Rosemount 753R with Integral 3051S Pressure Transmitter
Rosemount 753R with Remote Mounted HART Transmitter
Rosemount 753R with Integral 3051S Pressure Transmitter and
Remote Mounted HART Transmitter (Dual Drop)
Product Certifications
Start
End
Product Discontinued February 2010
00825-0100-4379, Rev DA
October 2008
Rosemount 753R Indicator
Rosemount 753R
Remote Web Based Monitoring Indicator
8200 Market Boulevard
Chanhassen, MN USA 55317
T (US) (800) 999-9307
T (Intnl) (952) 906-8888
F (952) 949-7001
This installation guide provides basic guidelines for the Rosemount 753R Web Based
Remote Monitoring Indicator (see Reference Manual Document Number
00809-0100-4379 for detailed instructions). It does not provide instructions for
diagnostics, maintenance, service, or troubleshooting. This document is also available
electronically on www.rosemount.com.
Removal or attempted removal of the antenna will void the device warranty.
Explosions could result in death or serious injury:
Installation of this transmitter in an explosive environment must be in accordance with the
appropriate local, national, and international standards, codes, and practices. Please
review the approvals section of the 753R reference manual for any restrictions associated
with a safe installation.
• Do not remove the transmitter cover in explosive environments when the circuit is live.
• Check that the instrument is installed in accordance with non-incendive field wiring
practices.
Process leaks may cause harm or result in death.
• Install and tighten process connectors before applying pressure.
Electrical shock can result in death or serious injury.
• Avoid contact with the leads and terminals. High voltage that may be present on leads
can cause electrical shock.
00825-0100-4379, Rev DA
October 2008
• The 753R is designed for monitoring purposes only.
Do not use for control or feedback applications.
• The 753R relies on 3rd party cellular networks for communications.
The 753R may not function properly due to cellular network failures.
2
Quick Installation Guide
RPS
Line Power
RPSLine Power
RPS
Line Power
00825-0100-4379, Rev DA
October 2008
Overview
The Rosemount 753R is available in three
primary configurations:
1. Rosemount 753R with Integral 3051S
Pressure Transmitter.
Instructions begin on page 4.
2. Rosemount 753R with Remote Mounted
HART™ Transmitter.
Instructions begin on page 6.
Rosemount 753R Indicator
3. Rosemount 753R with Integral 3051S
Pressure Transmitter and Remote Mounted
HART Transmitter (also known as Dual
Drop).
Instructions begin on page 9.
3
Quick Installation Guide
RPS
Line Power
Rosemount 753R Indicator
00825-0100-4379, Rev DA
October 2008
Rosemount 753R with Integral 3051S Pressure Transmitter
Measurement Transmitter Installation.
1. Install the 3051S according to the 3051S Quick Installation Guide included in the 753R
packaging.
2. To achieve best signal strength, the 753R should be installed so the antenna is
approximately 18 in. (457 mm) from the side of the tank or other obstructions.
Mounting and Positioning of the 753R.
1. Housing Rotation Consideration: To improve field access to wiring, or to obtain a better
view of the LCD display:
a. Use the 3/32 in. hex wrench to loosen the housing rotation set screw (See Figure 6 on
page 13).
b. Rotate the housing clockwise to the desired location. If the desired location cannot be
reached because of thread limits, rotate the housing counter clockwise to the desired
location (up to 360° from the thread limit).
c. Tighten the housing rotation set screw to 20 in.-lb.
2. Remote Power Supply (RPS) Positioning consideration: For devices powered by an
RPS, the RPS should be positioned for maximum sun exposure. It is important to tighten
the set screws after positioning the solar panel. (See Figure 7 on page 13).
3. It is recommended that the device be installed in a vertical and upright position. For best
signal reception, the antenna should be positioned vertically.
Power Application
1. Remove the housing cover labeled FIELD TERMINALS.
2. Ground the 753R housing according to local electrical codes.
3. For units with an RPS see Figure 9 on page 14:
a. The + lead should have been factory connected
b. Connect the - lead (black wire) to the terminal marked 6–24 VDC by sliding the female
quick connect fitting onto the male quick connect fitting.
4. For user-supplied 6–24 VDC line power see Figure 10 on page 14:
a. Route the power supply leads through the 753R housing conduit entry using the
appropriate strain relief and cable glands.
b. Attach the + lead to the terminal marked 6–24 VDC (+).
c. Connect the - lead to the terminal marked 6–24 VDC (-).
d. The RPS should never be connected for this option.
4
Quick Installation Guide
WAR N ING
00825-0100-4379, Rev DA
October 2008
To avoid a potential explosion that could result in death or serious injury, do not
connect both the 6–24 VDC power supply and the RPS at the same time.
Verify Operation of the 753R
1. When the power is applied, the LCD will light and display measurement and status
messages.
2. After the 753R has powered and cycled through the startup sequence, press and hold
the event button for 6-8 seconds, then release. The display will indicate Event Entry, and
measurement and status messages will be shown.
Seal the Unit
1. Replace the FIELD TERMINALS housing cover and tighten so metal touches metal.
2. The temporary orange plugs should be replaced with the included conduit plugs using
approved thread sealant. See Conduit Plug Illustration on page 13.
Verify that the 753R has successfully transmitted to iTraX
1. Log into iTraX (Figure 3 on page 11)
a. https://itrax.datacom.com.
b. Enter your username.
c. Enter your password.
2. Locate the tag on the Summary page as shown in Figure 4 on page 12, and verify
successful transmission at the time of installation. (See Received Time Column).
Configure the 753R
1. Log into iTraX (Figure 3 on page 11
a. https://itrax.datacom.com.
b. Enter your username.
c. Enter your password.
2. Locate and select the 753R tag on the Summary page.
3. Select Device from the menu on the left frame. (See Figure 5 on page 12.)
4. Navigate through the configuration options for any desired changes to the 753R
configuration.
5. Click Submit prior to leaving any page where the configuration has been updated to save
these changes.
Rosemount 753R Indicator
®
5
Quick Installation Guide
RPSLine Power
Rosemount 753R Indicator
00825-0100-4379, Rev DA
October 2008
Rosemount 753R with Remote Mounted HART™ Transmitter
Measurement Transmitter Installation.
1. Install the remote measurement transmitter according to the Quick Installation Guide
included in the measurement transmitter’s packaging.
Mounting and Positioning of the 753R.
1. Mount the 753R securely using the included brackets and bolts.
2. To achieve best signal strength, the 753R should be installed so the antenna is
approximately 18 in. (457 mm) from the side of the tank or other obstruction.
3. Housing Rotation Consideration: To improve field access to wiring, or to obtain a better
view of the LCD display:
a. Use the 3/32 in. hex wrench to loosen the housing rotation set screw (See Figure 6 on
page 13).
b. Rotate the housing clockwise to the desired location. If the desired location cannot be
reached because of thread limits, rotate the housing counter clockwise to the desired
location (up to 360° from the thread limit).
c. Tighten the housing rotation set screw to 20 in.-lb.
4. Remote Power Supply (RPS) Positioning Consideration: For devices powered by an
RPS, the RPS should be positioned for maximum sun exposure. It is important to tighten
the set screws after positioning the solar panel.(See Figure 7 on page 13.)
5. It is recommended that the device be installed in a vertical and upright position. Also, for
the best signal reception, the antenna should be positioned vertically.
6. Install conduit and conduit fittings between the measurement transmitter housing and the
753R housing.
a. Utilize strain relief where necessary
b. Create a drip loop or other run-off path so moisture does not pool where the conduit
enters the housing as shown in Figure 1 on page 6.
Figure 1. Drip Loop Illustration
c. Connect the HART + and - leads to the measurement transmitter according to the
wiring diagrams on page 14.
6
Quick Installation Guide
WAR N ING
00825-0100-4379, Rev DA
October 2008
Power Application
1. Remove the housing cover labeled FIELD TERMINALS.
2. Ground the 753R housing according to local electrical codes.
3. For units with an RPS see Figure 9 on page 14:
a. The + lead should have been factory connected.
b. Connect the - lead (black wire) to the terminal marked 6–24 VDC by sliding the female
quick connect fitting onto the male quick connect fitting.
4. For user-supplied 6–24 VDC line power see Figure 10 on page 14:
a. Route the power supply leads through the 753R housing conduit entry using the
appropriate strain relief and cable glands.
b. Attach the + lead to the terminal marked 6–24 VDC (+).
c. Connect the - lead to the terminal marked 6–24 VDC (-).
d. The RPS should never be connected for this option.
To avoid a potential explosion that could result in death or serious injury, do not
connect both the 6–24 VDC power supply and the RPS at the same time.
Verify Operation of the 753R
1. When the power is applied, the LCD will light and display measurement and status
messages.
2. After the 753R has powered and cycled through the startup sequence, press and hold
the event button for 6-8 seconds, then release. The display will indicate Event Entry, and
measurement and status messages will be shown.
Seal the Unit
1. Replace the FIELD TERMINALS housing cover and tighten so metal touches metal.
2. The temporary orange plugs should be replaced with the included conduit plugs using
approved thread sealant. See Conduit Plug Illustration Figure 8 on page 13.
Verify that the 753R has successfully transmitted to iTraX
1. Log into iTraX (Figure 3 on page 11)
a. https://itrax.datacom.com.
b. Enter your username.
c. Enter your password.
2. Locate the tag on the Summary page as shown in Figure 4 on page 12, and verify
successful completion of the transmission at the time of installation (see Received Time
Column). The tag for the measurement transmitter will be a T followed by the
transmitter’s Device ID number.
Rosemount 753R Indicator
®
7
Quick Installation Guide
Rosemount 753R Indicator
Configure the 753R
1. Log into iTraX
a. https://itrax.datacom.com.
b. Enter your username.
c. Enter your password.
2. Locate and select the 753R tag on the Summary page,
3. Select Device from the menu on the left frame. (See Figure 5 on page 12.)
4. Navigate through the configuration options for any desired changes to the 753R
configuration.
5. Click Submit prior to leaving any page where the configuration has been updated to save
these changes.
00825-0100-4379, Rev DA
October 2008
8
Quick Installation Guide
RPS
Line Power
00825-0100-4379, Rev DA
October 2008
Rosemount 753R Indicator
Rosemount 753R with Integral 3051S Pressure Transmitter and
Remote Mounted HART Transmitter
Measurement Transmitter Installation.
1. Install the remote measurement transmitter according to the Quick Installation Guide
included in the measurement transmitter’s packaging.
2. Install the 3051S according to the 3051S Quick Installation Guide included in the 753R
packaging.
3. To achieve best signal strength, the 753R should be installed so the antenna is
approximately 18 in. (457 mm) from the side of the tank of other obstructions.
Mounting and Positioning of the 753R.
1. Housing Rotation Consideration: To improve field access to wiring, or to obtain a better
view of the LCD display:
a. Use the 3/32 in. hex wrench to loosen the housing rotation set screw (see Figure 6 on
page 13).
b. Rotate the housing clockwise to the desired location. If the desired location cannot be
reached because of thread limits, rotate the housing counter clockwise to the desired
location (up to 360° from the thread limit).
c. Tighten the housing rotation set screw to 20 in.-lb.
2. Remote Power Supply (RPS) Positioning Consideration: For devices powered by an
RPS, the RPS should be positioned for maximum sun exposure. It is important to tighten
the set screws after positioning the solar panel. (See Figure 7 on page 13).
3. It is recommended that the device be installed in a vertical and upright position. Also, for
best signal reception, the antenna should be positioned vertically.
4. Install conduit and conduit fittings between the measurement transmitter housing, and
the 753R housing.
a. Utilize strain relief where necessary.
b. Create a drip loop or other run-off path so moisture does not pool where the conduit
enters the housing.
9
Quick Installation Guide
WAR N ING
Rosemount 753R Indicator
Figure 2. Drip Loop Illustration
5. Connect the HART + and - leads to the measurement transmitter according to the Quick
Installation Guide included with the measurement transmitter package.
6. Connect the HART + and - leads to the 753R according to the wiring diagrams on page
14.
Power Application
1. Remove the housing cover labeled FIELD TERMINALS.
2. Ground the 753R housing according to local electrical codes.
3. For units with an RPS see Figure 9 on page 14:
a. The + lead should have been factory connected
b. Connect the - lead (black wire) to the terminal marked 6–24 VDC by sliding the female
quick connect fitting onto the male quick connect fitting.
4. For user-supplied 6–24 VDC line power see Figure 10 on page 14:
a. Route the power supply leads through the 753R housing conduit entry using the
appropriate strain relief and cable glands.
b. Attach the + lead to the terminal marked 6–24 VDC (+).
c. Connect the - lead to the terminal marked 6–24 VDC (-.)
d. The RPS should never be connected for this option.
00825-0100-4379, Rev DA
October 2008
To avoid a potential explosion that could result in death or serious injury, do not
connect both the 6–24 VDC power supply and the RPS at the same time.
Verify Operation of the 753R
1. When the power is applied, the LCD will light and display measurement and status
messages.
2. After the 753R has powered and cycled through the startup sequence, press and hold
the event button for 6-8 seconds, then release. The display will indicate Event Entry, and
measurement and status messages will be shown.
Seal the Unit
1. Replace the FIELD TERMINALS housing cover and tighten so metal touches metal.
2. The temporary orange plugs should be replaced with the included conduit plugs using
approved thread sealant.See Conduit Plug Illustration Figure 8 on page 13.
10
Quick Installation Guide
00825-0100-4379, Rev DA
October 2008
Verify that the 753R has successfully transmitted to iTraX
1. Log into iTraX (Figure 3 on page 11)
a. https://itrax.datacom.com.
b. Enter your username.
c. Enter your password.
2. Locate the integral and remote tags on the Summary page as shown in Figure 4 on page
12 and verify successful completion of the transmission at the time of installation. (See
Received Time Column.) The tag for the remote measurement transmitter will be a T
followed by the transmitter’s Device ID number.
3. Configure the 753R
a. Log into iTraX
®
• https://itrax.datacom.com.
• Enter your username.
• Enter your password.
b. Locate and select the integral tag on the Summary page.
c. Select Device from the menu on the left side of the screen.
d. Navigate through the configuration options for any desired changes to the 753R
configuration.
e. Click Submit prior to leaving any page where the configuration has been updated to
save these changes.
f. Repeat steps b through e for the remote measurement transmitter.
Figure 3. Log In Screen
Rosemount 753R Indicator
®
11
Rosemount 753R Indicator
Figure 4. Summary Screen
Figure 5. Device Configuration Screen
Quick Installation Guide
00825-0100-4379, Rev DA
October 2008
12
Quick Installation Guide
Housing Rotation Set
Screw (3/32-inch)
RPS Positioning
Set Screw
RPS Positioning
Set Screw
Conduit Plug
00825-0100-4379, Rev DA
October 2008
Figure 6. Housing Rotation Set Screw Location
Figure 7. RPS Positioning Set Screws
Rosemount 753R Indicator
Figure 8. Conduit Plugs - Remove orange plastic insert, install the supplied conduit plug with sealant
13
Rosemount 753R Indicator
DI1
PUSH
BUTTON
6-24
V DC
HART
DI02
-
X
+
Customer Supplied
Remote Mounted
HART Transmitter
X
HART -
HART +
-
+
Remote Power Supply
Discrete Output
-
+
Push Button
Green
Black
Red
Rosemount 753R
DI1
PUSH
BUTTON
6-24
V DC
HART
DI02
-
X
+
Customer Supplied
Remote Mounted
HART Transmitter
X
HART -
HART +
-
+
6-24V DC Power Supply
Discrete Output
-
+
Push Button
Green
Black
Rosemount 753R
Customer Supplied
X
X
Figure 9. Wiring Diagram for 753R with Remote Power Supply (RPS)
Figure 10. Wiring Diagram for 753R with 6–24V DC Power Supply
Quick Installation Guide
00825-0100-4379, Rev DA
October 2008
14
Quick Installation Guide
PRODUCT CERTIFICATIONS
00825-0100-4379, Rev DA
October 2008
NOTE
The Rosemount 753R is intended for monitoring purposes only.
The Rosemount 753R is intended for web based monitoring applications and is not
designed to integrate into process control systems.
Rosemount 753R Indicator
Approved Manufacturing Locations
Rosemount Inc. — Chanhassen, Minnesota USA
Telecommunication/EMC Compliance
FCC ID: IHDT56FV1
IC ID: 109O-FV1 is contained within.
This device has met the applicable EMC requirements of EN 61326: 2006.
This device has met the applicable requirements of the R&TTE Directive.
Ordinary Locations Certifications for FM
As standard, the transmitter has been examined and tested to determine that the design
meets basic electrical, mechanical, and fire protection requirements by FM, a nationally
recognized testing laboratory (NRTL) as accredited by the Federal Occupational Safety and
Health Administration (OSHA).
Hazardous Locations Certifications
USA and Canadian Certifications
Factory Mutual (FM) Approvals
N5 FM Class I, Division 2
USA Certificate Number: 3023264
Canadian Certificate Number: 3027229
Class I, Division 2, Groups A, B, C, and D;
Temperature Class T4 Ta = 70° C
Enclosure Type 3R
Note: To maintain a Type 3R enclosure, the solar panel must be pointed upwards.
WARNI NG
Substitution of components may impair suitability for Division 2.
Explosion Hazard. Do not disconnect equipment when a flammable or combustible
atmosphere is present.
Explosion Hazard. Do not open enclosure or replace battery when flammable or
combustible atmosphere is present.
1
15
Rosemount 753R Indicator
Quick Installation Guide
00825-0100-4379, Rev DA
October 2008
16