–40 to 185 °F
–40 to 85 °C
–40 to 185 °F
–40 to 85 °C
1.During the surge event, device may exceed maximum EMC deviation limit
or reset; however, device will self-recover and return to normal operation
within specified start-up time.
Emerson.com/Rosemount
7
Page 8
THUM Adapter
Product Certifications
September 2017
Rev 2.2
European Directive Information
A copy of the EC Declaration of Conformity can be found at the
end of the Quick Start Guide. The most recent revision of the EC
Declaration of Conformity can be found at
Emerson.com/Rosemount
.
Ordinary Location Certification from
FM Approvals
As standard, the transmitter has been examined and tested to
determine that the design meets the basic electrical,
mechanical, and fire protection requirements by FM Approvals,
a nationally recognized test laboratory (NRTL) as accredited by
the Federal Occupational Safety and Health Administration
(OSHA).
All wireless devices require certification to ensure that they
adhere to regulations regarding the use of the RF spectrum.
Nearly every country requires this type of product certification.
Emerson is working with governmental agencies around the
world to supply fully compliant products and remove the risk of
violating country directives or laws governing wireless device
usage.
FCC and IC (for wireless products only)
This device complies with Part 15 of the FCC Rules. Operation is
subject to the following conditions: This device may not cause
harmful interference. This device must accept any interference
received, including interference that may cause undesired
operation. This device must be installed to ensure a minimum
antenna separation distance of 20 cm from all persons.
USA
E5USA Explosionproof
Certificate:CSA 2174201
Standards: FM Class 3600 - 2011, FM Class 3615 - 2006,
ANSI/UL 61010-1 3
Markings: Class I, Division 1, Groups A, B, C and D; T5, T6;
Type 4X and IP66 (–50 °C ≤ Ta ≤ +70 °C)
I5USA Intrinsically Safe (IS) and Non-incendive
Certificate: 3036224
Standards: FM Class 3600 - 1998, FM Class 3610 - 2007,
FM Class 3611 - 2004, FM Class 3810 - 2005,
NEMA 250 - 2003, IEC 60529 - 2004
Markings: IS CL I, DIV 1, GP A, B, C, D; CL II, DIV 1, GP E, F,
G; Class III; Class 1, Zone 0, AEx ia IIC T4; NI CL I,
DIV 2, GP A, B, C, D T4; T4(–50 °C ≤ T
when connected per Rosemount drawing
00775-0010; Type 4X/IP66
Markings: Intrinsically Safe Class I, Division 1, Groups A,
B, C, D T3C; Suitable for use in Class I, Division
2, Groups A, B, C, D T3C; T3C(–50 °C ≤ T
+70 °C) when installed per Rosemount drawing
00775-0012; Type 4X/IP66
≤ +70 °C)
a
≤ +70 °C)
a
≤
a
Installing Equipment in North America
The US National Electrical Code® (NEC) and the Canadian
Electrical Code (CEC) permit the use of Division marked
equipment in Zones and Zone marked equipment in Divisions.
The markings must be suitable for the area classification, gas,
and temperature class. This information is clearly defined in the
respective codes.
8
Europe
I1 ATEX Intrinsic Safety
Certificate: Baseefa09ATEX0125X
Standards: IEC 60079-0:2011; EN60079-11:2012;
Markings: II 1G Ex ia IIC T4 Ga, T4(–50 °C ≤ T
Emerson.com/Rosemount
≤ +70 °C)
a
Page 9
September 2017
THUM Adapter
Special Conditions for Safe Use (X):
1. The surface resistivity of the antenna is greater than 1GΩ.
To avoid electrostatic charge build-up, it must not be
rubbed or cleaned with solvents or dry cloth.
2. The Rosemount 775 enclosure may be made of aluminum
alloy and given a protective polyurethane paint finish;
however, care should be taken to protect it from impact or
abrasion if located in zone 0.
N1 ATEX Type n
Certificate: Baseefa09ATEX0131
Standards: IEC 60079-0:2011, EN 60079-15:2010
Markings: II 3G nA IIC T4 Gc, T4(–50 °C ≤ T
IP66
≤ +70 °C)
a
International
I7 IECEx Intrinsic Safety
Certificate: IECEx BAS 09.0050X
Standards: IEC 60079-0:2011, IEC 60079-11:2011
Markings: Ex ia IIC T4 Ga, T4(–50 °C ≤ T
Special Conditions for Safe Use (X):
1. The surface resistivity of the antenna is greater than 1 GΩ.
To avoid electrostatic charge build-up, it must not be
rubbed or cleaned with solvents or dry cloth.
2. The Rosemount 775 enclosure may be made of aluminum
alloy and given a protective polyurethane paint finish;
however, care should be taken to protect it from impact or
abrasion if located in zone 0.
N7 IECEx Type n
Certificate: IECEx BAS 09.0058
Standards: IEC 60079-0:2011, IEC 60079-15:2010;
Markings: Ex nA IIC T4 Gc, T4(–50 °C ≤ T
1. The surface resistivity of the antenna is greater than 1 GΩ.
To avoid electrostatic charge build-up, it must not be
rubbed or cleaned with solvents or dry cloth.
2. The enclosure may be made of aluminum alloy and given a
protective polyurethane paint finish; special care must be
taken to minimize the risk of impact or friction of the
housing which can cause the generation of sparks.
Standard Terms and Conditions of Sale can be found on the Ter ms a nd
Conditions of Sale page.
The Emerson logo is a trademark and service mark of Emerson Electric Co.
Micro Motion, SNAP-ON, SmartPower, MultiVariable, THUM Adapter,
TankRadar, Rosemount, and Rosemount logotype are trademarks of
Emerson.
HART and WirelessHART are registered trademarks of FieldComm Group.
HART-IP is a trademark of the FieldComm Group.
National Electrical Code is a registered trademark of National Fire
Protection Association, Inc.
All other marks are the property of their respective owners.